ONEAC ONm 300 I, ONm 600 J, ONm300 A User Instruction Manual

ON Series m UPS
ON Series m UPS
Introduction
Technical Support
Thank you for selecting this uninterruptible power supply (UPS). ONEAC’s ON Series offers the most reliable protection from the harmful effects of electrical line disturbances for your computing and communications equipment. ONEAC’s ISO 9001 certification represents our commitment to building world-class products. W e take pride in e very unit that leaves our manufacturing facility
ONEAC contact ONEAC Technical Services:
NOTE: All calls received befor e 7 a.m. or after 7p.m.
Central Standard Time are forwarded to a cell phone. An ONEAC T echnical Support Representative will return your call within one half hour between 5 p.m. and 10 p.m. Central Standard Time . Except for emergencies, calls received between 10 p.m. and 7 a.m. will be returned during normal business hours.
Please check with ONEAC Technical Services before attempting to repair or return any ONEAC product. If an ONEAC unit needs repair or replacement, ONEAC Technical Services issues a Return Material Authorization (RMA) number along with instructions on how to return the unit.
®
offers 24-hour technical support. To
• North America: (800) 327-8801 (opt. 3) or (847) 816-6000 (opt. 3)
• Europe: +44 (0) 2380 610311
• email: ts@oneac.com.
ON Series m UPS User Instruction Manual 1
Safety
Safety
Class 1 equipment Equipment not suitable for use in the presence
of a FLAMMABLE ANESTHETIC MIXTURE WITH AIR or WITH OXYGEN OR NITROUS OXIDE.
Not designed, intended or authorized for use in systems intended to support or sustain life.
For more details on life critical applications please refer to full disclaimer in Appendix A: Warranty on page 18 at the end of this manual.
WARNING: This equipment services power from
more than one source. The output receptacles may have voltages present even when the unit is unplugged.
UPSs present a different safety issue than most electrical equipment because unplugging the UPS puts it into backup mode. Unplugging the UPS does not remove the electrical charge. To ensure that the UPS is off, turn the power switch “OFF” before unplugging the UPS from the wall outlet.
CAUTION: This unit is intended to be used in a
system that has a grounded neutral conductor.
CAUTION: Operating this equipment without
proper grounding may present a risk of electrical shock.
Do not use A C adaptors with only tw o conductors to connect the input line cord to the wall socket as this will not connect the earth ground to the equipment.
WARNING: Dangerous voltages are present within
this unit! There ar e no user -serviceable parts inside. Any repairs or modifications by the user may result in out-of-warranty repair charges, unsafe electrical conditions, or violation of electrical code.
Do not remove the cover. All repairs should be done by qualified service personnel. Voltages inside the UPS may be lethal. Internal components are powered even when the po wer switch is in the “OFF”
2 ON Series m UPS User Instruction Manual
Features
position. Even with the battery disconnected and the unit unplugged, energy is stored in high voltage capacitors and represents a severe shock hazard.
Features
The ON Series m UPS models are listed for UL2601-1 and CSA-C22.2 compliance and carry the CE Mark for testing to the EN60601-1 standard for Medical Electrical equipment. Designs are compliant with all specification parameters for Class I, equipment (such as earth leakage and enclosure leakage currents). Units are available in 120 V and 230 V 50/60 Hz with IEC connectors to facilitate country-specific connector compatibility or NEMA 5-15R receptacles on the “A” models. An optically isolated communications interface is standard.
Your ONEA C ON Series m UPS features full output isolation and power conditioning with V irtual Kelvin
®
Ground level of protection from power line disturbances available.
Intelligent battery management system includes:
• Battery condition monitoring and status alerts
• Low battery indication
• Hot-swap, user-replaceable battery
• Battery charge indication
• ONBoost
• Controlled inverter shutdown if battery is
ONEAC UPSs also feature a five-year w arranty. See Appendix A, page 18 for full warranty details.
