11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699
www.onicon.com • sales@onicon.com
02-150808-7 / 19204
SAFETY INFORMATION
!
!
i
This meter was calibrated at the factory before shipment. To ensure correct use of the meter, please read this
manual thoroughly.
Regarding this Manual:
• This manual should be passed on to the end user.
• Before use, read this manual thoroughly to comprehend its contents.
• The contents of this manual may be changed without prior notice.
• All rights reserved. No part of this manual may be reproduced in any form without
ONICON’s written permission.
• ONICON makes no warranty of any kind with regard to this material, including, but not
limited to, implied warranties of merchantability and suitability for a particular purpose.
• All reasonable effort has been made to ensure the accuracy of the contents of this manual.
However, if any errors are found, please inform ONICON.
• ONICON assumes no responsibilities for this product except as stated in the warranty.
• If the customer or any third party is harmed by the use of this product, ONICON assumes no
responsibility for any such harm owing to any defects in the product which were not
predictable, or for any indirect damages.
Safety Precautions:
The following general safety precautions must be observed during all phases of installation, operation,
service,andrepairofthisproduct.FailuretocomplywiththeseprecautionsorwithspecicWARNINGS given elsewhere in this manual violates safety standards of design, manufacture,
and intended use of the product. ONICON Incorporated assumes no liability for the customer’s
manual, the protection provided by this product may be impaired.
The following symbols are used in this manual:
WARNING
Messages identied as WARNING contain information regarding the personal safety of individuals
involved in the installation, operation or service of this product.
CAUTION
Messages identied as CAUTION contain information regarding the potential damage to the product
or other ancillary products.
IMPORTANT NOTICE
Messages identied as IMPORTANT NOTICE contain information critical to the proper operation of
the product.
Hot tapping must be performed by a trained professional. U.S. regulations often require
a hot tap permit. The manufacturer of the hot tap equipment and/or the contractor
performing the hot tap is responsible for providing proof of such a permit.
To avoid potential electric shock, follow National Electric Code or your local code when
wiring this unit to a power source. Failure to do so could result in injury or death. All
AC power connections must be in accordance with published CE directives. All wiring
procedures must be performed with the power Off.
Unless you have specically ordered ONICON’s optional O2 cleaning, this ow
meter may not be t for oxygen service. Some models can only be properly
cleaned during the manufacturing process. ONICON Incorporated is not liable
for any damage or personal injury, whatsoever, resulting from the use of ONICON
Incorporated’s standard mass ow meters for oxygen gas.
No part of this publication may be copied or distributed, transmitted, transcribed,
stored in a retrieval system, or translated into any human or computer language,
in any form or by any means, electronic, mechanical, manual, or otherwise, or
disclosed to third parties without the express written permission of ONICON
Incorporated. The information contained in this manual is subject to change without
notice.
1.1 ONICON F-2600 & F-2700 SERIES VORTEX MASS FLOW METERS
The ONICON F-2600 Series In-line and F-2700 Series Insertion Vortex Flow Meters provide a
reliable solution for process ow measurement. From a single entry point in the pipeline, F-2600
meters offer precise measurements of mass or volumetric ow rates.
Multi-Parameter Mass Flow Meters
Mass ow meters utilize three primary sensing elements: a vortex shedding velocity sensor, an
RTD temperature sensor, and a solid state pressure sensor to measure the mass ow rate of gases,
liquids, and steam.
Meters are available as loop powered devices or with up to three 4-20 mA analog output signals
for monitoring your choice of the ve process variables (mass ow, volumetric ow, temperature,
pressure and uid density). The Energy Monitoring option permits
real-time calculation of energy consumption for a facility or process.
Volumetric Flow Meters
The primary sensing element of a volumetric ow meter is a vortex shedding velocity sensor.
Meters are loop powered. The analog 4-20 mA output signal offers your choice of volumetric
or mass ow rate. Mass ow rate is based on a constant value for uid density stored in the
instrument’s memory.
Both the mass and volumetric ow meters can be ordered with a local keypad/display
which provides instantaneous ow rate, total, and process parameters in engineering units. A
pulse output signal for remote totalization and BACnet MS/TP, MODBUS RTU RS485 or HART
communications are also available. Digital electronics allow for easy reconguration for most gases,
liquids and steam. ONICON meters’ simple installation combines with an easy-to-use interface that
provides quick set up, long term reliability and accurate mass ow measurement over a wide range
of ows, pressures and temperatures.
1.1.1 Using This Manual
This manual provides information needed to install and operate both the F-2600 Inline and
F-2700 insertion style ow meters.
Section 1 includes the introduction and product description.
Section 2 provides information needed for installation.
Section 3 describes system operation and programming.
Section 4 provides information on HART, MODBUS and BACnet protocols.
Section 5 covers troubleshooting and repair.
Appendix A - Product Specications
Appendix B– Flow Meter Calculations
Appendix C – Glossary of Terms
Appendix D – Terms & Conditions
When receiving an ONICON mass ow meter, carefully check the outside packing carton
for damage incurred in shipment. If the carton is damaged, notify the local carrier and
submit a report to the factory or distributor. Remove the packing slip and check that
all ordered components are present. Make sure any spare parts or accessories are not
discarded with the packing material. Do not return any equipment to the factory without
rst contacting ONICON Customer Service.
1.1.3 TECHNICAL ASSISTANCE
If you encounter a problem with your ow meter, review the conguration information
for each step of the installation, operation and set up procedures. Verify that your settings
and adjustments are consistent with factory recommendations. Refer to Section 5,
Troubleshooting, for specic information and recommendations.
If the problem persists after following the troubleshooting procedures outlined in Section
5, contact ONICON Incorporated Technical Support at (727) 447-6140 between 8:00 a.m.
and 5:00 p.m. EST. When calling Technical Support, have the following information on
hand:
The serial number and model number (shown on the meter nameplate)
The problem you are encountering and any corrective action taken
Application information (uid, pressure, temperature and piping conguration)
1.1.4 WARRANTY
Warranty
ONICON’s complete warranty is included in Appendix D of this manual
as part of the “Conditions of Sale”. ONICON provides a two-year warranty.
1.2 HOW THE ONICON VORTEX MASS FLOW METER OPERATES
Figure 1. In-Line Multi-Parameter Vortex Mass Flow Meter
ONICON F-2600 Series & F-2700 Series Vortex Mass Flow Meters use a unique sensor
head to monitor mass ow rate by directly measuring three variables. uid velocity,
temperature and pressure. The built-in ow computer calculates the mass ow rate
and volumetric ow rate based on these three direct measurements. The sensing head
is built into the vortex meter’s ow body. To measure uid velocity, the ow meter
incorporates a bluff body (shedder bar) in the ow stream and measures the frequency of
vortices created by the shedder bar. Temperature is measured using a platinum resistance
temperature detector (PRTD). Pressure measurement is achieved using a solid-state
pressure transducer. All three elements are combined into an integrated sensor head
assembly located downstream of the shedder bar within the ow body.
1.2.1 Velocity Measurement
ONICON’s vortex velocity sensor is a patented mechanical design that minimizes the
effects of pipeline vibration and pump noise, both of which are common error sources
in ow measurement with vortex ow meters. The velocity measurement is based on the
well-known Von Karman vortex shedding phenomenon. Vortices are shed from a shedder
bar, and the vortex velocity sensor located downstream of the shedder bar senses the
passage of these vortices. This method of velocity measurement has many advantages
including inherent linearity, high turndown, reliability and simplicity.
Von Karman vortices form downstream of a shedder bar into two distinct wakes.
The vortices of one wake rotate clockwise while those of the other wake rotate
counterclockwise. Vortices generate one at a time, alternating from the left side to the right
side of the shedder bar. Vortices interact with their surrounding space by over-powering
every other nearby swirl on the verge of development. Close to the shedder bar, the
distance (or wave length) between vortices is always constant and measurable. Therefore,
the volume encompassed by each vortex remains constant, as shown below. By sensing
the number of vortices passing by the velocity sensor, the F-2600 & F-2700 Flow Meter
computes the total uid volume.
Figure 2. Measurement Principle of Vortex Flow Meters
1.2.3 Vortex Frequency Sensing
The velocity sensor incorporates a piezoelectric element that senses the vortex frequency.
This element detects the alternating lift forces produced by the Von Karman vortices
owing downstream of the vortex shedder bar. The alternating electric charge generated by
the piezoelectric elements is processed by the transmitter’s electronic circuit to obtain the
vortex shedding frequency. The piezoelectric element is highly sensitive and operates over
a wide range of ows, pressures and temperatures.
To ensure trouble-free operation, vortex ow meters must be correctly sized so that the
ow velocity range through the meter lies within the measurable velocity range (with
acceptable pressure drop) and the linear range.
The measurable range is dened by the minimum and maximum velocity using the
following table.
Vmin
GasLiquid
25 ft/s
√ρ
1 ft/s
English ρ (lb/ft
3
)
Vmax
300 ft/s
30 ft/s
37 ft/s
Vmin
Vmax
√ρ
91 m/s
0.3 m/s
9.1 m/s
Metric ρ (kg/m
3
)
The pressure drop for F-2700 insertion meters is negligible. The pressure drop for F-2600
in-line meters is dened as:
∆P = .00024 ρ V2 English units (∆P in psi, ρ in lb/ft3, V in ft/sec)
∆P = .000011 ρ V2 Metric units (∆P in bar, ρ in kg/m3, V in m/sec)
The linear range is dened by the Reynolds number. The Reynolds number is the ratio of
the inertial forces to the viscous forces in a owing uid and is dened as:
Where
Re = Reynolds Number
ρ = mass density of the uid being measured
V = velocity of the uid being measured
D = internal diameter of the ow channel
= viscosity of the uid being measured
Re =
ρVD
The Strouhal number is the other dimensionless number that quanties the vortex
phenomenon. The Strouhal number is dened as:
Where
St = Strouhal Number
f = frequency of vortex shedding
d = shedder bar width
V = uid velocity
As shown in Figure 3, F-2600 & F-2700 meters exhibit a constant Strouhal number across
a large range of Reynolds numbers, indicating a consistent linear output over a wide
range of ows and uid types. Below this linear range, the intelligent electronics in the
meter automatically corrects for the variation in the Strouhal number with the Reynolds
number. The meter’s smart electronics corrects for this non-linearity via its simultaneous
measurements of the process uid temperature and pressure. This data is then used to
calculate the Reynolds number in real time. The meter automatically corrects down to a
Reynolds number of 5,000.
Figure 3. Reynolds Number Range for the meter
1.2.5 Temperature Measurement
This ow meter uses a 1000 ohm platinum resistance temperature detector (PRTD) to
measure uid temperature.
1.2.6 Pressure Measurement
Both versions of the meter incorporate a solid-state pressure transducer isolated by a 316
SS diaphragm. The transducer itself is micro-machined silicon, fabricated using integrated
circuit processing technology. A nine-point pressure/temperature calibration is performed
on every sensor. Digital compensation allows these transducers to operate within a 0.3%
of full scale accuracy band within the entire ambient temperature range of -40°F to 140°F
(-40°C to 60°C). Thermal isolation of the pressure transducer ensures the same accuracy
across the allowable process uid temperature range of -330°F to 750°F (-200°C to 400°C).
