Onan RST 60, RST 100, RST 200 Installation Manual

Page 1
RST 60/100/200 Automatic Transfer Panel
Printed U.S.A. 913-0602B 9-2004
Page 2
     
    !"
   #
  # $   #  % #   ##$   $      $  
PURPOSE
This supplement updates the LT, LC, and RST Operator’s, Installation, and Service Manuals to in­clude information on the 5-button exercise clock available on current production units.
SUPPLEMENT USE
Write Refer to Supplement on the pages of the manuals listed above that refer to the exercise clock.
Insert this supplement inside the front cover of the manuals listed above.
Page 1 of 8
Page 3
Page 2 of 8
Page 4
FIVE BUTTON EXERCISE CLOCKS
NOTE: After one minute of button inactivity, the
home menu (see Figure 2) will be redis­played and any changes made that weren’t saved by pressing the OK button will be lost.
24
6
18
7
6
5
4
3
2
1
12
OK
MENU
FIGURE 1. FIVE BUTTON EXERCISER CLOCK
Figure 3 shows the five operator buttons.
D The Menu button is used to activate a menu
or to break off the process.
D The Selector (Arrow) button is used to select
menu topics and one of the four available modes of operation (Automatic Operation Override Continuous Override Off
, Continuous Override On , and
).
, Manual
NOTE: The mode symbols are not included on the right side of the display (see Figure 2). They are included in this document for reference pur­poses only. The
button must point to the rela­tive position of the symbol shown in this docu­ment to select the desired mode (see Figure 3).
D The OK button is used to save changes.
Figure 3 also shows the following clock features.
D The available menu topics are displayed at the
top of the screen.
D When being programmed, indicators for change-
over (SU/Wi) and the date (D/M/Y) are displayed beneath the menu topics.
D The clock displays the time and the day of the
week (1 = Monday).
D Around the clock are segments showing when an
exercise period is set.
D Near the right bottom corner is a circle indicating
the exercise state (black = active, white = inac­tive).
NOTE: There is an audible click whenever an ex­ercise period starts or stops.
24
24
18
18
1234567
1234567
12
12
6
6
D The and buttons are used to change val-
ues.
SUMMER/WINTER INDICATOR
REAL TIME, SWITCHING TIME
CLR = DELETE SWITCHING TIMES
COPY = COPY SWITCHING TIMES
FrEE = DAYS WHEN NO EXERCISE
PERIOD IS SET
ACTUAL DAY OF THE WEEK
OR PROGRAM DAY
SEGMENT DISPLAY OF THE
EXISTING PROGRAM
(1 SEGMENT = 30 MINUTES)
MENU BUTTON ACTIVATES
THE MENU OR BREAKS
OFF THE PROCESS
SELECTOR BUTTON
SU/Wi
SU/Wi
MINUS AND PLUS BUTTONS CHANGE THE VALUES
MENU TOPICS
SET TIME CHECK... ON PROG DATE NEW...OFF
24
24
18
18
1234567
1234567
12
12
D/M/Y
6
6
OKMENU
FIGURE 2. EXERCISER CLOCK HOME MENU
DAY/MONTH/YEAR
SYMBOL FOR AUTOMATIC OPERATION*
SYMBOL FOR MANUAL OVERRIDE*
SYMBOL FOR CONTINUOUS OVERRIDE ON*
SYMBOL FOR CONTINUOUS OVERRIDE OFF*
EXERCISE STATE:
ACTIVE INACTIVE
OK BUTTON CONFIRMS THE INPUT AND SAVES THE CHANGES
* THESE SYMBOLS ARE NOT
INCLUDED ON THE CLOCK.
FIGURE 3. FIVE BUTTON EXERCISER CLOCK FEATURES
Page 3 of 8
Page 5
To reset the exerciser clock:
The clock is not pre-programmed. The clock can be reset to erase just the existing day and time settings or it can be reset to erase all existing day, time, and exercise program settings.
18
18
24
24
1234567
1234567
12
12
6
6
D To erase just the existing day and time settings,
simultaneously press the MENU, +, and − but- tons. The screen will go blank. When the buttons are released two sets of dashes will be momen­tarily displayed (−− −−) and then the clock is dis­played with the time set to midnight ( 0:00).
D To erase all existing day, time, and exercise pro-
gram settings, simultaneously press all five but­tons. The screen will go blank. Release the MENU button while continuing to press the other buttons. Two sets of dashes will be displayed (−− −−). After three seconds have passed, re­lease the remaining four buttons. The clock is then displayed with the time set to midnight ( 0:00).
To set the time:
1.. With the exerciser clock powered, press the
MENU button. Use the selector button
to se-
lect SET TIME which is displayed in the upper left-corner of the display (see Figure 4).
SET TIME
FIGURE 5. SET TIME
To set the date and summer/winter changeover:
1.. Press the MENU button. Use the selector but-
ton
to select SET TIME and press the OK
button.
2.. Press the selector button
to select DATE
and then press the OK button. The current year is displayed flashing and D/M/Y
is displayed
with the “Y” underlined (see Figure 6).
SET
DATE
D/M/Y
FIGURE 6. SETTING THE YEAR
3.. Press the + or buttons until the correct year is displayed. Press the OK button. The day and month will then be displayed with the day flash­ing and D
/M/Y is displayed with the “D” under-
lined (see Figure 7).
FIGURE 4. SETTING THE TIME
2.. Press the OK button. The word “DATE” is dis- played. Press the OK button again. The time is displayed with the hour value flashing. The time displayed is based upon a 24 hour clock (mili­tary time).
Example: 2:00 PM = 14:00.
3.. Press the + or buttons until the correct hour is displayed. Press the OK button. The minute value will then flash.
4.. Press the + or buttons until the correct minute is displayed. Press the OK button. The home menu is redisplayed showing the set time (see Figure 5).
Page 4 of 8
SET
DATE
D/M/Y
FIGURE 7. SETTING THE DAY AND MONTH
4.. Press the + or buttons until the correct day (1 thru 31) is displayed. Press the OK button. The month value will then flash and D/M
/Y will be
displayed with the “M” underlined.
5.. Press the + or buttons until the correct month (1 thru 12) is displayed. Press the OK button. The summer/winter changeover menu is dis­played with the selected region flashing (see Figure 8).
Page 6
SET
DATE
SU/Wi
FIGURE 8. SUMMER/WINTER CHANGEOVER
MENU
6.. To set the clock for summer/winter changeover
(daylight savings time), press the + or buttons to select the appropriate region (see Table 1) and then press the OK button. The home menu is redisplayed. The matching number for the current day of the week will be underlined.