See Appendix B: Typical Runtime on page 20 for battery runtimes. Full product specifications are available in Appendix C: Specifications and Characteristics on page 21.
output filtering. This provides the highest
®
, low line voltage compensation
without battery depletion
depleted
ON Series m UPS User Instruction Manual 3
Unpacking and Inspection
Unpacking and Inspection
Installation
Changing Frequency
Before shipment, this product was tested, inspected and found to be free of mechanical and electrical defects. Upon receipt of your UPS, carefully examine the packing containers for any sign of physical damage. Notify the carrier immediately if damage is present. After inspecting, carefully unpack the UPS. Retain the packaging materials for reuse or dispose of the materials properly. Once unpacked, inspect and test the unit for hidden damage that may have occurred in transit. If damage is evident, contact ONEAC Technical Services.
When selecting a location for your UPS, be sure that the unit is near a properly wired AC electrical outlet and is easily accessible for all other connections. Leave at least 2 inches of clearance on each side of the UPS for proper ventilation.
CAUTION: Do not cover or install the UPS in a
confined or enclosed space.
This ON Series m UPS was designed to operate at frequencies of either 50 Hz or 60 Hz.
The table below shows the frequency settings as shipped from the factory.
Table 1. Frequency Settings
Model From Factory Adjustable To
ONm 300 I, ONm 600 I 50 Hz 60 Hz ONm 300 J, ONm 600 J 60 Hz 50 Hz ONm300 A, ONm600 A 60 Hz 50 Hz
If an adjustment is necessary , perform the follo wing:
CAUTION: Before proceeding, be sure the UPS is
“OFF” and disconnected from the utility power.
4 ON Series m UPS User Instruction Manual
Installation
1. Lay the UPS on its right side.
2. Remove and retain the tw o Phillips head screws at the bottom front of the unit that secure the battery access door (fig. 1).
3. Carefully open the access door, then slide the batteries out of the unit.
WARNING: Do not contact the exposed battery
terminals due to the presence of electrical charge.
4. The frequency selector switch, located at the top of the UPS battery access panel, can be set to the desired frequency using a small, standard screwdriver or similar tool (fig. 1).
fig. 1: Frequency Selector Switch
5. Circle the selected frequency on the UPS label for later reference.
6. With the battery terminals toward the rear of the unit, slide the battery (pack) into the UPS. Make sure the battery wires retract without binding.
7. Close the battery access door and secure with the (2) screws removed in step 2. Return the desktop UPS to the upright position.
Connecting External Battery Enclosure(s)
ON Series m UPS User Instruction Manual 5
For additional runtime, some ON Series m UPSs can use extra batteries housed in a separate enclosure. Use only ONEAC model ONMXBC-217. The UPS power module and battery enclosure(s) are shipped separately.
1. Connect the battery cable from the closest battery enclosure to the external battery receptacle on the UPS, see fig. 2.
Installation
2. Connect the battery cable from the next external battery enclosure (if any) to the external battery receptacle on the battery enclosure connected in the previous step.
Repeat step 2 to connect additional external battery enclosures.
fig. 2: ON Series UPS and External Battery Connections
Connections
Before beginning, shut down and unplug the equipment to be protected. DO NOT make any connections or attempt to use any of the equipment until all the following connection instructions have been reviewed and completed.
The I and J model UPSs are equipped with (1) IEC320 (M) Input connector and (4) IEC320 (F) output connectors, as shown in fig. 4. The A model UPSs have (1) IEC320 (M) input connector and either (2) or (4) NEMA 5-15R hospital grade receptacles, as shown in fig. 5.