Our vortex mass ow meters are available in two model congurations:
In-line F-2600 Series Flow Meters (replaces a section of the pipeline)
Insertion F-2700 Series Flow Meters (requires a tap into an existing pipeline)
Both the in-line and insertion congurations are similar in that they both use identical electronics
and have similar sensor heads. Besides installation differences, the main difference between an
in-line ow meter and an insertion ow meter is their method of measurement.
For an in-line vortex ow meter, the shedder bar is located across the entire diameter of the
ow body. Thus, the entire pipeline ow is included in the vortex formation and measurement.
The sensing head, which directly measures velocity, temperature and pressure, is located just
downstream of the shedder bar.
Insertion vortex ow meters have a shedder bar located across the diameter of a short tube. The
velocity, temperature and pressure sensor is located within this tube just downstream of a builtin shedder bar. This entire assembly is called the insertion sensing head. It ts through any entry
port with a 1.875 inch minimum internal diameter.
The sensing head of an insertion vortex ow meter directly monitors the velocity at a point in
the cross-sectional area of a pipe, duct, or stack (referred to as “channels”). The velocity at a
point in the pipe varies as a function of the Reynolds number. The insertion vortex ow meter
computes the Reynolds number and then computes the total ow rate in the channel. The output
signal of insertion meters is the total ow rate in the channel. The accuracy of the total ow rate
computation depends on adherence to the piping installation requirements given in Section 2. If
adherence to those guidelines cannot be met, contact ONICON for specic installation advice.
1.3.1 Multivariable Options
The both versions of the meter are capable of providing the following ow measurement
options:
Volumetric ow; Mass ow with temperature compensation; Mass ow with temperature
and pressure compensation; Steam energy ow with temperature compensation;
Steam energy ow with temperature and pressure compensation, Mass or Energy ow
with temperature and external pressure compensation and Net Energy using a second
temperature sensor.
The in-line model is built for line sizes ½" through 4" wafer or ½" through 8" anged
design using ANSI 150, 300, 600, PN16, 40, or 64 class anges.
The insertion model can be used in line sizes 2" and greater and is built with a packing
gland design using 2" NPT, or 2" anged connections (ANSI 150, 300, 600, PN16, 40, or 64
class anges). The packing gland design can be ordered with a permanent or removable
retractor.
The standard in-line model is built with 316L stainless steel, A105 carbon steel and
Hastelloy C-276 versions are available via special order. The insertion model is built with
316L stainless steel.
1.3.3 Flow Meter Electronics
The ow meter electronics are available mounted directly to the ow body, or mounted
remotely. The electronics housing may be used indoors or outdoors, including wet
environments. Available input power options are: DC loop powered (2-wire), DC powered,
or AC powered. Three analog output signals are available for your choice of three of the
ve process variables: mass ow rate, volumetric ow rate, temperature, pressure or uid
density. A pulse output signal for remote totalization and BACnet, MODBUS or HART
communications is also available.
Each meter includes a local 2 x 16 character LCD display housed within the enclosure.
Local operation and reconguration is accomplished using six pushbuttons operated via
nger touch. For hazardous locations, the six buttons can be operated with the electronics
enclosure sealed using a hand-held magnet, thereby not compromising the integrity of the
hazardous location certication.
The electronics include nonvolatile memory that stores all conguration information. The
nonvolatile memory allows the ow meter to function immediately upon power up or after
an interruption in power. All owmeters are calibrated and congured for the customer’s
ow application.
ONICON F-2600 & F-2700 Vortex Flow Meter installations are simple and straightforward.
Both the in-line and the insertion type ow meter installations are covered in this chapter.
After reviewing the installation requirements given below, see page 21 for in-line installation
instructions. See page 24 for insertion style installation instructions. Wiring instructions begin on
page 38.
2.1.1 Flow Meter Installation Requirements
WARNING
Consult the ow meter nameplate for specic ow meter approvals before any hazardous location
installation.
Before installing the ow meter, verify the installation site allows for these considerations:
1. Line pressure and temperature will not exceed the ow meter rating.
2. The location meets the required minimum number of pipe diameters upstream and
downstream of the sensor head as illustrated in Figure 4.
3. Safe and convenient access with adequate overhead clearance for maintenance
purposes.
4. Verify that the cable entry into the instrument meets the specic standard required for
hazardous area installations.
5. For remote installations, verify the supplied cable length is sufcient to connect the
ow meter sensor to the remote electronics.
Also, before installation, check your ow system for anomalies such as:
• leaks
• valves or restrictions in the ow path that could create disturbances in the ow prole
that might cause unexpected ow rate indications
Select an installation site that will minimize possible distortion in the ow prole. Valves,
elbows, control valves and other piping components may cause ow disturbances. Check
your specic piping condition against the examples shown below. In order to achieve
accurate and repeatable performance, install the ow meter using the recommended
number of straight run pipe diameters upstream and downstream of the sensor.
Note: For liquid applications in vertical pipes, avoid installing with ow in the downward
direction because the pipe may not be full at all points. Choose to install the meter with
ow in the upward direction, if possible.
Flow straightener
(if used)
Flow straightener
(if used)
Flow straightener
(if used)
Flow straightener
Minimum Required
Upstream Diameters
No Flow
Straightener
(if used)
Downstream Diameters
With Flow StraightenerNo Flow
Straightener
Flow straightener (if used)
Minimum Required
With Flow
Straightener
ExampleAACC’BB
110 DN/AN/AN/A5 D5 D
215 D10 D8 D2 D5 D5 D
330 D15 D13 D2 D 5 D5 D
410 DN/AN/AN/A5 D5 D
520 D10 D8 D2 D5 D5 D
650 D25 D23 D2 D5 D5 D
D = Internal diameter of channel.
Figure 4. Recommended Pipe Length Requirements for Installation
Install the in-line ow meter between two conventional pipe anges as shown in Figures 6 and
7. Table 1 provides the recommended minimum stud bolt lengths for wafer-style meter body size
and different ange ratings.
The meter's inside diameter is equal to the same size nominal pipe ID in schedule 80. For
example, a 2” meter has an ID of 1.939” (2” schedule 80). Do not install the meter in a pipe with an inside diameter smaller than the inside diameter of the meter. For schedule 160 and higher
pipe, a special meter is required. Consult the factory before purchasing the meter.
In-line meters require customer-supplied gaskets. When selecting gasket material, make sure that
it is compatible with the process uid and pressure ratings of the specic installation. Verify that
the inside diameter of the gasket is larger than the inside diameter of the ow meter and adjacent
piping. If the gasket material extends into the ow stream, it will disturb the ow and cause
inaccurate measurements.
Table 1. Minimum Recommended Stud Bolt Lengths for Wafer Meters
The required bolt load for sealing the gasket joint is affected by several application-dependent
factors; therefore, the required torque for each application may be different. Refer to the ASME
Pressure Vessel Code guidelines for bolt tightening standards.
Install the wafer-style meter between two conventional pipe anges of the same nominal
size as the ow meter. If the process uid is a liquid, make sure the meter is located where
the pipe is always full. This may require locating the meter at a low point in the piping
system. Note: Vortex ow meters are not suitable for two-phase ows (i.e., liquid and gas
mixtures). For horizontal pipelines having a process temperature above 300° F, mount the
meter at a 45 or 90 angle to avoid overheating the electronics enclosure. To adjust the
viewing angle of the enclosure or display/keypad, see page 34 and 35.
Figure 6. Wafer-Style Flow Meter Installation
CAUTION
When using toxic or corrosive gases, purge the line with inert gas for a minimum of four hours at
full gas ow before installing the ow meter.
When installing the meter make sure the section marked with a ow arrow is positioned
upstream of the outlet, with the arrow head pointing in the direction of ow. (The mark
is on the wafer adjacent to the enclosure mounting neck.) This ensures that the sensor
head is positioned downstream of the vortex shedder bar and is correctly aligned to the
ow. Installing the meter opposite this direction will result in completely inaccurate ow
measurement. To install the meter:
1. Conrm that the installation site meets the required minimum upstream and
downstream pipe diameters. Turn off the ow of process gas, liquid or steam. Verify
that the line is not pressurized.
2. Insert the studs for the bottom side of the meter body between the pipe anges. Place
the wafer-style meter body between the anges with the end stamped with a ow arrow
on the upstream side, with the arrow head pointing in the direction of ow. Center the
meter body inside the diameter with respect to the inside diameter of the adjoining
piping.
3. Position the gasket material between the mating surfaces. Make sure both gaskets are
smooth and even with no gasket material extending into the ow prole. Obstructions
in the pipeline will disturb the ow and cause inaccurate measurements.
4. Place the remaining studs between the pipe anges. Tighten the nuts in the sequence
shown in Figure 5. Check for leaks after tightening the ange bolts.
Install the ange-style meter between two conventional pipe anges of the same nominal
size as the ow meter. If the process uid is a liquid, make sure the meter is located where
the pipe is always full. This may require locating the meter at a low point in the piping
system. Note: Vortex ow meters are not suitable for two-phase ows (i.e., liquid and gas
mixtures). For horizontal pipelines having a process temperature above 300° F, mount the
meter at a 45° or 90° angle to avoid overheating the electronics enclosure. To adjust the
viewing angle of the enclosure or display/keypad, see page 34 and 35.
Figure 7. Flange-Style Flow Meter Installation
CAUTION
When using toxic or corrosive gases, purge the line with inert gas for a minimum of four hours at
full gas ow before installing the ow meter.
When installing the meter make sure the ange marked with a ow arrow is positioned
upstream of the outlet ange, with the arrow head pointing in the direction of ow. (The
mark is on the ange adjacent to the enclosure mounting neck.) This ensures that the
sensor head is positioned downstream of the vortex shedder bar and is correctly aligned to
the ow. Installing the meter opposite this direction will result in completely inaccurate
ow measurement. To install the meter:
1. Conrm that the installation site meets the required minimum upstream and
downstream pipe diameters. Turn off the ow of process gas, liquid or steam. Verify
that the line is not pressurized.
2. Seat the meter level and square on the mating connections with the ange stamped
with a ow arrow on the upstream side, with the arrow head pointing in the direction
of ow. Position a gasket in place for each side. Make sure both gaskets are smooth
and even with no gasket material extending into the ow prole. Obstructions in the
pipeline will disturb the ow and cause inaccurate measurements.
3. Install bolts in both process connections. Tighten the nuts in the sequence shown in
Figure 5. Check for leaks after tightening the ange bolts.
2.3 F-2700 SERIES INSERTION FLOW METER INSTALLATION
Prepare the pipeline for installation using either a standard or hot tap method described on the
following pages. Refer to a standard code for all pipe tapping operations. The following tapping
instructions are general in nature and intended for guideline purposes only. Before installing the
meter, review the mounting position and isolation value requirements given below.