Examples: 1 = Monday
7 = Sunday
NOTE: If you do not wish any changeover, se-
lect the nonE setting. If you wish to set changeover times different from one of the preset times, select
and follow
the instructions included in Table 1.
TABLE 1. SUMMER/WINTER CHANGEOVER
INFORMATION
Choice
Euro Last Sunday in
Gb Last Sunday in
US First Sunday in
nonE No changeover No changeover
Beginning of
Summertime
March
March
April
Freely programmable date with regards to the change from summer to winter time.
Northern Hemisphere:
Use the + and buttons to put in the date at which the summer time starts and ends at your location/in your country. The weekday is automatically allocated to the date.
Southern Hemisphere:
For the southern hemisphere, the date at which the summer time starts/ends must be programmed for the same year.
Use the + and buttons to set the year and then press the OK button.
Use the + and buttons to set the actual day and month of summer time and then press the OK button.
Use the + and buttons to set the actual day and month of real time and then press the OK button.
End of
Summertime
Last Sunday in October
Last Sunday in October
Last Sunday in October
Country/
Area
European Union
Great Britian
North America
To set exercise start and stop times:
NOTE: The start and stop time for an exercise peri-
od must both be in the same day. For exam­ple, you cannot have a 30 minute exercise period start at 23:45 on one day and stop at 0:15 on the following day.
1.. Press the MENU button. The selector button will pointing at PROG. Press the OK button.
2.. The selector button
will be pointing at PROG
NEW. Press the OK button again. “ON” is dis- played in the top right corner of the screen and the first day of the week is underlined (see Fig­ure 9).
ON
PROG NEW
24
18
1234567
12
6
FIGURE 9. SETTING THE DAY OF THE WEEK THE
EXERCISE IS TO BEGIN
3.. To select a different day, press the + or buttons until the desired day is underlined.
NOTE: If an exercise period is already set for
the selected day, the program and CL r will be displayed. If you wish to delete the set program, press the OK button.
4.. Press the OK button. The starting time (0:00) is flashed (see Figure 10).
ON
PROG NEW
24
18
1234567
12
6
FIGURE 10. EXERCISE CLOCK MENU
5.. Press the + or buttons to set the starting time for the exercise (see Figure 11).
NOTE: If you lightly press the + or − buttons, the
value changes in one minute incre­ments. If you press and hold the + or buttons, the value changes in ten min­ute increments.
Page 5 of 8
Page 7
ON
PROG NEW
24
18
1234567
12
6
FIGURE 11. SETTING THE EXERCISE STARTING
TIME
6.. Press the OK button. The starting time is still
displayed and “OFF” is now displayed in the up­per right corner of the screen (see Figure 12). Press the + button to set the exercise stop time.
b. If you do not wish to set any additional exer-
cise periods, press the MENU button until the home menu is redisplayed.
NOTE: On the day that the exercise is to be-
come active, segments will be dis­played around the clock showing when the exercise period is set (see Figure 14).
24
OFF
PROG NEW
24
18
1234567
6
12
FIGURE 12. SETTING THE EXERCISE STOP TIME
7.. Press the OK button. Press the OK button again
to save the exercise program.
NOTE: If the Delete Program menu is dis-
played (see Figure 13), CL r is dis­played, indicating that the exercise pro­gram can be deleted by pressing the OK button.
PROG NEW
24
18
FIGURE 13. DELETE PROGRAM MENU
1234567
12
6
18
1234567
12
6
FIGURE 14. SET EXERCISE
To copy an exercise program:
1.. Once a set exercise program has been saved, press the selector button
to display the copy
menu (see Figure 15).
PROG NEW
24
18
1234567
12
6
FIGURE 15. COPY EXERCISE MENU
2.. Press the + button to select the day of the week that you wish to include the same exercise peri­od. Press the OK button.
8.. Copy the set program, set an additional exer­cise period, or exit the the program input.
a. If you wish to copy the set program, see “To
copy an exercise program” in the next col­umn.
Page 6 of 8
3.. If you want the exercise to occur on additional days, repeat the copy procedure.
4.. To terminate setting exercise programs, press the MENU button until the home menu is redis- played.
Page 8
To erase (delete) exercise programs:
1.. Press the MENU button. The selector button will pointing at PROG. Press the OK button.
2.. The selector button
will be pointing at PROG
NEW. Press the OK button again.
4.. Repeatedly press the OK button to view the ex-
ercise starting and stop times. A clock is dis­played showing the exercise start and stop times.
NOTE: If no exercise periods are set, FrEE is
displayed instead of the time.
3.. Use the + or buttons to select the day of the week that the exercise is set. When the correct day is selected, segments will be displayed around the clock showing when the exercise period is set and Cl r is displayed in the center of the clock (see Figure 16).
4.. Press the OK button. The clock will be reset to midnight ( 0:00) and new exercise settings can be entered. If you do not wish to set up a new exercise period, press the MENU button until the home menu is redisplayed.
PROG NEW
24
18
FIGURE 16. DELETING THE EXERCISE PROGRAM
1234567
12
6
TIME CHECK ON
24
18
1234567
6
12
FIGURE 17. CHECKING THE EXERCISE START
TIME
5.. To terminate checking the exercise program,
press he MENU button until the home menu is redisplayed.
Permanent On/Off Mode:
The Permanent On/Off (Manual Override) mode re­verses the set exercise state. It is initiated by using the selector button mode
(see Figure 18). The exercise state indica-
to select the Manual Override
tor shown in the bottom right corner of the display will then be reversed.
To check the exercise program:
1.. Press the MENU button. The selector button will pointing at PROG. Press the OK button.
2.. The selector button NEW. Press the selector button
will be pointing at PROG
button again
so that it points to TIME CHECK... Press the OK button.
3.. Use the + or buttons to select the day of the week that the exercise is set to begin. Press the OK button.
24
18
1234567
12
6
FIGURE 18. SELECTING PERMANENT ON/OFF
MODE
To exit the Permanent On/Off mode, press the selec­tor button
until the Automatic Operation mode is selected. The exercise state indicator shown in the bottom right corner of the display will go back to its normal state.
Page 7 of 8
Page 9
To initiate or override exercise program(s):
The exerciser clock has a built-in test feature. Once the clock time has been set, the selector button can be used to select Continuous Override ON mode Continuous Override OFF mode
to initiate a test (see Figure 19) or select
to cancel a test
in progress (see Figure 20).
