This guide explains how to configure the Onset meter so it properly reflects the physical reality of an installation. There are three sections to this guide: the first is a brief introduction to the web pages used
to configure the Onset meter, the second is the main section and consists of a list of examples reflecting
common installation scenarios. The third section contains tips on how to fix up installation mistakes through
the web configuration rather than having to go out to a site and correct the physical mistake.
Onset establishes a few basic rules. Following these rules is not strictly required, but they help to keep
things straight and properly working:
1. The direction in which the Current Transformers (CTs) point matters. The white sticker on the CTsshould always point towards the entity being measured. For example, towards the utility when
measuring power from the power grid, towards the inverter for solar and/or wind generators, towards
appliances when measuring loads, or towards the panels when measuring subpanels.
2. Power readings that are positive numbers indicate that power is being delivered from the entity be-ing measured whereas negative numbers indicate power being delivered to the entity. For example,
when a solar system produces more power than a site uses, the excess power is delivered back into
the grid. In this case, the power reading for the grid will be negative, since the grid is consuming the
excess power.
1
Page 2
Onset EG4xxx Configuration Guide1 OVERVIEW
To configure the meter, start a compatible browser on a computer and connect to the device’s web page.
See the Owner’s Manual for details on how to do that. Once connected to the device, click on the “LANAccess” link in the top-right of the page. This redirects the browser to a page ensuring a direct LAN
connection to the device. If the page does not load, you will not be able to make changes to the device
settings, unless remote administration is enabled. Please contact Onset technical support for details on
how to enable that. Once the page has loaded, click on the “Settings” link in the top-right of the page,
then click on “Installation” in the navigation-bar on the left of the new page.
As illustrated in Figure 1, the Installation page has five sections:
1. Potential Transformers (PTs)
2. Current Transformers (CTs)
3. Remote Devices
4. Registers
5. Totals and Virtual Registers
We describe the purpose of each section in more detail below.
After any of the settings have been changed, they need to be saved by clicking on the “Save” button near
the bottom of the page. When doing that for the first time, you may be prompted for authorization to make
the changes. You can enter “owner” as the user name. By default, the password is “default” (no quotes).
If you receive an error stating you are not authorized to make changes, make sure to click on the “LANAccess” link in the top-right of the page.
To restore the settings which are currently active on the device, click on the “Reset” button. This will revert
any changes you have made to the page since the last save.
April 18, 20182
Page 3
Onset EG4xxx Configuration Guide1 OVERVIEW
Figure 1: Example of meter Installation-Settings Page
1.1Potential Transformer (PT) Configuration
This section is used to inform the device of any potential-transformers (PTs) that may be installed. Usually,
no PTs are installed and the settings here can be left at the default value of “direct (no PT)”.
April 18, 20183
Page 4
Onset EG4xxx Configuration Guide1 OVERVIEW
1.2Current Transformer (CT) Configuration
This section defines what kind of current-transformer (CT) is connected to each of the CT positions. A
blank entry indicates that no CT is connected. When a CT is connected to the device, simply select the
appropriate CT selection from the pull-down list for the position the CT is plugged into. For example, if a
100A 0.94” J&D split-core CT is plugged into CT position 2, click on the pull-down list for CT2 and select
“JD JS 24mm/0.94" 100A”.
The format of the CT drop-down option is “[MFG] [MODEL] [SIZE MM]/[SIZE IN] [AMPERAGE]”
[MFG]2-letter manufacturer code (see table 1)
[MODEL]CT Model (see table 2)
[SIZE MM]Inner-diameter in millimeters
[SIZE IN]Inner-diameter in inches
[AMPERAGE]Amperage rating of CT (not breaker amperage)
MFG codeManufactuer
JDJ&D
CCContinental Control Systems
MLMagnelab
AEAccuEnergy
CRCR Magnetics
A multiplicative scale can be applied to the CT reading by entering a positive number greater than 0 to the
box right of the CT pull-down option. This is generally used if a single CT is measuring one set of parallel
feeds of the same phase.
WARNING: in many cases, parallel feeds are not perfectly balanced, and could have significant differences.
Because of this, we suggest monitoring each conductor, either by using a CT for each individual conductor,
or by using larger diameter CTs to encompass multiple parallel feeds (of the same phase).
