Automatically cancels up to 3 kΩ (typ) of resistance in series
with remote diode to allow noise filtering
Extended, switchable temperature measurement range
0°C to +127°C (default) or –55°C to +150°C
Pin- and register-compatible with the ADM1032
2-wire SMBus serial interface with SMBus alert support
Two SMBus address versions available:
ADT7461 SMBus address is 0x4C
ADT7461-2 SMBus address is 0x4D
Programmable over/under temperature limits
Offset registers for system calibration
Up to two over temperature fail-safe
Small 8-lead SOIC or8-lead MSOP packages
170 μA operating current, 5.5 μA standby current
APPLICATIONS
Desktop and notebook computers
Industrial controllers
Smart batteries
Embedded systems
Instrumentation
THERM
outputs
Series Resistance Cancellation
ADT7461
GENERAL DESCRIPTION
The ADT74611 is a dual-channel digital thermometer and
under/over temperature alarm intended for use in PCs and
thermal management systems. It is pin- and register-compatible
with the ADM1032. The ADT7461 has three additional
features: series resistance cancellation (where up to 3 kΩ
(typical) of resistance in series with the temperature monitoring
diode may be automatically cancelled from the temperature
result, allowing noise filtering); configurable
and an extended, switchable temperature measurement range.
The ADT7461 can accurately measure the temperature of a
remote thermal diode to ±1°C and the ambient temperature to
±3°C. The temperature measurement range defaults to 0°C to
+127°C, compatible with the ADM1032, but can be switched to
a wider measurement range of −55°C to +150°C. The ADT7461
communicates over a 2-wire serial interface compatible with
system management bus (SMBus) standards. An
signals when the on-chip or remote temperature is out of range.
THERM
The
control of a cooling fan. The
as a second
output is a comparator output that allows on/off
ALERT
output can be reconfigured
THERM
output, if required.
The SMBus address of the ADT7461 is 0x4C. An ADT7461-2
is also available, which uses SMBus Address 0x4D.
1
Protected by U.S. Patents 5,195,827; 5,867,012;5,982,221; 6,097,239;
Changes to the Ordering Guide......................................................22
10/04—Rev. 0 to Rev. A
Change to SMBus Specifications.....................................................4
Changes to Figure 6 and Figure 10 .................................................7
Added Figure 9 and Figure 13 ......................................................... 7
Changes to Temperature Measurement Section .........................10
Changes to Figure 19 and Figure 25 .............................................16
Changes to Serial Bus Interface Section.......................................23
10/03—Revision 0: Initial Version
Rev. 3 | Page 2 of 23 | www.onsemi.com
ADT7461
SPECIFICATIONS
TA = −40°C to +120°C, VDD = 3 V to 5.5 V, unless otherwise noted.
Table 1.
Parameter Min Typ Max Unit Test Conditions
POWER SUPPLY
Supply Voltage, VDD 3.0 3.30 5.5 V
Average Operating Supply Current, IDD 170 215 μA 0.0625 conversions/sec rate1
5.5 10 μA Standby mode, –40°C ≤ TA ≤ +85°C
5.5 20 μA Standby mode, +85°C ≤ TA ≤ +120°C
Undervoltage Lockout Threshold 2.2 2.55 2.8 V VDD input, disables ADC, rising edge
Power-On-Reset Threshold 1 2.5 V
TEMPERATURE-TO-DIGITAL CONVERTER
Local Sensor Accuracy ±1 ±3 °C −40°C ≤ TA ≤ +100°C, 3 V ≤ VDD ≤ 3.6 V
Resolution 1 °C
Remote Diode Sensor Accuracy ±1 °C +60°C ≤ TA ≤ +100°C, −55°C ≤ T
±3 °C −40°C ≤ TA ≤ +120°C, −55°C ≤ T
Resolution 0.25 °C
Remote Sensor Source Current 96 μA High level3
36 μA Middle level3
6 μA Low level3
Conversion Time 32.13 114.6 ms From stop bit to conversion complete (both channels),
one-shot mode with averaging switched on
3.2 12.56 ms One-shot mode with averaging off (that is,
conversion rate = 16, 32, or 64 conversions per second)
Maximum Series Resistance Cancelled 3 kΩ Resistance split evenly on both the D+ and D– inputs
OPEN-DRAIN DIGITAL OUTPUTS
THERM, ALERT/THERM2
(
)
Output Low Voltage, VOL 0.4 V I
High Level Output Leakage Current, IOH 0.1 1 μA V
ALERT
Output Low Sink Current
= −6.0 mA3
OUT
= V
OUT
1 mA
ALERT
3
DD
forced to 0.4 V
SMBus INTERFACE3, 4
Logic Input High Voltage, VIH 2.1 V 3 V ≤ VDD ≤ 3.6 V
SCLK, SDATA
Logic Input Low Voltage, VIL 0.8 V 3 V ≤ VDD ≤ 3.6 V
SCLK, SDATA
Hysteresis 500 mV
SMBus Output Low Sink Current 6 mA SDATA forced to 0.6 V
Logic Input Current, IIH, IIL −1 +1 μA
SMBus Input Capacitance, SCLK, SDATA 5 pF
SMBus Clock Frequency 400 kHz
SMBus Timeout5 25 64 ms User programmable
SCLK Falling Edge to SDATA Valid Time 1 μs Master clocking in data
1
See Table 8 for information on other conversion rates.
2
Guaranteed by characterization, but not production tested.
3
Guaranteed by design, but not production tested.
4
See the SMBUS Timing Specifications section for more information.
5
Disabled by default; see the Serial Bus Interface section for details on enabling it.
2
≤ +150°C, 3 V ≤ VDD ≤ 3.6 V
D
2
≤ +150°C, 3 V ≤ VDD ≤ 5.5 V
D
Rev. 3 | Page 3 of 23 | www.onsemi.com
ADT7461
SMBus TIMING SPECIFICATIONS
Table 2. SMBus Timing Specifications
Parameter Limit at T
f
400 kHz max
SCLK
t
1.3 μs min Clock low period, between 10% points
LOW
t
0.6 μs min Clock high period, between 90% points
HIGH
MIN
and T
tR 300 ns max Clock/data rise time
tF 300 ns max Clock/data fall time
t
600 ns min Start condition setup time
SU; STA
2
t
600 ns min Start condition hold time
HD; STA
3
t
100 ns min Data setup time
SU; DAT
t
300 ns min Data hold time
HD; DAT
4
t
600 ns min Stop condition setup time
SU; STO
t
1.3 μs min Bus free time between stop and start conditions
BUF
1
Guaranteed by design, but not production tested.
2
Time from 10% of SDATA to 90% of SCLK.
3
Time for 10% or 90% of SDATA to 10% of SCLK.
4
Time for 90% of SCLK to 10% of SDATA.
1
Unit Description
MAX
SCLK
SDATA
t
t
HD;DAT
R
t
LOW
t
HD;STA
t
BUF
STOP STARTSTOPSTART
t
F
t
HIGH
t
SU;DAT
Figure 2. Serial Bus Timing
t
SU;STA
t
HD;STA
t
SU;STO
04110-0-001
Rev. 3 | Page 4 of 23 | www.onsemi.com
ADT7461
ABSOLUTE MAXIMUM RATINGS
Table 3.
