Online USV Xanto X10000 User Manual

1 / 58
X6000-20000_usermanual_engl_3_years_warranty_202003.docx
User manual
Models 6000 – 20000
Germany
Italy
Switzerland
ONLINE USV-Systeme AG Luise-Ullrich-Str. 8 D-82031 Grünwald
Phone +49 (89) 2423990-10 Fax +49 (89) 2423990-20
www.online-usv.de
ONLINE UPS-Systems S.r.l. Via Ferruccio Gilera 110 I-20862 Arcore (MB)
Phone +39 (039) 2051444 Fax +39 (039) 2051435
www.online-ups.it
ONLINE USV-Systeme AG c/o swizzconnexx Pilatusstrasse 17 CH-5630 Muri
Phone +41 (41) 5002868 Fax +49 (89) 242399020
www.online-usv.ch
2 / 58
X6000-20000_usermanual_engl_3_years_warranty_202003.docx
Content
User manual ...................................................................................... 1
1. Introduction ................................................................................. 5
2. Safety warnings .......................................................................... 7
3. Installation .................................................................................. 8
3.1 Checking the delivery .......................................................... 8
3.2 Unpacking the UPS system ................................................ 8
3.3 Checking the accessories ................................................... 9
3.4 XANTO 6000 and XANTO 10000: Installation as tower,
connecting battery .......................................................................... 9
3.5 XANTO 6000 and XANTO 10000: Installation in rack,
connecting battery ........................................................................ 11
3.6 Installation of XANTO 10000 3/1 – 20000 3/1, connecting the
battery .......................................................................................... 13
3.7 Electrical installation for single system.............................. 14
Recommended cable cross sections ........................................... 14
Terminal strip ............................................................................... 15
3.8 Getting started single system ............................................ 16
3.9 Electrical installation for parallel system ........................... 18
Electrical installation for redundant / parallel system ................... 18
3.10 Quick start for parallel system ........................................... 23
4. Operation .................................................................................. 26
4.1 Control panel ..................................................................... 26
4.2 LED indicators ................................................................... 27
4.3 Display and menu.............................................................. 28
4.4 Settings ............................................................................. 31
4.5 Operating statuses ............................................................ 34
5. Communication and interfaces ................................................. 38
5.1 RS 232 and USB interface ................................................ 38
5.2 Slot for interface cards ...................................................... 39
5.3 Emergency Power Off (EPO) function .............................. 39
5.4 DataWatch software .......................................................... 41
6. Maintenance ............................................................................. 43
6.1 Care and maintenance ...................................................... 43
6.2 Storage .............................................................................. 43
6.3 When to change the batteries ........................................... 43
6.4 Replacing the batteries ..................................................... 44
6.5 Testing the new batteries .................................................. 45
3 / 58
X6000-20000_usermanual_engl_3_years_warranty_202003.docx
6.6 Disposing of the old batteries or UPS system ................... 45
7. Troubleshooting ........................................................................ 46
7.1 Error codes ........................................................................ 46
7.2 Warnings ........................................................................... 47
7.3 Troubleshooting................................................................. 48
7.4 Muting the alarm................................................................ 49
7.5 Support .............................................................................. 50
8. Technical data .......................................................................... 51
8.1 List of device types ............................................................ 51
8.2 Dimensions and weight ..................................................... 51
8.3 Electrical connections ....................................................... 51
8.4 Electrical specifications ..................................................... 52
8.5 Batteries and autonomy time ............................................ 53
8.6 Rear view .......................................................................... 54
8.7 CE confirmation ................................................................. 57
9. Warranty ................................................................................... 58
List of Illustrations
Figure 1: XANTO 6000 – 10000 in the rack ......................................... 6
Figure 2: XANTO 6000 - 10000 as tower ............................................. 6
Figure 3: XANTO 10000 3/1 ................................................................. 6
