10 MAINTENANCE RECORD 10-1
11 WIRING DIAGRAMS 11-1
General 11-1
Page 4
Safety Precautions
Before operating the generator set, read the
erator's Manual and become familiar with
equipment. Safe
achieved only
ated
and
maintained. Many accidents are caused
by failure
tions.
The following symbols, found throughout this manual,
the operator, seivice personnel,
rUJMtHil This symbol warns
hazards which will result
jury
IAWARNINGI This symbol refers
safe practice which
sonal Injury
to
alert you
or
death.
and
efficient operation
If
the equipment
follow fundamental rules
to
potentially dangerous conditions
In
can
or
death.
is
properly oper-
and
or
the equipment.
of
immediate
severe personal
to
a hazard or un-
result
in
severe per-
Op-
it
and
can be
precau-
in-
the
to
•
Be
sure all fuel supplies have a positive shutoff
valve.
•
Be
sure battery area
prior
to
servicing near
emit a highly explosive hydrogen
be ignited
EXHAUST
• Provide
erly expel discharged gases away from
closed
dividuals are likely to congregate. Visually
audibly inspect
the maintenance schedule. Ensure that
haust manifolds
Do
not use
ment.
•
Be
sure
by
arcing, sparking, smoking,
GASES
an
adequate exhaust system
or
sheltered areas
exhaust gases
the
unit
has
been well-ventilated
it.
Lead-acid batteries
ARE
DEADLY
and
the
exhaust daily
are
secured
is
well ventilated.
areas where
and not
to
heat a compart-
gas
for
that
can
etc..
to
prop-
en and
leaks
per
ex-
warped.
in-
IACAUTIONI This symbol refers
safe practice which can result In personal injury
or product or property damage.
FUEL
AND
Fire,
explosion, and personal injury or
sult from improper practices.
•
DO NOT
unless tanks
ment. Fuel contact with
is a potential fire hazard.
• DO NOT permit any
spark, arcing equipment,
source near the generator
• Fuel lines must
free
should
Do
copper will become brittle
brated
FUMES
fill fuel tanks while engine
of
leaks. Fuel connection
be
made with
not use
or
repeatedly bent.
ARE
are
outside
flame,
be
adequately secured
an
copper piping
to
a hazard or un-
FLAMMABLE
death
the
engine compart-
hot
engine
cigarette, pilot light,
or
other ignition
set or
at the
approved flexible line.
on
flexible lines
if
continuously
can
is
running,
or
exhaust
fuel tank.
and
engine
re-
as
vi-
MOVING
PERSONAL
• Keep your hands, clothing,
• Before starting work on
• Make sure that fasteners
•
Do
•
If
PARTS
from moving parts.
connect battery charger from
then disconnect starting batteries, negative
cable first. This
are secure. Tighten supports
keep guards
etc.
not wear loose clothing
cinity
of
moving
trical equipment. Loose clothing
can become caught
can short
shock
or
adjustment must
running,
folds,
moving parts,
CAN
INJURY
in
out
electrical contacts
buming.
use extreme caution around hot mani-
CAUSE
OR
DEATH
the
will
prevent accidental starting.
position over fans, drive belts,
parts,
or while working on elec-
in
moving parts. Jewelry
be
made while
etc.
SEVERE
and
jewelry away
generator set, dis-
its AC
on the
or
generator
and
jewelry
source,
clamps,
in the
and
and
the
(-)
set
vi-
jewelry
cause
unit
is
in
LS-10
Page 5
ELECTRICAL
SEVERE
• Remove electric power before removing protective shields or touching electrical equipment. Use rubber insulative mats placed on
dry wood platforms over floors that are metal or
concrete when around electrical equipment.
Do not wear damp clothing (particularly wet
shoes) or allow skin surface to be damp when
handling electrical equipment.
• Use extreme caution when working on electrical components. High voltages can cause injury or
• Follow all applicable state and local electrical
codes. Have all electrical installations performed by a qualified licensed electrician. Tag
open switches to avoid accidental closure.