1.2.1 High-gain mode
Available on EG4xxx models, High-gain mode amplifies the signal to the meter CT ports by 10 times. This
allows, for example, a 100A CT to act as a 10A CT. High-gain mode affects all CT inputs. Note, selecting
high-gain mode immediately changes the CT drop-down option to its respective lower amperage-rated
value. For example, enabling high-gain mode with a 100A CT will change the drop-down option to indicate
a 10A CT. Likewise, a CT configured for 75A will appear as a 7.5A CT.
April 18, 20184
Page 5
Onset EG4xxx Configuration Guide1 OVERVIEW
1.2.2 Rope CTs (Rogowski Coils)
Self-powered rope CTs are wired directly to the meter with a green 2-pin power plug. Rope CTs are
excellent for bus-bars and large switch-gear applications. Self-powered rope CTs are flexible and easy to
install but will not be accurate at low amperages. Rope CTs are configured like split-core CTs. For example,
the 4“ AccuEnergy 106mm rope should be configured as AE RCT 106mm/4.17" 2775A.
Rope CTs should not be used to monitor solar arrays, as solar uses a large range of amperages, often
insufficient for accurate monitoring with rope CTs when the inverter is in standby.
1.3Remote Devices
EG4xxx can read data from Modbus TCP and RTU. For remote device configuration assistance, please
contact Onset support.
1.4Register Configuration
This section defines what data gets recorded in the internal database of the meter. Each register has a
unique name that identifies what it is recording.
1.4.1 Register Name
Register names may contain any ASCII/UTF-8 characters except for control characters. With English characters, register-names can be up to 31 characters long.
1.4.2 Register Type
Each register can be configured to record one of several types of data. The type can be selected from the
drop-down menu to the right of a register-name. In our example, the drop-down menu looks as follows:
The entries in this popup-menu have the following meaning:
P: Records the power calculated from one or more current/voltage-pairs.
I: Records the RMS current measured by one of the connected CTs.
Idc: Records the DC (mean) current measured by one of the connected CTs.
April 18, 20185
Page 6
Onset EG4xxx Configuration Guide1 OVERVIEW
V: Records the RMS voltage measured by one of the connected line voltages.
Vdc: Records the DC (mean) voltage measured by one of the connect CTs.
F: Records the frequency measured on one of the channel inputs (CTs or voltage lines).
#: This is a special debug register.
=: Formula register. Records the value obtained by evaluating the specified formula. See Sec-
tion 1.4.4 for details.
In the example of Figure 1, we see five rows in the Registers section: the first two calculate power (P).
We will discuss those in more detail in the next section.
The third row is a register that records the current (I) of CT1, and the fourth records the voltage (V) of line
voltage input L1. Lastly the fifth register records frequency (F) of line voltage input L1.
A register can be added by clicking on the “Add Register” button. An existing register can be deleted by
clicking on the remove iconto the right of the register name.
1.4.3 Recording Power
There are two parts to configuring a register to record power: first, the subtype(s) to be recorded need to be
selected, second, the power-components that should be used to calculate the power need to be specified.
Power Subtypes The subtypes to record for a power register are selected by clicking on the subtypeselector button to the right of the register-type button. This will pop up the dialog shown below:
As shown here, there are five subtypes which can be recorded by turning on the corresponding checkbox:
= (net): Checking this box ensures that the net flow of power is available as a register-value. The
value of such a register increases when the calculated real power is positive and decreases
when it is negative. This is equivalent to a utility’s net-meter, for example.
+ (positive-only): Checking this box ensures that a register-value is available that increases only
when the calculated real power is positive. When the real power is negative, the registervalue does not change. This can be used, for example, to record only the power generated
by an inverter or only the power consumed from the utility.
- (negative-only): Checking this box ensures that a register-value is available that increases only
when the calculated real power is negative. When the real power is positive, the registervalue does not change. This can be used, for example, to record only the power consumed
by an inverter when there is no sun or only the power fed back into the grid.
April 18, 20186
Page 7
Onset EG4xxx Configuration Guide1 OVERVIEW
| (absolute): Checking this box ensures that a register-value is available that counts indepen-
dent of the sign of the calculated real power. That is, the register-value increases by the
absolute value of the real power regardless of whether it is positive or negative. This is not
often used.
(apparent): Checking this box ensures that apparent power is recorded in a register. Apparent
*
power is the sum of the product of the RMS voltage and current of each power-component.
As such, apparent power always has a non-negative value. This can be used, for example,
to track the quality of the power as the ratio of apparent power and absolute real power is
the power-factor.