Mounting Position
Allow clearance between the electronics enclosure top and any other obstruction when the meter
is fully retracted.
Isolation Valve Selection
Always install an isolation valve with insertion style meters. If you supply the isolation valve, it
must meet the following requirements:
1. A minimum valve bore diameter of 1.875" is required, and the valve’s body size should be 2".
Normally, gate valves are used.
2. Verify that the valve’s body and ange
rating are within the ow meter’s maximum operating pressure and temperature.
3. Choose an isolation valve with at least two inches existing between the ange face and the
gate portion of the valve. This ensures that the ow meter’s sensor head will not interfere with
the operation of the isolation valve.
When using toxic or corrosive gases, purge the line with inert gas for a minimum of four hours at
full gas ow before installing the ow meter.
Refer to a standard code for all pipe tapping operations. The following tapping
instructions are general in nature and intended as a guideline only.
1. Conrm that the installation site meets the minimum upstream and downstream pipe
diameter requirements. See Figure 4.
2. Turn off the ow of process gas, liquid or steam. Verify that the line is not pressurized.
3. Use a cutting torch or sharp cutting tool to tap into the pipe. The pipe opening must be
at least 1.875" in diameter. (Do not attempt to insert the sensor probe through a smaller
hole.)
4. Remove all burrs from the hole. Rough edges may cause ow prole distortions that
could affect ow meter accuracy. Also, obstructions could damage the sensor assembly
when inserting into the pipe.
WARNING
All ow meter connections, isolation valves and ttings for cold tapping must have the same or
higher pressure rating as the main pipeline.
5. After cutting, measure the thickness of the cut-out and record this number for
calculating the insertion depth.
6. Weld the ow meter pipe connection onto the pipe.
Make sure this connection is within ± 5°
perpendicular to the pipe centerline.
7. Install the isolation valve.
8. When welding is complete and all ttings are installed, close the isolation valve or cap
the line. Run a static pressure check on the welds. If pressure loss or leaks are detected,
repair the joint and re-test.
9. Connect the meter to the pipe process connection.
10. Calculate the sensor probe insertion depth and insert the sensor probe into the pipe as
described on the following pages.
Connect meter to valve, calculate
insertion depth, install flow meter
WARNING
Hot tapping must be performed by a trained professional. US regulations often require a hot tap
permit. The manufacturer of the hot tap equipment and/or the contractor performing the hot tap is
responsible for providing proof of such a permit.
Refer to a standard code for all pipe tapping operations. The following tapping instructions
are general in nature and intended as a guideline only.
1. Conrm that the installation site meets the minimum upstream and downstream pipe
diameter requirements.
2. Weld a 2" mounting adapter on the pipe. Make sure the mounting adapter is within ± 5°
perpendicular to the pipe centerline (see previous page). The pipe opening must be at least
1.875" in diameter.
3. Connect a 2" process connection on the mounting adapter.
4. Connect an isolation valve on the process connection. The valve’s full open bore must be
at least 1.875" in diameter.
5. Run a static pressure check on the welds. If pressure loss or leaks are detected, repair the
joint and re-test.
6. Connect the hot tapping equipment to the isolation valve, open the isolation valve and
drill at least a 1.875" diameter hole.
7. Retract the drill, close the isolation valve, and remove the hot tapping equipment.
8. Connect the ow meter to the isolation valve and open the isolation valve.
9. Calculate the sensor probe insertion depth and insert the sensor probe into the pipe as
described on the following pages.
WARNING
All ow meter connections, isolation valves, and ttings for hot tapping must have the same or
higher pressure rating as the main pipeline.
The sensor head must be properly positioned in the pipe. For this reason, it is important that
insertion length calculations are carefully followed. A sensor probe inserted at the wrong depth
in the pipe will result in inaccurate readings.
Insertion ow meters are applicable to pipes 2" and larger. For pipe sizes 10" and smaller, the
centerline of the meter’s sensing head is located at the pipe’s centerline. For pipe sizes larger than
10", the centerline of the sensing head is located in the pipe’s cross section 5" from the inner wall
of the pipe; i.e., its “wetted” depth from the wall to the centerline of the sensing head is 5".
Insertion ow meters are available in two probe lengths:
Standard Probe conguration is used with most ow meter process connections. The length, S, of
the stem is 29.47".
12-Inch Extended Probe conguration is used with exceptionally lengthy ow meter process
connections. The length, S, of the stem is 41.47".
Use the Correct Insertion Formula
Depending on your ow meter’s process connection, use the applicable insertion length formula
and installation procedure as follows:
• Flow meters with a packing gland type connection (NPT or anged) congured with an
insertion tool, follow the instructions beginning on page 29.
• Flow meters with a packing gland type connection (NPT or anged) without an insertion tool,
follow the instructions beginning on page 32.
WARNING
An insertion tool must be used for any installation where a ow meter is inserted under pressure
greater than 50 psig.
2.4.1 Installing Flow Meters with a Packing Gland Connection*
Use the formula below to determine the insertion depth for ow meters (NPT and anged)
equipped with an insertion tool. To install, see the next page for instructions for meters
with a permanent insertion tool. For meters with a removable insertion tool, see page 33.
Insertion Length Formula
I = F + R + t – 1.35
Where:
I
I = Insertion length.
F = Distance from the raised face of the ange or top of
the process connection for NPT style meters to the
top outside of the process pipe.
F
t
R
R = Pipe inside diameter ÷ 2 for pipes ten" & smaller.
R = Five" for pipe diameters larger than ten".
t = Thickness of the pipe wall. (Measure the disk
cutout from the tapping procedure or check a piping
handbook for thickness.)
Figure 10. Insertion Calculation (Meters with Insertion Tool)
Example 1: Flange Style Meters:
To install an insertion style ow meter into a 14" schedule 40 pipe, the following
measurements are taken:
F = 12"
R = 5"
t = 0.438"
The example insertion length is 16.09".
Example 2: NPT Style Meters:
The length of thread engagement on the NPT style meters is also subtracted in the equation.
The length of the threaded portion of the NPT meter is 1.18". Measure the thread portion
still showing after the installation and subtract that amount from 1.18". This gives you the
thread engagement length. If this cannot be measured use .55" for this amount.
2.4.2 Insertion Procedure for Flow Meters with Permanent Insertion Tool
!
!i !
Figure 11. Flow Meter with Permanent Insertion Tool
1. Calculate the required sensor probe insertion length (see previous page). Measure
from the depth marker arrow down the stanchion and scribe a mark at the calculated
insertion depth.
2. Fully retract the ow meter until the sensor head is touching the bottom of the stem
housing. Attach the meter assembly to the 2" full-port isolation valve, if used. Use
Teon tape or pipe sealant to improve seal and prevent seizing on NPT style.
3. Loosen the two packing gland nuts on the stem housing of the meter. Loosen the
stem lock bolt adjacent to the sensor alignment pointer. Align the sensor head using
the sensor alignment pointer. Adjust the alignment pointer parallel to the pipe and
pointing downstream. Tighten the stem lock bolt to secure the sensor position.
4. Slowly open the isolation valve to the full open position. If necessary, slightly
tighten the two packing gland nuts to reduce the leakage around the stem.
5. Turn the insertion tool handle clockwise to insert the sensor head into the pipe.
Continue until the top of the upper retractor bracket aligns with the insertion length
position scribed on the stanchion. Do not force the stem into the pipe.
6. Tighten the packing gland nuts to stop leakage around the stem. Do not torque over
20 ft-lb.
CAUTION
The sensor alignment pointer must point downstream, in the direction of ow.
IMPORTANT NOTE
If line pressure is above 500 psig, it could require up to 25 ft lb of torque to insert the ow meter.
Do not confuse this with possible interference in the pipe.
2.4.3 Insertion Procedure for Flow Meters with Removable Insertion Tool
!
!i !
Figure 12. Flow Meter with Removable Insertion Tool
1. Calculate the required sensor probe insertion length. Measure from the depth marker
arrow down the stanchion and scribe a mark at the calculated insertion depth.
2. Fully retract the ow meter until the sensor head is touching the bottom of the stem
housing. Attach the meter assembly to the 2" full-port isolation valve, if used. Use
Teon tape or pipe sealant to improve seal and prevent seizing on NPT style.
3. Remove the two top stem clamp nuts and loosen two stem clamp bolts. Slide the stem
clamp away to expose the packing gland nuts.
4. Loosen the two packing gland nuts. Loosen the stem lock bolt adjacent to the sensor
alignment pointer. Align the sensor head using the sensor alignment pointer. Adjust
the alignment pointer parallel to the pipe and pointing downstream. Tighten the stem
lock bolt to secure the sensor position.
5. Slowly open the isolation valve to the full open position. If necessary, slightly tighten
the two packing gland nuts to reduce the leakage around the stem.
6. Turn the insertion tool handle clockwise to insert the stem into the pipe. Continue
until the top of the upper retractor bracket lines up with the insertion length mark
scribed on the stanchion. Do not force the stem into the pipe.
CAUTION
The sensor alignment pointer must point downstream in the direction of ow.
IMPORTANT NOTE
If line pressure is above 500 psig, it could require up to 25 ft lb of torque to insert the ow meter.
Do not confuse this with possible interference in the pipe.
7. Tighten the packing gland nuts to stop leakage around the stem. Do not torque over 20 ft-lbs.
8. Slide the stem clamp back into position. Torque stem clamp bolts to 15 ft-lbs. Replace the stem
clamp nuts and torque to 10-15 ft-lbs.
9. To separate the insertion tool from the ow meter, remove four socket head cap bolts securing
the upper and lower retractor brackets. Remove the insertion tool.
2.4.4 Installation of Meters with Packing Gland Connection (No Insertion Tool)*
Use the following formula to determine insertion depth for meters with a packing gland
connection (NPT and anged) without an insertion tool.
Insertion Length Formula
I = S - F - R - t
Where:
I = Insertion length.
S = Stem length - the distance from the center of the sensor
head to the base of the enclosure adapter (S = 29.47"
for standard probes; S = 41.47" for 12" extended probes).
F = Distance from the raised face of the ange or top of NPT
stem housing to the outside of the pipe wall.
R = Pipe inside diameter ÷ 2 for pipes 10" & smaller.
R = 5" for pipe diameters larger than 10".
t = Thickness of the pipe wall. (Measure the disk cutout
from the tapping procedure or check a piping
handbook for thickness.)
Figure 13. Insertion Calculation (Meters without Insertion Tool)
Example:
To install an insertion style ow meter with a standard probe (S = 29.47) into a 14"
schedule 40 pipe, the following measurements are taken:
F = 3"
R = 5"
t = 0.438"
The example insertion length is 21.03".
2.4.5 Insertion Procedure for Flow Meters with No Insertion Tool (Packing Gland Connection)
!
!