• DO NOT CONNECT GENERATOR SET DIRECTLY TO ANY BUILDING ELECTRICAL
SYSTEM.
the generator set into the utility line. This creates a potential for electrocution or property
damage. Connect only through an approved
isolation switch or an approved paralleling device.
GENERAL SAFETY
• Coolants under pressure have a higher boiling
point than water. DO NOT open a radiator or
heat exchanger pressure cap while the engine
is running. Allow the generator set to cool and
bleed the system pressure first.
SHOCK
PERSONAL
death.
DO NOT tamper with interlocks.
Hazardous voltages can flow from
CAN
INJURY
PRECAUTIONS
CAUSE
OR
DEATH
Benzene and
have been identified by some state and federal
agencies as causing cancer or reproductive
toxicity. When checking, draining or adding
gasoline, take care not to ingest, breathe the
fumes, or contact gasoline.
Used engine oils have been identified by some
state or federal agencies as causing cancer or
reproductive toxicity. When checking or
changing engine oil, take care not to ingest,
breathe the fumes, or contact used oil.
Provide appropriate fire extinguishers and install them in convenient locations. Consult the
local fire department for the correct type of ex-
tinguisher to
fires.
Use extinguishers rated ABC by NFPA.
Make sure that rags are not left on or near the
engine.
Remove all unnecessary grease and oil from
the unit. Accumulated grease and oil can
cause overheating and engine damage which
present a potential fire hazard.
Keep the generator set and the surrounding
area clean and free from obstructions. Remove any debris from the set
clean and dry.
Do not work on this equipment when mentally
or physically fatigued, or after consuming any
alcohol or drug that makes the operation of
equipment unsafe.
Substances in exhaust gases have been iden-
tified by some state or federal agencies as
causing cancer or reproductive toxicity. Take
care not to breath or ingest or come into contact
with exhaust gases.
lead,
found in some gasoline,
use.
Do not use foam on electrical
and
keep the floor
KEEP
THIS MANUAL
NEAR
THE
GENSET
iv
FOR
EASY REFERENCE
Page 6
1.
Introduction
ABOUT
This manual provides installation instructions, and
information on
the Onan® RDJC generator set
manual carefully and comply with each of its warnings and
and performing regular maintenance can result in
longer unit life, better performance, and safer operation.
The generator set has been carefully designed to
provide safe and efficient service when properly installed and operated. However, the overall safety
and reliability of the complete system is dependent
on many factors outside the control ofthe generator
set manufacturer. To avoid possible safety hazards,
make all mechanical and electrical connec-
tions to the generator set exactly as specified in this
manual.
exhaust, electrical, etc.) must comply with all applicable codes. Make certain all required inspections
and tests have been completed and all code requirements have been satisfied before certifying
the installation is complete and ready for service.
operating,
cautions.
SAFETY
All systems external to the generator (fuel,
THIS
Using the generator set properly
CONSIDERATIONS
MANUAL
maintaining and adjusting
(genset).
Study this
HOW TO OBTAIN
When the generator set requires
your nearestl Cummins®/Onan® dealer or distributor. Factory-trained Parts and Service representatives are ready to handle all your seivice needs.
If you are unable to locate a dealer or distributor,
consultthe Yellow Pages. Typically, our distributors
are listed under:
GENERATORS-ELECTRIC or
ELECTRICAL PRODUCTS
Forthe name of your local Cummins/Onan or Onanonly distributor in the United States or Canada, call
1-800-888-ONAN
touch-tone phones only). By entering your area
code and the first three digits ofyour local telephone
number, you will receive the name and telephone
number of the distributor nearest you.
For outside North America, call Onan Corporation,
1-612-574-5000, 7:30 AM to 4:00 PM, Central
Standard Time, Monday through Friday. Or, send a
fax to Onan using the fax number 1 -612-574-8087.
When contacting your distributor, always supply the
complete Model Number and Serial Number as
shown on the generator set nameplate.
