HOBO® UX120 Plug Load Logger
Measures power and energy consumption of 120V ofce equipment plug loads
Onset’s HOBO Plug Load Logger is a high-accuracy, easy-todeploy data logger that measures and records the power and
energy consumption of 120V plug loads from office equipment,
vending machines, and other devices.
The logger provides 0.5% measurement accuracy with a
measurement resolution of 1 watt, making it an ideal choice for
building audits where detailed energy use data is required. The
rugged housing is designed to withstand the rigors of real-world
handling, providing reliable performance despite bumps, drops,
and use under desks.
Supported Measurements: AC Current, AC Voltage, Amps,
Kilowatt Hours, Power Factor, Volt-Amps, Volts, Watt Hours,
Watts
Key Advantages:
• 0.5% measurement accuracy enables more reliable plug load energy use data
• “Meter Mode” provides instant viewing of real-time plug load variables
• Large memory enables faster logging intervals for more comprehensive plug load profiles
• Battery back-up ensures logged data remains intact in the event of a power outage or load failure
• Full-featured LCD display provides visual diagnostics for easy deployment
• Factory calibrated (see user’s manual for details)
Minimum System Requirements:
Software USB cable*
For complete information and accessories, please visit: www.onsetcomp.com
Part number UX120-018
RMS Voltage Accuracy,
RMS Current Accuracy,
Active Power Accuracy,
Power Factor Accuracy
Power Factor Accuracy ±0.02
Drift Up to 0.5% typical within 1 year
Memory 4 MB (1.4 million measurements, maximum)
Logging rate 1 second to 18 hours, 12 minutes, 15 seconds
Sampling rate 60 Hz or 16.67 mS single-cycle
Battery life
Power source Line-powered with 0.92 m (3 ft) AC power cord or two AAA 1.5 V alkaline batteries, user replaceable
Resolution 1 Watt Load at 120 V AC 15 Amp
Operating
temperature range
Dimensions 13.97 x 7.62 x 4.75 cm (5.5 x 3 x 1.87 in.)
CE Compliant Ye s
0.5% up to 14 Amp continuous; up to 1.0% over 14 Amp when equipment being monitored is at 100% duty cycle
2 years with line power; 6 months battery only (no line power) with logging rate of 1 minute or greater operating at
25°C (77°F)
Logging: 5° to 40°C (41° to 104°F); 0 to 95% RH (non-condensing)
*USB cable included with software

HOBO UX120 4-Channel Analog Logger
Flexible, Accurate, 4-channel Analog Logger
The HOBO UX120-006M Analog Logger is a high-performance,
LCD display data logger for building performance monitoring
applications.
As Onset’s highest-accuracy data logger, it provides twice
the accuracy of previous models, a deployment-friendly LCD,
and flexible support up to four external sensors for measuring
temperature, current, CO2, voltage, and more.
Supported Measurements: Temperature, 4-20mA, AC Current,
AC Voltage, Air Velocity, Carbon Dioxide, Compressed Air Flow,
DC Current, DC Voltage, Gauge Pressure, Kilowatts, Volatile
Organic Compound
Key Advantages:
• Twice the accuracy over previous models
• 16-bit resolution
• Flexible support for a wide range of external sensors
• LCD confirms logger operation and displays near real-time measurement data
• Provides minimum, maximum, average, and standard deviation logging options
• On-screen alarms notify you when a sensor reading exceeds set thresholds
• Stores 1.9 million measurements for longer deployments between offloads
Minimum System Requirements:
Software USB cable*
For complete information and accessories, please visit: www.onsetcomp.com
Part number UX120-006M
Memory 1.9 Million
Logging Rate 1 second to 18 hours, user selectable
Logging Modes Normal, Burst, Statistics
Memory Modes Wrap when full or stop when full
Time Accuracy ±1 minute per month at 25°C (77°F)
Battery Life 1 year typical with logging rate of 1 minute and sampling interval of 15 seconds or greater, user replaceable, 2 AAA
Dimensions 10.8 x 5.41 x 2.54 cm (4.25 x 2.13 x 1 in.)
Operating Range Logging: -20° to 70°C (-4° to 158°F); 0 to 95% RH (non-condensing)
Accuracy ±0.1 mV ±0.1% of reading
CE Compliant Yes
*USB cable included with software part # BHW-PRO-CD