When you are done selecting subtypes, click on the OK button to save the selection or on the Cancel button
to revert to the previously existing configuration.
Power Components The power components define which currents and voltages are to be combined to calculate a register’s power figure. In our example, the power components for the Main Panel (3 phase)
and Subpanel (single phase) registers look as follows:
This shows that Main Service (3 phase) power is calculated as the product of the current measured
by CT1 and the voltage measured on line L1 (e.g., black leg) plus the current measured by CT2 and the
voltage measured on line L2 (e.g., red leg), plus the current measured by CT3 and the voltage measured
on line L3 (e.g., blue leg).
The Subpanel (single phase) power is calculated from CT4 on L1, plus CT5 on L2.
To add a new power-component to a register, click on the “Add Component” button. To delete a component, click on the remove iconto the right of the component.
1.4.4 Formula Registers
Formula registers are a powerful tool to record quantities that can be derived from other, directly-measured
registers. For example register Main Panel measures the real power used at a site, then register Main
Panel*would measure the apparent power used at the same site. To record the power-factor for the site,
we would have to divide Main Service by Main Service*and take the absolute value. This can be
accomplished by defining a formula register as shown below:
In this example, we named the register “Main Panel Power Factor” and selected the equal-sign (formularegister) as the register type (see Section 1.4.2). We set the unit type as ”number with 3 decimals”. Finally,
we entered a formula of abs($"Main Panel"/$"Main Panel∗") for calculating the value of the register. Here, $"regname" is used to obtain the current (second-by-second) value of register regname, so
$"Main Service" will evaluate to the current site-usage (in Watts) and $"Main Service∗" evaluates
April 18, 20187
Page 8
Onset EG4xxx Configuration Guide1 OVERVIEW
to the apparent power used by the site. The abs() function calculates the absolute value of the value
passed to it (i.e., it’s always positive).
An online-version of the function-list can be found in the Help section of the meter web-pages.
Several caveats apply to using formula registers:
• Do not reference a formula register from another formula register. The result can be unpredictable.
• Calculating formulas takes time. Do not overload the meter with unnecessary formula registers.
• All calculations are performed using single-precision IEEE-754 floating-point numbers. The final value
of a formula register is then rounded to a 64-bit signed integer number.
1.5Totals and Virtual Registers Configuration
Virtual registers are calculated as a sum or difference of real (physical) registers. Virtual registers to not take
up any space, and a virtual register can be added and removed in the same manner as physical registers.
A register is added by clicking on the Add Register button. A register can be removed by clicking on the
remove iconto the right of the register drop-down menu. You can select whether there register should
be added to or subtracted from the virtual registers value by selecting + or - from the drop-down menu to
the left of the register name, respectively.
Each power register will show up in several variations in the menu, namely with one variant for each selected
subtype (see “Power Subtypes” in section 1.4.3 Recording Power). Positive-only registers end in a ’+’,
negative-only registers end in a ’-’, absolute-registers end in a ’|’, and apparent power registers end in a
’*’. Net registers do not have an appended symbol and just appear as the register name.
In the image below, Register 1 has net, positive-only, and apparent power subtypes selected, so the
virtual register has choices for net, positive-only, negative-only, apparent power, and absolute (negativeonly and absolute are calculated on-the-fly because both ’net’ and ’positive-only’ subtypes are chosen).
The menu also has entries of the form MAX(reg,0) and MIN(reg,0). Those are for backwards compatibility with configurations created by older firmware and should no longer be used.
There are two special virtual registers called Usage and Generation. These are called totals and their
value is used to represent total site usage and total site generation. In the dashboard graph, total usage
is represented by a thick red line, and total generation is represented as a thick green line. The totals are
always present (cannot be deleted), but if a site does not measure usage or if there is no site-local power
generation, the respective total can be left blank.
1.5.2 Defining Views
Views can be used to define a restricted or alternate view of the data recorded by the meter. For example,
views could be used to view the usage/generation data for an individual condo when a single meter is used
to meter several condos.
A view is defined by pre-pending the view-name and a dot in front of a register name. In our example, the
virtual-register rows shown below define a view called A:
With this setup, selecting view A in the dash-board will display register Mech Room Panel as the total site
usage and nothing (zero) as the total site generation. That is, within a view, the register-names Usage and
Generation serve as the totals for that view. You can define an arbitrary number of other register names
within a view to display additional information in that view.