24
To exit either mode, press the selector button un­til Automatic Operation mode
is selected. The ex­ercise state indicator shown in the bottom right cor­ner of the display will go back to its normal state.
Mains Failure:
If the clock is disconnected from AC power or the AC power source fails, “no U” is displayed (see Figure
21).
18
1234567
6
12
FIGURE 19. CONTINUOUS OVERRIDE ON
24
18
1234567
12
6
FIGURE 20. CONTINUOUS OVERRIDE OFF
FIGURE 21. AC POWER FAILURE INDICATION
Page 8 of 8
Page 10
Table of Contents
SECTION TITLE PAGE
SAFETY PRECAUTIONS ii. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 INTRODUCTION 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Manual 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transfer Panel Application 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transfer Panel Protection 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Model Identification 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How To Obtain Service 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 MOUNTING 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Location 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wall Mounting 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Outline Drawing − Cabinet Type 1 60/100 Amp 2-3. . . . . . . . . . . . . . . . . . .
Outline Drawing − Cabinet Type 1 200 Amp 2-4. . . . . . . . . . . . . . . . . . . . . .
3 WIRING 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Considerations 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC Connections 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Connections 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inspection And Cleanup 3-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 SETUP AND CALIBRATION 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Before Calibrating 4-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Voltage Sensors 4-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Time Delays 4-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-Wire Start Module (Optional) 4-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exerciser Clock 4-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Float Battery Charger 4-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 SYSTEM CHECKOUT 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting Test 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Test Transfer With Load 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Test Overcrank Function for Three-Wire Starting 5-2. . . . . . . . . . . . . . . . . . .
INCORRECT SERVICE OR REPLACEMENT OF PARTS CAN RESULT IN DEATH, SEVERE PERSONAL INJURY, AND/OR EQUIPMENT DAMAGE. SER­VICE PERSONNEL MUST BE QUALIFIED TO PERFORM ELECTRICAL AND/ OR MECHANICAL SERVICE.
WARNING
i
Page 11
Safety Precautions
This manual includes the following symbols to indicate potentially dangerous conditions. Read the manual carefully and know when these conditions exist. Then take the necessary steps to protect personnel and the equipment.
DANGER
WARNING
This symbol warns of immediate hazards that will result in severe personal injury or death. This symbol refers to a hazard or unsafe practice that can result in severe personal injury
or death.
CAUTION
This symbol refers to a hazard or unsafe practice that can result in personal injury or prod-
uct or property damage.
High voltage in transfer panel components presents serious shock hazards that can result in severe personal injury or death. Read and follow these suggestions.
Keep the transfer panel cabinet closed and locked. Make sure only authorized service personnel have access to the cabinet.
Due to the serious shock hazard from high voltages within the cabinet, all service and adjustments to the trans­fer panel must be performed only by an electrician or authorized service personnel.
Instructions to Authorized Service Personnel
If the cabinet must be opened for any reason:
1. Move the operation selector switch on the generator set to OFF. If the transfer panel is equipped with the 3-Wire Start Option, move the toggle switch to the Stop position.
2. Remove the AC power source to the cabinet.
3. Disconnect the starting batteries of the generator set (remove the ground [−] lead first).
Place rubber insulative mats on dry wood platforms over metal or concrete floors when working on any electri­cal equipment. Do not wear damp clothing (particularly wet shoes) or allow skin surfaces to be damp when handling any electrical equipment.
Jewelry is a good conductor of electricity and should be removed when working on the electrical equipment. Do not work on this equipment when mentally or physically fatigued, or after consuming alcohol or any drug
that makes the operation of equipment unsafe.
ii
Page 12
1. Introduction
INSTALLATION MANUAL
This manual provides information necessary for installing an RST (residential standby) transfer pan­el.
INTRODUCTION
The transfer panel is capable of automatic opera­tion without operator involvement. It performs the following basic functions:
1. Senses interruption of the Normal power source.
2. Sends a start signal to the generator set (Emer­gency power source).
3. Transfers the load to the Emergency power source.
4. Senses the return of the Normal power source.
5. Retransfers the load to the Normal power source.
6. Sends a stop signal to the generator set.
NORMAL
OVERCURRENT
PROTECTIVE DEVICE
LOAD
OVERCURRENT
PROTECTIVE DEVICE
TRANSFER PANEL APPLICATION
Transfer panels are an essential part of a building’s standby or emergency power system. The Normal power source, commonly the utility line, is backed up by an Emergency power source, often an electric generating set. The transfer panel supplies the electrical load with power from either of these two sources.
The load is connected to the common of the transfer panel (Figure 2-1). Under normal conditions, the load is supplied with power from the Normal source (as illustrated). If the Normal power source is inter­rupted, the load is transferred to the Emergency power source. When Normal power returns, the load is retransferred to the Normal power source. The transfer and retransfer of the load are the two basic functions of a transfer panel.
RST Transfer Panel is a trademark of Onan Corporation.
EMERGENCY
FIGURE 2-1. LOAD TRANSFER PANEL
(TYPICAL FUNCTION)
TRANSFER PANEL PROTECTION
Transfer panels are continuously rated devices. With proper maintenance, they carry load currents up to their nameplate ratings for any time duration. Transfer panels are designed to withstand normally occurring surge currents from electrical devices in their load circuits. They are also designed to with­stand the surge currents, which can occur on a short circuit or fault condition, as long as the avail­able fault current does not exceed the rating of the panel and it’s protective device, and the transfer panel is installed with proper protective equipment.
Automatic transfer panels are required to be installed with appropriate overcurrent protection on
1-1
Page 13
the normal source side and the emergency side of the transfer panel (Figure 2-1). Protective devices may be circuit breakers, fuses, or other suitable overcurrent protective system components. A list of allowable protective equipment is affixed to the transfer panel. The listed protective device must be installed at some point in the circuit between the transfer panel and the electrical services that feed the device.
MODEL IDENTIFICATION
Identify your model by referring to the Model and Specification number as shown on the nameplate. Electrical characteristics are shown on the lower portion of the nameplate, which is located on the cabinet door.
When contacting the dealer or distributor regarding the transfer panel, always give the complete Model, Specification, and Serial number. This information is necessary to properly identify your unit among the many types manufactured.
HOW TO OBTAIN SERVICE
When the transfer panel requires servicing, contact your nearest dealer or distributor. Factory-trained Parts and Service representatives are ready to han­dle all your service needs.
If unable to locate a dealer or distributor, consult the Yellow Pages. Typically, our distributors are listed under:
GENERATORS-ELECTRIC, ENGINES-GASOLINE OR DIESEL, OR RECREATIONAL VEHICLES-EQUIPMENT, PARTS AND SERVICE.