(this automated service utilizes
SERVICE
servicing,
contact
IAWARNING
INCORRECT SERVICE OR PARTS REPLACEMENT CAN RESULT IN SEVERE PERSONAL INJURY, DEATH, AND/OR EQUIPMENTDAMAGE. SERVICE PERSONNEL MUST BE QUALIFIED
TO PERFORM ELECTRICAL AND/OR MECHANICAL SERVICE.
Onan is a registered trademark of Onan Corporation.
Cummins is a registered trademark of Cummins Engine
Number of Cylinders 4
Engine Speed (50/60 Hz) 1500/1800 rpm
Recommended Fuel #1 or #2 diesel
Exhaust Connection (pipe tapped) 1.5 in. (38.1 mm)
Fuel Pump Maximum Lift 6 feet (1.8 mm)
Oil Filter Full flow type
Fuel Consumption (full load) 1.6 gallons/h (6 liters/h) (60 Hz)
1.4 gallons/h (5 liters/h) (50 Hz)
ELECTRICAL
Starting Voltage 12 Volts DC
Cranking Current 225 amps at ambient temp, of 32° F (0° C)
Battery 12 Volt, negative ground
Battery Size 560 amps (cold cranking) at 32° F (0° C)
Battery Charge Rate 2 to 5 amps (adjustable)
GENERATOR
Power
15.0 RDJC 15kW(60Hz)
12.5 RDJC 12.5 kW (50 Hz)
Output Rating 1.0 power factor (single-phase)
CAPACITIES
Coolant System (Includes Radiator) 13 U.S. quarts (121)
Oil Capacity 6.5 U.S. quarts (6.0 I)
TUNE-UP
Start-Disconnect Centrifugal Switch Point Gap
Cylinder Head Bolt Torque 44 - 46 ft-lb (60 - 62 N»m)
Glow Plug Torque 10-15 ft-lb (14 - 20 N»m)
Valve Clearances
Intake 0.011 in. (0.28 mm)
Exhaust 0.016 in. (0.41 mm)
Injector Firing Order 1, 2, 4, 3
SYSTEM
SPECIFICATIONS
800 amps (cold cranking) at 0° F (-18° C)
0.8 power factor (three-phase)
0.020
in. (0.51 mm)
2-1
Page 8
3. Installation
GENERAL
Most generator set installations must be designed
so that the generator set will function property under
all anticipated operating conditions. Use these
instructions as a general guide only. Follow the
instmctions of the consulting engineer when locat-
Requirements to be considered priorto installation:
• Level mounting surface
• Adequate cooling air
• Adequate fresh induction air
• Discharge of circulated air
• Discharge of exhaust gases
• Electrical connections
• Fuel connections
• Accessibility for operation and servicing
• Noise levels
• Vibration isolation
• Electrical connections
LOCATION
Provide a location for the genset that is dry, clean,
dust-free, well-ventilated, and protected from the
weather (see Figure 3-1). Generator set location is
decided mainly by related systems such as ventilation,
wiring,
fuel,
and exhaust. The set should be lo-
cated as near as possible to the main power fuse
box.
Provide a location away from extreme ambient
temperatures and protect the generator set from adverse weather conditions. An optional housing is
available for outside operation.
COOL AIR IN
GENERATOR SET
NOT LOCATE CLOSER
THAN 24"
[61
OMM] TO
ANY WALL)
AUTOMATIC LOAD
TRANSFER SWITCH
METER
CANVAS
SECTION
HEATED
AIR OUT
RETURN
LINE
TO FUEL TANK
G1079-1
FIGURE
3-1.
TYPICAL
3-1
INSTALLATION
Page 9
MOUNTING
Generator sets are mounted on a steel skid that provides proper support. The engine-generator assembly is isolated from the skid frame by mbber
mounts that provide adequate vibration isolation for
normal installations. For critical installations, install
vibration isolators between the skid base and
foundation.
Mount the genset on a substantial and level base
such as a concrete pad.
Use
3/4-inch
diameter, anchored mounting bolts to
secure the generator set skid to the floor to prevent
movement. Secure the skid using a flat washer and
hex nut for each bolt (Figure 3-2).