Parameter Rating
Positive Supply Voltage (VDD) to GND −0.3 V, +5.5 V
D+ −0.3 V to VDD + 0.3 V
D− to GND −0.3 V to +0.6 V
SCLK, SDATA,
THERM
Input Current, SDATA,
Input Current, D− ±1 mA
ESD Rating, All Pins (Human Body Model) 2000 V
Maximum Junction Temperature (TJ max) 150°C
Storage Temperature Range −65°C to +150°C
IR Reflow Peak Temperature 220°C
Pb-Free Parts Only 260°C (±0.5°C)
Lead Temperature (Soldering 10 sec) 300°C
ALERT
THERM
−0.3 V to +5.5 V
−0.3 V to VDD + 0.3 V
−1 mA, +50 mA
THERMAL CHARACTERISTICS
8-lead SOIC package
θ
= 121°C/W
JA
8-lead MSOP package
= 142°C/W
θ
JA
Stresses above those listed under Absolute Maximum Ratings
may cause permanent damage to the device. This is a stress
rating only; functional operation of the device at these or any
other conditions above those indicated in the operational
section of this specification is not implied. Exposure to absolute
maximum rating conditions for extended periods may affect
device reliability.
ESD CAUTION
ESD (electrostatic discharge) sensitive device. Electrostatic charges as high as 4000 V readily accumulate on the
human body and test equipment and can discharge without detection. Although this product features
proprietary ESD protection circuitry, permanent damage may occur on devices subjected to high energy
electrostatic discharges. Therefore, proper ESD precautions are recommended to avoid performance
degradation or loss of functionality.
Rev. 3 | Page 5 of 23 | www.onsemi.com
ADT7461
PIN CONFIGURATION AND FUNCTION DESCRIPTIONS
V
THERM
DD
D+
D–
1
2
ADT7461
TOP VIEW
3
(Not to Scale)
4
SCLK
8
SDATA
7
ALERT/THERM2
6
GND
5
04110-0-013
Figure 3. Pin Configuration
Table 4. Pin Function Descriptions
Pin No. Mnemonic Description
1 VDD Positive Supply, 3 V to 5.5 V.
2 D+ Positive Connection to Remote Temperature Sensor.
3 D− Negative Connection to Remote Temperature Sensor.
4
THERM
Open-drain output that can be used to turn a fan on/off or throttle a CPU clock in the event of an
overtemperature condition. Requires pull-up to V
.
DD
5 GND Supply Ground Connection.
/
THERM2
6
ALERT
Open-Drain Logic Output Used as Interrupt or SMBus Alert. This may also be configured as a second
Figure 15. Temperature Error vs. Series Resistance
04110-0-023
Rev. 3 | Page 8 of 23 | www.onsemi.com
ADT7461
FUNCTIONAL DESCRIPTION
The ADT7461 is a local and remote temperature sensor and
over/under temperature alarm, with the added ability to automatically cancel the effect of 3 kΩ (typical) of resistance in
series with the temperature monitoring diode. When the
ADT7461 is operating normally, the on-board ADC operates
in a free-running mode. The analog input multiplexer
alternately selects either the on-chip temperature sensor to
measure its local temperature or the remote temperature sensor.
The ADC digitizes these signals and the results are stored in the
local and remote temperature value registers.
The local and remote measurement results are compared with
the corresponding high, low, and
stored in eight on-chip registers. Out-of-limit comparisons
generate flags that are stored in the status register. A result that
exceeds the high temperature limit, the low temperature limit,
or an external diode fault causes the
low. Exceeding
THERM
output to assert low. The
as a second
THERM
temperature limits causes the
ALERT
output.
The limit registers can be programmed and the device controlled and configured via the serial SMBus. The contents
of any register can also be read back via the SMBus.
Control and configuration functions consist of switching the
device between normal operation and standby mode, selecting
the temperature measurement scale, masking or enabling the
ALERT
output, switching Pin 6 between
and selecting the conversion rate.
SERIES RESISTANCE CANCELLATION
Parasitic resistance to the D+ and D− inputs to the ADT7461,
seen in series with the remote diode, is caused by a variety of
factors, including PCB track resistance and track length. This
series resistance appears as a temperature offset in the remote
sensor’s temperature measurement. This error typically causes
a 0.5°C offset per ohm of parasitic resistance in series with the
remote diode.
The ADT7461 automatically cancels out the effect of this series
resistance on the temperature reading, giving a more accurate
result, without the need for user characterization of this resistance. The ADT7461 is designed to automatically cancel typically
up to 3 kΩ of resistance. By using an advanced temperature
measurement method, this is transparent to the user. This
feature allows resistances to be added to the sensor path to
produce a filter, allowing the part to be used in noisy environments. See the Noise Filtering section for more details.
THERM
temperature limits,
ALERT
output to assert
THERM
output can be reprogrammed
ALERT
and
THERM2
,
TEMPERATURE MEASUREMENT METHOD
A simple method of measuring temperature is to exploit the
negative temperature coefficient of a diode by measuring the
base-emitter voltage (V
current. However, this technique requires calibration to null out
the effect of the absolute value of V
to device.
The technique used in the ADT7461 is to measure the change
when the device is operated at three different currents.
in V
BE
Previous devices have used only two operating currents, but it is
the use of a third current that allows automatic cancellation of
resistances in series with the external temperature sensor.
Figure 16 shows the input signal conditioning used to measure
the output of an external temperature sensor. This figure shows
the external sensor as a substrate transistor, but it could equally
be a discrete transistor. If a discrete transistor is used, the collector will not be grounded and should be linked to the base. To
prevent ground noise interfering with the measurement, the
more negative terminal of the sensor is not referenced to
ground, but is biased above ground by an internal diode at the
D− input. C1 may be added as a noise filter (a recommended
maximum value of 1,000 pF). However, a better option in noisy
environments is to add a filter, as described in the Noise
Filtering section. See the Layout Considerations section for
more information on C1.
To m e as u re Δ V
BE
switched among three related currents. Figure 16 shows
N1 × I and N2 × I as different multiples of the current, I. The
currents through the temperature diode are switched between
I and N1 × I, giving ΔV
giving ΔV
two ΔV
. The temperature may then be calculated using the
BE2
measurements. This method can also be shown to
BE
cancel the effect of any series resistance on the temperature
measurement.
The resulting ΔV
low-pass filter to remove noise and then to a chopper-stabilized
amplifier. This amplifies and rectifies the waveform to produce
a dc voltage proportional to ΔV
age and a temperature measurement is produced. To reduce the
effects of noise, digital filtering is performed by averaging the
results of 16 measurement cycles for low conversion rates. At
rates of 16, 32, and 64 conversions per second, no digital
averaging takes place.
Signal conditioning and measurement of the internal temperature sensor is performed in the same manner.
) of a transistor operated at constant
BE
, which varies from device
BE
, the operating current through the sensor is
, and then between I and N2 × I,
BE1
waveforms are passed through a 65 kHz
BE
. The ADC digitizes this volt-
BE
Rev. 3 | Page 9 of 23 | www.onsemi.com
ADT7461
I
N1
×IN2×I
D+
REMOTE
SENSING
TRANSISTOR
C1*
D–
*CAPACITOR C1 IS OPTIONAL. IT SHOULD ONLY BE USED IN NOISY ENVIRONMENTS.
BIAS
DIODE
Figure 16. Input Signal Conditioning
TEMPERATURE MEASUREMENT RESULTS
The results of the local and remote temperature measurements
are stored in the local and remote temperature value registers
and are compared with limits programmed into the local and
remote high and low limit registers.