For the name of your local Cummins
/Onan or Onan-only distributor in the United States or Cana­da, call 1-800-888-ONAN. (This automated service utilizes touch-tone phones only.) By entering your area code and the first three digits of your local tele­phone number, you will receive the name and tele­phone number of the distributor nearest you.
For the name of your local Cummins-only distribu­tor, or if you need more assistance, please call:
Onan Corporation, 1-612-574-5000, 7:30 AM to 4:00 PM, Central Standard Time, Monday through Friday.
When contacting your distributor, always supply the complete Model Number and Serial Number as shown on the nameplate.
Cummins is a registered trademark of Cummins Engine Company. Onan is a registered trademark of Onan Corporation. PowerCommand is a trademark of Onan Corporation.
1-2
Page 14
2. Mounting
LOCATION
The location of the transfer panel varies with the ap­plication. Locate the panel in proximity of the com­mercial power supply circuit breaker. There should be enough room to add another circuit breaker to the emergency side of the transfer panel. A typical residential installation is shown in Figure 2-1.
The National Electrical Code (NFPA No. 70, Art 702−6) should be used as a guide for all AC wir­ing connections.
WARNING
installed by qualified electricians. Improper installation presents hazards of electrical shock and improper operation, resulting in se­vere personal injury or property damage.
There must be a service disconnect in the commer­cial supply power line ahead of the transfer panel.
Cabinet dimensions are listed in Table 2-1.
Choose a vibration-free mounting surface that will support the weight of the panel. Avoid locations where unauthorized persons can damage or open the cabinet or that are near flammable liquids or gases; such as fuel tanks, or are hot, moist, or dusty; such as dryer vent lines.
Electrical connections must be
WALL MOUNTING
1. Use four 3/8 inch bolts for wall mounting. Refer to Figures 2-2 and 2-3 for the outline drawing of the panel. Measure and mark wall for drilling. Before drilling, check the location to be sure that no wires, or plumbing, gas, or exhaust lines run behind the wall.
2. Install two mounting bolts in the wall for the top cabinet mounting keyholes.
3. With the shipping box standing so the cabinet is upright, carefully remove the top and sides of the shipping box.
4. Raise the cabinet and mount it on the two mounting bolts in the wall. Provide support for the cabinet during installation.
WARNING
vere personal injury. Have sufficient per­sonnel for lifting and mounting the cabinet.
5. Install two bottom mounting bolts, but do not tighten. (Do not remove the cabinet support un­til all bolts are installed.)
6. Push the cabinet against the wall. If the cabinet will not align flush against the wall, shim the mounting bosses as required.
Improper lifting can cause se-
WARNING
Because an electrical arc will occur during transfer, the panel must not be located near batteries, fuel tanks, solvents, or other sources of flammable liquids or gases.
Amp
Rating
60, 120 lbs 29 in 18 in 11.06 in 28.43 in 100 (54.43kg) (737mm) (457mm) (281mm) (722mm) 200 155 lbs 34 in 21.5 in 11.06 in 31.87 in
7. Tighten all mounting bolts.
Refer to the outline drawings shown in Figures 2-2 and 2-3 for mounting hole dimensions.
TABLE 2-1. APPROXIMATE NEMA 1
CABINET DIMENSIONS
Depth With
Weight Height Width
(70.31kg) (864mm) (546mm) (281mm) (809mm)
Door
Closed Open
2-1
Page 15
UTILITY
ELECTRIC
SERVICE
GENSET
MAIN DISTRIBUTION PANEL
SUB-PANEL
TRANSFER
PANEL
ELECTRIC
DISCONNECT
GAS
LINE
ELECTRICAL SERVICE
FROM GENSET
NOTE:The transfer panel, sub-panel, and main distribution
panel must be installed inside the building
FIGURE 2-1. TYPICAL WALL-MOUNT INSTALLATION
2-2
Page 16
FIGURE 2-2 TYPICAL 60 & 100 AMP OUTLINE DRAWING
310-0924 REV. A
MODIFIED 6/99
2-3
Page 17
FIGURE 2-3. TYPICAL 200 AMP OUTLINE DRAWING
310-0925 REV. A
MODIFIED 6/99
2-4
Page 18
3. Wiring
WARNING
AC voltages and currents present an electrical shock hazard that can cause se­vere personal injury or death. Only trained and experienced personnel are to perform the fol­lowing procedures.
WIRING CONSIDERATIONS
The correct wiring hub must be used when installing conduit to maintain the cabinet rating. When instal­ling conduit, observe the following precautions:
1. Before beginning conduit installation, cover the transfer panel to prevent accidental entry of metal chips.
2. If using rigid conduit between the generator set and the transfer panel, install at least 2 feet (610 mm) of flexible conduit between the rigid conduit and generator set to absorb vibration.
3. Run control circuit wiring in separate conduit from the AC wiring; otherwise, induced cur­rents could cause operational problems within the panel.
Control wire must be of the stranded type. Do not use solid wire.
AC CONNECTIONS
Perform wiring in the following sequence:
1. Test the operation of the generator set from its own controls.
2. Stop the generator set by pushing the control switch to OFF and disconnect the negative (−) lead from the cranking battery to prevent start­ing.
WARNING
set from starting before wiring procedures are performed presents a shock hazard that can cause severe personal injury or death.
Table 4-1 shows the type and range of con­ductor sizes the transfer panel will accept.
TABLE 4-1. TERMINAL LUG CAPACITY
(FOR COPPER (CU) OR ALUMINUM (AL)
Panel Number of Size Range of
Amp Rating Conductors Conductors
60 1 2 - 10 AWG CU 100 1 2/0 - 14 AWG CU/AL 200 1 300 MCM − 6 AWG
GROUND LUG 1 4 - 14 AWG CU
Failure to prevent the generator
CONDUCTORS)
CU/AL
4. Cutouts can be made through the top, bottom, or sides of the cabinet. (Refer to the transfer panel control box outline drawings in section
2.)
CAUTION
Installation debris can cause equipment failure and damage. Use ex­treme care to keep drill chips and filings out of the relays, contacts, and other parts of the automatic transfer panel when mount­ing or connecting conduit. Screwdrivers should be used carefully to prevent dam­age to components.
3. Connect conductors of sufficient size to carry rated current from the line, load, and generator set directly to the transfer panel terminals.
The Normal power and Emergency power con­nections are marked L1, L2 and L3 The load connections are marked T1, T2 and T3. A neu­tral bar with lugs is standard. See Figure 3-1.