Indicator Lights Power Switch
fig. 3: ON Series m UPS Front Panel
6 ON Series m UPS User Instruction Manual
IEC 320 (M) Input Connector
IEC 320 (F) Output Connectors
External Battery
ONm 300 ONm 600
ONm 300 A Models
Input Connector
fig. 4: ON Series m UPS I and J Models Back Panel
IEC 320 (M) Input Connector
IEC 320 (F) Output Connectors
External Battery Input Connector
ONm 600 A Models
Installation
fig. 5: ON Series m UPS A Models - Back Panel
Load to UPS
ON Series m “A” models have (2/4) NEMA 5-15R Receptacles and are shipped with a hospital grade IEC 5-15P line cord. Use the supplied line cord to connect the UPS to the AC power source. Connect the protected devices directly to the 5-15R receptacles on the UPS. On ON Series I and J models a 6 foot IEC 320 (M/F) cord is provided for connection of one device to the UPS. If more than one device will be connected to the UPS, use additional IEC 320 (M/F) cords as shown in figure 4. Contact ONEAC for additional IEC 320 (M/F) cords if needed.
ON Series m UPS User Instruction Manual 7
Installation
1. Disconnect the input power cord(s) from the device(s) the UPS will be protecting.
NOTE: One of the disconnected power cords will be
used as the input power cord for the UPS.
2. Use IEC 320 (M/F) cord(s) to connect the device(s) to the UPS IEC 320 (F) output connectors.
Contact ONEAC Technical Support if your equipment does not have a detachable IEC 320 power cord.
UPS to Power Source
T o connect the UPS to the AC power source, use the input power cord supplied with the device to be protected.
Connect the UPS to the AC utility power source as shown in figure fig. 6.
Utility Power
ONm UPS
Input power cord disconnected from protected device IEC320 M/F power cord, (1) provided
fig. 6: Connecting Load(s) to UPS and Connecting UPS to AC Power Source
Device #1 to be Protected
Device #2 to be Protected
Device #3 to be Protected
8 ON Series m UPS User Instruction Manual
Operating Instructions
Operating Instructions
Power Switch
Self Test
With the UPS connected to a properly wired AC input power source, toggle the power switch to the ( | ) “ON” position. Power is immediately supplied to the output connectors.
Toggling the power switch to the( ) “standby” position will turn the power to the output connectors “OFF”. The internal charger will continue to char ge and maintain the battery as long as the line cord is connected to a live input AC power source.
Indicator Lights
Power Switch
fig. 7: ON Series m UPS Front Panel
The UPS checks vital functions when it is first plugged in and indicates the status with the three LEDs on the front panel. A green LED indicates normal A C output. A blinking yellow LED sho ws the battery is being charged. The UPS will continuously monitor the condition of the battery. If the battery cannot be charged, is disconnected or takes too long to charge, a code is represented in the LED Display.
NOTE: The System Code Status Chart on the back of
the UPS (and on page 11 of this manual) provides a quick refer ence for interpretation of the system status LEDs.
On Battery
ON Series m UPS User Instruction Manual 9
If the AC input power source to the UPS rises too high, too low or fails, the UPS will switch to the internal inverter to deliver power to the outlets from the battery(ies). The LEDs will indicate that the UPS is on battery. An audible alarm will also sound every minute.
Operating Instructions
Low Battery
Overload
Battery Replacement
When the battery voltage falls to a predetermined value, the audible alarm will sound continuously and the green and yellow LEDs will blink. If the UPS continues to operate in this mode for two minutes or more, the UPS will shutdown and remove power from the output connectors.
When power returns, the UPS will return to on-line operation and the battery(ies) will automatically recharge.
If the load on the UPS exceeds its capacity, the red and green LEDs will blink. The audible alarm will sound once every minute.
If the UPS is heavily overloaded, the audible alarm will sound continuously and will shut down in a few seconds. The input breaker may also trip. T o reset the breaker, first turn the UPS power switch to the “OFF” position, remove the load and push the breaker back into its housing. If the electronic overload has tripped, the UPS will hav e to be reset by toggling the power switch “OFF”, then “ON” to restore output power.