The local temperature value is in Register 0x00 and has a
resolution of 1°C. The external temperature value is stored in
two registers, with the upper byte in Register 0x01 and the
lower byte in Register 0x10. Only the two MSBs in the external
temperature low byte are used. This gives the external
temperature measurement a resolution of 0.25°C. Table 5 shows
the data format for the external temperature low byte.
Table 5. Extended Temperature Resolution (Remote
Temperature Low Byte)
Extended Resolution Remote Temperature Low Byte
0.00°C 0 000 0000
0.25°C 0 100 0000
0.50°C 1 000 0000
0.75°C 1 100 0000
When reading the full external temperature value, both the high
and low byte, the two registers should be read in succession.
Reading one register does not lock the other, so both should be
read before the next conversion finishes. In practice, there is
more than enough time to read both registers, as transactions
over the SMBus are significantly faster than a conversion time.
TEMPERATURE MEASUREMENT RANGE
The temperature measurement range for both internal and
external measurements is, by default, 0°C to +127°C. However,
the ADT7461 can be operated using an extended temperature
range. It can measure the full temperature range of an external
diode, from −55°C to +150°C. The user can switch between
these two temperature ranges by setting or clearing Bit 2 in the
configuration register. A valid result is available in the next
measurement cycle after changing the temperature range.
In extended temperature mode, the upper and lower temperature that can be measured by the ADT7461 is limited by the
remote diode selection. The temperature registers themselves
can have values from −64°C to +191°C. However, most
temperature sensing diodes have a maximum temperature
I
BIAS
LOW-PASS FILTER
f
= 65kHz
C
range of −55°C to +150°C.
Above 150°C, they may lose their semiconductor characteristics
and approximate conductors instead. This results in a diode
short. In this case, a read of the temperature result register gives
the last good temperature measurement. The user should be
aware that the temperature measurement on the external channel
may not be accurate for temperatures that are outside the
operating range of the remote sensor.
While both local and remote temperature measurements can be
made while the part is in extended temperature mode, the
ADT7461 itself should not be exposed to temperatures greater than
those specified in the Absolute Maximum Ratings section. Also,
the device is guaranteed to operate only as specified at ambient
temperatures from −40°C to +120°C.
TEMPERATURE DATA FORMAT
The ADT7461 has two temperature data formats. When the
temperature measurement range is from 0°C to +127°C
(default), the temperature data format for both internal and
external temperature results is binary. When the measurement
range is in extended mode, an offset binary data format is used
for both internal and external results. Temperature values in the
offset binary data format are offset by 64°C. Examples of temperatures in both data formats are shown in Table 6.
Table 6. Temperature Data Format (Local and Remote
Temperature High Byte)
Offset binary scale temperature values are offset by 64°C.
2
Binary scale temperature measurement retur ns 0°C for all temperatures < 0°C.
3
Binary scale temperature measurement returns 127°C for all temperatures > 127°C.
V
DD
V
OUT+
TO ADC
V
OUT–
04110-0-002
Rev. 3 | Page 10 of 23 | www.onsemi.com
ADT7461
The user can switch between measurement ranges at any time.
Switching the range also switches the data format. The next
temperature result following the switching is reported back to
the register in the new format. However, the contents of the
limit registers are not changed. The user must ensure that the
limit registers are reprogrammed, as necessary, when the data
format changes. See the Limit Registers section for more
information.
ADT7461 REGISTERS
The ADT7461 contains a total of 22 8-bit registers. These registers are used to store the results of remote and local temperature
measurements and high and low temperature limits and to
configure and control the device. A description of these registers
follows. Additional details are provided in Table 7 to Table 11.
Address Pointer Register
The address pointer register does not have or require an
address, as the first byte of every write operation is automatically written to this register. The data in this first byte always
contains the address of another register on the ADT7461, which
is stored in the address pointer register. This register address is
written to by the second byte of a write operation or is used for
a subsequent read operation.
The power-on default value of the address pointer register is
0x00. Therefore, if a read operation is performed immediately
after power-on, without first writing to the address pointer, the
value of the local temperature is returned, since its register
address is 0x00.
Temperature Value Registers
The ADT7461 has three registers to store the results of local and
remote temperature measurements. These registers can only be
written to by the ADC and can be read by the user over the
SMBus. The local temperature value register is at Address 0x00.
The external temperature value high byte register is at
Address 0x01, with the low byte register at Address 0x10.
The power-on default for all three registers is 0x00.
Configuration Register
The configuration register is Address 0x03 at read and
Address 0x09 at write. Its power-on default is 0x00. Only four
bits of the configuration register are used. Bits 0, 1, 3, and 4 are
reserved and should not be written to by the user.
Bit 7 of the configuration register is used to mask the
ALERT
output. If Bit 7 is 0, the
power-on default. If Bit 7 is set to 1, the
output is enabled. This is the
ALERT
disabled. This only applies if Pin 6 is configured as
Pin 6 is configured as
THERM2
, the value of Bit 7 has no effect.
ALERT
output is
ALERT
. If
If Bit 6 is set to 0 (the power-on default), the device is in
operating mode with the ADC converting. If Bit 6 is set to 1, the
device is in standby mode and the ADC does not convert. The
SMBus does, however, remain active in standby mode, so values
can be read from or written to the ADT7461 via the SMBus in
this mode. The
ALERT
and
THERM
outputs are also active in
standby mode. Changes made to the registers in standby mode
that affect the
THERM
or
ALERT
outputs cause these signals to
be updated.
Bit 5 determines the configuration of Pin 6 on the ADT7461. If
Bit 5 is 0 (default), then Pin 6 is configured as an
output. If Bit 5 is 1, then Pin 6 is configured as a
ALERT
output. Bit 7, the
configured as an
mask bit, is only active when Pin 6 is
ALERT
output. If Pin 6 is set up as a
ALERT
THERM2
THERM2
output, then Bit 7 has no effect.
Bit 2 sets the temperature measurement range. If Bit 2 is 0
(default), the temperature measurement range is set between
0°C to +127°C. Setting Bit 2 to 1 means that the measurement
range is set to the extended temperature range.
Table 7. Configuration Register Bit Assignments
Power-On
Bit Name Function
ALERT
7 MASK1
6 RUN/STOP
ALERT/THERM2
5
4, 3 Reserved 0
Temperature
2
Range Select
1, 0 Reserved 0
0 =
1 =
0 = Run
1 = Standby
0 =
1 =
0 = 0°C to 127°C
1 = Extended range
enabled
ALERT
masked
ALERT
THERM2
Default
0
0
0
0
Conversion Rate Register
The conversion rate register is Address 0x04 at read and
Address 0x0A at write. The lowest four bits of this register are
used to program the conversion rate by dividing the internal
oscillator clock by 1, 2, 4, 8, 16, 32, 64, 128, 256, 512, or 1024 to
give conversion times from 15.5 ms (Code 0x0A) to 16 seconds
(Code 0x00). For example, a conversion rate of 8 conversions
per second means that beginning at 125 ms intervals, the device
performs a conversion on the internal and external temperature
channels.
This register can be written to and read back over the SMBus.