2Configuration Examples
The following pages illustrate various common installation scenarios and matching configurations. For
clarity, the diagrams have been simplified in the following manner:
• No circuit breakers are shown.
• The CT wires are not shown.
• The Neutral and Ground wiring is not shown.
• Most examples are partial configurations. For a complete system, the configurations from various
examples may have to be combined.
Please review the Owner’s Manual for detailed installation requirements. For safety, the meter always must
be wired to a breaker and the breaker should be labeled “Onset Meter Disconnect.”
• White stickers on CTs should point in the direction indicated in above diagram.
• Register definitions must be consistent with the wiring. CT1 and CT3 are on leg L1, so they must be
multiplied by L1; CT2 is on leg L2, so it must be multiplied by L2.
• With single-phase inverter, the current flowing at any given instant on leg L2 is the negative of the
current flowing on leg L1. Hence, rather than using a fourth CT, simply multiply the negated value of
CT3 with L2 to calculate the power on that leg.
• The totaling rules indicate that total usage (consumption) is calculated as the sum of the power reported for register Grid and, the positive-only register Solar+. If the power reported for Solar is
negative (indicating that the inverter is consuming power, e.g., during the night), then total usage is
simply equal to the power reported for register Grid. It would be (slightly) wrong to define the Usage
totaling rule as Grid + Solar because in this case, the inverter’s consumption would be canceled
out of the usage, giving a lower than real consumption figure.
Same as Standard Split-Phase installation, except that the inverter feeds directly into the power utility’s grid.
That is, the Solar CT is closer to the utility than the Grid CTs. This situation often arises when solar power
is delivered via a line-side tap.
• The only difference compared to the standard installation is that Solar+ was replaced by Solar- in
the totaling rule for Usage. This is because the Grid CTs already capture total consumption, including
any power coming from the solar system. The only exception is that when the inverter is consuming
power (e.g., at night), that consumption is not captured by the Grid CTs. Adding Solar- corrects that
because it will be equal to the amount of power consumed by the inverter, or zero when the inverter
is producing power.
2.3Three-Phase 120/208 or 277/480 Wye w/ single-phase inverter
Standard three-phase installation measuring power coming from a power utility (grid) and from a singlephase solar-system inverter. The color coding shows 120/208V, but applies to 277/480V as well. This
diagram is for a Wye system with a neutral. Refer to delta diagrams for systems without neutral.
• Three-phase installations are set up the same as split-phase systems, except that a third voltage-tap
(L3) and a third Grid CT is required to measure power flow on phase 3.
• With multiple inverters, add one Solar CT per inverter and define a separate register for each inverter
(e.g., Solar 1 and Solar 2). Adjust the register definition according to the CT that is measuring
the current and the phases that the inverter feeds onto. For example, CT5 measuring current onto L2
and also feeding onto L3: Solar 2 = CT5*L2 + -CT5*L3.
• If there are more than three single-phase inverters, it is more economical to measure the total solar
output with one CT per phase.
2.4Three-Phase 120/208 or 277/480 Wye w/ three-phase inverter
Standard three-phase installation measuring power coming from a power utility (grid) and from a threephase solar-system inverter. The color coding shows 120/208V, but applies to 277/480V as well. This
diagram is for a Wye system with a neutral. Refer to delta diagrams for systems without neutral.
• Three-phase inverter installations are the same as single-phase inverters on a three-phase system,
but require a CT on each leg. Typically, even balanced three-phase inverters will not be balanced
during the evening while in standby, so using a single CT may result in overnight generation or higher
than actual inverter draw.
Three-phase delta installation measuring power coming from a power utility (grid).
Registers
Grid=[P] [= ] CT1*L1 + CT2*L2
Totals and Virtual Registers
Usage=Grid
Notes:
• CAUTION: Since there is no neutral and none of the phases may be grounded, all conductive/metallic
parts, including CT-plug screws and CT wiring should be considered live and hazardous!
• If one of the phases is grounded, wire that phase to the Neutral (N) pin on the meter.
• For best communication-performance, ensure that phases wired to L1 and N are the ones that are
• Registers defined for appliances do not appear in the totaling rules. Just defining the registers will
make them appear in the appropriate places (e.g., in the legend of the dashboard graph).
• A single CT is sufficient both for 120Vac and pure 240Vac appliances. 240Vac appliances with asymmetric currents on the two legs (i.e., with a non-zero current on Neutral) require separate CTs per
leg/phase.