FLATWASHER
HEX NUT
SKID
12 INCH
(305 mm)
MOUNTING BOLT
FIGURE
3-2.
BOLT
in 627
DIAGRAM
3-2
Page 10
VENTILATION
Generator sets create a large amount of
heat,
which
must be removed by ventilation. An outdoor installation can rely on natural air circulation, but indoor
installations need enough properly sized vents in
the correct positions to maintain the necessary air
flow.
The presence or absence of a fan and radiator determines ventilation system design. With a radiator,
engine-pusher fan size is large enough to remove
heat from the engine, generator, and a few feet
(roughly a metre) of uninsulated exhaust pipe. Re-
strictive ducting or heat sources otherthan the
gen-
erator set require extra fans to increase airflow.
With other cooling options, ventilation fans are
needed.
Fan size must be large enough to remove
the heat in the room given off by the generator set,
uninsulated exhaust pipes and any other heat-producing equipment. A temperature differential of 20°
to 30° F
(110 to 17° C) is usually satisfactory.
IACAUTIONI Operating the generator set with
any of the cooling system components removed can cause equipment damage. Do not
operate the generator set with any of the cooling system components removed.
RADIATOR
COOLING
Cooling air travels from the rear to the front of the
set. Locate the room/compartment air inlet where it
is most convenient, preferably to the rear of the set.
The minimum inlet opening should be at least 1 -1/2
times the size ofthe radiator
area.
Increase the size
of the opening if it will be restricted with louvers or
filters (see Figure 3-1).
Engine heat is removed by a pusher fan which
blows cooling air through the front of the radiator.
The cooling air outlet should be directly in front of
the radiator, and as close to it as is
practical.
The un-
restricted outlet opening must be at least as large as
the radiator opening. A flexible section must
con-
nect the radiator and the air outlet opening, to prevent recirculation of heated air.
Generator cooling air is discharged through the engine-to-generator adapter on the left side of the engine.
3-3
Page 11
EXHAUST
Pipe exhaust gases outside the enclosure. The exhaust outlet is 1 -1/2-inch pipe size. Locate the ex-
haust outlet far from the air inlet to avoid gases reentering the enclosure. Use flexible seamless tubing to connect between the engine exhaust and any
rigid pipe extension to prevent transmission of vibration.
IAWARNINGI Exhaust gas Is poisonous. Inhala-
tion .can result In severe personal Injury or
death. Modifying the exhaust system can allow
poisonous exhaust gases to escape. Use only
original equipment replacement parts when
servicing the exhaust system. Unauthorized
modifications will also void the warranty and
cancel the UL Listing/CSA Certification. Liability for injury or damages due to unauthorized
modifications becomes the responsibility ofthe
person making the change.
Because an exhaust system is subjected to detri-
mental conditions such as extreme heat, infrequent
operation,
and light operating
load,
inspect the ex-
haust system frequently to be sure that it remains
fume-tight.
I AWARNING] Inhalation of exhaust gases can re-
sult In severe personal Injury or death. Do not
use exhaust heat to warm a room, compartment
or storage area.
An approved thimble must be used (Figure 3-3) to
pass exhaust pipes through walls or partitions.
Build this thimble according to code (see National
Fire Protection Association bulletin, Volume 4, siection 211 on "Standards for Chimneys, Fireplaces,
and Vents").
As the exhaust pipe length and number of bends increases, a larger pipe is required to reduce excessive exhaust restriction and back pressure. Excessive exhaust back pressure will reduce the air-fuel
ratio,
resulting in reduced output, smoke, wasted
power, high exhaust temperatures and reduced engine life.
Total back pressure of ail system components must
not exceed maximum back pressure limits. Note
that any exhaust restriction, even if less than maximum,
will affect performance.
AVOID SHARP BENDS
IF EXHAUST LINE MUST BE PITCHED
UPWARD CONSTRUCT A TRAP OF PIPE
FITTINGS AT POINT OF RISE
(228.60
mm)
h-9" —
INNER SLEEVE
9"^
DRAIN CONDENSATION TRAP
SINGLE THIMBLE DIAMETER
12 INCHES (305 MM)
LARGER THAN EXHAUST LINE
HOLES IN END
EXHAUST
THROUGH
PERIODICALLY
LINE
WALL
PASSING
OR PARTITION
EXS1175
FIGURE
3-3.