1. Calculate the required sensor probe insertion length.
2. Fully retract the stem until the sensor head is touching the bottom of the stem housing.
Remove the two top stem clamp nuts and loosen two stem clamp bolts. Slide the stem
clamp away to expose the packing gland nuts. Loosen the two packing gland nuts.
3. Align the sensor head using the sensor alignment pointer. Adjust the alignment pointer
parallel to the pipe and pointing downstream.
4. Insert the sensor head into the pipe until insertion length, I, is achieved. Do not force
the stem into the pipe.
5. Tighten the packing gland nuts to stop leakage around the stem. Do not torque over 20
ft-lbs.
6. Slide the stem clamp back into position. Torque stem clamp bolts to 15 ft-lbs. Replace
the stem clamp nuts and torque to 10-15 ft-lbs.
WARNING
The line pressure must be less than 50 psig for installation.
CAUTION
The sensor alignment pointer must point downstream, in the direction of ow.
Depending on installation requirements, you may need to adjust the meter orientation. There
are two adjustments available. The rst rotates the position of the LCD display/keypad and is
available on both in-line and insertion meters. The second is to rotate the enclosure position.
This adjustment is only allowed on in-line meters.
2.5.1 Display/Keypad Adjustment (All Meters)
Figure 14. Display/Keypad Viewing Adjustment
The electronics boards are electrostatically sensitive. Wear a grounding wrist strap
and make sure to observe proper handling precautions required for static-sensitive
components. To adjust the display:
1. Disconnect power to the ow meter.
2. Loosen the small set screw which secures the electronics enclosure cover. Unscrew
and remove the cover.
3. Loosen the four captive screws.
4. Carefully pull the display/microprocessor board away from the meter standoffs. Make
sure not to damage the connected ribbon cable.
5. Rotate the display/microprocessor board to the desired position. Maximum turn, two
positions left or two positions right (180°).
6. Align the board with the captive screws. Check that the ribbon cable is folded neatly
behind the board with no twists or crimps.
7. Tighten the screws. Replace the cover and set screw. Restore power to the meter.
To avoid potential electric shock, follow National Electric Code safety practices or your local code
when wiring this unit to a power source and to peripheral devices. Failure to do so could result in
injury or death. All wiring procedures must be performed with the power off.
The NEMA 4X enclosure contains an integral wiring compartment with one dual strip terminal
block (located in the smaller end of the enclosure). Two ¾" female NPT conduit entries are
available for separate power and signal wiring. For all hazardous area installations, make sure
to use an agency-approved tting at each conduit entry. If conduit seals are used, they must be
installed within 18" (457 mm) of the enclosure.
Figure 16. Wiring Terminals for Loop-Powered Version
2.6.1 Input Power Connections
To access the wiring terminal blocks, locate and loosen the small set screw which locks
the small enclosure cover in place. Unscrew the cover to expose the terminal block.
DC Power Wiring
Connect 4-20 mA loop power (12 to 36 VDC at 25 mA, 1W max.) to the +Loop Power and
–Loop Power terminals on the terminal block. Torque all connections to 4.43 to 5.31 in-lbs
(0.5 to 0.6 Nm). The DC power wire size must be 20 to 10 AWG with the wire stripped ¼"
(7 mm).
The loop powered meter has a single 4-20 mA loop. The 4-20 mA loop current is
controlled by the meter electronics. The electronics must be wired in series with the sense
resistor or current meter. The current control electronics requires at least 12 volts at the
input terminals to operate correctly.
The maximum loop resistance (load) for the current loop output is dependent upon the
supply voltage and is given in Figure 18. The 4-20 mA loop is optically isolated from the
ow meter electronics.
R
is the total resistance in the loop, including the wiring resistance (R
load
To calculate R
, the maximum Rl
max
from the supply voltage and divide by the maximum loop current, 20 mA. Thus:
= R
for the loop, subtract the minimum terminal voltage
The pulse output is used for remote totalization. When the preset volume or mass (dened
in the totalizer settings, see page 62) has passed the meter, the output provides a 50
millisecond square pulse.
The pulse output requires a separate 5 to 36 VDC power supply. The pulse output optical
relay is a normally-open single-pole relay. The relay has a nominal 200 volt/160 ohm
rating. This means that it has a nominal on-resistance of 160 ohms, and the largest voltage
that it can withstand across the output terminals is 200 volts. However, there are current
and power specications that must be observed. The relay can conduct a current up
to 40 mA and can dissipate up to 320 mW. The relay output is isolated from the meter
electronics and power supply.
Figure 19. Isolated Pulse Output Using External Power Supply
Figure 20. Non-Isolated Pulse Output Using External Power Supply
Select resistor so that current
through Freq. Out <= 40 mA
Freq. Out voltage = +V
Select resistor so that current through Freq. Out <= 40 mA
Freq. Out
+
Freq. Out -
12 to 36 VDC
35 mA max.
The frequency output is used for a remote counter. It can be scaled to output a 1 to 10 kHz
signal proportional to mass or volume ow, temperature, pressure or density.
The frequency output requires a separate 5 to 36 VDC power supply and there are current
and power specications that must be observed when using this output. The output can
conduct a current up to 40 mA and can dissipate up to 200 mW. The output is isolated
from the meter electronics and power supply.
Figure 21. Isolated Frequency Output Using External Power Supply
Figure 22. Non-Isolated Frequency Output Using External Power Supply
2.6.5 Optional Backlight Connection
The loop power meter has an optional backlight connection provided. It is intended to be
powered by a separate 12 to 36 VDC at 35 mA max. power supply or by the pulse power
input. Both options are shown below.
The remote electronics enclosure should be mounted in a convenient, easy to reach
location. For hazardous location installations, make sure to observe agency requirements
for installation. Allow some slack in the interface cable between the junction box and the
remote electronics enclosure. To prevent damage to the wiring connections, do not put
stress on the terminations at any time.
The meter is shipped with temporary strain relief glands at each end of the cable.
Disconnect the cable from the meter’s terminal block inside the junction box - not at the
remote electronics enclosure. Remove both glands and install appropriate conduit entry
glands and conduit. When installation is complete, re-connect each labeled wire to the
corresponding terminal position on the junction box terminal block. Make sure to connect
each wire pair’s shield. Note: Incorrect connection will cause the meter to malfunction.
To avoid potential electric shock, follow National Electric Code safety practices or your local code
when wiring this unit to a power source and to peripheral devices. Failure to do so could result in
injury or death. All AC power connections must be in accordance with published CE directives.
All wiring procedures must be performed with the power off.
The NEMA 4X enclosure contains an integral wiring compartment with one dual strip terminal
block (located in the smaller end of the enclosure). Two 3/4" female NPT conduit entries are
available for separate power and signal wiring. For all hazardous area installations, make sure
to use an agency-approved tting at each conduit entry. If conduit seals are used, they must be
installed within 18" (457 mm) of the enclosure.
Figure 26. AC Wiring Terminals
2.7.1 Input Power Connections
To access the wiring terminal blocks, locate and loosen the small set screw which locks
the small enclosure cover in place. Unscrew the cover to expose the terminal block.
The AC wire insulation temperature rating must meet or exceed 85°C (185°F).
AC Power Wiring
The AC power wire size must be 20 to 10 AWG with the wire stripped 1/4 inch (7 mm).
The wire insulation temperature must meet or exceed 185°F (85°C). Connect 100 to 240
VAC (5 W maximum) to the Hot and Neutral terminals on the terminal block. Connect the
ground wire to the safety ground lug ( ). Torque all connections to 4.43 to 5.31 in-lbs
(0.5 to 0.6 Nm). Use a separate conduit entry for signal lines to reduce the possibility of
AC noise interference.
100 to 240 VAC @ 5 Watts Max.
Chassis screw safety
ground must be used
for proper operation.
Figure 27. AC Power Connections
4-20
mA 3
4-20
mA 1
DC
PWR
+ - +
4-20
mA 2
- + - +
RS485
RS485
RS485 GND
-
OPTION 2
+
ALARM
2
PULSE
OUT
FREQ
OUT
+ -+
ALARM
1
-+-
4
OPTION 1
1 2 3152 3
ALARM
3
- + -
4 5
+
-
!
18 to 36 VDC @ 300 mA Max.
Figure 28. DC Wiring Terminals
DC Power Wiring
The DC power wire size must be 20 to 10 AWG with the wire stripped 1/4" (7 mm).
Connect 18 to 36 VDC (300 mA, 9 W maximum) to the +DC Pwr and –DC Pwr terminals
on the terminal block. Torque all connections to 4.43 to 5.31 in-lbs (0.5 to 0.6 Nm).
Figure 29. DC Power Connections
CAUTION
The DC wire insulation temperature rating must meet or exceed 185°F (85°C).
The externally powered versions of the meters have a single 4-20 mA loop powered
output. Two additional loops are available on the optional communication board. The 4-20
mA loop current is controlled by the meter electronics. The electronics must be wired in
series with the sense resistor or current meter. The current control electronics require a
minimum of 12 volts at the input terminals to operate correctly.
The maximum loop resistance (load) for the current loop output is dependent upon the
supply voltage and is given in Figure 30. The 4-20 mA loop is optically isolated from the
ow meter electronics.
R
is the total resistance in the loop, including the wiring resistance (R
load
To calculate R
, the maximum R
max
load
from the supply voltage and divide by the maximum loop current, 20 mA. Thus:
load
= R
wire
+ R
sense
).
for the loop, subtract the minimum terminal voltage
The maximum resistance R
load
= R
max
= (V
– 12V) / 0.020 A
supply
Figure 30. Load Resistance Versus Input Voltage
4-20 mA voltage = +V
For Hart communications,
signal loop must have a
minimum of 250 ohms load
resistance RL.
R
L
> 250
mA
Meter
Figure 31. Isolated 4–20 mA Output Using External Power Supply
For HART
communications
the signal loop
must have a
minimum of 250
ohms load
resistance.
AC units only
Meter Provided DC
Power
R
L
> 250 Ohm
24 VDC
24 VDC
For HART
communications
the signal loop
must have a
minimum of 250
ohms load
resistance.
mA Meter
Figure 32. Non-Isolated 4–20 mA Output Using Meter Input Power Supply
Figure 33. Isolated 4–20 mA Output Using Meter Provided Power Supply
2.7.3 Frequency Output Connections
The frequency output is used for a remote counter. It can be scaled to output a 1 to 10 kHz
signal proportional to mass or volume ow, temperature, pressure or density.
The frequency output requires a separate 5 to 36 VDC power supply; however, there are
current and power specications that must be observed. The output can conduct a current
up to 40 mA and can dissipate up to 200 mW. The output is isolated from the meter
electronics and power supply.
There are three connection options for the frequency output. The rst has a separate power
supply (Figure 36). The second uses the ow meter power supply (Figure 37)
(DC powered units only), and the third uses the internal 24 VDC power supply (Figure 38)
(AC powered units only). Use the rst option with a separate power supply (5 to 36 VDC)
if a specic voltage is needed for the frequency output. Use the second conguration if
the voltage at the ow meter power supply is an acceptable driver voltage for the load
connected. (Take into account that the current used by the frequency load comes from the
meter’s power supply). Use the third conguration if you have an AC powered unit only.