The higher four bits of this register are unused and must be set
to 0. The default value of this register is 0x08, giving a rate of
16 conversions per second. Use of slower conversion times
greatly reduces the device power consumption, as shown in
The ADT7461 has eight limit registers: high, low, and
temperature limits for both local and remote temperature
measurements. The remote temperature high and low limits
span two registers each to contain an upper and lower byte for
each limit. There is also a
THERM
registers can be written to and read back over the SMBus. See
Table 12 for address details of the limit registers and their
power-on default values.
When Pin 6 is configured as an
ALERT
registers perform a > comparison while the low limit registers
perform a ≤ comparison. For example, if the high limit register
is programmed with 80°C, then measuring 81°C results in an
out-of-limit condition, setting a flag in the status register. If the
low limit register is programmed with 0°C, measuring 0°C or
lower results in an out-of-limit condition.
Exceeding either the local or remote
THERM
low. When Pin 6 is configured as
either the local or remote high limit asserts
default hysteresis value of 10°C is provided that applies to both
THERM
channels. This hysteresis value may be reprogrammed
to any value after power-up (Register Address 0x21).
It is important to remember that the temperature limits data
format is the same as the temperature measurement data
format. So, if the temperature measurement uses default binary,
the temperature limits also use the binary scale. If the
temperature measurement scale is switched, however, the
temperature limits do not switch automatically. The user must
reprogram the limit registers to the desired value in the correct
data format. For example, if the remote low limit is set at 10°C
and the default binary scale is being used, the limit register
value should be 0000 1010b. If the scale is switched to offset
binary, the value in the low temperature limit register should be
reprogrammed to be 0100 1010b.
Status Register
The status register is a read-only register at Address 0x02. It
μA Typ at VDD = 5.5 V
THERM
hysteresis register. All limit
output, the high limit
THERM
limit asserts
THERM2
THERM2
, exceeding
low. A
contains status information for the ADT7461.
Bit 7 of the status register indicates the ADC is busy converting
when it is high. The other bits in this register flag the out-oflimit temperature measurements (Bits 6 to 3 and Bits 1 to 0) and
the remote sensor open circuit (Bit 2).
If Pin 6 is configured as an
ALERT
output, the following applies. If
the local temperature measurement exceeds its limits, Bit 6 (high
limit) or Bit 5 (low limit) of the status register asserts to flag this
condition. If the remote temperature measurement exceeds its
limits, then Bit 4 (high limit) or Bit 3 (low limit) asserts. Bit 2
asserts to flag an open-circuit condition on the remote sensor.
These five flags are NOR’d together so if any of them is high, the
ALERT
interrupt latch is set and the
ALERT
output goes low.
Reading the status register clears the five flags, Bits 6 to 2, provided the error conditions causing the flags to be set have gone
away. A flag bit can be reset only if the corresponding value
register contains an in-limit measurement or if the sensor is
good.
ALERT
The
register. It resets when the
interrupt latch is not reset by reading the status
ALERT
output has been serviced by
the master reading the device address, provided the error
condition has gone away and the status register flag bits are
reset.
When Flag 1 and/or Flag 0 are set, the
THERM
output goes low
to indicate the temperature measurements are outside the
programmed limits. The
reset, unlike the
ALERT
THERM
output does not need to be
output. Once the measurements are
within the limits, the corresponding status register bits are reset
automatically and the
add hysteresis by programming Register 0x21. The
THERM
output goes high. The user may
THERM
output is reset only when the temperature falls to limit value
minus hysteresis value.
When Pin 6 is configured as
THERM2
, only the high temperature limits are relevant. If Flag 6 and/or Flag 4 are set, the
THERM2
output goes low to indicate the temperature
measurements are outside the programmed limits. Flag 5 and
Flag 3 have no effect on
otherwise the same as
THERM2
THERM
. The behavior of
.
THERM2
is
Table 9. Status Register Bit Assignments
Bit Name Function
7 BUSY 1 when ADC is converting
6 LHIGH1 1 when local high temperature limit is tripped
5 LLOW1 1 when local low temperature limit is tripped
4 RHIGH1 1 when remote high temperature limit is tripped
3 RLOW1 1 when remote low temperature limit is tripped
2 OPEN1 1 when remote sensor is an open circuit
1 RTHRM
0 LTHRM
1
These flags stay high until the status register is read or they are reset by POR.
1 when remote
1 when local
THERM
THERM
limit is tripped
limit is tripped
Rev. 3 | Page 12 of 23 | www.onsemi.com
ADT7461
Offset Register
Offset errors may be introduced into the remote temperature
measurement by clock noise or by the thermal diode being
located away from the hot spot. To achieve the specified
accuracy on this channel, these offsets must be removed.
The offset value is stored as a 10-bit, twos complement value in
Registers 0x11 (high byte) and 0x12 (low byte, left justified).
Only the upper 2 bits of Register 0x12 are used. The MSB of
Register 0x11 is the sign bit. The minimum offset that can be
programmed is −128°C, and the maximum is +127.75°C. The
value in the offset register is added to the measured value of the
remote temperature.
The offset register powers up with a default value of 0°C and
has no effect unless the user writes a different value to it.
The one-shot register is used to initiate a conversion and
comparison cycle when the ADT7461 is in standby mode, after
which the device returns to standby. Writing to the one-shot
register address (0x0F) causes the ADT7461 to perform a
conversion and comparison on both the internal and the
external temperature channels. This is not a data register as
such; the write operation to Address 0x0F causes the one-shot
conversion. The data written to this address is irrelevant and is
not stored.
Table 12. List of Registers
Read Address (Hex) Write Address (Hex) Name Power-On Default
Not applicable Not applicable Address Pointer Undefined
0x00 Not applicable Local Temperature Value 0000 0000 (0x00)
0x01 Not applicable External Temperature Value High Byte 0000 0000 (0x00)
0x02 Not applicable Status Undefined
0x03 0x09 Configuration 0000 0000 (0x00)
0x04 0x0A Conversion Rate 0000 1000 (0x08)
0x05 0x0B Local Temperature High Limit 0101 0101 (0x55) (85°C)
0x06 0x0C Local Temperature Low Limit 0000 0000 (0x00) (0°C)
0x07 0x0D External Temperature High Limit High Byte 0101 0101 (0x55) (85°C)
0x08 0x0E External Temperature Low Limit High Byte 0000 0000 (0x00) (0°C)
Not applicable 0x0F1 One-Shot
0x10 Not applicable External Temperature Value Low Byte 0000 0000
0x11 0x11 External Temperature Offset High Byte 0000 0000
0x12 0x12 External Temperature Offset Low Byte 0000 0000
0x13 0x13 External Temperature High Limit Low Byte 0000 0000
0x14 0x14 External Temperature Low Limit Low Byte 0000 0000
0x19 0x19
0x20 0x20
0x21 0x21
0x22 0x22
0xFE Not applicable Manufacturer ID 0100 0001 (0x41)
0xFF Not applicable Die Revision Code 0101 0001 (0x51)
1
Writing to Address 0x0F causes the ADT7461 to perform a single measurement. It is not a data register; therefore, data written to it is irrelevant.
THERM
External
THERM
Local
THERM
Hysteresis
Consecutive
Consecutive ALERT Register
The value written to this register determines how many out-oflimit measurements must occur before an
ALERT
is generated.
The default value is that one out-of-limit measurement
generates an
ALERT
. The maximum value that can be chosen is
4. The purpose of this register is to allow the user to perform
some filtering of the output. This is particularly useful at the
fastest three conversion rates, where no averaging takes place.
