Onity RFRCU Users Manual

FCC Part 15.247 Certification
Test Report
FCC ID: R32-RFRCU
ACS Report Number: 04-0170-15C
Manufacturer: Onity, Inc.
Equipment Type: Modular Radio
Model: RFRCU
Installation and Operators Guide
5015 B.U. Bowman Drive Buford, GA 30518 USA Voice: 770-831-8048 Fax: 770-831-8598
EUT – Product Manual
Room Control Unit
The Room Control Unit (RCU) is the ‘brain’ of Onity’s new Wireless Energy Management System(EMS). It receives the temperature, humidity, guest settings, fan mode, motion status, and door status from the various system devices and determines how to operate the HVAC system and lighting control.
The RCU has six relay drivers for outputs, a local door switch input, three setup buttons, three LED indicators, a local temperature sensor input, and a Real Time Clock (RTC) interface. The RCU receives transmissions from all the wireless devices via its on board radio.
RCU Power Up
When power is first supplied to the RCU, the three LEDs each flash once, the initial configuration check is started, and the 16 DIP Switch settings are read. These DIP Switch settings are ONLY read during
the power up routine. Any changes made to these settings will not take effect until the unit is shut down and powered back up.
If there is no response from the on board radio, the CFG LED (red) will flash. The unit will try once per second to communicate with the on board radio. As long as no communication is found, the red LED will continue to flash.
BFR – Building, Floor, Room. The unique ID of the RCU. This ID is configured in all the devices that will transmit to this RCU..
If there is a response from the on board radio, the state of the LED will depend on whether or not the unit has been configured. If the unit has been configured with a valid BFR, the red LED will turn ON. If the unit has not yet been configured with a valid BFR, the red LED will turn OFF.
Onity, Inc. 2100A Nancy Hanks Drive. Norcross GA 30071 USA Phone 1-770-935-4228. Toll Free 1-866-to-Onity Fax1-770-488-6305. www.onity.biz
RCU Buttons
As stated above the RCU has 3 setup buttons. These are explained below.
Configuration Button (CFG)
The CFG button is used to configure the BFR (Building, Floor, Room) of the unit. At this time, the BFR is a randomly generated number.
Press and hold the CFG button for 3 seconds, then release. Upon release, the red LED will flash once. Random numbers are generated to make the BFR and these are written to the radio. The radio then transmits an inquire message. If the BFR is already in use by another device in the area, an ‘in use’ message is received. In this case, a new BFR is generated and an inquire transmitted. This is repeated until no ‘in use’ transmission is received. If no ‘in use’ is received, then the BFR is free to use and the red LED will turn on solid.
OB/CB Button
When the OB/CB button is pressed, the radio will send the Open Binding message once per second for one minute, or until the OB/CB button is pressed again. While the unit is transmitting this message, the green LED will flash once per second.
While the unit is in the open binding mode, wireless devices such as the WDDC can be bound to this RCU.
When either one minute has passed or the button is again pressed, a close binding message is sent and the RCU exits the open binding mode.
Fast Clock Button
The fast clock button is for testing purposes only. Whe n pr essed, one second is the equivalent of one minute real time. Because the devices bound to the RCU do not have a fast clock mode, this feature is not recommended for use in the field. It was added only to facilitate testing of the unit in the lab.
Monitoring of Wireless Devices
When the RCU receives status messages from the wireless room devices, the settings are logged in the RCU memory. Anytime the RCU needs to check one of these statuses, it will check its memory to see the latest status from any of the wireless devices.
For example, if the RCU receives a message indicating that motion has been detected, it registers this in its memory. This status will not
Onity, Inc. 2100A Nancy Hanks Drive. Norcross GA 30071 USA Phone 1-770-935-4228. Toll Free 1-866-to-Onity Fax1-770-488-6305. www.onity.biz