EXHAUST
PIPING
3-4
Page 12
FUEL
IAWARNINGI Fuel tanks present the risk of explo-
TANK AND
LINES
sion and fire, which can cause severe personal
Injury or death. Because fuel leaks create fire
hazards, always use flexible tubing between the
engine and the fuel supply,
to
avoid leaks due to
vibration and/or fuel line fallure. Do not allow
the fuel line to contact rough, sharp or hot surfaces.
The top of the fuel tank must be lower than the fuel
pump to prevent siphoning if a system leak occurs.
Install a shutoff valve at the
icing.
If the fuel tank is shared, do not connect it to
an existing
line
at a point above the fuel supply level,
fuel
tank,
to enable serv-
to avoid starving either engine.
Use an approved flexible fuel line next to the en-
gine.
Diesel engines require a fuel supply line and a
separate fuel return line. Install the fuel supply line
from
the supply tankto the inverted flare male elbow
mounted in the inlet ofthe fuel pump. The pump is
threaded
7/16-24
NPTF (American Standard Inter-
nal Tapered Pipe Thread).
Install fuel retum line from the
7/16-24
size opening
in the overflow fitting located on injection pump
(where nozzle fuel retum line is also connected) to
the top of the fuel supply tank. Shield the line with
fire-retardant material if it passes through a combustible wall or partition.
IAWARNINGI Always use flexible tubing between
engine and fule supply to avoid line failure and
teaks due to vibration.
IACAUTIONI Never use galvanized or copper fuel
lines, fittings or fuel tanks. Condensation In the
tank and lines combines with the sulfur In diesel
fuel to produce sulfuric acid. The molecular
structure of the copper or galvanized lines or
tanks reacts with the acid and contaminates the
fuel.
Carefully clean all fuel system components before
putting the set into
operation.
Any dirt or contamina-
tion may cause major damage to the fuel injection
system.
IACAUTIONI Dirt In the system can severely dam-
age both the Injection pump and the Injection
nozzles. Dirty fuel Is one of the major causes of
engine fallure. Even a tiny particle of dirt In the
Injection system may stop the engine. Because
diesel Injection systems have extremely precise tolerances, make certain that fuel Is kept
clean.
FUEL RETURN
LINES
NOZZLES
CONNECT FUEL
RETURN LINE
HERE (FLEXIBLE)
INJECTION
PUMP
F8I111
FIGURE 3-4. FUEL LINE CONNECTIONS
3-5
Page 13
Separate
The fuel tank top must be lower
Fuel
Tanks
than
the fuel pump
level to prevent putting a static head on the fuel
pump
inlet.
Ifthe
fuel
tank
is
shared
gine,
use separate fuel lines for both engines tp
with
another
en-
avoid starving either one.
The following restrictions apply to separate fuel
tank installation:
1.
The bottom of the fuel tank must not be more
than 6 feet (1.8
m)
below
the
fuel
transfer pump
inlet, unless an auxiliary electric fuel pump is
added.
fer pump
The maximum lift capacity of
is
six
feet.
See
the
Wiring Diagram for
the
trans-
the connection.
2.
If the tank is installed above the fuel pump inlet
level without a supply line shutoff
tured pump diaphragm could cause
valve,
oil
dilution,
a rup-
fuel loss, and fuel leakage to the crankcase.
3. If the maximum fuel lift must be exceeded on
any
installation,
ual
T-030
consult
Onan
Application Man-
for information on installing a day
tank and an electric solenoid shutoff valve.
4.
Use an electric or manual shutoff valve if the
minimum
fuel
level in the tank
is
higherthan the
pump inlet, to provide positive fuel shutoff
when the engine is stopped. This valve also
prevents loss of fuel from possible leaks be-
tween the tank and the fuel pump.