This register is at Address 0x22.
Table 11. Consecutive ALERT
Register Bit
Number of Out-of-Limit
Register Value1, 2
Measurements Required
yxxx 000x 1
yxxx 001x 2
yxxx 011x 3
yxxx 111x 4
1
x = don’t care bit.
2
y = SMBus timeout bit; default = 0. See the Serial Bus Interface section.
Limit
Limit
ALERT
0110 1100 (0x55) (85°C)
0101 0101 (0x55) (85°C)
0000 1010 (0x0A) (10°C)
0000 0001 (0x01)
Rev. 3 | Page 14 of 23 | www.onsemi.com
ADT7461
SERIAL BUS INTERFACE
Control of the ADT7461 is carried out via the serial bus. The
ADT7461 is connected to this bus as a slave device, under the
control of a master device.
After a conversion sequence completes, there should be no
SMBus transactions to the ADT7461 for at least one conversion
time, to allow the next conversion to complete. The conversion
time depends on the value programmed in the conversion rate
register.
The ADT7461 has an SMBus timeout feature. When this is
enabled, the SMBus times out typically after 25 ms of inactivity.
However, this feature is not enabled by default. Bit 7 of the
consecutive alert register (Address = 0x22) should be set to
enable it.
Consult the SMBus 1.1 specification for more information
(www.smbus.org).
ADDRESSING THE DEVICE
In general, every SMBus device has a 7-bit device address,
except for some devices that have extended 10-bit addresses.
When the master device sends a device address over the bus,
the slave device with that address responds. The ADT7461 is
available with one device address, 0x4C (1001 100b). The
ADT7461-2 is also available with one device address, 0x4D
(1001 101b)
The serial bus protocol operates as follows:
1. The master initiates data transfer by establishing a start
condition, defined as a high-to-low transition on the serial
data line SDATA, while the serial clock line SCLK remains
high. This indicates that an address/data stream will follow.
All slave peripherals connected to the serial bus respond to
the start condition and shift in the next eight bits, consisting of a 7-bit address (MSB first) plus an R/
determines the direction of the data transfer, that is,
whether data will be written to or read from the slave
device. The peripheral whose address corresponds to the
transmitted address responds by pulling the data line low
during the low period before the ninth clock pulse, known
as the acknowledge bit. All other devices on the bus now
remain idle while the selected device waits for data to be
read from or written to it. If the R/
writes to the slave device. If the R/
reads from the slave device.
W
W
W
bit, which
bit is a 0, the master
bit is a 1, the master
2. Data is sent over the serial bus in a sequence of nine clock
pulses, eight bits of data followed by an acknowledge bit
from the slave device. Transitions on the data line must
occur during the low period of the clock signal and remain
stable during the high period, since a low-to-high transition
when the clock is high may be interpreted as a stop signal.
The number of data bytes that can be transmitted over the
serial bus in a single read or write operation is limited only
by what the master and slave devices can handle.
3. When all data bytes have been read or written, stop condi-
tions are established. In write mode, the master pulls the
data line high during the tenth clock pulse to assert a stop
condition. In read mode, the master device overrides the
acknowledge bit by pulling the data line high during the
low period before the ninth clock pulse. This is known as
a no acknowledge. The master then takes the data line low
during the low period before the tenth clock pulse, then
high during the tenth clock pulse to assert a stop condition.
Any number of bytes of data may be transferred over the serial
bus in one operation, but it is not possible to mix read and write
in one operation because the type of operation is determined at
the beginning and cannot subsequently be changed without
starting a new operation. With the ADT7461, write operations
contain either one or two bytes, while read operations contain
one byte.
To write data to one of the device data registers or to read data
from it, the address pointer register must be set so that the
correct data register is addressed. The first byte of a write
operation always contains a valid address that is stored in the
address pointer register. If data is to be written to the device, the
write operation contains a second data byte that is written to the
register selected by the address pointer register.
This is illustrated in Figure 17. The device address is sent over
the bus followed by R/
bytes. The first data byte is the address of the internal data
register to be written to, which is stored in the address pointer
register. The second data byte is the data to be written to the
internal data register. The examples shown in Figure 17 to
Figure 19 use the ADT7461 SMBus Address 0x4C.
W
set to 0. This is followed by two data
Rev. 3 | Page 15 of 23 | www.onsemi.com
ADT7461
A
S
A
S
A
1919
SCLK
SDAT
START BY
MASTER
A6
A5A4A3A2A1A0R/WD7
FRAME 1
SERIAL BUS ADDRESS BYTE
SCLK (CONTINUED)
SDATA (CONTINUED)
ACK. BY
ADT7461
D7D6D5D4D3
D6D5D4D3D2D1D0
ADDRESS POINTER REGISTER BYTE
FRAME 2
FRAME 3
DATA BYTE
D2
D1D0
ACK. BY
ADT7461
91
ACK. BY
ADT7461
STOP BY
MASTER
04110-0-003
Figure 17. Writing a Register Address to the Address Pointer Register, then Writing Data to the Selected Register
1919
SCLK
DAT
A6A5A4A3A2A1A0 R/WD7D6D5D4D3D2D1D0
START BY
MASTER
FRAME 1
SERIAL BUS ADDRESS BYTE
ACK. BY
ADT7461
ADDRESS POINTER REGISTER BYTE
FRAME 2
ACK. BY
ADT7461
STOP BY
MASTER
04110-0-004
Figure 18. Writing to the Address Pointer Register Only
191 9
SCLK
DAT
START BY
MASTER
A6A5A4A3A2A1A0R/WD7D6D5D4D3D2D1D0
ACK. BY
FRAME 1
SERIAL BUS ADDRESS BYTE
ADT7461
Figure 19. Reading from a Previously Selected Register
When reading data from a register there are two possibilities.
1. If the ADT7461’s address pointer register value is unknown
or not the desired value, it is necessary to set it to the
correct value before data can be read from the desired data
register. This is done by writing to the ADT7461 as before,
but only the data byte containing the register read address
is sent, since data is not to be written to the register. This is
shown in Figure 18.
A read operation is then performed consisting of the serial
bus address, R/
W
bit set to 1, followed by the data byte
read from the data register. This is shown in Figure 19.
2. If the address pointer register is known to be at the desired
address, data can be read from the corresponding data
register without first writing to the address pointer register
FRAME 2
DATA BYTE FROM ADT7461
NACK. BY
MASTER
STOP BY
MASTER
04110-0-005
and the bus transaction shown in Figure 18 can be omitted.
Although it is possible to read a data byte from a data register
without first writing to the address pointer register, if the
address pointer register is already at the correct value, it is not
possible to write data to a register without writing to the
address pointer register because the first data byte of a write is
always written to the address pointer register.
Also, some of the registers have different addresses for read and
write operations. The write address of a register must be written
to the address pointer if data is to be written to that register, but
it may not be possible to read data from that address. The read
address of a register must be written to the address pointer
before data can be read from that register.
Rev. 3 | Page 16 of 23 | www.onsemi.com
ADT7461
ALERT
This is applicable when Pin 6 is configured as an
output. The
OUTPUT
ALERT
ALERT
output goes low whenever an out-of-limit
measurement is detected, or if the remote temperature sensor is
open circuit. It is an open-drain output and requires a pull-up
to V
. Several
DD
the common line goes low if one or more of the
ALERT
outputs can be wire-ORed together, so
ALERT
outputs
goes low.