In any case, the voltage of the frequency output is the same as the voltage supplied to the
circuit.
Freq. Out voltage = +V
Select resistor so that current
through Freq. Out ≤ 40 mA.
Figure 34. Isolated Frequency Output Using External Power Supply
DC powered meters only
DC Powered meters only
R current limit ~10K
PWR
PWR
Freq. Out voltage = + Power voltage for meter
. Out +
Freq
Freq. Out -
Figure 35. Non-Isolated Frequency Output Using Input Power Supply
AC units only
Meter provided DC power
Figure 36. Isolated Frequency Output Using Meter Provided Power Supply
2.7.4 Pulse Output Connections
The pulse output is used for a remote counter. When the preset volume or mass (dened
in the totalizer settings, on page 62) has passed the meter, the output provides a 50
millisecond square pulse.
The pulse output optical relay is a normally-open single-pole relay. The relay has a
nominal 200 V / 160 ohm rating. This means that it has a nominal on-resistance of 160
ohms, and the largest voltage that it can withstand across the output terminals is 200 V.
However, there are current and power specications that must be observed. The relay
can conduct a current up to 40 mA and can dissipate up to 320 mW. The relay output is
isolated from the meter electronics and power supply.
There are three connection options for the pulse output. The rst had a separate power
supply (Figure 34). The second uses the ow meter power supply (Figure 35)
(DC powered units only), and the third uses the internal 24 VDC power supply (Figure
2-32)(AC powered units only). Use the rst option with a separate power supply (5 to 36
VDC) if a specic voltage is needed for the pulse output. Use the second conguration
if the voltage at the ow meter power supply is an acceptable driver voltage for the load
connected. (Take into account that the current used by the pulse load comes from the
meter’s power supply). Use the third conguration if you have an AC powered unit
only. In any case, the voltage of the pulse output is the same as the voltage supplied to
the circuit.
One alarm output (Alarm 1) is included on the standard meter. Two or more alarms (Alarm
2 and Alarm 3) are included on the optional communication board. The alarm output
optical relays are normally open single-pole relays. The relays have a nominal 200 V /
160 ohm rating. This means that each relay has a nominal on-resistance of 160 ohms and
the largest voltage that it can withstand across the output terminals is 200 V. However,
there are current and power specications that must be observed. The relay can conduct
a current up to 40 mA and can dissipate up to 320 mW. The relay output is isolated from
the meter electronics and power supply. When the alarm relay is closed, the current draw
will be constant. Make sure to size Rload appropriately.
There are three connection options for the alarm output. The rst has separate power
supply (Figure 37). The second uses the ow meter power supply (Figure 38) (DC powered
units only) and the third uses the meter provided power supply (Figure 39)(AC powered
units only). Use the rst option with a separate power supply (5 to 36 VDC) if a specic
voltage is needed for the alarm output. Use the second conguration if the voltage at the
ow meter power supply is an acceptable driver voltage for the load connected. (Take into
account that the current used by the alarm load comes from the meter’s power supply).
Use the third if you have an AC powered unit only. In any case, the voltage of the alarm
output is the same as the voltage supplied to the circuit.
The alarm output is used for transmitting high or low process conditions as dened in the
alarm settings (see page 61).
Pulse voltage = +V
Select resistor so that current
through pulse ≤ 40 mA.
Figure 40 Isolated Alarm Output Using External Power Supply
Figure 41. Non-Isolated Alarm Output Using Internal Power Supply
AC units only
Meter provided
DC power
Figure 42. Isolated Alarm Output Using Meter Provided Power Supply
The remote electronics enclosure should be mounted in a convenient, easy to reach
location. For hazardous location installations, make sure to observe agency requirements
for installation. Allow some slack in the interface cable between the junction box and the
remote electronics enclosure. To prevent damage to the wiring connections, do not put
stress on the terminations at any time.
The meter is shipped with temporary strain relief glands at each end of the cable.
Disconnect the cable from the meter’s terminal block inside the junction box, not at the
remote electronics enclosure. Remove both glands and install appropriate conduit entry
glands and conduit. When installation is complete, re-connect each labeled wire to the
corresponding terminal position on the junction box terminal block. Make sure to connect
each wire pair’s shield. Note: Incorrect connection will cause the meter to malfunction.
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com
Figure 43. High Power Flow Meter Junction Box Sensor Connections
IMPORTANT NOTE
Numeric code in junction box label matches wire labels.
The meter has two optional input wiring terminals. These can be used to input a remote
or second RTD input in the case of an energy monitoring meter, for the input of a remote
pressure transducer, to pass a contact closure or for a remote density measurement to
name a few. In any case, the wiring diagram will be included with the meter if any of the
options are specied. Otherwise, the optional terminal blocks will be left blank and
non-functional.
2.7.8 OPTIONAL ENERGY EMS RTD INPUT WIRING
Figure 44. Optional Energy EMS RTD Input Wiring
The recommended customer supplied second RTD is a Class A 1000 ohm 4-wire platinum
RTD. If a second RTD is not being used, then the factory supplied 1000 ohm resistor needs
to be installed in its place.
The meter is set to have Option 1 used for the external input. Programming menus that
pertain to the optional 4-20 mA input are located in the Hidden Diagnostics Menu in
section 5.
Figure 45. External 4-20 mA Input Wiring - External Power Supply
Follow the above diagram to wire the external 4-20 mA input into the ow meter using an
external power supply.
Figure 46. External 4-20 mA Input Wiring - DC Powered Meter
Follow the above diagram to wire the external 4-20 mA input into the ow meter using
power supplied to the input of a DC powered meter.
Option 2Option 1
1234512345
Ext. 4-20 mA
Input Device
+ 24 VDC OUT
- 24 VDC OUT
AC units only. Meter
provided DC power.
Option 2Option 1
1234512345
Figure 47. External 4-20 mA Input Wiring - AC Powered Meter
Follow the above diagram to wire the external 4-20 mA input into the ow meter using
power from the 24 VDC output of an AC powered meter.
2.7.10 OPTIONAL CONTACT CLOSURE INPUT WIRING
Figure 48. Optional Contact Closure Input Wiring
Follow the above diagram to wire an external switch input into the ow meter. The meter
is congured to have Option 1 used for the external input. If the above switch is used
to remotely reset the totalizer, a pushbutton switch with a momentary contact closure is
recommended.
After installing the vortex ow meter, you are ready to begin operation. The sections in this chapter
explain the display/keypad commands, meter start-up and programming. The meter is ready to operate
at start-up without any special programming. To enter parameters and system settings unique to your
operation, see the following pages for instructions on using the set-up menus.
3.1 FLOW METER DISPLAY/KEYPAD
The ow meter’s digital electronics allow you to set, adjust
and monitor system parameters and performance. A full range
of commands are available through the display/keypad. The
LCD display gives 2 x 16 characters for ow monitoring and
programming. The six push-buttons can be operated with the
enclosure cover removed. Or, the explosion proof cover can
remain in place and the keypad operated with a hand-held
magnet positioned at the side of the enclosure as shown in the
illustration at the left.
From the Run Mode, the ENTER key allows access
to the Set-up Menus (through a password screen).
Within the Set-up Menus (through a password
screen). Within the Set-up Menus, pressing ENTER
activates the current eld. To set new parameters,
press the ENTER key until an underline cursor
appears. Use the ⇑ ⇓ ⇐ ⇒ keys to select new
parameters. Press ENTER to continue. (If change
is not allowed, ENTER has no effect.) All outputs
are disabled when using the Set-up Menus.
The EXIT key is active within the Set-up Menus.
When using a Set-up Menu, EXIT returns you to
the Run Mode. If you are changing a parameter
and make a mistake, EXIT allows you to start over.
The ⇑ ⇓⇐⇒ keys advance through each screen
of the current menu. When changing a system
parameter, all ⇑ ⇓ ⇐ ⇒ keys are available to enter
1. Verify the ow meter is installed and wired as described in Section 2.
2. Apply power to the meter. At start-up, the unit runs a series of self-tests that check the RAM,
ROM, EPROM and all ow sensing components. After completing the self-test sequence, the
Run Mode screens appear.
3. The Run Mode displays ow information as determined by system settings. Some screens
depicted on the next page may not be displayed based on these settings. Press the ⇑⇓ arrow
keys to view the Run Mode screens.
4. Press the ENTER key from any Run Mode screen to access the Set-up Menus. Use the Set-up
Menus to congure the meter’s multi-parameter features to t your application.
IMPORTANT NOTICE
Starting the ow meter or pressing EXIT will always display the Run Mode screens.
1. Enter the Set-up Menu by pressing the ENTER key until prompted for a password. (All
outputs are disabled while using the Set-up Menus.)
2. Use the ⇑ ⇓ ⇐ ⇒keys to select the password characters (1234 is the factory-set
password). When the password is correctly displayed, press ENTER to continue.
3. Use the Set-up Menus described on the following pages to customize the
multiparameter features of F-2600 & F-2700 Flow Meters. (The entire lower display
line is available for entering parameters.) Some items depicted in the graphic on the
preceding page may not be displayed based on ow meter conguration settings.
4. To activate a parameter, press ENTER. Use the ⇑ ⇓ ⇐ ⇒ keys to make selections. Press
ENTER to continue. Press EXIT to save or discard changes and return to Run Mode.
5. Program the UNITS menu rst because later menus will be based on the units selected.
The following shows how to set Output 1 to measure mass ow with 4 mA = 0 lb/hr and
20 mA = 100 lb/hr with a time constant of ve seconds. (All outputs are disabled while
using the Set-up Menus.)
First, set the desired units of measurement:
1. Use ⇐⇒keys to move to the Units Menu (see page 64).
2. Press ⇓ key until Mass Flow Unit appears. Press ENTER.
3. Press ⇓ key until lb appears in the numerator. Press ⇒ key to move the underline
cursor to the denominator. Press the ⇓ key until hr appears in the denominator.
Press ENTER to select.
4. Press ⇑ key until Units Menu appears.
Second, set the analog output:
1. Use ⇐⇒ keys to move to the Output Menu.
2. Press the ⇓ key until 4-20 mA Output 1 appears.
3. Press ⇓ key to access Measure selections. Press ENTER and press the ⇓ key to select
Mass. Press ENTER.
4. Press ⇒ key to set the 4 mA point in the units you have selected for mass of lb/hr.
Press ENTER and use ⇑⇓⇐⇒ keys to set 0 or 0.0. Press ENTER.
5. Press ⇒ key to set the 20 mA point. Press ENTER and use ⇑⇓⇐⇒ keys to set 100
or 100.0. Press ENTER.
6. Press ⇒ key to select the Time Constant. Press ENTER and use ⇑⇓⇐⇒ keys to
select 5. Press ENTER.
7. Press the EXIT key and answer YES to permanently save your changes.
If Cycle Time is set to zero, manual advance is required.
Used to set the number of digits displayed after the decimal point.