If the UPS has determined that the battery is no longer functional, the green and red LEDs will be on continuously and the yellow LED will flash. The audible alarm will sound every five minutes.
Indicator Lights
10 ON Series m UPS User Instruction Manual
GREEN - When the green LED is on, either solid or blinking, power is being supplied to the output. If blinking, it indicates the UPS is on inverter or there is an overload condition.
YELLOW - When the yellow LED is on solid, the UPS is on inverter . If blinking, it indicates the battery is charging when on line or low battery if running on inverter .
RED - When the red LED is on solid, it indicates there is a problem with the battery charger or
❋ O ❋
Operating Instructions
inverter. If blinking, it indicates no battery, overload or high line and no battery present.
Table 2. System Code Status Chart
Power Battery Fault Unit Status
O O O OFF
O O ON/AC Present
●❋❋
●❋ O ON AC/Battery Charging
●❋● ON AC/Replace Battery
❋● O ON Battery Power ❋❋ O ON Battery/Battery Low
OO ❋ O ●● OO ●
O = Off, ● = On, ❋ = Blinking
ON AC/No Battery
ON AC/Overload
Off/Overload
Off/No AC - Fault
Off/Unit Fault
Communications (Factory Installed Options)
The isolated Basic Interface Option will send On Battery and Low Battery signals to the host computer. It will also accept a shutdown signal to turn the inverter off to conserve battery life.
Pins 1 and 10 (simulated relay closures) are open collector transistor outputs which must be pulled up to a common reference supply no greater than +15V DC. They are opto-isolated open collector transistors capable of a maximum noninductive load of 10mA DC. Pin 11 is the common for all of the relay closure pins and is isolated from the UPS chassis ground.
Pins 20 and 21 are used to shut down the UPS when it is operating on battery . A positi v e signal (3 to 24V DC) on pin 20 with respect to pin 21 shuts down the UPS. A signal at or belo w ground allows the UPS to keep running.
ON Series m UPS User Instruction Manual 11
Replacing Battery(ies)
The shell of the interface connector is connected to the UPS chassis ground.
Table 3. Pin Signals
Interface Pin No. Signal
1 Low Battery - normally open 10 Line Fail - normally open 11 Output Signal Common 20 Shutdown (to UPS) 21 Shutdown (to UPS)
Interface Port
ONm 300 ONm 600
fig. 8: ON Series m UPS Rear Panel
Replacing Battery(ies)
12 ON Series m UPS User Instruction Manual
NOTE: To obtain new battery(ies), contact ONEAC
Technical Services at (847) 816-6000, or toll free at (800)-327-8801, ext. 3. In Europe, dial +44 (0) 1235 534721.
Battery replacement is a safe procedure that is isolated from electrical hazards. You can leave the UPS and attached loads powered “ON” during the procedure. If the unit is “ON, ” the audible alarm will sound when the battery is disconnected and the yellow and red LEDs will blink.
NOTE: The UPS cannot protect against power
outages while the batteries are disconnected.
Replacing Battery(ies)
Procedures
1. Lay the UPS on its right side.
2. Open the battery access door on the bottom by removing the two (2) Phillips head screws at the front. Retain the screws for use in step 8 later.
3. Carefully open the battery access door and slide the batteries out of the unit.
4. For the ONm Series 300 VA UPS disconnect the black wire, then the red wire from the battery pack.
For the ONm Series 600 VA UPS remove the battery connector by squeezing the two “ears” on the sides of the connector and pulling straight out.
WARNING: Once the wires are removed from the
battery(ies), use caution to not contact the exposed battery terminals due to the presence of electrical charge.
5. For the ONm Series 300 VA UPS, using the new battery(ies), connect the red wire to the red positive (+) terminal on the battery.
NOTE: In the next step be aware that a small ar c may
occur while connecting the black wir e to the battery terminal.
6. Connect the black wire to the (-) terminal on the battery.
For the ONm Series 600 VA UPS, insert the battery connector in the plug in the battery compartment.