Use the National Electrical Code (NFPA No. 70, Ar t 702−6) as a guide for AC wiring connec­tions and type between the genset and the transfer panel.
3-1
Page 19
NORMAL
POWER SOURCE
EMERGENCY
POWER SOURCE
A B C
L1 L2 L3
GND TERMINAL
FIGURE 3-1. RST GENSET LINE CONNECTIONS
4. On this 240-volt single phase switch, connect the two hot lines to the L1 and L3 lugs and con­nect the neutral line to the neutral bar.
5. Connect power cables to the load terminals T 1 and T3. Tighten the lugs as indicated in Table 4-2.
A B C
L1 L2 L3
NEUTRAL BAR
T1 T2 T3
A B C
LOAD
NOTE: 200 Amp panel is shown as reference only.
CONTROL CONNECTIONS
Connections of standard and optional control wiring are made at terminal blocks TB2 and (Figure 3-2).
optional
TB3
6. Make sure both AC power sources are discon­nected.
WARNING
AC voltages and currents pres­ent an electrical shock hazard that can cause severe personal injury or death. Make sure that both AC power sources are disconnected.
TABLE 4-2. LUG TORQUES
SET SCREW SOCKET SIZE MINIMUM TORQUE (ACROSS FLATS) FOR PROPER OPERATION
3/16 IN 80 IN-LBS (9 NM)
1/4 IN 200 IN-LBS (23 NM)
5/16 IN 275 IN-LBS (31 NM)
3/8 IN 375 IN-LBS (43 NM) 1/2 IN 500 IN-LBS (57 NM)
9/16 IN 600 IN-LBS (68 NM)
3-2
TB2
TB3 (OPTIONAL)
FIGURE 3-2. CONTROL WIRING CONNECTIONS
Page 20
Remote Start-Stop Connections
Use number 18 to number 12 AWG wire. Resist­ance must not exceed 0.5 ohm per line. Use stranded wire only. For connections to the TB2 screw terminals, use number 8 ring or spade termi­nals. For connections to TB3, strip the insulation back 3/8 inch (10 mm).
Two-Wire Starting:
ter-cooled generator sets uses terminals B+, GND (ground), and RMT of terminal block TB2.
Two-wire starting for Onan wa-
tached to TB2) is installed from TB2-2 to TB2-B+ and another from TB2-B+ to TB3-1. Make no other connections to TB2; terminals GND, 2, B+, and RMT.
WARNING
Improper wiring of start-stop con­nections can result in severe personal injury or equipment damage. Carefully follow all wiring instructions and make no other connections to TB2; terminals GND, 2, B+, and RMT when a three-wire start system is used.
(OPTIONAL) Three-Wire Starting:
(Available only
with a field installed 3-Wire Start Kit.) Three-wire starting for Onan generator sets uses
terminals 1, 2 , 3 , 4 , and 5 of terminal block TB3 (Fig­ure 3-4).
Connect terminals 1, 2, 3, and 4 to terminals on the generator set, as shown in Figure 3-4. With diesel sets that use the preheat circuit, connect terminal 5 on TB3 to terminal H on the generator set control.
Terminals 6, 7 , and 8 of TB3 (Figure 3-5) are for con­nection to the overcrank alarm contacts. These (Form C) contacts are rated for 4 amperes at 120 VAC or 3 amperes at 30 VDC and are provided for customer use.
Ground Switching:
Determine whether your gener­ator set has a switching ground or a switching B+ remote start system:
1. Measure the DC voltage from the Start terminal to the Ground terminal. (The starting battery must be connected.)
If 12 VDC is measured, it is a switching ground system.
If 0 VDC is measured, it is a switching B+ system.
For 3-wire start systems using a switching ground, install or make sure a jumper (provided in envelope attached to TB2) is connected from TB2-GND to TB2-2. Make no other connections to TB2; termi­nals GND, 2, B+, and RMT.
For 3-wire start systems using switching B+, install or make sure a jumper (provided in envelope at-
INSTALL JUMPER
TB2-1 TO TB2−2
FOR REMOTE
GROUND SIGNAL
INSTALL JUMPER
TB2-2 TO TB2-3 FOR
B+ REMOTE START
SIGNAL
TB2
GRD 2 B+ RMT 5 6 7 8
FIGURE 3-3. TWO WIRE START CONNECTIONS
GENERATOR SET
TERMINALS
BATTERY+
GROUND
STOP
START
PREHEAT
NO
COM
NC
OVERCRANK
ALARM CONTACTS
TB3
1
2
3
4
5
6
7
8
9
10
FIGURE 3-4. THREE-WIRE START CONNECTIONS
3-3
Page 21
INSPECTION AND CLEANUP
Inspect all wiring to be certain that:
Wiring does not interfere with switch operation.
Wiring will not be damaged as door opens and
closes.
No wiring is left loose and unconnected.
After mounting and wiring the cabinet, clean the in­terior with a vacuum cleaner to remove any chips, filings, or dirt from the cabinet interior and compo­nents.
Installation is not yet complete. Do not energize the transfer panel until instructed to
do so in Sections 4 and 5.
3-4
Page 22
4. Setup and Calibration
BEFORE CALIBRATING
The RST transfer panel is equipped with two control package options:
Control package A has preset undervoltage sensing and time delays.
Control package B has adjustable undervol­tage sensing and adjustable time delays.
After installing the transfer panel, the undervoltage sensing must be calibrated. Control package B and any optional electronic modules must be adjusted to the desired settings.
LOAD/NO-LOAD SWITCH
LOCATED ON CIRCUIT BOARD
EXERCISER CLOCK
LOCATED BEHIND COVER (CONTROL PACKAGE B ONLY)
CONTROL
BOARD COVER
LOCATED ON CIRCUIT BOARD
Install J1 Connector
Install connector J1 when all of the wiring is com­plete. Also install connectors for any installed op­tions.
WARNING
rear side of the cabinet door present a shock hazard that can cause severe personal injury or death. Use extreme caution to avoid touching electrical contactors whenever the cabinet door is open.