MF = Mass Flow
Vf = Volume Flow
Te = Temperature
Pr = Pressure
De = Density
T = Total
A1 = Alarm 1 Status
A2 = Alarm 2 Status
A3 = Alarm 3 Status
Fl = Fluid
Dt = Density
For each parameter:
Select Yes to view parameter in Run Mode.
Select No to hide parameter in Run Mode.
Display TC (sec)
1
TC = Display Time constant, used to smooth display.
*
E = Energy
*
Energy Meters Only
Use
keys to access menus
Use the Display Menu to set the cycle time for automatic screen sequencing used in the
Run Mode, change the precision of displayed values, smooth the values or enable or
disable each item displayed in the Run Mode screens.
Example for Changing a Run Mode Display Item
The following shows how to remove the temperature screen from the Run Mode screens.
Note: All outputs are disabled while using the Set-up Menus.
1. Use ⇐ ⇒ keys to move to the Display Menu.
2. Press ⇓ key until Mf Vf Pr Te De T appears.
3. Press ENTER to select. Press ⇒key until the cursor is positioned below Te.
4. Press ⇓ key until N appears. Press ENTER to select.
5. Press EXIT and then ENTER to save changes and return to the Run Mode.
Physical Layer does not exist on Two Wire
Mass - Accessible via HART
<Measure>
None
Mass
Volume
Temp 1,2
Press
Density
**
Energy
<Measure>
None
Mass
Volume
Temp 1,2
Press
Density
**
Energy
<Measure>
None
Mass
Volume
Temp 1,2
Press
Density
**
Energy
<Mode>
None
HIGH Alarm (>)
LOW Alarm (<)
<Mode>
None
HIGH Alarm (>)
LOW Alarm (<)
<Mode>
None
HIGH Alarm (>)
LOW Alarm (<)
<Measure> units
<Measure> units
*
**
Energy Meters Only
Example for Setting an Alarm
The following shows how to set Relay Alarm 1 to activate if the mass ow rate is greater
than 100 lb/hr. You can check the alarm conguration in the Run Mode by pressing the
⇑⇓ keys until Alarm (1) appears. The lower line displays the mass ow rate at which the
alarm activates. Note: All outputs are disabled while using the Set-up Menus.
First, set the desired units of measurement:
1. Use ⇐⇒ keys to move to the Units Menu (see to page 64).
2. Press ⇓ key until Mass Flow Unit appears. Press ENTER.
3. Press ⇓ key until lb appears in the numerator. Press ⇒ key to move the underline
cursor to the denominator. Press the ⇓ key until hr appears in the denominator. Press
ENTER to select.
4. Press ⇑ key until Units Menu appears.
Second, set the alarm:
1. Use ⇐⇒ keys to move to the Alarms Menu.
2. Press the ⇓ key until Relay Alarm 1 appears.
3. Press ⇒ key to access Measure selections. Press ENTER and use the ⇓ key to select
Mass. Press ENTER.
4. Press ⇒ key to select the alarm Mode. Press ENTER and use ⇓ key to select HIGH
Alarm. Press ENTER.
5. Press ⇒ key to select the value that must be exceeded before the alarm activates.
Press ENTER and use ⇑⇓⇐⇒ keys to set 100 or 100.0. Press ENTER.
6. Press the EXIT key to save your changes. (Alarm changes are always permanently
saved. Up to three relay alarm outputs are available depending on meter
conguration.)
If unit per pulse is set to 600 gallons per pulse,
the totalizer will pulse once every minute.
Reset Total ?
YES or NO
Use the Totalizer Menu to congure and monitor the totalizer. The totalizer output is a 50
millisecond (.05 second) positive pulse (relay closed for 50 milliseconds). The totalizer
cannot operate faster than one pulse every 100 millisecond (.1 second). A good rule to
follow is to set the unit per pulse value equal to the maximum ow in the same units per
second. This will limit the pulse to no faster than one pulse every second.
If unit per pulse is set to 10 gallons per pulse,
the totalizer will pulse once every second.
Example for Setting the Totalizer
The following shows how to set the totalizer to track mass ow in kg/sec. (All outputs are
disabled while using the Set-up Menus.)
First, set the desired units of measurement:
1. Use ⇐⇒ keys to move to the Units Menu (see to page 64).
2. Press ⇓ key until Mass Flow Unit appears. Press ENTER.
3. Press ⇓ key until kg appears in the numerator. Press ⇒ key to move the underline
cursor to the denominator. Press the ⇓ key until sec appears in the denominator. Press
ENTER to select.
4. Press ⇑ key until Units Menu appears.
Second, set the pulse output:
1. Use ⇐⇒ keys to move to the Totalizer Menu.
2. Press the ⇓ key until Totaling appears.
3. Press ENTER and press the ⇓ key to select Mass. Press ENTER.
4. Press ⇓ key to set the pulse output in the units you have selected for mass ow of kg/
sec. Press ENTER and use ⇑⇓⇐⇒ keys to set the pulse value equal to the maximum
ow in the same units per second. Press ENTER.
5. To reset the totalizer, press ⇓ key until Reset Total? appears. Press ENTER and the ⇓
key to reset the totalizer if desired. Press ENTER.
6. Press the EXIT key and answer YES to permanently save your changes.
There are several possibilities regarding the measurement of water or steam energy given
the location of the meter and the use of a second RTD. The table below summarizes the
possibilities:
FluidMeter LocationSecond RTDMeasurement
Water“Sent” Flow Line“Return” Flow LineChange in Energy
Water“Return” Flow Line“Sent” Flow LineChange in Energy
Water“Sent” Flow LineNoneOutgoing Energy
Steam“Sent” Flow Line“Return” Flow Line (condensate)Change in Energy
Steam“Sent” Flow LineNoneOutgoing Energy
As above, you must properly congure the meter in the Energy Menu.
1. Loc in Sent Flow? Select Yes or No based on where the meter is located. Refer to the
above table.
2. Heating System? Select Yes for a hot water system used for heating. Select No for a
chilled water system used for cooling. Always select Yes for a steam system.
3. % Returned. Select a number between 0% and 100%. Estimate the amount of water
that returns. It is usually 100%, or can be less than 100% if historical data shows
the amount of makeup water used. If a second RTD is not used, set to 0%. When 0%
is selected, the energy calculation represents the outgoing energy only (no return
energy is subtracted).
IMPORTANT NOTICE
The meter ships from the factory assuming 0% return and has a 1000 ohm resistor installed in the
RTD #2 wiring location. This needs to be removed if the meter is to be used in a manner other than
with 0% return and with the customer supplied RTD in its place.
Select “Steam T & P Comp” for VT and
VTP models. The VT model will display
“Sat Steam T Comp” for the fluid type
in the run mode screens.
For a V model in any fluid, enter nominal operating temperature and
pressure as simulated values in the diagnostics menu.
xxxx
xxxx
< BL
xxxx
< K1 >
xxxx
< CRIT TEMP >
xxxx
< AL >
xxxx
<MoleFract CO2>
xxxx
< CRIT Z >
xxxx
< BL
xxxx
<Ref Temp(F)>
xxxx
< AL >
xxxx
< Ref Press(PSIA)
xxxx
< BL
xxxx
< Specific Gravity >
xxxx
< Liquified Gas
Carbon Dioxide
Nitrogen
Hydrogen
Oxygen
Argon
Nitrous Oxide
< Compress (Z) >
xxxx
< Viscosity
xxxx
Use the Fluid Menu to congure the ow meter for use with common gases, liquids and
steam. Your ow meter is pre-programmed at the factory for your application’s process
uid.
Reference Richard W. Miller, Flow Measurement Engineering Handbook (Third Edition,
1996), page 2-75 for denition and use of the Goyal-Doraiswamy equation and page 2-76 for
the denition and use of the API 2540 equation. Also, see Appendix B for Fluid Calculation
equations.
The units of measurement used in the Fluid Menu are preset and are as follows:
Mole Weight = lbm/(lbm•mol), CRIT PRESS = psia, CRIT TEMP = °R, Density = kg /m3 and
Viscosity = cP (centipoise).
Ston = Short Ton = 2000 lb
Lton = Long Ton = 2240 lb
Mton = Metric Ton = 1000 kg
MilG = Million gallons
ImpG
= Imperial gallon = 1.20095 US gallons
bbl = barrels = 42 US gallons
MilL = Million liters
MBTU = Thousand BTU
MMBTU = Million BTU
Density Unit
lbm/ft3, kg/m3, gm/cc, lbm/gal,
gm/mlit, kg/lit, gm/lit, lbm/in3
Pressure Unit
psi, inH2O, ftH2O, mmH2O, in HG,
mmHG, ATM, Bar, mBar, gm/cm2, kg/cm2,
Pascal, KiloPa, MegaPa, Torr, 4inH20, 4mmH2O
Gauge Pressure Unit
Absolute / Gauge
Atm. Pressure
14.6959
4inH2O and 4mmH2O are based on
water at 4 degrees C.
Transducer reads in Absolute – if Gauge is desired
then atmospheric pressure at meter is needed.
Menu is only activated if Gage Pressure is chosen.
Enter the value in PSIA
Use the Units Menu to congure the ow meter with the desired units of measurement.
(These are global settings and determine what appears on all screens.)
Use the Time and Date Menu to enter the correct time and date into the ow meter’s
memory. The parameters are used in the Run Mode and the alarm and system log les.
Password
ENTER
Time & Date
Menu
Set Time
xx:xx:xx
Set Date
xx/xx/xx
Use
keys to access menus
IMPORTANT NOTICE
Time is displayed in AM/PM format, but military format is used to set the time. For example; 1:00
PM is entered as 13:00:00 in the Set Time menu.
Example for Setting the Time
How to set the time to 12:00:00. You can check the time in the Run Mode by pressing the
⇑ ⇓ keys until the Time & Date screen appears. Note: All outputs are disabled while using
the Set-up Menus.
1. Use ⇐⇒ keys to move to the Time and Date Menu.
2. Press ⇓ key until Set Time appears. Press ENTER.
3. Press ⇓ key until 1 appears. Press ⇒ key to move the underline cursor to the next digit.
Press the ⇓ key until 2 appears. Continue sequence until all desired parameters are
entered. Press ENTER to return to the Time and Date Menu.
For a volumetric flow meter used with any fluid, enter nominal operating
temperature and pressure as simulated values in the diagnostics menu.
* The unit of measure of the displayed value is the
same as the unit configured for the flow meter.
Momentarily displayed
Use Left and Right
SysLog File #xx System Log File
arrows to access all
system log files.
Clear Sys LOG?
YES or NO
Time
Date
Press EXIT to return
to System LOG
Use the Diagnostics Menu to simulate operation and review the system les. The
system log les contain time/date stamped messages including: power on, power off,
programming time outs, parameter faults, incorrect password entry and other various
information relative to system operation and programming.
The simulated inputs are for testing the meter to verify that the programming is correct.