Figure 4: XANTO 20000 3/1 ................................................................. 6
Figure 5: Foot mounting...................................................................... 10
Figure 6: Installation of the rack/tower versatile model as a tower..... 10
Figure 7: Removing the frontpanel ..................................................... 12
Figure 8: Rotating the display ............................................................. 12
Figure 9: Securing the mounting bracket ............................................ 12
Figure 10: Rack mounting................................................................... 12
Figure 11: XANTO 6000 / 10000 terminal strip .................................. 15
Figure 12: XANTO 10000 3/1 terminal strip ....................................... 15
Figure 13: XANTO 20000 3/1 terminal strip ....................................... 16
Figure 14: Connection plan for operating two XANTO 6000 / 10000 in
parallel ......................................................................................... 20
Figure 15: Connection plan for operating two XANTO 10000 3/1 in
parallel ......................................................................................... 20
Figure 16: Connection plan for operating two XANTO 20000 3/1 in
parallel ......................................................................................... 21
4 / 58
X6000-20000_usermanual_engl_3_years_warranty_202003.docx
Figure 17: Block circuit diagram for parallel connection ..................... 22
Figure 18: Control panel ..................................................................... 26
Figure 19: Display in normal mode ..................................................... 34
Figure 20: Battery mode display ......................................................... 34
Figure 21: Display in standby mode ................................................... 35
Figure 22: Display in high-efficiency mode ......................................... 36
Figure 23: Display in bypass mode .................................................... 36
Figure 24: Display in frequency converter mode ................................ 37
Figure 25: RS-232 interface (DB-9 connector) ................................... 38
Figure 26: Emergency power off connector........................................ 40
Figure 27: Rear view of XANTO 6000 and 10000 .............................. 54
Figure 28: Rear view of XANTO 10000 3/1 ........................................ 55
Figure 29: Rear view of XANTO 20000 3/1 ........................................ 56
List of tables
Table 1: Package contents ................................................................... 9
Table 2: Cable cross-sections ............................................................ 15
Table 3: Descriptions of display .......................................................... 27
Table 4: LED indicators ...................................................................... 27
Table 5: Display .................................................................................. 29
Table 6: Acoustic alarm ...................................................................... 29
Table 7: Overview of operating status ................................................ 31
Table 8: Configuration menu .............................................................. 33
Table 9: Pin assignment for RS-232 interface .................................... 38
Table 10: Interface cards .................................................................... 39
Table 11: Error codes ......................................................................... 46
Table 12: Warnings ............................................................................. 48
Table 13: Troubleshooting .................................................................. 49
Table 14: Overview of UPS systems and battery packs .................... 51
Table 15: Dimensions and weight ...................................................... 51
Table 16: Electrical connections ......................................................... 51
Table 17: Electrical specifications ...................................................... 53
Table 18: Batteries .............................................................................. 53
Table 19: Autonomy times (in minutes) at 50 / 100% load, pf=0.7 ..... 53
INTRODUCTION
5 / 58
X6000-20000_usermanual_engl_3_years_warranty_202003.docx
1. Introduction
ONLINE USV-Systeme AG (ONLINE) is one of the leading manufac­turers of uninterruptible power supplies (UPS). Since 1988, the Ger­man company has focussed on the development, production, sale and support of UPS systems. Based on unit numbers sold, ONLINE prod­ucts are the German number one in the UPS market and internation­ally recognised because of their top quality and excellent support.
The power supply often fails when you least expect it. There can also be significant fluctuation in the quality of the power supply. Network problems can lead to the destruction of critical data, data which is not backed up can be lost and hardware damaged. This means expensive repairs and downtime.
Models of the XANTO series are the best way of preparing for these kinds of scenarios. These UPS system offer top class power supply protection for your delicate electronic systems. They protect against the most common supply problems such as power outage, voltage blips, surge voltage and low voltage, voltage drops, interference, switching and voltage peaks, frequency deviations and harmonic dis­tortion.