April 18, 201818
Page 19
Onset EG4xxx Configuration Guide3 TROUBLESHOOTING
3Troubleshooting
If an installation does not work as expected, we recommend using the channel checker tool to troubleshoot
the problem. This tool is available through “Tools” link in the top right menu of the meter web pages then
click on “Channel Checker” in the left menu. Figure 2 provides an example of what this tool looks like. Note,
the two channel checker tables are displayed vertically one next to the other in the device interface. It is
displayed horizontally on this page for readability.
Figure 2: Example of meter Channel Checker Tool
The channel checker reports the real-time voltages measured for each active voltage probe and currents
for each active CT (If a voltage or a CT is not used by any register, it is deactivated).
RMS (AC) and mean (DC) values for both CTs and voltage inputs are calculated. Frequencies for each
channel input are also calculated and displayed here.
April 18, 201819
Page 20
Onset EG4xxx Configuration Guide3 TROUBLESHOOTING
In addition to the currents and voltages, the page also reports power figure for each component of all
registers. The power figure is accompanied by a power-factor, which is a value between 0 and 1. A value
of 1 indicates a purely resistive load whereas a value of 0 indicates either a purely inductive or purely
capacitive load. An unexpected power factor may be caused by a phase mixup, in which a CT amperage is
applied to an incorrect phase it is not on.
3.1Identify correct phasing
To identify a phase mixup or adequately confirm correct phasing, use a handheld voltmeter set to AC voltage
for the electrical system the meter is monitoring. Connect one probe to the L1 screw terminal of the meter
5-pin power plug, and connect the other probe to the conductor a CT is monitoring. DO NOT make contact
with the 2-pin CT plug, only to the high voltage conductor a CT is monitoring.
If the voltmeter shows phase-to-phase voltage, the probes are on two different phases and the conductor
is not on L1. If the voltmeter shows 0V differential, the probes are on the same phase and the conductor is
on L1.
This process should be repeated for all lines and conductors monitored.
3.2Fixing Leg/Phase Mixups
For installations involving multiple subpanels, it is sometimes not easy to track down which conductor belongs to what leg or phase. If a CT is thought to have been installed on a conductor wired to L1 but actually
was on a conductor wired to L2, the reported power will be wrong. In a split-phase system, the power will
have wrong polarity (negative when it should be positive and vice versa). In a three-phase system, the
power-factor will be significantly lower than expected. Rather than moving the CTs or the CT wiring, it may
be easier to adjust the configuration to match reality. This can be done by adjusting the register definitions
such that the incorrectly installed CT(s) are multiplied by the voltages that they’re actually connected to. If
the polarity of the reported power is correct and the power-factor is close to 1, that usually can be taken as
a sign that the correct phases are being used. It is usually a good idea to temporarily turn off any renewable energy systems to confirm that the polarities and power-factors make sense even when there is no
renewable power.
3.3Fixing CTs Pointing in the Wrong Direction
If a CT accidentally was installed pointing in the wrong direction, its polarity will be reversed (i.e., the power
will read negative when it should be positive and vice versa). Since fixing the installation may be timeconsuming, it is usually easier to adjust the configuration. This can be done easily by adjusting all register
definitions which use the incorrectly installed CT to use the CT value of opposite polarity. For example, if
CT3 was installed incorrectly, change all appearances of CT3 to -CT3 and vice versa.
April 18, 201820
Page 21
Onset EG4xxx Configuration GuideA FORMULA OPERATORS AND FUNCTIONS
AFormula Operators and Functions
The following operators are available in register formulas (in decreasing order of precedence):
Operator:Precedence:Description:
$”r”6The value of register r.
(e)5The value of parenthesized sub-expression e.
−e4The negative of e.
e1∗ e
2
e1/e
2
e1+ e
2
e1− e
2
e1< e
2
e1> e
2
e1<= e
e1>= e
e1= e
e1? e2: e
2
2
2
3
Caveat: Care needs to be taken when comparing floating-point values for equality. Except when comparing
the result of a conditional operator, it is usually better to replace e1= e2with a test of the form abs(e1−e2) <, where is the largest expected error.
3The product e1· e2.
3The quotient e1/e2.
2The sum e1+ e2.
2The difference e1− e2.
11 if e1< e2, 0 otherwise.
11 if e1> e2, 0 otherwise.
11 if e1≤ e2, 0 otherwise.