They are also used to enter nominal operating temperature and pressure for the V
(volumetric) only model. Simulated vortex frequency allows you to enter any value for
the sensor input in Hz. The meter will calculate a ow rate based on the corresponding
value and update all analog outputs. The totalizer display and output is not affected by a simulated frequency. The simulated pressure and temperature settings work the same
way. The meter will output these new values and will use them to calculate a new density
for mass ow measurement. Note: When your diagnostic work is complete, make sure to
return the values to zero to allow the electronics to use the actual transducer values. For
the V only model, keep the temperature and pressure at nominal operating conditions.
If the meter display indicates a temperature or pressure fault, a substitute value can be
entered to allow ow calculations to continue at a xed value until the source of the fault
is identied and corrected. The units of measure of the displayed values are the same as
The Calibration Menu contains the calibration coefcients for the ow meter. These values
should be changed only by properly trained personnel. The Vortex Coef Ck and Low Flow
Cutoff are set at the factory. Consult the factory for help with these settings if the meter is
showing erratic ow rate.
The HART Communications Protocol (Highway Addressable Remote Transducer Protocol) is a
bidirectional digital serial communications protocol. The HART signal is based on the Bell 202
standard and is superimposed on 4-20 mA Output 1. Peer-to-peer (analog / digital) and multi-drop
(digital only) modes are supported.
4.1.1 WIRING
The diagrams below detail the proper connections required for HART communications:
Loop Powered Meter Wiring
Figure 50. Loop Powered Meter Wiring (HART)
WARNING
Place controls in manual mode when making conguration changes to the vortex meter.
1 Date
2 h
3 min
4 s
5 Password
6 Meter Size
7 Dev id
8 Tag
9
Descriptor
Message
Final assy num
Poll adr
Num req preams
Config Code
Compile Date
Compile Time
Signal Board Version
Hardware rev
Software rev
Master reset
1 Fix Analog Output
2 Trim Analog Output
3 Configure AO1
4 PV is
5 PV AO1 Out
6 PV % rnge
7 Configure AO2
8 SV is
9 SV AO2 Out
SV % rnge
Configure AO3
TV is
TV AO
TV % rnge
Configure AO4
QV is
QV AO
QV % rnge
1 PV is
2 PV AO1 Out
3 PV
4 PV % rnge
5 Apply values
6 PV Rnge unit
7 PV LRV
8 PV URV
9 PV AO1 Lo end pt
PV AO1 Hi end pt
PV AO1 Added damp
1 SV is
2 SV AO2 Out
3 SV
4 SV % rnge
5 Apply values
6 SV Rnge unit
7 SV LRV
8 SV URV
9 SV AO2 Lo end pt
SV AO2 Hi end pt
SV AO2 Added damp
1 TV is
2 TV AO
3 TV
4 TV % rnge
5 Apply values
6 TV Rnge unit
7 TV LRV
8 TV URV
9 TV AO3 Lo end pt
TV AO3 Hi end pt
TV AO3 Added damp
1 QV is
2 QV AO
3 QV
4 QV % rnge
5 Apply values
6 QV Rnge unit
7 QV LRV
8 QV URV
9 QV AO1 Lo end pt
QV AO1 Hi end pt
QV AO1 Added damp
1 Status group 1
2 Status group 2
3 Status group 3
SPI not communicating
Freq. Input Overrange
FRAM CRC error
Signal Board Power ...
RTD1 Fault
RTD2 Fault
Press. Transducer Fault
Totalizer Relay Overrange
Alarm 1 Set
Alarm 2 Set
Alarm 3 Set
1 Model
2 Distributor
3 Write protect
4 Manufacturer
5 Dev id
6 Tag
7 Descriptor
8 Message
9 Date
Final asmbly num
Universal rev
Fld dev rev
Software rev
Burst mode
Burst option
Poll addr
Num req preams
1,1,1SnsrViewPrimary variable value
1,1,2AI % RngeViewAnalog output % range
1,1,3AO1ViewAnalog output, mA
1,2,1Test DeviceN/ANot used
1,2,2,14 mAViewLoop test, x analog output at 4 mA
1,2,2,220 mAViewLoop test, x analog output at 20 mA
1,2,2,3OtherEditLoop test, x analog output at mA value entered
1,2,2,4EndExit loop test
1,2,3,1,14 mAN/ANot used, apply values
1,2,3,1,220 mAN/ANot used, apply values
1,2,3,1,3ExitExit apply values
1,2,3,2,1PV LRVEditPrimary variable lower range value
1,2,3,2,2PV URVEditPrimary variable upper range value
1,2,3,2,3PV USLViewPrimary variable upper sensor limit
1,2,3,2,4PV LSLViewPrimary variable lower sensor limit
1,2,4D/A TrimEditCalibrate electronics 4mA and 20mAvalues
1,3,1TagEditTag
1,3,2PV unitEditPrimary variable units
1,3,3,1PV LRVEditPrimary variable lower range value
1,3,3,2PV URVEditPrimary variable upper range value
1,3,3,3PV LSLViewPrimary variable upper sensor limit
1,3,3,4PV USLViewPrimary variable lower sensor limit
1,3,4,1DistributorN/ANot used
1,3,4,2ModelN/ANot used
1,3,4,3Dev idViewDevice identication
1,3,4,4Ta gEditTa g
1,3,4,5DateEditDate
1,3,4,6Write ProtectViewWrite protect
1,3,4,7DescriptorEditVortex owmeter
1,3,4,8MessageEdit32 character alphanumeric message
1,3,4,9PV snsr s/nViewPrimary variable sensor serial number
1,3,4,menuFinal assy #EditFinal assembly number
1,3,4,menu,1Universal RevViewUniversal revision
1,3,4,menu,2Fld dev RevViewField device revision
1,3,4,menu,3Software RevViewSoftware revision
1,3,5PV Xfer fnctn ViewLinear
1,3,6PV DampEditPrimary variable damping (time constant) in seconds
1,4,1,1PVViewPrimary variable value
1,4,1,2PV Sensor UnitEditPrimary variable units
1,4,1,3Sensor Information ViewPV LSL, PV USL, PV Min span
1,4,2,1Snsr DampEditPrimary variable damping (time constant) in seconds
1,4,2,2,1PV LRVEditPrimary variable low range value
1,4,2,2,2PV URVEditPrimary variable upper range value
1,4,2,3,1PV LRVEditPrimary variable low range value
1,4,2,3,2PV URVEditPrimary variable upper range value
1,4,2,4Xfer FnctnViewLinear
1,4,2,5AI % rngeViewAnalog output % range
1,4,3,1,1AO1ViewAnalog output, mA
1,4,3,1,2AO alarm typN/ANot used
1,4,3,1,3,14 mAViewLoop test, x analog output at 4 mA
1,4,3,1,3,220 mAViewLoop test, x analog output at 20 mA
1,4,3,1,3,3OtherEditLoop test, x analog output at mA value entered
1,4,3,1,3,4EndExit loop test
1,4,3,1,4D/A trimEditCalibrate electronics 4mA and 20mAvalues
1,4,3,1,5Scaled D/A trimN/ANot used
1,4,3,2,1Poll addrEditPoll address
1,4,3,2,2Num req. preamsViewNumber of required preambles
1,4,3,2,3Burst modeN/ANot used
1,4,3,2,4Burst optionN/ANot used
1,4,4,1DistributorN/ANot used
1,4,4,2ModelN/ANot used
1,4,4,3Dev idViewDevice identication
1,4,4,4Ta gEditTa g
1,4,4,5DateEditDate
1,4,4,6Write ProtectViewWrite protect
1,4,4,7DescriptorEditVortex owmeter
1,4,4,8MessageEdit32 character alphanumeric message
1,4,4,9PV snsr s/nViewPrimary variable sensor serial number
1,4,4,menuFinal assy #EditFinal assembly number
1,4,4,menu,1Universal RevViewUniversal revision
1,4,4,menu,2Fld dev RevViewField device revision
1,4,4,menu,3Software RevViewSoftware revision
1,5ReviewN/ANot used
2PVViewPrimary variable value
3PV AOViewAnalog output, mA
4,1PV LRVEditPrimary variable lower range value
4,2PV URVEditPrimary variable upper range value
5,1PV LRVEditPrimary variable lower range value
5,2PV URVEditPrimary variable upper range value
Applicable Flow Meter Models: ONICON F-2600 & F-2700 Series Mass Flow Meters with Modbus
communication protocol and rmware version 4.00.58 and above.
WARNING
Place controls in manual mode when making conguration changes to the vortex meter.
Overview
This document describes the preliminary implementation of the Modbus communication protocol
for use in monitoring common process variables in the ONICON F2600 Series Mass Vortex Flow
Meter. The physical layer utilizes the half-duplex RS-485 port and the Modbus protocol.
Reference Documents
The following documents are available online from www.modbus.org.
Modbus Application Protocol Specication V1.1
Modbus Over Serial Line Specication & Implementation Guide V1.0
Modicon Modbus Protocol Reference Guide PI–MBUS–300 Rev. J
4.2.1 Wiring
An RS-485 daisy chained network conguration as depicted below is recommended. Do
not use a star, ring, or cluster arrangement.
The following menu items are in the Output Menu and allow selection and control of the
Modbus communication protocol.
Address
When the Modbus protocol is selected, the Modbus address is equal to the user's
programmable device address if it is in the range 1…247 in accordance with the Modbus
specication. If the device address is zero or is greater than 247, then the Modbus address
is internally set to 1.
Comm Protocol
The Comm Protocol menu allows selection of “Modbus RTU Even,” “Modbus RTU Odd,”
or “Modbus RTU None2,” or “Modbus RTU None1,” (non-standard Modbus) with Even,
Odd and None referring to the parity selection. When even or odd parity is selected, the
unit is congured for 8 data bits, 1 parity bit and 1 stop bit; with no parity, the number of
stop bits is 1 (non-standard) or 2. When changing the protocol, the change is made as soon
as the Enter key is pressed.
Modbus Units
The Modbus Units menu is to control which units, where applicable, the meter’s variables
will be displayed in. Internal – (these are the base units of the meter, °F, psia, lbm/sec , ft3/
sec, Btu/sec , lbm/ft3 Display) – variables are displayed in user selected display unit.
Modbus Order
The byte order within registers and the order in which multiple registers containing
oating point or long integer data are transmitted may be changed with this menu item.
According to the Modbus specication, the most signicant byte of a register is transmitted
rst, followed by the least signicant byte. The Modbus specication does not prescribe
the order in which registers are transmitted when multiple registers represent values
longer than 16 bits. Using this menu item, the word order and byte order for oating point
and long integer values may be reversed to accommodate different Modbus operating
systems.
The following four selections are available in this menu. When selecting an item, the
protocol is changed immediately without having to press the ENTER key.
0-1:2-3Most signicant register rst, most signicant byte rst (default)
2-3:0-1Least signicant register rst, least signicant byte rst
1-0:3-2Most signicant register rst, least signicant byte rst
3-2:1-0Least signicant register rst, most signicant byte rst
Note that all of the registers are affected by the byte order, including strings and registers
representing 16-bit integers. The register order only affects the order of those registers
representing 32-bit oating point and long integer data, but does not affect single 16-bit
integers or strings.