IAWARNINGI Fuel
hazards which can
leaks create lire
result
In
severe
and
explosion
personal In-
jury or death. Always use flexible tubing be-
tween engine
ure and
must
Extend
has a
IAWARNINGI Do notposltlon
leaks
meet applicable codes.
the
1/2-inch
drain
and fuel
due
OIL
to suit the
supply to
to vibration. The
DRAIN
installation.
pipe size tapped hole.
the
oil
avoid
fuel
The
drain
line fail-
system
oil
base
so
that
oil might drip onto the muffler, any exhaust
components,
fire
hazard.
personal
IAWARNINGI Fuel and oil must be
disposed of properly to avoid
damage and
state and local
tanks
and secondary containment and disposal
or any other hot parts,
Fire
presents
Injury
or
death.
clean-up liability.
regulations
causing
the hazard of
severe
contained and
environmental
Check all federal,
regarding storage
requirements.
a
3-6
Page 14
4.
Preparation
GENERAL
The genset electrical system includes connecting
the
load,
installing the control wiring and connecting
the batteries. Connect the batteries last to avoid accidental starting of the unit during installation.
IACAUTIONI Always disconnect a battery
charger from Its AC source before disconnecting the battery cables. Otherwise, disconnecting the cables can result In voltage spikes high
enough to damage the DC control circuits ofthe
set
IAWARNINGI Accidental starting of the generator
set while working on It can cause severe personal Injury or death. Prevent accidental starting by disconnecting the starting battery cables
(negative [-] first).
Arcing can Ignite the explosive hydrogen gas
given off by batteries, causing severe personal
Injury. Arcing can occur If the negative (-) bat-
tery cable Is connected and a tool being used to
connect or disconnect the positive (+) battery
cable accidentally touches the frame or other
grounded metal part of the set To prevent arc-
ing, always remove the negative (-) cable first,
and reconnect It last.
The following paragraphs contain the procedures
that are used to connect the electrical system ofthe
genset.
Connecting the genset electrical system involves:
• Installation of transfer switch (standby service
only)
• Generator voltage connections
• Load connection
• Control wiring
• Battery connection
Local regulations often require that wiring connec-
tions be made by a licensed electrician, and that the
installation be inspected and approved before operation.
etc. must conform to the requirements of electrical
codes in effect at the installation site.
IAWARNINGI Improper wiring can cause a fire or
electrocution, resulting In severe personal Injury or death and/or property and equipment dam-
age.
Before starting the genset, verify that all electrical
connections are secure, and that all wiring is complete.
have been removed during installation. Check that
the load cables from the genset are properly
nected.
All connections, wire sizes, materials used,
Replace and secure any access panels that
con-
IAWARNINGI Each of the operations described In
this section should be done only by persons
trained and experienced In electrical maintenance. Improper procedures may result In property damage, bodily Injury or death.
IAWARNINGI Backfeed to utility system can
cause electrocution or property damage. Do
not connect to any building electrical system
except through an approved device and after
building main switch Is opened.
4-1
Page 15
TRANSFER
If the installation is for standby service, a transfer
switch must be used for switching the load from the
normal power source to the genset (see Figure 4-1).
Either a manual or automatic transfer switch may be
used.
Follow the installation instructions provided
with the transfer switch when connecting the load
and control
Delay Module'"\n this section, for generator set remote start connections.
wiring.
Referto heading "Preheat/Time-
SWITCH
NORMAL
SOURCE
1
•LOAD
GENSET
. - J
;8C-1101
(FIGURE
4^.1
.^PICAULOAD TRANSFER
^FUNdriON
4-2
Page 16
GENERATOR
IACAUTIONI Reconnecting factory connected
VOLTAGE
CONNECTIONS
generator sets to lower voltages may reduce set
ratings, and also render line circuit breakers too
small. Consult with your distributor before per-
forming reconnection for different voltage.
The generator output voltages and maximum current rating are specified on the generator nameplate.
Line-to-neutral voltage is always the lower
voltage shown on the nameplate. Line-to-line voltage is the higher rating.