NOTE: The plug is polarized and only will fit in one
way.
7. With the battery terminals toward the rear of the unit, slide the battery (pack) into the UPS. Make sure the battery wires retract without binding.
8. Close the battery access door and secure with the (2) screws removed in step 2. Return the desktop UPS to the upright position.
9. Dispose of the old battery pack according to
ON Series m UPS User Instruction Manual 13
Replacing Battery(ies)
ON Series m UPS
Battery Wires
Battery
fig. 9: ON Series m UPS Battery Replacement
current environmental regulations. See Battery Disposal, below, if you would like ONEAC to dispose of battery.
Replacing External Battery Enclosure(s)
For additional runtime, some ON Series m UPSs can use extra batteries housed in a separate enclosure. The UPS power module and battery enclosure(s) are shipped separately.
NOTE: The UPS and attached loads may remain
powered ON during the battery enclosure(s) replacement procedures.
The batteries inside the external battery enclosure(s) are not user-replaceable. The entire battery enclosure must be replaced or the enclosure may be returned to ONEAC for battery replacement.
To disconnect the battery cable coming from an external battery to the UPS or another external battery, squeeze the two locking “ears” on the sides of the battery connector and pull straight out (see fig.
10).
fig. 10: ON Series m External Battery Replacement
14 ON Series m UPS User Instruction Manual
Battery Disposal
Connect the battery cable from the closest battery enclosure to the external battery receptacle on the UPS, see fig. 2.
Connect the battery cable from the next external battery enclosure (if any) to the external battery receptacle on the battery enclosure connected in the previous step.
Repeat to connect additional external battery enclosures.
Battery Disposal
UPS Disposal
UPS batteries contain toxic and acidic materials. Disposal method must adhere to local/national recycling laws. Dispose of the battery in one of three ways:
1. Return batteries prepaid to ONEAC for proper recycling. Contact ONEAC Technical Services at (847) 816-6000, toll free at (800) 327-8801 option 3 or in Europe at +44 (0) 1235 534721 for an RMA number. Mark the RMA number on the packing slip and shipping carton.
2. Phone ONEAC Corporation for the number of a local battery collection site (US only).
3. Make arrangements with a local auto shop that collects automotive batteries for reprocessing.
CAUTION: DO NOT dispose of battery in a fir e. The
battery may explode. Do not open or mutilate the battery or battery enclosure. Released electrolyte is harmful to the skin and eyes and is toxic.
Once your UPS has reached the end of its useful life and it is necessary to dispose of the unit:
1. Remove the batteries as instructed in Replacing Battery(ies) on page 12.
2. Dispose of the batteries as instructed in Battery Disposal on page 15.
3. Dispose of the unit in accordance with local/ national recycling or disposal ordinances.
ON Series m UPS User Instruction Manual 15
Troubleshooting
Troubleshooting
ONEAC offers 24-hour technical support. If you have questions or problems regarding your ON Series m UPS:
1. Refer to the T roubleshooting table on page 17 for corrective or recommended action.
2. If you are unable to troubleshoot the problem, contact Technical Services. Refer to page 1, Technical Support, for the correct telephone number in your area. T echnical Services will ask you to describe the problem. They will help solve the problem over the telephone or issue a Return Material Authorization (RMA) number along with instructions on how to return the UPS for repair.
NOTE: You will need to supply the service
repr esentative with the UPS part number and serial number. You can access these numbers on the back panel of the unit on a label located near the receptacles.
Always check with ONEAC Technical Services before attempting to repair or return any ONEAC product.
16 ON Series m UPS User Instruction Manual
Troubleshooting
If you have questions or problems regarding you ON Series m UPS, refer to the troubleshooting table below.
Table 4. Troubleshooting
Problem Possible Cause Solution
UPS will not turn ON
UPS operates on battery even with line voltage present.