ALERT
The
processor, or it may be used as an
output can be used as an interrupt signal to a
SMBALERT
. Slave devices on
the SMBus cannot normally signal to the bus master that they
want to talk, but the
One or more
SMBALERT
SMBALERT
line that is connected to the master. When the
line is pulled low by one of the devices, the
SMBALERT
ALERT
outputs can be connected to a common
function allows them to do so.
procedure shown in Figure 20 occurs.
MASTER
RECEIVES
SMBALERT
SMBALERT
1.
ALERT RESPONSE
ADDRESS
MASTER SENDS
ARA AND READ
COMMAND
Figure 20. Use of SMBALERT
is pulled low.
RDSTARTACK
DEVICE
ADDRESSNOACK
DEVICE SENDS
ITS ADDRESS
STOP
2. Master initiates a read operation and sends the alert
response address (ARA = 0001 100). This is a general call
address that must not be used as a specific device address.
3. The device whose
ALERT
output is low responds to the
alert response address and the master reads its device
address. As the device address is seven bits, an LSB of 1 is
added. The address of the device is now known and can be
interrogated in the usual way.
ALERT
4. If the
output is low on more than one device, the
one with the lowest device address has priority, in
accordance with normal SMBus arbitration.
5. Once the ADT7461 has responded to the alert response
ALERT
address, it resets its
condition that caused the
SMBALERT
line remains low, the master sends the ARA
output, provided the error
ALERT
no longer exists. If the
again; this sequence continues until all devices whose
ALERT
out-puts were low have responded.
04110-0-006
LOW POWER STANDBY MODE
The ADT7461 can be put into low power standby mode by setting Bit 6 of the configuration register. When Bit 6 is low, the
ADT7461 operates normally. When Bit 6 is high, the ADC is
inhibited, and any conversion in progress is terminated without
writing the result to the corresponding value register.
The SMBus is still enabled. Power consumption in the standby
mode is reduced to less than 10 μA if there is no SMBus activity
or 100 μA if there are clock and data signals on the bus.
When the device is in standby mode, it is still possible to initiate
a one-shot conversion of both channels by writing to the oneshot register (Address 0x0F), after which the device returns to
standby. It does not matter what is written to the one-shot
register, as all data written to it is ignored. It is also possible to
write new values to the limit register while in standby mode. If
the values stored in the temperature value registers are now
outside the new limits, an
ALERT
is generated even though the
ADT7461 is still in standby.
SENSOR FAULT DETECTION
At its D+ input, the ADT7461 contains internal sensor fault
detection circuitry. This circuit can detect situations where an
external remote diode is either not connected or incorrectly
connected to the ADT7461. A simple voltage comparator trips
if the voltage at D+ exceeds V
−1 V (typical), signifying an
DD
open circuit between D+ and D−. The output of this
comparator is checked when a conversion is initiated. Bit 2 of
the status register (open flag) is set if a fault is detected. If the
ALERT
pin is enabled, setting this flag causes
ALERT
to assert
low.
If the user does not wish to use an external sensor with the
ADT7461, then to prevent continuous setting of the OPEN flag,
the user should tie the D+ and D− inputs together.
THE ADT7461 INTERRUPT SYSTEM
The ADT7461 has two interrupt outputs,
Both have different functions and behavior.
ALERT
ALERT
and responds to violations of software-programmed temperature limits or an open-circuit fault on the external diode.
THERM
is intended as a fail-safe interrupt output that cannot
be masked.
If the external or local temperature exceeds the programmed
high temperature limits or equals or exceeds the low temperature limits, the
fault on the external diode also causes
ALERT
output is asserted low. An open-circuit
ALERT
to assert.
is reset when serviced by a master reading its device address,
provided the error condition has gone away and the status
register has been reset.
THERM
The
ture exceeds the programmed
output asserts low if the external or local tempera-
THERM
limits.
temperature limits should normally be equal to or greater than
and
is maskable
THERM
THERM
ALERT
.
Rev. 3 | Page 17 of 23 | www.onsemi.com
ADT7461
T
the high temperature limits.
when the temperature falls back within the
external limit is set by default to 85°C, as is the local
limit. A hysteresis value can be programmed so that
resets when the temperature falls to the limit value minus the
hysteresis value. This applies to both local and remote
measurement channels. The power-on hysteresis default value is
10°C, but this may be reprogrammed to any value after powerup.
The hysteresis loop on the
THERM
is used for on/off control of a fan. The user’s system
can be set up so that when
switched on to cool the system. When
the fan can be switched off. Programming an hysteresis value
protects from fan jitter where the temperature hovers around
THERM
the
Table 13. THERM
THERM
limit, and the fan is constantly being switched.
Hysteresis
Hysteresis
0°C 0 000 0000
1°C 0 000 0001
10°C 0 000 1010
Figure 21 shows how the
A user may choose to use the
to signal to the host via the SMBus that the temperature has
risen. The user could use the
cool the system, if the temperature continues to increase. This
method would ensure there is a fail-safe mechanism to cool the
system without the need for host intervention.
EMPERATURE
100°C
90°C
80°C
70°C
60°C
50°C
40°C
ALERT
THERM
1
Figure 21. Operation of the ALERT
1. If the measured temperature exceeds the high temperature
limit, the
ALERT
2. If the temperature continues to increase and exceeds the
THERM
limit, the
used to throttle the CPU clock or switch on a fan.
THERM
THERM
THERM
is reset automatically
outputs is useful when
asserts, a fan can be
THERM
Binary Representation
THERM
ALERT
THERM
ALERT
and
output as an
output to turn on a fan to
32
and THERM Interrupts
output asserts low.
THERM
output asserts low. This can be
THERM
limit. The
THERM
THERM
goes high again,
outputs operate.
SMBALERT
THERM LIMIT
THERM LIMIT-HYSTERESIS
HIGH TEMP LIMIT
RESET BY MASTER
4
04110-0-007
default hysteresis value of 10°C is shown in Figure 21.
4. The
ALERT
output deasserts only when the temperature
falls below the high temperature limit, and the master has
read the device address and cleared the status register.
ALERT
Pin 6 on the ADT7461 can be configured as either an
output or as an additional
THERM
output.
THERM2
asserts
low when the temperature exceeds the programmed local
and/or remote high temperature limits. It is reset in the same
manner as
hysteresis value applies to
Figure 22 shows how
THERM
, and it is not maskable. The programmed
THERM2
THERM
and
also.
THERM2
might operate
together to implement two methods of cooling the system. In
this example, the
THERM
limits. The
THERM2
THERM2
limits are set lower than the
output could be used to turn on
a fan. If the temperature continues to rise and exceeds the
THERM
limits, the
THERM
output could provide additional
cooling by throttling the CPU.
TEMPERATURE
90°C
80°C
70°C
60°C
50°C
40°C
30°C
THERM2
THERM
1. When the
1
Figure 22. Operation of the THERM
THERM2
3
2
limit is exceeded, the
4
and THERM2 Interrupts
THERM LIMIT
THERM2 LIMIT
THERM2
signal
04110-0-008
asserts low.
2. If the temperature continues to increase and exceeds the
THERM
3. The
limit, the
THERM
temperature falls to
hysteresis value is shown in Figure 22.