The
factory
panels
the customer. Standard
are shipped
separated
ships
especially
with
in the
special-order
wired
forthe
sets
sets
voltage
without
the T1-T4 or T1-T12
output
box.
These
with
control
specified
by
instruments
output
leads
single-phase
and broad-range generators may be connected to
provide any
connection
check
any
necessary
sired
voltage.
ofthe
output
voltages
Diagram. The Installer must
the stator lead
connections
reconnections to obtain the de-
shown
in
the Re-
always
and perfonn
Refer to the Reconnection Diagram when reviewing
the voltage connection information, and use the
electrical schematic supplied with your genset
when actually performing load connections. (A reconnection diagram is located on the inside of the
power output box cover.)
A DANGER
HAZARDOUS VOLTAGE! Touching
uninsulated live parts Inside the control and
power output boxes can result In severe per-
sonal Injury or death. Measurements and ad-
justments must be done with care to avoid
touching uninsulated live parts.
For your protection, stand on a dry wooden plat-
form or rubber insulating mat, make sure your
clothing and shoes are
dry,
remove jewelry from
your hands and use tools with Insulated
handles.
The genset control panel box contains the auto-
matic voltage regulator (AVR) printed circuit board.
The AVR controls the output of the generator so that
a constant voltage is maintained under varying load
conditions. There are two types of AVR's available;
one requiring jumper adjustments when connecting
or changing load connections. If the genset
tains the AVR shown in Figure 4-2, be sure to
con-
connect jumper W10 between terminal V4 (common)
and
V1,
V2, or V3 as listed on the reconnection dia-
gram.
AUTOMATIC VOLTAGE REGULATOR
(VR21)
V3 V1 W10 V2
O
V4
(COM)
FIGURE
4-2. AVR
SELECTION
4-3
JUMPERS
(P/N
300-1540)
Page 17
IAWARNINGI
LOAD
HAZARDOUS VOLTAGE! Touching
CONNECTION
uninsulated live parts Inside the AC power out-
put box can result In severe personal Injury or
death. Shut down the set and disconnect ALL
power sources to the generator set before removing the cover of the AC power output box.
See Figure 4-3.
Load wires can be brought into the power output
box through the holes that are shown in Figure 4-3.
Use flexible conduit and stranded load wires near
the set to isolate vibration and permit movement.
Use suitable size insulated wires forthe load rating
applied.
When installing sets with AC meters.'the generator
output leads must be routed through current transformers for proper meter operation. The transformers are labeled
CT21,
CT22and CT23. Referto
Figure 4-3 and the reconnection diagram to identify the
output leads that must be routed through each current transformer, and also appropriate transformer
post selection for meter sensing leads.
Without optional main circuit breaker: Connect
each load wire to the proper generator output lead
inside the output box. Insulate bare ends of un-
grounded wires. Use bolt provided on the output
box to connect the generator ground lead or earth
wire.
Install a fused main switch (or circuit breaker)
between the generator and
load.
If a test-run
indicates wrong rotation of 3 phase motors in the load
circuit, switch the connections at any two ofthe
generator terminals.
With optional main circuit breaker: To attach the
load wires to the optional circuit breaker, remove
the access plate that is located directly below the
circuit breaker. Attach the load cables to the base of
the circuit breaker and install the access panel. If a
test-run indicates wrong rotation of 3 phase motors
in the load circuit, switch the connections at any two
of the generator terminals.
IAWARNINGI Backfeed to utility system can
cause electrocution or property damage. Do not
connect to any building electrical system except through an approved device and after
building main switch Is opened.
IACAUTIONI Phase rotation of the genset and
utility must be the same. Equipment damage
can occur. Check and reconnect as necessary.
Check the rotation of 3-phase motors before
loading and reconnect If necessary.
Balancing
Loads
When connecting loads to the genset, balance the
loads so that the currentflowfrom each line terminal
(L1,
L2 and L3) is about the same. This is especially
important if both single phase and three phase
loads are connected. Any combination of single
phase and three phase loading may be used as
long as all line currents are roughly the same (within
10 percent of median value) and no line current exceeds the nameplate rating ofthe generator. Check
the current flow from each load cable after connections are made, by observing the control panel am-
meter.
