Onset MAG-0400 Operating Manual

Magnelab Mini AC Current Transformer (CT) Connection Instructions
For use with HOBO® H22 and U30 Series Data Loggers
Applies to these Magnelab CTs
Onset Part No. Rated Current Output Magnelab Part No.
T-MAG-0400-05 5 Amps 0-333mV AC representing 0 to 5 Amps AC SCT-0400-005 T-MAG-0400-10 10 Amps 0-333mV AC representing 0 to 10 Amps AC SCT-0400-010 T-MAG-0400-20 20 Amps 0-333mV AC representing 0 to 20 Amps AC SCT-0400-020 T-MAG-0400-50 50 Amps 0-333mV AC representing 0 to 50 Amps AC SCT-0400-050 T-MAG-0400-75 75 Amps 0-333mV AC representing 0 to 75 Amps AC SCT-0400-075
DANGER!—HIGH VOLTAGE HAZARD
Installing CTs in an energized electrical enclosure or on any energ ized conductor can result in severe injury or death. These CTs are for installation by qualified personnel only. To avoid electrical shock, do not perform any installation or servicing of these CTs unless you are qualified to do so. Disconnect and lock-out all power sources during installation and servicing.
This document provides instructions on connecting the Magnelab CTs listed above to the FlexSmart lists configuration values used by HOB O ware
TRMS Module used with either HOBO H22 or U30 series data loggers. It also
®
Pro software to configure the logger for each
CT.
Required
Selected Magnelab CT
HOBO H22 or U30 Series Data Logger
FlexSmart TRMS Module, Onset Part No: S-FS-TRMSA (for H22 series only) or
S-FS-TRMSA-D (for H22 and U30 series)
HOBOware Pro Software, version 2.2.1 or higher (2.4.0 or higher for U30 series)
Connecting the CT to the FlexSmart TRMS Module
HOBO H22 or U30 Series Data Logger
(H22-001 shown)
S-FS-TRMSA / S-FS-TRMSA-D*
FlexSmart TRMS Module
S-FS-TRMSA-D*
*The S-FS-TRMSA-D has a modular connector for connecting to a Smart Sensor port and thus is compatible with both H22 and U30 series data loggers. The S-FS-TRMSA is compatible with the H22 series only.
T-MAG-0400-xx
Current Transformer
1. Open CT.
Source Face
See below for wire capture procedure
LINE
2. Place CT around the individual wire carrying the phase to be monitored.
3. Snap CT closed.
LOAD
Magnelab Mini AC
Current Transformer
S-FS-TRMSA (or S-FS-TRMSA-D)
FlexSmart TRMS Module
Terminal Block
S1~
S2~
S2~
S1~
Black
S2~
White
S2~
Black White
Black White
Wiring Diagram for Single CT
S-FS-TRMSA (or S-FS-TRMSA-D)
FlexSmart TRMS Module
Terminal Block
S1~
S1~
Wiring Diagram for Two CTs
From CT
From CT
From CT
© 2010 Onset Computer Corporation. All rights reserved. Onset, HOBO, and HOBOware are registered trademarks of Onset Computer Corporation. Other products and brand names may be trademarks or registered trademarks of their respective owners.
Manual Part No: MAN-MINI-CT-x Doc No: 14255-A
Magnelab Mini AC Current Transducer (CT) Connection Instructions
Configuring the Data Logger for the CT, using HOBOware Pro Software
HOBOware Pro software provides configuration files for the CTs. The table below lists the recommended configuration values for each CT that these files contain. For information on loading configuration files, refer to the software documentation.
Onset Part No: Channel Name Raw Value 1 (mV) Raw Value 2 (mV) Scaled Value 1 Scaled Value 2 Scaled Units
T-MAG-0400-05 Current 0 333 0 5 A T-MAG-0400-10 Current 0 333 0 10 A T-MAG-0400-20 Current 0 333 0 20 A T-MAG-0400-50 Current 0 333 0 50 A T-MAG-0400-75 Current 0 333 0 75 A
2