Fault LED is ON.
Fault LED is blinking
Front Panel Switch not “ON”.
UPS’s input circuit breaker tripped.
Unit not plugged in. Plug unit into wall outlet.
UPS’s input circuit breaker tripped.
High or low line. Contact qualified electrician.
Out of frequency range.
If yellow LED is blinking, the battery needs to be replaced.
If yellow LED is off or on solid, there is an internal UPS fault.
If yellow LED is blinking, there is no battery connected or detected.
If green LED is blinking or off, the output is overloaded.
Switch the Power Switch to (I)
Reduce the load on the UPS by unplugging the load and press the circuit breaker in on the rear panel.
Reduce the load on the UPS by unplugging the load and press the circuit breaker in on the rear panel.
Check for UPS compatibility with power source.
Allow batteries to charge for 4 hours. If the problem continues, replace the battery(ies).
Do not attempt to use the UPS. Turn the UPS off, unplug from the power line and call Technical Service: (800)-327-8801, opt. 3 immediately.
Connect install or replace the battery(ies).
Reduce the load on the UPS until the LED goes out. If green LED is off, recycle power switch to reset.
ON Series m UPS User Instruction Manual 17
Appendix A: Warranty
Appendix A:
Warranty
Batteries
Life Critical Applications
ONEAC products are warranted free from defects in materials and workmanship for five years. This warranty is limited to repairing or replacing, at ONEAC’s option, any defective component, circuit board, or module contained within the product only when it is returned with an ONEAC Return Material Authorization (RMA) number to ONEAC or to an ONEAC-designated repair facility. In all cases, the customer is responsible for shipping charges to and from ONEAC or the ONEAC-designated repair facility.
Certain modules or peripherals included with the product, but not manufactured by ONEAC, including but not limited to batteries or battery enclosures, are warranted for two years or the extent of the manufacturer’s warranty, whichever is longer.
While ONEAC belie ves it designs and manufactures very reliable products, many of the vendors that ONEAC sources components from do not recommend or endorse the use of their products in life critical applications. By extension, ONEAC must adhere to the same business policy and does not recommend the use of our products in life critical applications.
Disclaimer
18 ON Series m UPS User Instruction Manual
ONEAC products are not designed, intended or authorized for use in systems intended to support or sustain life, or for any other application in which the failure of the ONEAC product could create a situation where personal injury or death may occur. Should the Buyer purchase or use ONEAC product for any such unintended or unauthorized application, the Buyer shall indemnify and hold ONEAC and its officers, employees, subsidiaries, affiliates and distributors harmless against all claims, costs, damages and expenses, and reasonable attorney fees arising out of, directly or indirectly, any claim or personal injury or death associated with such unintended or unauthorized use, even if such claim alleges that ONEAC was negligent regarding the design or manufacture of the part.
Appendix A: Warranty
Limitations of Warranty
Exclusive Remedies
Return Procedure
This limited warranty does not cover any losses or damage resulting from shipment to or from the customer, or from improper installation, inappropriate environment, abuse, modifications, adjustments, or unauthorized repair.
For full details of the warranty, see ONEAC Warranty, Policy and Procedures (part number 955-053).
T o return a UPS, contact ONEA C Technical Support for a Return Material Authorization (RMA) number. This number must be marked on the shipping carton and packing slip of the unit returned. The customer is responsible for repair charges for damages incurred in shipment that result from inadequate or improper packing of the product.
ON Series m UPS User Instruction Manual 19
Appendix B: Typical Runtime
Appendix B: Typical Runtime
Table 5. Typical Runtime by System Load
Typical Runtime by System
Load
VA LOAD RUNTIME (HOURS:MINUTES)
75 VA 0:41 1:32 100 VA 0:21 1:09 150 VA 0:16 0:40 200 VA 0:10 0:30 250 VA 0:07 0:20 300 VA 0:05. 0:15
NOTE: Due to application specific conditions, your actual run time may be different.
