Part #: MAN-CSV-A8, Doc #: 7951-C
Installation Instructions
• This product is not intended for life or safety
applications. This product is not intended for
installation in hazardous or classified
locations.
• Potential electrocution hazard exists.
Installing sensors in an energized motor
control center or on any energized conductor
can be hazardous.
• Read instructions thoroughly prior to
installation.
Severe injury or death can result from electrical shock
during contact with high voltage conductors or related
equipment. Disconnect and lock-out all power sources
during installation and service. Applications shown are
suggested means of installing sensors, but it is the
responsibility of the installer to ensure that the
installation is in compliance with all national and local
codes. Installation should be attempted only by
individuals who are familiar with codes, standards, and
proper safety procedures for high-voltage installations.
CSV-A8
Split-Core Adjustable
Current Switch
Onset Computer Corporation
470 MacArthur Blvd.
Bourne, MA 02532
Mailing Address:
P.O. Box 3450
Pocasset, MA 02559-3450
Phone: 1-800-LOGGERS (1-800-564-4377) or 508-759-9500
Fax: 508-759-9100
Email: loggerhelp@onsetcomp.com
www.onsetcomp.com
INSTALLATION
1. Ensure power conductor to be monitored is
disconnected and locked out from the power source!
2. Install the removable mounting bracket to the back
of the electrical enclosure.
3. Snap the split core around the conductor being
monitored and close until the core snaps shut.
4. Connect current switch output to DDC controller or
switched load.
NOTE:
• Contacts are solid state and work just like dry
contacts. When the switch is closed, 1 Ohm is
present. When the switch is open, more than 1
Meg Ohm is present.
5. Calibrate the sensor (see calibration section)
1
WIRING EXAMPLE
contacto
motor
HOBO UX90-001/M, UX90-004/M,
UX120-017/M
fan or pump
CALIBRATION AFTER INSTALLATION
Orient the current switch so the status output terminal is
facing you and follow method (A) (undercurrent) or (B)
(over-current), below. The monitored motor must be
running normally.
A. For under current status indication: (Belt loss,
coupling shear, fan & pump status)
STEP 1: Turn the setpoint screw clockwise until the
Status Closed LED turns off and the Status Open
LED turns on.
STEP 2: Slowly turn the setpoint screw counterclockwise until the Status Closed LED turns on and
the Status Open LED turns off.
STEP 3: Turn the setpoint screw 1/4 turn more
counter-clockwise to create a grace margin.
STEP 4: The sensor is now calibrated to provide
indication of current flows below normal full load
amps.
Output Status:
Normal: Output Closed
Alarm: Output Open
B. For over current status indication: (Locked rotor,
seized impeller)
Part #: MAN-CSV-A8, Doc #: 7951-C
STEP 3: Turn the setpoint screw 1/4 turn more
clockwise to create a grace margin.
STEP 4: The sensor is now calibrated to provide
indication of current flows above normal full load
amps.
Output Status:
Normal: Output Open
Alarm: Output Closed
SPECIFICATIONS
Amperage Range .............. 0.5-175A Continuous
Sensor Supply Voltage ...... Induced from monitored conductor
Isolation ............................. 600VAC rms. (max. voltage when
monitoring an uninsulated
conductor)
Temperature Range .......... -15º to 60ºC
Humidity Range ................. 0-95% non-condensing
Status Output Ratings ....... N.O. 1.0A@30VAC/DC not polarity
sensitive
Off-state Leakage .............. 0 (open switch represents 1+ MEG
ohms of resistance)
Listings .............................. UL508 E150462
TROUBLESHOOTING
1. The unit will not come on at all.
A. Check to be sure that no more than 30VAC/DC or
1.0A has passed through the contact. Voltages or
currents above these levels will damage the unit.
B. Verify that the conductor you are monitoring is
carrying at least 0.5 Amps.
C. Verify that the setpoint is not above operating
amps by turning screw counter-clockwise (up to
20 full turns) until the contacts close (status
closed LED turns on).
STEP 1: Turn the setpoint screw counter-clockwise
until the Status Open LED turns off and the Status
Closed LED turns on. (Sensor should be in this state
right out of the box.)
STEP 2: Slowly turn the setpoint screw clockwise
until the Status Closed LED turns off and the Status
Open LED turns on.
2
2. Set-point screw has no stops. Keeps turning.
A. The 20 turn set-point screw has a slip clutch
which prevents damage at either end. To start the
calibration process over again turn the screw 20
full turns counter-clockwise. This sets the device
in its original and most sensitive position.
Resume calibration from the beginning.
3. Both LEDs are lit.
A. If the setpoint screw has been turned too far to
the right the user will be notified that the current
switch is out of calibration by seeing both LEDs
lit. To correct this, turn the set-point screw 20 full
turns counterclockwise and resume calibration
from the begi
nning.