AUTO/MANUAL SWITCH
CONTROL STATUS INDICATOR LEDS
LOCATED ON CIRCUIT BOARD
J1/P1 CONNECTOR
AC power within the cabinet and the
3-PHASE/1−PHASE
SWITCH LOCATED
BEHIND COVER
(CONTROL
PACKAGE B ONLY)
OPTIONAL
EXERCISER
CLOCK
(CONTROL
PACKAGE A)
OPTIONAL
3-WIRE START
BATTERY
CHARGER
GROUNDING LUGS
TB2
CONTACTOR
ASSEMBLY
NEUTRAL
BAR
FIGURE 4-1. LOCATION OF CONTROL COMPONENTS
4-1
Page 23
Connect the Battery
Make sure that the RUN switch on the generator is in the OFF position and connect the battery (nega­tive [−] lead last). If applicable, reconnect the exter­nal battery charger.
WARNING
Ignition of explosive battery gases can cause severe personal injury. Do not smoke or cause any arc, spark, or flame while servicing batteries.
Connect AC Line Power
Connect AC line power to the automatic transfer panel. The Normal Available and Normal Con­nected LEDs on the control board will light if the volt­age sensors are calibrated. See Figure 4-2.
VOLTAGE SENSORS
Control package A has undervoltage sensing for one phase of the Normal and Emergency sides with fixed pickup and dropout settings. The Pickup volt­age is preset to 85% of Normal, and Dropout is pre­set to 75% of Pickup.
Control package B has three phase undervoltage sensing for the Normal side and single phase sens­ing of the Emergency side. This control has adjust­able pickup and dropout settings. Pickup is adjust­able from 85% to 100% of Normal, and Dropout is adjustable from 75% to 98% of Pickup. The adjust­ment procedure is described in the following sec­tion.
FIGURE 4-2. CONTROL BOARD LEDs
NORMAL
PICKUP
EMERGENCY
CALIBRATION
NORMAL
CALIBRATION
NORMAL
DROPOUT
EMERGENCY
PICKUP
EMERGENCY
DROPOUT
STOP
RETRANSFER
DELAY
TRANSFER
DELAY
START
FIGURE 4-3. CONTROL PACKAGE B ADJUSTMENTS
4-2
Page 24
Undervoltage Sensor Calibration
Voltage sensors monitor the Normal and Emergen­cy power sources for an undervoltage condition.
The Emergency sensor monitors the Emer-
gency (generator set) power source.
To calibrate the undervoltage sensors:
CAUTION
Incorrect setting of the calibration (Cal) adjustments will result in abnormal opera­tion of the transfer switch.
WARNING
AC power within the cabinet and the rear side of the cabinet door presents a shock hazard that can cause severe personal injury or death. Use extreme caution to avoid touching electrical contacts whenever the cabinet door is open.
All adjustments are made by turning the appropriate potentiometer with a screwdriver. The adjustment potentiometers are accessed by removing the cov­er from the control board.
A separate voltage sensor is used for each power source. The adjustment pot locations are shown in Figure 4-4.
The Normal sensor monitors the Normal (util-
ity) power source.
Control Package A
1. Check that nominal voltage is present on all phases of the source being calibrated (Normal and Emergency).
2. Move the calibration switch (Figure 4-4) to the CAL position. Turn the Normal or Emergency calibration potentiometer fully counterclock­wise.
3. Slowly turn the Normal or Emergency calibra­tion (Cal) potentiometer counterclockwise until the Source Available LED corresponding to the source sensor being calibrated turns ON.
4. The undervoltage sensor is now calibrated. Repeat this procedure for the other source.
5. Move the calibration switch to the 85% posi­tion. This sets the sensor to 85% pickup and 75% dropout.
UNDERVOLTAGE
PICKUP AND
DROPOUT
ADJUSTMENT POTS
(4) CONTROL
PACKAGE B ONLY
FIGURE 4-4. UNDERVOLTAGE CALIBRATION, PICKUP AND DROPOUT ADJUSTMENT
CALIBRATION
SWITCH (S4)
CONTROL
PACKAGE A ONLY
POTENTIOMETERS
4-3
Page 25
Control Package B
1. Check that nominal volatage is present on all phases of the source being calibrated (Normal and Emergency).
2. Perform the following for the Normal source un­dervoltage sensor:
a. Turn the Normal Pickup pot (Figure 4-4)
fully clockwise to 100% pickup.
b. Turn the Normal calibration (Cal) pot fully
counterclockwise.
c. Turn the Normal Dropout pot fully clock-
wise to 97% dropout.
3. Turn on Normal source and check for nominal voltage.
4. Slowly turn the Normal calibration (Cal) poten­tiometer clockwise until the Normal Available lamp just turns ON.
5. Perform the following for the Emergency source undervoltage sensor:
a. Turn the Emergency Pickup pot fully clock-
wise to 100% pickup.
b. Turn the Emergency calibration (Cal) pot
fully counterclockwise.
c. Turn the Emergency Dropout pot fully
clockwise to 97% dropout.
6. Turn on Emergency source and check for nom­inal voltage.
7 Slowly turn the Emergency calibration (Cal) po-
tentiometer clockwise until the Emergency Available lamp just turns ON.
8. Turn off both power sources.
Proceed to Undervoltage Pickup and Dropout Ad­justments.
Undervoltage Pickup and Dropout Adjustments (Control Package B Only)
Undervoltage dropout occurs when an undervol­tage condition is sensed. Pickup occurs when an acceptable voltage is sensed. Undervoltage drop­out and pickup are preset on control package A. Un­dervoltage dropout and pickup are adjustable over the following ranges on control package B:
FUNCTION ADJUSTMENT RANGE
Pickup 85% to 100% of nominal voltage Dropout 75% to 98% of pickup voltage
To set the pickup and dropout percentages, align the slots on the potentiometers with the desired markings as shown in Figure 4-4).
4-4
Page 26
TIME DELAYS
The time delays control the four following functions:
Start time delay
Stop time delay
Transfer time delay
Retransfer time delay
The time delays on control package A are preset as follows:
DELAY SETTING
Start 3 seconds Stop 5 minutes Transfer 3 seconds Retransfer 5 minutes
The time delays on control package B are adjust­able over the following ranges:
DELAY ADJUSTMENT RANGE
Start 0 to 15 seconds Stop 0 to 10 minutes Transfer 0 to 120 seconds Retransfer 0 to 30 minutes
To set the time delays, align the slots on the poten­tiometers with the desired markings (see Figure 4-5).
FIGURE 4-5. CONTROL PACKAGE B TIME DELAY ADJUSTMENT
4-5
Page 27
3-WIRE START MODULE (OPTIONAL)
The 3-Wire Start module has two adjustable timers. The Preheat timer delays the start signal to allow
preheating the generator set. The Preheat timer’s range of adjustment is 0 to 60 seconds.
If a preheat delay is desired, make sure that the Pre­heat timer’s On/Off switch is in the On position.