THERM
output asserts low.
output deasserts (goes high) when the
THERM
limit minus hysteresis. No
4. As the system continues to cool and the temperature falls
below the
THERM2
limit, the
Again, no hysteresis value is shown for
THERM2
signal resets.
THERM2
.
Both the external and internal temperature measurements cause
THERM
and
THERM2
to operate as described.
3. The
THERM
output deasserts (goes high) when the
temperature falls to
THERM
limit minus hysteresis. The
Rev. 3 | Page 18 of 23 | www.onsemi.com
ADT7461
T
APPLICATION INFORMATION
Noise Filtering
For temperature sensors operating in noisy environments, the
industry standard practice was to place a capacitor across the
D+ and D− pins to help combat the effects of noise. However,
large capacitances affect the accuracy of the temperature
measurement, leading to a recommended maximum capacitor
value of 1,000 pF. While this capacitor reduces the noise, it does
not eliminate it, making it difficult to use the sensor in a very
noisy environment.
The ADT7461 has a major advantage over other devices for
eliminating the effects of noise on the external sensor. The
series resistance cancellation feature allows a filter to be
constructed between the external temperature sensor and the
part. The effect of any filter resistance seen in series with the remote
sensor is automatically cancelled from the temperature result.
The construction of a filter allows the ADT7461 and the remote
temperature sensor to operate in noisy environments. Figure 23
shows a low-pass R-C-R filter with the following values:
R = 100 Ω and C = 1 nF. This filtering reduces both commonmode noise and differential noise.
100Ω
REMOTE
EMPERATURE
SENSOR
Figure 23. Filter Between Remote Sensor and ADT7461
Factors Affecting Diode Accuracy
100Ω
Remote Sensing Diode
The ADT7461 is designed to work with substrate transistors
built into processors or with discrete transistors. Substrate
transistors are generally PNP types with the collector connected
to the substrate. Discrete types can be either PNP or NPN
transistor connected as a diode (base-shorted to collector). If an
NPN transistor is used, the collector and base are connected to
D+ and the emitter to D−. If a PNP transistor is used, the
collector and base are connected to D− and the emitter to D+.
To reduce the error due to variations in both substrate and
discrete transistors, several factors should be taken into
consideration:
•The ideality factor, n
, of the transistor is a measure of the
F
deviation of the thermal diode from ideal behavior. The
ADT7461 is trimmed for an n
value of 1.008. The
F
following equation may be used to calculate the error
introduced at a temperature T (°C), when using a transistor
whose n
sheet for the n
does not equal 1.008. Consult the processor data
f
values.
F
ΔT = (n
− 1.008)/1.008 × (273.15 Kelvin + T)
F
To factor this in, the user can write the ΔT value to the
1nF
D+
D–
04110-0-009
offset register. It is then automatically added to or
subtracted from the temperature measurement by
the ADT7461.
•Some CPU manufacturers specify the high and low current
levels of the substrate transistors. The high current level of
the ADT7461, I
, is 6 μA. If the ADT7461 current levels do not match
I
LOW
, is 96 μA, and the low level current,
HIGH
the current levels specified by the CPU manufacturer, it
may become necessary to remove an offset. The CPUs data
sheet advises whether this offset needs to be removed and
how to calculate it. This offset may be programmed to the
offset register. It is important to note that if more than one
offset must be considered, the algebraic sum of these
offsets must be programmed to the offset register.
If a discrete transistor is being used with the ADT7461, the best
accuracy is obtained by choosing devices according to the
following criteria:
•Base-emitter voltage greater than 0.25 V at 6 μA, at the
highest operating temperature.
•Base-emitter voltage less than 0.95 V at 100 μA, at the
lowest operating temperature.
• Base resistance less than 100 Ω.
• Small variation in h
control of V
BE
(50 to 150) that indicates tight
FE
characteristics.
Transistors, such as the 2N3904, 2N3906, or equivalents in
SOT-23 packages are suitable devices to use.
THERMAL INERTIA AND SELF-HEATING
Accuracy depends on the temperature of the remote sensing
diode and/or the internal temperature sensor being at the same
temperature as the environment being measured; many factors
can affect this. Ideally, the sensor should be in good thermal
contact with the part of the system being measured. If it is not,
the thermal inertia caused by the sensor’s mass causes a lag in
the response of the sensor to a temperature change. With a
remote sensor, this should not be a problem since it will be
either a substrate transistor in the processor or a small package
device, such as the SOT-23, placed in close proximity to it.
The on-chip sensor, however, is often remote from the
processor and only monitors the general ambient temperature
around the package. The thermal time constant of the SOIC-8
package in still air is about 140 seconds, and if the ambient air
temperature quickly changed by 100 degrees, it would take
about 12 minutes (5 time constants) for the junction temperature of the ADT7461 to settle within 1 degree of this. In
practice, the ADT7461 package is in electrical, and hence
Rev. 3 | Page 19 of 23 | www.onsemi.com
ADT7461
thermal, contact with a PCB and may also be in a forced airflow.
How accurately the temperature of the board and/or the forced
airflow reflects the temperature to be measured also affects the
accuracy. Self-heating due to the power dissipated in the
ADT7461 or the remote sensor causes the chip temperature of
the device or remote sensor to rise above ambient.
However, the current forced through the remote sensor is so
small that self-heating is negligible. With the ADT7461, the
worst-case condition occurs when the device is converting at 64
conversions per second while sinking the maximum current of
1 mA at the
ALERT
power dissipation in the device is about 4.5 mW. The thermal
resistance, θ
, of the SOIC-8 package is about 121°C/W.
JA
LAYOUT CONSIDERATIONS
Digital boards can be electrically noisy environments, and the
ADT7461 is measuring very small voltages from the remote
sensor, so care must be taken to minimize noise induced at the
sensor inputs. The following precautions should be taken:
and
THERM
output. In this case, the total
3. Try to minimize the number of copper/solder joints
that can cause thermocouple effects. Where copper/solder
joints are used, make sure that they are in both the D+ and
D− path and at the same temperature.
Thermocouple effects should not be a major problem as
1°C corresponds to about 200 mV, and thermocouple
voltages are about 3 mV/°C of temperature difference.
Unless there are two thermocouples with a big temperature
differential between them, thermocouple voltages should
be much less than 200 mV.
4. Place a 0.1 μF bypass capacitor close to the V
pin. In
DD
extremely noisy environments, an input filter capacitor
may be placed across D+ and D− close to the ADT7461.
This capacitance can effect the temperature measurement,
so care must be taken to ensure any capacitance seen at D+
and D− is a maximum of 1,000 pF. This maximum value
includes the filter capacitance plus any cable or stray
capacitance between the pins and the sensor diode.
1. Place the ADT7461 as close as possible to the remote
sensing diode. Provided the worst noise sources, such as
clock generators, data/address buses, and CRTs, are
avoided, this distance can be 4 inches to 8 inches.
2. Route the D+ and D– tracks close together, in parallel, with
grounded guard tracks on each side. To minimize
inductance and reduce noise pick-up, a 5 mil track width
and spacing is recommended. Provide a ground plane
under the tracks if possible.
GND
D+
D–
GND
Figure 24. Typical Arrangement of Signal Tracks
5MIL
5MIL
5MIL
5MIL
5MIL
5MIL
5MIL
04110-0-010
5. If the distance to the remote sensor is more than 8 inches,
the use of twisted pair cable is recommended. This works
up to about 6 feet to 12 feet.