XANTO reliably protects your systems from power supply problems and the functionality of the devices is retained. As well as first-class performance and reliability, XANTO has the following unique benefits:
True double conversion technology (VFI-SS-111)
Pioneering power factor 1.0 (1 kVA = 1kW)*
Pure sinewave output voltage
Redundancy function for double safety
Parallel operation for power increase
Frequency converter mode
Automatic and manual bypass
Scalable autonomy time with additional battery packages
Efficiency of up to 98 %.
Rack/Tower versatile model at 6,000VA and 10,000VA with just
4 HU
Battery deep-discharge-protection
Cold start function, starts the UPS system without utility power
Switchable output sockets to extend the autonomy time for crit-
ical loads (not X6000 and X10000)
INTRODUCTION
6 / 58
X6000-20000_usermanual_engl_3_years_warranty_202003.docx
RS-232 and USB interface
Slot for optional SNMP adapter or AS400- / dry-contact inter-
face-card
Emergency-off function (EPO = Emergency Power Off)
Built-in maintenance bypass (not X6000, X10000)
2 years warranty incl. battery and 24h advance replacement
* XANTO 10000 3/1 and XANTO 20000 3/1 only powerfactor 0.9
Figure 1: XANTO 6000 – 10000 in the
rack
Figure 2: XANTO 6000 - 10000 as tower
Figure 3: XANTO 10000 3/1
Figure 4: XANTO 20000 3/1
SAFETY WARNINGS
7 / 58
X6000-20000_usermanual_engl_3_years_warranty_202003.docx
2. Safety warnings
This manual contains important instructions that you must follow dur­ing the installation and maintenance of the UPS system and the bat­teries. Please read all the instructions in the manual before working with the device. Keep the manual in a safe place.
CAUTION
The UPS system carries life-threatening voltages. All repair and maintenance work must be carried out by customer ser­vice personnel.
The UPS system has its own energy source (batteries). The output of the UPS system can be live even when the UPS sys­tem is not connected to a source of alternating current.
In order to reduce the risk of fire or electric shock, the UPS system may only be installed in buildings with controlled tem­perature and air humidity in which there are no conductive contaminants. The ambient temperature must not exceed 40°C. The UPS system must not be operated near water or in extremely high air humidity (>90%).
Before transporting the UPS system, make sure that it is dis- connected from the power supply and switched off.
Batteries can pose a risk of electric shock or catch fire as a result of high short circuit current. Please take the necessary precautionary measures. Maintenance must be carried out by qualified personnel who are trained in handling batteries and have good knowledge of the necessary precautionary measures, see Chapter 6 Maintenance. Keep unauthorised personnel away from batteries
Batteries must be disposed of properly. Local regulations must be taken into consideration.
Batteries must not be burnt. There is risk of explosion.
INSTALLATION
8 / 58
X6000-20000_usermanual_engl_3_years_warranty_202003.docx
3. Installation
3.1 Checking the delivery
Keep the transport box and the packaging material for the carrier or sales point. If parts of the system have been damaged in transit, sub­mit a transport damage complaint to your supplier within 24 hours. If you only discover damage after accepting the device, please submit a complain for concealed damage.
3.2 Unpacking the UPS system
CAUTION
Unpacking the UPS system at a low ambient temperature can lead to the formation of condensation inside and outside the casing. Only install the UPS system if the inside and outside are completely dry (risk of electric shock).
The UPS system is very heavy (see Chapter 8 Technical data). Be careful when unpacking and transporting the UPS.
PLEASE NOTE
Move and open the packaged UPS system carefully. Leave the components in their packaging until they are installed.
To unpack the UPS system and accessories:
1. Open the external box and take the accessories packed with the UPS system out.
2. Carefully lift the UPS system out of the external box. This may require two people under some circumstances.
3. Place the UPS system in a protected, adequately ventilated po­sition which is free of humidity, flammable gasses and corro­sion.
