A-3 SYSTEM-10 BTU METER N2 BOARD with Optional Digital Input Pulse (Di3)
1 1451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com
System-10-N2 BTU Meter Installation and Operation Guide 05/14 - 0655-5 / 18322 Page 3
1 1451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com
System-10-N2 BTU Meter Installation and Operation Guide 05/14 - 0655-5 / 18322 Page 4
SECTION 1: INTRODUCTION
1.1 PURPOSE OF THIS GUIDE
The purpose of this guide is to provide installation and commissioning procedures and basic
installation and operating instructions for the ONICON System-10-N2 serial interface.
1.2 TYPICAL SYSTEM-10 NETWORK INTERFACE MODULE
ONICON’s System-10 is a true heat (Btu) computer which accepts data from several sensors,
performs a series of computations with that data, and displays and/or transmits the results as an
indication of the amount of heat (Btu’s) being transferred per unit time or as a totalized amount.
It can also be provided with an optional Metasys
building control network.
BTU X 10,000
SCROLL RESET PROGRAM
SYSTEM-10
BTU METER
®
N2 serial interface to communicate data to the
ONICON insertion
flow meter
(purchased separately)
1 1451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com
System-10-N2 BTU Meter Installation and Operation Guide 05/14 - 0655-5 / 18322 Page 5
1.4 NETWORK SIGNAL CONNECTIONS
!
!
1.4.1 RS485N2 RS485, 2-wire (half-duplex) serial output connections are connected to
terminal as shown. Do not exceed 4.4 in-lb (0.5 Nm) of torque when tightening.
CAUTION
Only qualied service personnel should make connections between the System-10-N2 BTU Meter
and the user’s external equipment. ONICON assumes no responsibility for damage caused to the
external equipment as a result of an improper installation.
N2 (-)
N2 (+)
CAUTION
Incoming and outgoing RS485 cable shield wires should be connected together, but must not be
connected to the System-10.
1 1451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com
System-10-N2 BTU Meter Installation and Operation Guide 05/14 - 0655-5 / 18322 Page 6
1.4.2 Optional Network Interface With Isolated Digital Pulse Input (Di3)
The System-10 BTU Meter can be provided with an auxiliary pulse input for totalizing
pulse outputs from external devices such as water or gas meters. Pulses are accumulated
in an internal register, and the totalized value is available on the network. This register
can be zeroed via the network. The maximum register total is 9,999,999. The register will
rollover to zero when this value is exceeded.
If the auxiliary pulse input option was ordered at the same time the Btu meter was
ordered, it will arrive fully congured and ready to use. If it was ordered after the Btu
meter was delivered and is being installed as a eld upgrade, it may be necessary to
congure the pulse input. The information required to congure the input is provided
below and on the following pages:
The input pulse must meet the following criteria:
1. Frequency input range, 50 Hz maximum
2. 10 millisecond minimum pulse duration
Input Pulse Denition:
In order to congure the communications card auxiliary pulse input, you must rst
determine which type of pulse your meter produces. The allowable types of input
pulses are described on the following pages. Based on the type of pulse, set the selector
switch (S1) on the communications circuit board (Fig. 1) to the correct setting.
Fig. 1
AUX. PULSE INPUT (Di3)
1 1451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com
System-10-N2 BTU Meter Installation and Operation Guide 05/14 - 0655-5 / 18322 Page 7
Powered Pulse:
This type of output refers to a pulse which has an associated voltage with it (see Fig. 2).
Set the selector switch, S1 to Pwrd Pulse. The allowable voltage range is 5-24 VDC. The
input impedance is set at the factory to be 11 KOHM via the impedance selector jumper
(J1, see Fig. 1). A lower impedance, 3 KOHM can be selected if required by the instrument
providing the pulse output. Consult the instrument manufacturer or ONICON if you are
uncertain as to the proper jumper selection.
Fig. 2
ONICON BTU Meter
Di3 In (+)
Di3 In (-)
Open Collector (Sourcing):
This type of output refers to an open Collector Switch congured for a sourcing function
(see Fig. 3). Set the selector switch, S1 to SRC. The switch must be rated for at least 20mA
at 20VDC.
Fig. 3
ONICON BTU Meter
Di3 In (+)
Di3 In (-)
1 1451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com
System-10-N2 BTU Meter Installation and Operation Guide 05/14 - 0655-5 / 18322 Page 8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.