11 if e1≥ e2, 0 otherwise.
11 if e1= e2, 0 otherwise.
0e2if e1is not 0, e3otherwise.
April 18, 201821
Page 22
Onset EG4xxx Configuration GuideA FORMULA OPERATORS AND FUNCTIONS
The following table describes the list of functions that are available in formula registers using up-to-date
firmware. Please refer to the function documentation on your specific device for the most up-to-date listing
of available functions and full descriptions. This may be found at http://DEV-URL/fundoc.html, where
DEV-URL is is the URL of your eGague device.
Function:Description:
abs(x)Absolute value of x.
max(x,y)The greater value of x and y.
min(x,y)The smaller value of x and y.
mod(x,y)The remainder of dividing x by y.
sqr(x)x2.
sqrt(x)
√
x.
exp(x)10x.
log(x)Common (base-10) logarithm of x.
floor(x)Largest integral value not greater than x.
VAr(r,a)Given real power r and apparent power a, return reactive power.
month()Number of months since January (0 . . . 11).
wday()Number of days since Monday (0. . . 6).
mday()Returns the day of the month (1 . . . 31).
time()Number of hours since midnight (0 .. . 23). Fractional part gives the
part of the hour that has elapsed already, i.e., 0.5 for 30 minutes.
P_PV(i,t,p,c)Given irradiance i, panel temperature t, STC-rated power p, and
pref(”p”)Returns value of preference-setting named p (e.g., "global.pro-
duction.rated").
FFTarg2(f, c, r)Returns phase-angle of the spectral component at frequency f of the
signal at input channel c relative to the reference channel r.
FFTmag(f, c)Returns magnitude of spectral component at frequency f of input
channel c.
P SunPower(i, t, p)Calculates expected power of SunPower array given irradiance i,
panel temperature t and rated power p.
THD(f, c)Returns total harmonic distortion of channel c for fundamental fre-
quency f.
conn qual()Returns connection quality as percentage.
conn tech()Returns the connection technology as an integer.
temp internal()Returns device-internal temperature in degrees centigrade.
isinf(x)Returns 1 if x is positive infinity or -1 if x is negative infinity, or 0
otherwise.
isnan(x)Returns non-zero value if x is Not-a-Number.
P est(J, F, M,..)Returns current estimated average production in Watts given ex-
pected monthly production values (in kWh). J is January, F is February, M is March, and so on for each of the 12 months.
chan(s)Returns channel number for name s. s may be one of ”L1” through
”L3” for voltage inputs, or ”CT1” through ”CT12” for current inputs.
rand()Returns random number in the range from 0 to 1 (inclusive).
ravg(r, n)Calculates the running average of register r over the most recent n
minute interval.
savg(r, n)Calculates the set average of register r over the previous n minute
interval.
April 18, 201822
Page 23
Onset EG4xxx Configuration GuideB PHYSICAL UNIT
BPhysical Unit
The table below lists the various physical units supported by the meter. In this table, column Name lists
the name as it appears in the Web configuration interface (see Section 1.4.4). Column Records shows
the physical quantity the register records and column Unit shows the physical unit that the data is being
recorded with. The meter records data as discrete quantities. Column Res shows the smallest value that
can be recorded by the register and column Max @ 30 yr shows the maximum value that can be recorded
without causing an overflow for a period of at least 30 years. The final column, Code, lists the type-code
used for the register in XML data.
NameRecordsUnitResMax @ 30 yrCode
power [Watts](Real) powerW1W19.4GWP
app. power [VA]Apparent powerVA1VA19.4GVAS
react. power [var]Reactive powervar1var19.4GvarPQ
voltage [V]VoltageV1mV19.4MVV
current [A]CurrentA1mA19.4MAI
freq. [Hz]FrequencyHz1mHz19.4MHzF
irrad. [W/mˆ2](Solar) irradianceW/m21W/m
temp. [C]Temperature
◦
C1m◦C19.4M◦CT
humidity [%]Relative humidity%0.1%194M%h
mass flow [kg/s]Mass flowkg /sg/s19.4Gg/sQ
volumetric
Note: Monetary registers do not have a pre-defined unit. Instead, such values are displayed
using the currency-symbol selected via one of the preference settings, for example $. The resolution for this type is very fine because the cost of electricity per second is generally extremely
low. For example, if the cost of electricity were $0.40/kWh, the cost per Watt-second is only
$0.11µ.
April 18, 201824
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.