INSTALLATION
9 / 58
X6000-20000_usermanual_engl_3_years_warranty_202003.docx
3.3 Checking the accessories
Description
XANTO 6000 XANTO 10000 XANTO 6000 battery pack XANTO 10000 battery pack XANTO 10000 3/1 XANTO 20000 3/1 XANTO 10000 / 20000 battery pack
19"mounting bracket (left and right)
2 2 2
2
Feet for tower mounting (sets)
2 2
Extension for feet for tower fitting
2 2
USB interface cable
1 1 1 1
Parallel cable
1 1 1
1 Synchronisation cable (share current)
1 1 1
1
Battery cable
1
1 1
1
Quick start guide
1 1 1 1 1 1 1
DataWatch software*
Manual*
*Download from www.online-ups.com
Table 1: Package contents
3.4 XANTO 6000 and XANTO 10000: Installation as tower, connecting battery
The UPS system is delivered fully assembled.
CAUTION
The casing is very heavy (see Chapter 8 Technical data).
INSTALLATION
10 / 58
X6000-20000_usermanual_engl_3_years_warranty_202003.docx
1. Position the UPS system on an even, stable surface for its final location. The XANTO 6000 and 10000 UPS models have no internal batteries so the minimum configuration is always at least two housings: the UPS system and a battery pack.
2. If you install additional battery packs, also position them in their final position next to the UPS system.
3. For 6000 and 10000 UPS push them and its battery packs into the two feet from above (see Figure 6). Depending on the num­ber of additional battery packs, you can also use the feet exten­sions for stabilisation (supplied with the battery packs). Make sure the distance between the two feet is as great as possible to ensure stability.
Figure 5: Foot mounting
Figure 6: Installation of the
rack/tower versatile model as a
tower
Connecting additional battery packs
1. In order to install additional battery packs, remove the covers to connect the battery packs on the back of the UPS system and the battery packs, see Chapter 8.6 Rear view. If you are in­stalling multiple battery packs, remove all the covers apart from
the “V DC Input” cover on the last battery pack. Keep the covers
and the screws.
2. Connect all plug connections between the battery packs and the
UPS system. This involves connecting the “VDC Output” on a
battery pack with the “VDC Input” on the upstream battery pack.
INSTALLATION
11 / 58
X6000-20000_usermanual_engl_3_years_warranty_202003.docx
The battery pack connected directly to the UPS system is con-
nected to the “VDC Input” on the UPS system. Connect each of
the earth conductors on the battery cable with the housing of the UPS system and the battery pack. A maximum of four addi­tional battery packs can be connected to the first standard bat­tery pack on the UPS system.
3. Enter the number of battery packs used in menu no. 7 (see Chapter 4.4 Settings).
4. Continue the getting started process (see Chapter 3.8 Getting started single system)
3.5 XANTO 6000 and XANTO 10000: Installation in rack, connecting battery
The UPS system is delivered fully assembled.
CAUTION
The casing is very heavy (see Chapter 8 Technical data).
Optional slide rails (serial no. Rack Kit) are available for installation in the rack. The slide rails fit 48 cm (19 inch) racks with a depth of 48 to 78 cm.
1. Fit the rack kit (separate assembly instructions provided with the rack kit).
2. The next step is to adjust the display direction of the UPS sys­tem for horizontal rack installation. To do this, remove the front panel by pulling it forward. Then push the plastic catches on the display apart to release it. Rotate it 90 degrees and insert it back into the front panel.
INSTALLATION
12 / 58
X6000-20000_usermanual_engl_3_years_warranty_202003.docx
Figure 7: Removing the frontpanel
Figure 8: Rotating the display
3. Reverse the sequence to refit the front panel and repeat for the additional battery packs.
4. Align the mounting bracket (L = left and R = right) with the screw holes on either side of the UPS system and the battery packs and affix it using the M4 x 8 countersunk screws provided (see Figure 9).