For extremely long distances (up to 100 feet), use a
shielded twisted pair, such as the Belden No. 8451
microphone cable. Connect the twisted pair to D+ and D−
and the shield to GND close to the ADT7461. Leave the
remote end of the shield unconnected to avoid ground
loops.
Because the measurement technique uses switched current
sources, excessive cable or filter capacitance can affect the
measurement. When using long cables, the filter capacitance
may be reduced or removed.
Rev. 3 | Page 20 of 23 | www.onsemi.com
ADT7461
APPLICATION CIRCUIT
Figure 25 shows a typical application circuit for the ADT7461
using a discrete sensor transistor connected via a shielded,
twisted pair cable. The pull-ups on SCLK, SDATA, and
ALERT
are required only if they are not already provided elsewhere in
the system.
ADT7461
D+
D–
OR
CPU THERMAL
DIODE
SHIELD2N3906
Figure 25. Typical Application Circuit
SCLK
SDATA
ALERT/
THERM2
THERM
GND
V
The SCLK and SDATA pins of the ADT7461 can be interfaced
directly to the SMBus of an I/O controller, such as the Intel® 820
chipset.
DD
0.1μF
V
DD
FAN
ENABLE
TYP 10kΩ
TYP 10kΩ
FAN
CONTROL
CIRCUIT
3V TO 3.6V
SMBUS
CONTROLLER
5V OR 12V
04110-0-011
Rev. 3 | Page 21 of 23 | www.onsemi.com
ADT7461
0
0
OUTLINE DIMENSIONS
4.00 (0.1574)
3.80 (0.1497)
5.00 (0.1968)
4.80 (0.1890)
85
6.20 (0.2440)
5.80 (0.2284)
41
1.27 (0.0500)
BSC
0.25 (0.0098)
0.10 (0.0040)
COPLANAR ITY
0.10
CONTROLLING DIMENSIONS ARE IN MILLIMETERS; INCH DIMENSIONS
(IN PARENTHESES) ARE ROUNDED-OFF MILLIMETER EQUIVALENTS FOR
REFERENCE ONLY AND ARE NOT APPROPRIATE FOR USE IN DESIGN
SEATING
PLANE
COMPLIANT TO JEDEC STANDARDS MS-012-AA
1.75 (0.0688)
1.35 (0.0532)
0.51 (0.0201)
0.31 (0.0122)
0.25 (0.0098)
0.17 (0.0067)
0.50 (0.0196)
0.25 (0.0099)
8°
1.27 (0.0500)
0°
0.40 (0.0157)
Figure 26. 8-Lead Standard Small Outline Package [SOIC_N]
Narrow Body
(R-8)
Dimensions shown in millimeters and (inches)
3.00
BSC
8
5
4
SEATING
PLANE
4.90
BSC
1.10 MAX
0.23
0.08
8°
0°
0.80
0.60
0.40
3.00
BSC
1
PIN 1
0.65 BSC
.15
.00
0.38
0.22
COPLANAR ITY
0.10
COMPLIANT TO JEDEC STANDARDS MO-187-AA
Figure 27. 8-Lead Mini Small Outline Package [MSOP]
(RM-8)
Dimensions shown in millimeters
× 45°
Rev. 3 | Page 22 of 23 | www.onsemi.com
ADT7461
ORDERING GUIDE
Model Temperature Range Package Description Package Option Branding SMBus Address
ADT7461AR −40°C to +125°C 8-Lead SOIC_N R-8 4C
ADT7461AR-REEL −40°C to +125°C 8-Lead SOIC_N R-8 4C
ADT7461AR-REEL7 −40°C to +125°C 8-Lead SOIC_N R-8 4C
ADT7461ARZ1 −40°C to +125°C 8-Lead SOIC_N R-8 4C
ADT7461ARZ-REEL1 −40°C to +125°C 8-Lead SOIC_N R-8 4C
ADT7461ARZ-REEL71 −40°C to +125°C 8-Lead SOIC_N R-8 4C
ADT7461ARM −40°C to +125°C 8-Lead MSOP RM-8 T1B 4C
ADT7461ARM-REEL −40°C to +125°C 8-Lead MSOP RM-8 T1B 4C
ADT7461ARM-REEL7 −40°C to +125°C 8-Lead MSOP RM-8 T1B 4C
ADT7461ARMZ1 −40°C to +125°C 8-Lead MSOP RM-8 T1B 4C
ADT7461ARMZ-REEL1 −40°C to +125°C 8-Lead MSOP RM-8 T1B 4C
ADT7461ARMZ-R71 −40°C to +125°C 8-Lead MSOP RM-8 T1B 4C
ADT7461ARMZ-21 −40°C to +125°C 8-Lead MSOP RM-8 T1F 4D
ADT7461ARMZ-2R1 −40°C to +125°C 8-Lead MSOP RM-8 T1F 4D
ADT7461ARMZ-2RL71 −40°C to +125°C 8-Lead MSOP RM-8 T1F 4D
EVAL-ADT7461EB Evaluation Board
1
Z = Pb-free part.
ON Semiconductor and are registered trademarks of Semiconductor Components Industries, LLC (SCILLC). SCILLC reserves the right to make changes without further notice to any
products herein. SCILLC makes no warranty, representation or guarantee regarding the suitability of its products for any particular purpose, nor does SCILLC assume any liability arising
out of the application or use of any product or circuit, and specifically disclaims any and all liability, including without limitation special, consequential or incidental damages. “Typical”
parameters which may be provided in SCILLC data sheets and/or specifications can and do vary in different applications and actual performance may vary over time. All operating
parameters, including “Typicals” must be validated for each customer application by customer's technical experts. SCILLC does not convey any license under its patent rights nor the
rights of others. SCILLC products are not designed, intended, or authorized for use as components in systems intended for surgical implant into the body, or other applications intended to
support or sustain life, or for any other application in which the failure of the SCILLC product could create a situation where personal injury or death may occur. Should Buyer purchase or
use SCILLC products for any such unintended or unauthorized application, Buyer shall indemnify and hold SCILLC and its officers, employees, subsidiaries, affiliates, and distributors
harmless against all claims, costs, damages, and expenses, and reasonable attorney fees arising out of, directly or indirectly, any claim of personal injury or death associated with such
unintended or unauthorized use, even if such claim alleges that SCILLC was negligent regarding the design or manufacture of the part. SCILLC is an Equal Opportunity/Affirmative Action
Employer. This literature is subject to all applicable copyright laws and is not for resale in any manner.
PUBLICATION ORDERING INFORMATION
LITERAT URE FULFILLMENT:
Literature Distribution Center for ON Semiconductor
P.O. Box 5163, Denver, Colorado 80217 USA
Phone: 303-675-2175 or 800-344-3860 Toll Free USA/Canada
Fax: 303-675-2176 or 800-344-3867 Toll Free USA/Canada
Email: orderlit@onsemi.com
N. American Technical Support: 800-282-9855
Toll Free USA/Canada
Europe, Middle East and Africa Technical Support:
Phone: 421 33 790 2910
Japan Customer Focus Center
Phone: 81-3-5773-3850
ON Semiconductor Website: www.onsemi.com
Order Literature: http://www.onsemi.com/orderlit
For additional information, please contact your local
Sales Representative
Rev. 3 | Page 23 of 23 | www.onsemi.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.