Modbus Protocol
The Modbus RTU protocol is supported in this implementation. Supported baud rates are
1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200. The default baud rate is 19200
baud. Depending upon the Modbus protocol selected, data is transmitted in 8-bit data
frames with even or odd parity and 1 stop bit or no parity and 2 or 1 (non-standard) stop
bits.
Table 2. Byte Order
The current Modbus protocol specication does not dene register usage, but there is an
informal register numbering convention derived from the original (now obsolete) Modicon
Modbus protocol specication which is still used by many vendors of Modbus capable
products.
Registers Usage Valid Function Codes
00001–09999 Read/write bits ("coils") 01 (read coils) 05 (write single
Each range of register numbers maps to a unique range of addresses that are determined by
the function code and the register number. The address is equal to the least signicant four
digits of the register number minus one, as shown in the following table.
RegistersFunction CodesData Type and Address Range
The meter serial number and those variables that are commonly monitored (mass, volume
and energy ow rates, total, pressure, temperature, density, viscosity, Reynolds number,
and diagnostic variables such as frequency, velocity, gain, amplitude and lter setting) are
accessible via the Modbus protocol. Long integer and oating point numbers are accessed
as pairs of 16-bit registers in the register order selected in the Modbus Order menu.
Floating point numbers are formatted as single precision IEEE 754 oating point values.
The ow rate, temperature, pressure, and density variables may be accessed as either
the ow meter internal base units or in the user-programmed display units, which is
determined by the programming Output Menu’s “Modbus Units” item. The display units
strings may be examined by accessing their associated registers. Each of these units string
registers contain two characters of the string, and the strings may be two to 12 characters
in length with unused characters set to zero. Note that the byte order affects the order in
which the strings are transmitted. If the Modbus Order menu (see Section 4.2.2) is set to
0-1:2-3 or 2-3:0-1, then the characters are transmitted in the correct order. If set to 1-0:3-2
or 3-2:1-0, then each pair of characters will be transmitted in reverse order.
Registers Variable Data Type Units Function Code Addresses
65100-65101 Serial number unsigned long — 03, 04
30525-30526 Totalizer unsigned long display units 03, 04 524-525
32037-32042 Totalizer units string — 03, 04 2036-2041
30009-30010 Mass ow oat display units 03, 04 8-9
30007-30008 Volume ow oat display units 03, 04 6-7
30005-30006 Pressure oat display units 03, 04 4-5
30001-30002 Temperature oat display units 03, 04 0-1
30029-30030 Velocity oat ft/sec 03, 04 28-29
30015-30016 Density oat display units 03, 04 14-15
30013-30014 Viscosity oat cP 03, 04 12-13
30031-30032 Reynolds number oat — 03, 04 30-31
30025-30026 Vortex frequency oat Hz 03, 04 24-25
34532 Gain char — 03, 04 4531
30085-30086 Vortex amplitude oat Vrms 03, 04 84-85
30027-30028 Filter setting oat Hz 03, 04 26-27
Table 3. Register Denitions
The following registers are available with the energy meter rmware:
Registers Variable Data Type Units Function Code Addresses
30527-30528 Totalizer #2 unsigned long display units 03, 04 526-527
32043-32048 Totalizer #2 units string — 03, 04 2042-2047
30003-30004 Temperature #2 oat display units 03, 04 2-3
30011-30012 Energy ow oat display units03, 04 10-11
The following registers contain the display units strings:
Registers Variable Data Type Units Function Code Addresses
32007-32012 Volume ow units string — 03, 04 2006-2011
32001-32006 Mass ow units string — 03, 04 2000-2005
32025-32030 Temperature units string — 03, 04 2024-2029
32019-32024 Pressure units string — 03, 04 2018-2023
32031-32036 Density units string — 03, 04 2030-2035
32013-32017 Energy ow units string — 03, 04 2012-2017
Function codes 03 (read holding registers) and 04 (read input registers) are the only codes
supported for reading these registers, and function codes for writing holding registers are
not implemented. We recommend that the oating point and long integer registers be read
in a single operation with the number of registers being a multiple of two. If this data is
read in two separate operations, each reading a single 16-bit register, then the value will
likely be invalid.
The oating point registers with values in display units are scaled to the same units as
are displayed, but are instantaneous values that are not smoothed. If display smoothing
is enabled (non-zero value entered in the Display TC item in the Display Menu), then the
register values will not agree exactly with the displayed values.
Exception Status Denitions
The Read Exception Status command (function code 07) returns the exception status byte,
which is dened as follows. This byte may be cleared by setting “coil” register #00003
(function code 5, address 2, data = 0xff00).
The status of the three alarms may be monitored via the Modbus Read Discrete Input
command (function code 02). The value returned indicates the state of the alarm, and will
be #1 only if the alarm is enabled and active. A zero value is transmitted for alarms that
are either disabled or inactive.
Registers Variable Function Code Address
10001 Alarm #1 state 02 0
10002 Alarm #2 state 02 1
10003 Alarm #3 state 02 2
The only writeable registers in this implementation are the Reset Exception Status, Reset
Meter and Reset Totalizer functions, which are implemented as ”coils” which may be
written with the Write Single Coil command (function code 05) to address 8 through 10,
respectively (register #00009 through #00011). The value sent with this command must be
either 0x0000 or 0xff00, or the meter will respond with an error message. The totalizer will
be reset or exception status cleared only with a value of 0xff00.
Error Responses
If an error is detected in the message received by the unit, the function code in the
response is the received function code with the most signicant bit set, and the data eld
will contain the exception code byte as follows:
Exception
Code
Description
01 Invalid function code — function code not supported by device
02
03
If the rst byte of a message is not equal to the unit’s Modbus address, if the unit detects a
parity error in any character in the received message (with even or odd parity enabled), or
if the message CRC is incorrect, the unit will not respond.
Command Message Format
The start address is equal to the desired rst register number minus one. The addresses
derived from the start address and the number of registers must all be mapped to valid
dened registers, or an invalid data address exception will occur.
Device Address
8 bits, 1...247
Invalid data address — address dened by the start address and
number of registers is out of range
Invalid data value — number of registers = 0 or >125 or incorrect
data with the Write Single Coil command
01 Device address
84 Function code with most signicant bit set indicates error response
02 Exception code 2 = invalid data address
C2 C1 CRC
Request the state all three alarms:
01 02 00 00 00 03 38 0B
01 Device address
02 Function code 2 = read discrete inputs
00 00 Starting address
00 03 Number of inputs = 3
38 0B CRC
And the unit responds with:
01 02 01 02 20 49
01 Device address
02 Function code
01 Number of data bytes = 1
02 Alarm #2 on, alarms #1 and #3 off
20 49 CRC
To reset the totalizer:
01 05 00 00 FF 00 8C 3A
01 Device address
05 Function code 5 = write single coil
00 09 Coil address = 9
FF 00 Data to reset totalizer
8C 3A CRC (not the correct CRC EJS-02-06-07)
The unit responds with an identical message to that transmitted, and the totalizer is reset.
If the “coil” is turned off as in the following message, the response is also identical to the
transmitted message, but the totalizer is not affected.
01 05 00 00 00 00 CD CA
01 Device address
05 Function code 5 = write single coil
00 00 Coil address = 0
00 00 Data to “turn off coil” does not reset totalizer
CD CA CRC
The BACnet Master-Slave/Token-Passing (MSTP) driver implements a data link protocol that
uses the services of the RS-485 physical layer. The MS/TP bus is based on BACnet standard
protocol SSPC-135, Clause 9. BACnet MS/TP protocol is a peer-to-peer, multiple master
protocols based on token passing. Only master devices can receive the token, and only the
device holding the token is allowed to originate a message on the bus. The token is passed from
master device to master device using a small message. The token is passed in consecutive order
starting with the lowest address. Slave devices on the bus only communicate on the bus when
responding to a data request from a master device.
4.3.2. Baud Rates on the MS/TP Bus
An MS/TP bus can be congured to communicate at one of four different baud rates. It
is very important that all of the devices on an MS/TP bus communicate at the same baud
rate. The baud rate setting determines the rate at which devices communicate data over
the bus. The available baud rate settings available on F-2600 and F-2700 Flow Meters are
9600, 19200 and 38400.
4.3.2.1. Baud Rate and MAC address conguration
1. Power on the meter
2. Press Enter to go conguration menu
3. Give the factory password 16363 (Use Up and Down arrows to enter the digits)
4. Navigate to Diagnostics menu
5. Press Enter and press right button immediately
6. Navigate to Cong Code screen by continuous pressing down button
7. After reaching cong code screen, press right to navigate to Comm. Type screen
8. Change the comm. Type to “Modbus” and press Enter
Note: Modbus will enable Baud Rate and MAC address screens
9. Press Exit twice to reach Diagnostics menu back
10. Navigate to Output Menu by using right or left arrow buttons
11. Press Down button and reach Baud Rate and MAC address screens
12. Change the required settings and press Exit & Enter buttons to save the conguration
13. Do steps from b to g, and change the comm. Type as Hart.
14. Reboot the device by power off and on.
Note:
a. Baud rates are 9600, 19200 or 38400
b. MAC address range is 0-127
4.3.3. Supported BACnet Objects
A BACnet object represents physical or virtual equipment information, as a digital input
or parameters. ONICON F-2600 and F-2700 Flow Meters present the following object
types:
a. Device Object
b. Analog Input
c. Binary Input
d. Binary Value
Each object type denes a data structure composed by properties that allow the access
to the object information. The below table shows the implemented properties for each
Vortex Mass Flow Meters object type.
Vortex Mass Flow Meters Binary Input type objects are described
in the below Table.
Object InstanceObject NameDescription
1Alarm1The status of the three alarms may be monitored via the Modbus
2Alarm2
3Alarm3
4ExternalTBD
command. The value returned indicates the state of the alarm, and will be
1 only if the alarm is enabled and active. A zero value is transmitted for
alarms that are either disabled or inactive
Note - Binary Input 4, Present value always read zero, because no information available from
client, so the polarity property doesn’t impact on Present value property when the Out of
service property is false.
3.4. Binary Value Object:
Vortex Mass Flow Meters Binary Value type objects are described
in the below Table.
The menus shown on the following page can be accessed using the password 16363, then moving to
the display that reads “Diagnostics Menu” and pressing ENTER (rather than one of the arrow keys).
Use the right arrow key to move to the second level. Press EXIT to move from the second level back
to the rst. Press EXIT while in the rst level to return to the set-up menus.
CAUTION
Password 16363 will allow full access to the conguration and should be used carefully to avoid
changes that can adversely alter the function of the meter.
Each of the menus on the following page will rst be dened followed by specic troubleshooting
steps.
WARNING
Before attempting any ow meter repair, verify that the line is not pressurized. Always remove
main power before disassembling any part of the mass ow meter.