5. Push the UPS system and the relevant number of battery packs into the rack.
6. Secure the mounting bracket of the UPS system and the battery packs in the rack (see Figure 10).
Figure 9: Securing the mounting
bracket
Figure 10: Rack mounting
Connecting additional battery packs
1. In order to install additional battery packs, remove the covers to connect the battery packs on the back of the UPS system and
INSTALLATION
13 / 58
X6000-20000_usermanual_engl_3_years_warranty_202003.docx
the battery packs, see Chapter 8.6 Rear view. If you are in­stalling multiple battery packs, remove all the covers apart from the “V DC Input” cover on the last battery pack. Keep the covers and the screws.
2. Connect all plug connections between the battery packs and the
UPS system. This involves connecting the “VDC Output” on a battery pack with the “VDC Input” on the upstream battery pack.
The battery pack connected directly to the UPS system is con-
nected to the “VDC Input” on the UPS system. Connect each of
the earth conductors on the battery cable with the housing of the UPS system and the battery pack. A maximum of four addi­tional battery packs can be connected to the first standard bat­tery pack on the UPS system.
3. Enter the number of battery packs used in menu no. 7 (see Chapter 4.4 Settings).
4. Continue the getting started process (see Chapter 3.8 Getting started single system).
3.6 Installation of XANTO 10000 3/1 – 20000 3/1, con­necting the battery
The UPS system is delivered fully assembled.
CAUTION
The casing is very heavy (see Chapter 8 Technical data).
1. Position the UPS system on an even, stable surface for its final location.
The XANTO 20.000 3/1 UPS system has no internal batteries so the minimum configuration is always at least two housings: the UPS system and a battery pack.
2. If you install additional battery packs, position them in their final position next to the UPS system.
3. In order to install additional battery packs, remove the covers to connect the battery packs on the back of the UPS system and
INSTALLATION
14 / 58
X6000-20000_usermanual_engl_3_years_warranty_202003.docx
the battery packs, see (Chapter 8.6 Rear view). If you are in­stalling multiple battery packs, remove all the covers apart from
the “V DC Input” cover on the last battery pack. Keep the covers
and the screws.
4. Connect all plug connections between the battery packs and the
UPS system. This involves connecting the “VDC Output” on a
battery pack with the “VDC Input” on the upstream battery pack.
The battery pack connected directly to the UPS system is con-
nected to the “VDC Input” on the UPS system or to the battery
terminals on the XANTO 20000 3/1. Connect each of the earth conductors on the battery cable with the housing of the UPS system and the battery pack.
5. A maximum of four battery packs can be connected to the XANTO 10.000 3/1 UPS system. For the XANTO 20.000 3/1, a maximum of three additional battery packs can be connected to the first standard battery pack on the UPS system.
6. Enter the number of battery packs used in menu no. 7 (see Chapter 4.4 Settings).
7. Continue the getting started process (see Chapter 3.8 Getting started single system).
3.7 Electrical installation for single system
CAUTION
Always connect the earth conductor first.
Do not make any unauthorised changes to the UPS system,
as these could damage the system and invalidate the guaran­tee.
The UPS system must be connected to the mains voltage by a qualified electrician.
Recommended cable cross sections
XANTO 6000
XANTO 10000
XANTO 10000 3/1
XANTO 20000 3/1
Input
6mm2
10mm2
10mm2
16mm2
INSTALLATION
15 / 58
X6000-20000_usermanual_engl_3_years_warranty_202003.docx
Output
6mm2
10mm2
10mm2
16mm2
Earth conduc­tor
6mm2
10mm2
10mm2
16mm2
Connection fittings
M5
M5
M5
M6
Cable plug, external max.
10mm
10mm
12mm
18mm
Fuse in bat­tery pack
50A
50A
100A
100A
Table 2: Cable cross-sections
Terminal strip
1. Remove the cover on the terminal strip.
2. Connect the cables as shown in the diagram.
Figure 11: XANTO 6000 / 10000 terminal strip
Figure 12: XANTO 10000 3/1 terminal strip
INSTALLATION
16 / 58
X6000-20000_usermanual_engl_3_years_warranty_202003.docx
Figure 13: XANTO 20000 3/1 terminal strip
3. Replace the cover on the terminal strip.
3.8 Getting started single system
PLEASE NOTE
Make sure that the overall rated power of the loads connected does not exceed the capacity of the UPS system. The power consumption of inductive loads or laser printers can be very high, please take this into consideration when specifying your UPS system.