Programming the exerciser clock requires setting the time of day and entering the exercise start and stop times as described in the following sections. The exerciser clock has backup power for approxi­mately six hours. After six hours the day and time will have to be reset. Exercise programs will not be lost during a power outage (exercise programs are stored in EEPROM).
To reset the exerciser clock program:
The Overcrank timer limits the time that the genera­tor set starter is allowed to operate. The Overcrank timer’s range of adjustment is 0 to 120 seconds.
To set the timers, align the slots on the potentiome­ters with the desired markings on the faceplate (Fig­ure 4-6).
Resetting the exerciser clock erases all exist­ing day, time and exercise program settings.
Depress and hold the arrow, plus and set but­tons () (+) (
) simultaneously. Release the plus and set buttons while continuing to hold the arrow button. When all aspects of the LCD display appear, release the arrow button.
To set the day and time:
1. With the exerciser clock powered, press all three buttons simultaneously to reset the time. The time display area will show (− − : − −) and a small clock symbol will appear in the upper left­corner of the display. Refer to Figure 4-7.
2. Press the arrow () button once to set the day­of-week. The clock symbol will begin flashing to indicate the clock is being programmed and the display will show midnight ( 0:00).
CLOCK
SYMBOL
PR INDICATES
PROGRAMMING
MODE
FIGURE 4-6. 3-WIRE START
EXERCISER CLOCK
The exercise clock is optional on RST Transfer Pan­els with control package A and is standard equip­ment on RST T ransfer Panels with control package B.
The exerciser clock is used to start and run the gen­erator set at programmable intervals and for se­lected durations. It is a 7-day, 24-hour clock that can store and execute up to four start/stop programs per day (one minute minimum duration). The exerciser clock also has a test feature that can be used to initi­ate a genset start and run cycle.
4-6
TIME
DISPLAY
DAY
DISPLAY
ARROW
FIGURE 4-7. EXERCISER CLOCK
PLUS
SET
Page 28
3. Press the plus (+) button as many times as nec­essary until the current day-of-week is dis­played.
Example: 1 = Monday, 2 = Tuesday, etc.
4. Press the arrow () button again to set the hour of the day. The clock uses 24-hour (mili­tary) time.
5. Press the plus (+) button until the current hour is displayed.
Example: 2:00 PM is 14:00.
6. Press the arrow () button again to set the minutes.
7. Press the plus (+) button until the current min­utes are displayed. Note that by holding the plus (+) button down, the minutes will increment in 5 minute intervals.
8. To set or change the exercise program, press the arrow () button again and go to step two in the following section. To return to the normal operating mode, press the arrow () button eight times (clock symbol appears in the dis­play).
To set the exercise start and stop time:
1. Press the arrow () button four times to start the programming mode.
2. The letters Pr will appear in the lower right hand corner of the display when the programing mode is reached (Pr will be flashing if there are no existing programs).
Press the arrow () button as many times as necessary to advance to the day to be pro­grammed.
reached, press the set ( indicated, Figure 4-8).
Then increment the time with the plus (+) but­ton to the desired Stop time. When the Stop time is reached, press the set ( Mode is indicated, Figure 4-8).
) button (ON Mode is
) button (OFF
Example to exercise the genset one hour: Set Start at 7:00 PM (19:00) Set Stop at 8:00 PM (20:00)
Note that the exercise time is indicated by a band of segments illuminated around the outer ring of the clock from the start to the stop time.
To clear the program, press the plus and set (+) (
) buttons at the same time.
4. Pressing the arrow () button advances to the next day. The program is copied to the next day if the next day does not have an existing pro­gram.
To change or clear the program, press the plus and set (+) (
Double check the program setting for each day . Press the arrow () button repeatedly until the clock mode is passed and the pro­gram mode (Pr) is reached. Carefully check each days program and clear any unwanted programs.
5. When finished programming, press the arrow () button until the clock appears in the upper left corner of the display.
During the exercise period, the ON mode is indi­cated in the ellipse in the upper right corner of the display (Figure 4-8).
) buttons at the same time.
To check the programs:
To clear an existing program for the day se­lected, press the plus and set (+) (
the same time.
3. Press the plus (+) button to increment the Start time of the exercise program. The display will show midnight ( 0:00). Note that by holding the (+) button down, the minutes increment in 15 minute intervals. When the Start time is
) buttons at
Push the arrow () button to review each setting.
To erase (clear) a program:
Press the arrow () button until the program mode (Pr) is reached. Press the arrow () button again to select the desired day. To clear the program for the
day selected, press the plus and set (+) ( at the same time.
4-7
) buttons
Page 29
SEGMENTS INDICATE
EXERCISE TIME
TEMPORARY OVERRIDE MODE
(FLASHING HANDS INDICATES
PERMANENT ON/OFF MODE)
OFF MODE
ON MODE
To Initiate or Override an Exercise Program:
The exerciser clock has a built-in test feature. Once the clock time has been set, the set button (
) can be used to initiate a test or to cancel a test in prog­ress.
With the normal source connected and available, pressing the set (
) button once initiates a test se­quence. A hand is displayed in the upper left corner of the display and the ON mode is indicated inside the ellipse in upper right corner of the display (Fig-
ure 4-8). Pressing the set (
) button again stops
the test and the ellipse indicates the OFF mode.
To temporarily override an activated exercise pro­gram,
momentarily
press the set ( ) button. A small hand will appear in the upper left corner of the dis­play (Figure 4-8). The current program is overrid­den and the clock automatically sets the next pro­gram. Momentarily pressing the set (
) button
again returns to the current program.
FIGURE 4-8. EXERCISER CLOCK ON/OFF MODE
Permanent On/Off Mode:
Holding the set ( ) button down until a
hand appears
in the upper left corner of the display
flashing
initiates the permanent On/Off mode. The ON mode is indicated by a continuous band of segments illu­minated around the clock. The OFF mode is indi­cated by all of the segments around the clock being
off. Pressing the set (
) button momentarily toggles between the permanent On and permanent Off modes. Holding the set (
) button down until the clock symbol returns to the upper left corner of the display, ends the continuous On/Off mode and returns to the normal program mode.
4-8
Page 30
FLOAT BATTERY CHARGER
The float-charge battery charger regulates its charge voltage to continuously charge the battery. As the battery approaches full charge, the charging current automatically tapers to zero amperes or to steady-state load on the battery.
CAUTION
Always disconnect the battery char­ger from its AC source (remove the charger’s AC input fuses) before disconnecting the bat­tery cables. Otherwise, disconnecting the cables can result in voltage spikes high enough to damage DC control circuits.
