Onset T-VER-PX3UL Operating Manual

Veris Differential Pressure Transducer Connection Instructions
For use with HOBO® H22, U12, U30, UX120-006M, and RX3000 data loggers and HOBO ZW data nodes
Applies to these Veris Differential Pressure Transducers:
T-VER-PX3UL 0-10” WC 4-20mA (or 0-5V/0-10V) representing 0 to 10” WC PX3ULX05
This document provides instructions on connecting the Veris Differential Pressure Transducer listed above to each of the following:
FlexSmart
Analog Sensor Port/Module used with HOBO U30 and RX3000 series data
loggers
Voltage adapter used with the U12 and UX120-006M data loggers and ZW series
data nodes
It also lists configuration values used by HOBOware each transducer. Note: For information on connecting the differential pressure transducer to the pressure source, and other transducer details, refer to the documentation provided by Veris.
Required
Selected Veris Differential Pressure Transducer
HOBO H22, U12, U30, UX120-006M, or RX3000 data logger, or HOBO ZW data node
FlexSmart Analog Module, Onset Part No: S-FS-CVIA (for H22 series); Analog Sensor Port/Module option (for U30 and
RX3000 series); voltage adapter, Onset Part No. CABLE-ADAP5 or CABLE-ADAP10 (for U12, UX120-006M, or ZW series)
HOBOware software, version 2.2.1 or higher (2.4.0 or higher for U30 series; 3.6 or higher for UX120-006M);
HOBOware Pro 3.0 or higher for ZW series
HOBOlink (for RX3000 series data loggers)
Customer-supplied length of 18 AWG, shielded, multi-conductor cable
Analog Module used with HOBO H22 series data loggers
®
software to configure the logger for
Veris Differential Pressure Transducer
Connecting the Differential Pressure Transducer to the Analog Module or Port
© 2018 Onset Computer Corporation. All rights reserved. Onset, HOBO, HOBOware, and HOBOlink are registered trademarks and FlexSmart is a trademark of Onset Computer Corporation. Other products and brand names may be trademarks or registered trademarks of their respective owners.
22415-A
Veris Differential Pressure Transducer Connection Instructions
U30 or RX3000 Connection (U30 Shown)
ZW, U12, and UX120-006M Connection
HOBO ZW Series Wireless Data Node; U12 or
UX120-006M Logger (ZW shown)
Page 2 of 3
Veris Differential Pressure Transducer Connection Instructions
Configuring the Data Logger for the Differential Pressure Transducer using HOBOware Software
HOBOware software provides configuration files for the transducers. The table below lists the recommended configuration values that these files contain. For information on loading configuration files, refer to the software documentation.
Onset Part Nos. Channel
Name
T-VER-PX3UL Diff Pressure 20 sec Current 4 20 mA 0 0.1 (or 0.25,
Velocity 20 sec Current 4 20 mA 0 500, 1000,
Warm-Up Measurement
Type
Voltage 0 5 (or 10) V
Voltage 0 5 (or 10) V
Raw Value 1
Raw Value 2
Raw Units
Scaled Value 1
Scaled Value 2
0.5, 1, 2.5, 5, or 10)
2000, 3000, 4000, 5000, 6000, or 7000
Notes:
Excitation power provided by the FlexSmart Analog Module (Onset Part No. S-FS-CVIA) with H22; by the Analog
Sensor Port/Module with U30 and RX3000; and by power adapter (Onset Part No. AC-SENS-1) with ZW, U12, or UX120-006M.
Both differential pressure transducer models have switch-selectable ranges and scales, as listed.
Scaled Units
in WC
ft/min
Page 3 of 3