ONm300 A, I and J Models
One 12V, 7AH Battery
ONm300D A, I and J Models
Two 12V, 7AH Batteries
Table 6. ON Series m 600 VA Extendable Runtimes
Typical Runtime by System Load
VA LOAD RUNTIME (HOURS:MINUTES)
100 VA 1:05 4:40 8:50* 10:30* 13:30* 16:40* 200 VA 0:35 2:40 5:00* 7:00* 9:00* 11:10* 400 VA 0:15 1:20 2:20* 3:30* 4:30* 5:30* 600 VA 0:05 0:30 1:10* 2:20* 3:00* 3:45
NOTE: Due to application specific conditions, your actual run time may be different. NOTE: External Battery - Two 12V, 17AH per battery enclosure.
* Values shown are calculated.
ONm600X
Two 12 V, 7 AH
Batteries
Plus1
External
Battery
Plus2
External
Batteries
Plus 3
External
Batteries
Plus 4
External
Batteries
Plus 5
External
Batteries
20 ON Series m UPS User Instruction Manual
Appendix C: Specifications and Characteristics
Appendix C: Specifications and Characteristics
Table 7. Physical/Electrical Specifications
and Performance Characteristics*
Specification and Characteristics ONm300J ONm600J ONm300I ONm600I ONm300A ONm600A
Maximum Load - VA/Watts
Load Power Factor Range UPS .65 to 1.0 (3) - will support loads rated 0.5 to 1.0
Crest Factor <3 Nominal Input Voltage 120 VA C 230 V A C 120 VAC Low Limit for On-line Operation
@ 50% Load High Limit for On-line Operation
@ 50% Load Unit Start-up Range 93-138VAC 190-266 VAC 93-138 VAC Frequency Limits (on-line) 50/60 Hz +/- 5% Input Connection IEC 320 (M) inlet Input Over Current Protection resettable, linked dual pole (L & N) breaker
Boost Voltage
Output Voltage on Backup @ 50% Load
On Battery Waveshape amplitude stabilized stepped sine-wave On Battery Frequency 50/60 Hz +/- 1% T ransf er Time 4mS, typ Output Connection (4) IEC 320 (F) connectors (2/4) 5-15R Battery Type maintenance free, spill proof, sealed lead-acid Typical Battery Life 3-6 years, depending on number of discharges and ambient temperature Recharge Time (60% Recovery) 6-10 hours Communications isolated basic signaling
Interface Connector 25 pin male sub D style
Output Signals
Input Signal
Maximum Collector Voltage (VDC) 15 Maximum Collector Current (mADC) 10 Maximum Output Voltage @ 5
mADC
300/200 600/400 300/200 600/400 300/200 600/400
87 VA C 183 VAC 87 VA C
138 VA C 266 VAC 138 VAC
approximately 10% boost to output voltage when input voltage falls below 80%
of nominal
110 VAC ± 10% 220 VAC ±10% 110 VAC ± 10%
on battery (pin10) / low battery (pin 1)
(TRUE condition causes “short” to RETURN signal (pin 11))
inverter shut down [pin 20 (+) to pin 21 (-)]
(high shuts down inverter)
0.8
ON Series m UPS User Instruction Manual 21
Appendix C: Specifications and Characteristics
Table 7. Physical/Electrical Specifications
and Performance Characteristics* (Continued)
Specification and Characteristics ONm300J ONm600J ONm300I ONm600I ONm300A ONm600A
Output Type opto-isolated open collector transistor Input Type opto isolator input diode with anti-parallel diode and 500 ohms in series
Table continued on next page
Minimum Input to Activate Shutdown (mA)
Maximum Input Current (mA) 20 Operating Temperature 0º to +40ºC (32 to 104ºF) Storage Temperature -15 to 45ºC (+5 to 113ºF) Relative Humidity 0 to 95%, non-condensing Operating Elevation 0 to 3,000 m (0 to 10,000 ft) Storage Elevation 0 to 15,000 m (0 to 50,000 ft) Size (HxWxL) inches 7.38 x 6.00 x 15.00
Shipping Weights lbs.