NOTE: The pulsing meter indicates the charger is working.
The battery charger is rated for 2 amperes at 12 or 24 VDC.
Power to the battery charger is supplied directly from the Normal source through connector J6/P6. The output of the battery charger is connected to the GND and B+ terminals of TB2 (or TB3 if the 3-Wire Start module is used). Refer to sheets 2 and 4 of the schematic and wiring diagram package.
Battery Charger Float Voltage
The float voltage is set at the correct value at the factory and should not require adjustment. Howev­er, if the battery shows signs of being overcharged or undercharged, the float voltage can be adjusted. A high specific gravity, bubbling of electrolyte, and loss of water indicate a high float voltage. A low specific gravity indicates a low float voltage.
WARNING
can cause severe personal injury. Do not smoke or cause any spark, arc, or flame while servicing batteries.
To check and adjust the float voltage, the following tools are needed:
Ignition of explosive battery gases
1. Turn the operation selector switch for the gen­erator set to OFF and disconnect the starting battery (negative [−] lead first).
The selector switch is located on the genera­tor set control panel on two-wire start sys­tems and on 3-Wire Start module on three­wire start systems.
2. Connect the fully charged battery (negative [−] lead last) to the generator set and verify the charge condition with the hydrometer.
A fully charged lead-acid battery will have a specific gravity of 1.260 at 77
° F (25° C).
3. Connect the voltmeter directly to the battery terminals and measure the voltage.
Make sure the 12/24 volt selector switch is in the correct position.
4. Compare the voltage reading with the value shown in Table 5-1. If the voltage is above or below the recommended float voltage, open the cabinet door and adjust as specified in Step
5. If the voltage is correct, proceed to Step 7.
a fully charged test battery
a hydrometer
a small screwdriver
an accurate voltmeter (0.5% accuracy
Checking the voltage:
Use the following proce-
dures to check the float voltage.
CAUTION
Do not attempt to adjust or test the battery charger with a deeply discharged bat­tery. Use a fresh, fully charged battery when ad­justing or testing the charger.
TABLE 5-1. BATTERY FLOAT
VOLTAGES
Lead-Acid Batteries
Battery Voltage Float Voltage
12 13.3
Nickel-Cadmium Batteries
Float Voltage Charge Per Cell
1.38 to 1.45 volts
Example: Float charge for 10 cell battery should
be 13.8 to 14.5 volts.
4-9
Page 31
5. Use a small screwdriver to turn the adjustment potentiometer (located on charger panel) counterclockwise to decrease the float voltage and clockwise to increase the float voltage. Ad­just in small steps and wait five minutes for the voltage to stabilize before making additional adjustments.
WARNING
AC power within the cabinet and the rear side of the cabinet door pres­ents a shock hazard that can cause severe personal injury or death. Avoid touching electrical contacts. Do not wear jewelry or loose clo t h i n g . S t and on a dry , non-conduc­tive surface such as a rubber mat or wood­en platform.
6. When adjustments are complete, close and lock the transfer panel cabinet door.
7. Disconnect the voltmeter from the battery ter­minals and disconnect the test battery (nega­tive [−] lead first) from the generator set.
8. Reconnect the generator set starting battery (negative [−] lead last) and place the operation selector switch in the Auto (three-wire start) or Remote (two-wire start) position.
4-10
Page 32
5. System Checkout
WARNING
AC power within the cabinet and the rear side of the cabinet door presents a shock hazard that can cause severe personal injury or death. Use extreme caution to avoid touching electrical contacts whenever the cabinet door is open.
WARNING
Improper operation of the genera­tor set presents a hazard that can cause severe personal injury or death. Observe all safety pre­cautions in your generator set Operation and Installation manuals.
STARTING TEST
Two-Wire Starting
1. Move the selector switch on the engine control to RUN. The generator set should start and run.
2. Move the selector switch to OFF. The genera­tor set should stop. Return the selector switch to Remote for automatic operation.
Three-Wire Starting (Optional)
2. Push the start button on the generator set con­trol. The generator set should start and run.
3. Move the Stop/Auto/Handcrank switch from Handcrank to Stop. The generator set should stop.
4. Move the Stop/Auto/Handcrank switch to Auto. The generator set should not start.
TEST TRANSFER WITH LOAD
1. Move the Load/No-Load switch on the control circuit board to the Load position (Figure 4−1).
2. Keep the Auto/Man switch in the Auto position at all times to enable the automatic retransfer function.
3. Replace the cover over the circuit board and close the cabinet door.
WARNING
and the rear side of the cabinet door pres­ents a shock hazard that can cause severe personal injury or death. Close the cabinet door.
AC power within the cabinet
1. Move the Stop/Auto/Handcrank switch on the 3-Wire Start module to Handcrank.
LOAD/NOLOAD SWITCH
FIGURE 4−1. CONTROL CIRCUIT BOARD
4. Notify occupants prior to removing utility pow­er.
AUTO/MAN SWITCH
5-1
Page 33
5. Turn o ff any electronic devices, computers etc. prior to removing utility power.
TEST OVERCRANK FUNCTION
THREE-WIRE STARTING
If the standby power is supporting all circuits within the home, turn off any electronic ap­pliances and reduce other loads until the total load does not exceed 80% of the generator’s kW rating.
6. Remove the AC utility power to the transfer panel.
If the transfer panel is wired to a secondary dis­tribution panel, open the breaker(s) in the main distribution panel that supply utility power to the transfer panel.
7. After testing, return AC utility power.
8. Keep the transfer panel door securely closed at all times and make sure only qualified service personnel have access to the cabinet.
If the optional 3-Wire Start module is installed:
1. Disconnect the positive start lead from the start solenoid or starter.
2. Move the Stop/Auto/Handcrank switch on the 3-Wire Start module to Auto.
3. Turn On the remote test switch (if connected). The Lockout lamp on the 3-Wire Start module should light at the end of the crank period (0 to 120 seconds—per setting).
4. Turn off the remote test switch.
5. Move the Stop/Auto/Handcrank switch to Stop and push the Overcrank Reset button (the Lockout lamp should go out).
6. Reconnect the positive lead to the starter or start solenoid.
7. Move the Stop/Auto/Handcrank switch to Auto.
5-2
Page 34
Cummins Power Generation 1400 73rd Avenue N.E. Minneapolis, MN 55432 1-800-888-6626 763-574-5000 International Use Fax: 763-528-7229
Cummins is a registered trademark of Cummins Inc.
Loading...