1. If you install additional battery packs, make sure they are properly connect (see Chapters 3.4 to 3.6) and the battery fuse on the back of the battery packs is switched on.
2. Connect the loads with the UPS system without switching them on. Make sure that the XANTO 10000 3/1 and 20000 3/1 UPS systems have two groups of output sockets. The programmable output sockets can be switched independently of the remaining sockets. The programmable output sockets are primarily de­signed for less critical loads which cannot be brought down us­ing software. Critical loads should not be connected to the pro­grammable output sockets.
3. Switch the supply voltage on and then switch the input switch
on the back of the UPS system to “ON”. The fan starts working.
INSTALLATION
17 / 58
X6000-20000_usermanual_engl_3_years_warranty_202003.docx
The display on the UPS system lights up and shows “Sb” after a short initialisation phase.
4. Hold the “ON / ” button on the UPS system down until you hear a short beep.
5. The UPS system carries out a self-test, after which “OK” ap- pears on the display. The UPS system is now operating in nor­mal mode and supplying the loads with reliable power.
6. If an additional emergency off switch has been installed, the emergency stop function needs to be tested.
7. Switch the loads on one by one.
PLEASE NOTE
The internal batteries charge up to 90% of their full capacity in five hours. ONLINE recommends charging the batteries for 48 hours after installation or extended periods of non-use.
The batteries start to charge as soon as the UPS system is connected to the utility power and supplied with power, irre­spective of the operating mode.
Starting in battery mode
1. Hold the “ON / ” button on the UPS system down until you hear a beep.
2. The UPS system starts and then shows on the display to indicate that the bypass is outside the tolerance.
3. Then press the “ON / “ button until you hear another beep.
The UPS system indicates the start process by showing “ON”
in the display, then starting the self-test and then switching to battery mode (see Chapter 4.5 Operating statuses) and sup­plies the loads connected with reliable electricity.
4. If the display is lit, fix all warnings (see Chapter 7.3 Trouble- shooting) and restart the UPS system.
INSTALLATION
18 / 58
X6000-20000_usermanual_engl_3_years_warranty_202003.docx
Switching off
1. Hold the “OFF / ESC” button on the UPS system down for 2 seconds. When the continuous beep ends, the UPS system switches to standby mode.
PLEASE NOTE
If the “OFF / ESC” button is released after less than 2 seconds,
the unit is not switched off.
2. Switch the input switch on the back of the UPS system to “OFF” and then switch the supply voltage off. The display on the UPS system goes out after a short time and the UPS system switches off completely.
3.9 Electrical installation for parallel system
The XANTO 6000 / 10000 and XANTO 10000 / 20000 3/1 UPS sys­tems enable redundancy and parallel operation.
Redundant operation:
The redundant mode offers dual security. Up to three UPS systems are operated in parallel. If a UPS system fails, the remaining systems take over with no interruption. Redundancy mode is possible up to the rated power of the UPS system (6000VA, 10,000VA, 20,000VA). If this power is exceeded, the group automatically switches to parallel mode. Parallel mode is indicated in the UPS menu by PAxxx.
Parallel mode:
This mode enables an increase in the power range of the UPS system, but there is no redundancy. In parallel mode, for example, a XANTO 6000 could be connected to two more XANTO 6000 units to increase the overall power available to 18,000VA.
Electrical installation for redundant / parallel system
PLEASE NOTE
A maximum of three UPS systems (with the same output power) can be connected as an n+1 group.
All UPS system must be connected to the same utility power.
Loading...
+ 40 hidden pages