Surge Voltage Withstand Capability ANSI/IEEE C62.41 Category A&B, 6KV/200 and 500 Amp, 100KHz Ringwave
Surge Voltage Let-Through
Normal and Common Mode Clamping Response Time
* ± 2 volt tolerance on all measurements.
Less than 10V normal mode (L-N), less than 0.5V Common mode (N-G) when
subjected to C62.41 6kV Cat. A pulse
1
37/43
(single/double battery)
instantaneous
22 ON Series m UPS User Instruction Manual
Appendix C: Specifications and Characteristics
T able 8. Physical/Electrical Specifications and P erformance Characteristics for ONMXBC-217 External Battery
Specifications and
Characteristics
Voltage 2x 12 V Current 40 A Batteries two at 12 V, 17 AH Operating Temperature 0º to +40ºC (32 to 104ºF) Storage Temperature -15 to 45ºC (+5 to 113ºF) Relative Humidity 0 to 95%, non-condensing Operating Elevation 0 to 3,000 m (0 to 10,000 ft) Storage Elevation 0 to 15,000 m (0 to 50,000 ft) Size (HxWxL) inches (cm) 3.75” x 7.0” x 17” (9.5 x 18 x 43) Shipping Weights lbs. (kg) 38 (17)
ONMXBC-217
ON Series m UPS User Instruction Manual 23
Appendix C: Specifications and Characteristics
Safety & Approvals
Table 9. Emissions Test Regulations
Emissions Test Regulations
United States 47 CFR Part 15 Subpart B:1999
Canada Interference-Causing Equipment Standard (ICES-003 Issue 2, Rev.1)
Europe EMC-Directive 89/336/EEC as amended by 92/31/EEC and 93/68/EEC
EN 50091-2 / 09.95 (UPS Equipment) EN 50081-1 / 01.92 (Generic Emission - Residential, Commercial and
Light Industrial) EN 60601-1-2 / 05.93 (Medical equipment) EN 55011 / (ISM Equipment) EN 55022 / 08.94 (ITE Equipment) EN 61000-3-2 / 04.95 EN 61000-3-3 / 01.95
24 ON Series m UPS User Instruction Manual
Appendix C: Specifications and Characteristics
Table 10. Immunity Test Regulations
Immunity Test Regulations
Europe EMC-Directive 89/336/EEC as amended b y 92/31/EEC and 93/68/EEC
EN 50091-2 / 09.95 (UPS Equipment) EN 50082-1/08.97 (Generic Immunity - Residential, Commercial and
Light Industrial) EN 60601-1-2 / 05.93 (Medical equipment) EN 61000-4-2 / 03.95 (IEC 1000-4-2 / 01.95) EN 61000-4-3 / 1995 (IEC 1000-4-3 / 02.95) ENV 50204 / 03.95 EN 61000-4-4 / 03.95 (IEC 1000-4-4/01.95) EN 61000-4-5 / 03.95 (IEC 1000-4-5 / 02.95) EN 61000-4-6 / 07.96 (IEC 1000-4-6 / 03.96) EN 61000-4-11 / 08.94 (IEC 1000-4-11 / 06.94) IEC 1000-2-2 / 09.95
Table 11. Safety Regulations
Safety Regulations
UL1778 (Uninterruptible Power Supply Equipment)
United States
Canada CSA 22.2
Europe
UL2601-1 (Medical Electrical Equipment, Part 1 General Requirements for Safety)
EN 60601-1 Medical Electrical Equipment EN60950 Information Technology Equipment as amended by
EN 50091-1 Standard for Uninterruptible Power Systems
ON Series m UPS User Instruction Manual 25
Loading...