Grounding
Grounding involves making a conducting connection between the metal parts of the generator set or
one of its electrical circuits and the earth. The de-
sign and installation of a grounding system is affected by many factors such as the use of multiple
transformers, ground fault protection requirements,
and physical location of the generator. Follow the
recommendations of the consulting engineer when
installing the grounding system.
IAWARNINGI Contact with electrical equipment
can result In severe personal Injury or death. It
Is extremely Important that bonding and equip-
ment grounding be properly done. All metallic
parts that could become energized under ab-
normal conditions must be properly grounded.
4-4
Page 18
LINE CIRCUIT
BREAKERS (WHEN
PROVIDED)
TERMINALS FOR
CONNECTING GENERATOR
LEADS ON OPTIONAL
CIRCUIT BREAKER
CT22-I
PRP/BLK
AC CONTROL
WIRING HARNESS
GENERATOR LEAD
ENTRANCE
LOAD WIRING
ENTRANCE
Frem
Conlrol:
Gi-or/Blk
Loads
And OO
Grar/Blk
Bolo.
Abovo
Aro CT.'
Loodo
300 VAC
300 VAC
To:
Coooon
Connoct
-2 For
-3 For
LOAD TERMINALS ON
OPTIONAL CIRCUIT
BREAKER
FIGURE
4-3.
POWER
CURRENT
TRANSFORMERS CT21,
CT22 AND CT23 (WHEN
PROVIDED) THE POLARITY
DOTS MUST BE DOWN.
OUTPUT BOX
4-5
Page 19
CONTROL
The generator set control panel box contains
WIRING
connection points for remote control and monitor options.
These connection points are located on the
engine control monitor board (ECM), the preheat/
time-delay module and the optional auxiliary relay
board (ARB). (Note that if the optional ARB is
installed,
no remote monitor connections are at-
tached to the ECM. The ARB provides all remote
monitor connection points.)
If the distance between the genset and the remote
station Is less than 1000 feet (305 m), use 18 gauge
stranded copper
wire.
If the distance is 1000 to 2000
feet (305 to 610 m), use 16 gauge stranded copper
wire.
Always run control circuit wiring in a separate
metal conduit from AC power cables to avoid Inducing currents that could cause problems within the
control.
IAWARNINGI HAZARDOUS VOLTAGE Touching
uninsulated live parts Inside the control panel
box can result In severe personal Injury or
death. Control wire Installation must be done
with care to avoid touching uninsulated live
parts.
For your protection, stand on a dry wooden platform or rubber Insulating mat, make sure your
clothing and shoes are dry, remove jewelry from
your hands and use tools with Insulated handles.
ENGINE
MONITOR
BOARD
(ECM-A11)
The heart of the engine control system is the engine
monitor (A11). It is a printed circuit board assembly
mounted on the back wall ofthe control box (Figure
4-4).
It starts and stops the engine in response to
the control panel switches, engine sensors and re-
mote control signals.
Remote Monitor Connections
The optional Detector 12 Control (12 light panel)
provides the capability of attaching a remote moni-
tor panel. Connections are made on the terminal
block (TB2) located on the ECM board. See Page
11-3 for typical connections at TB2 of the ECM
board.
(If the optional ARB is
installed,
remote mon-
itor connections attach to the ARB, not the ECM.)
4-6
Page 20
TB1
5.
Is
s
o
Ft
o
KE
•
U3
18
A
: V—\
15A TBI-7.B*
Cl
CRI
a
R5
[ZZ
Ri
EZZ
5
ll R in iii
TBI
O
W8
2 LilB
W9
I
8 | 7 | 6 |
Kl
51|
TBS
PI
FLT
4 ||
K4
LJ
g|lN
K3
CR2
5» CONTROL
F4
K7
Wl
CR3 IZI
CRI
a
RA
CRS
CREB
VR3
a
IC10
RB
R7
RG
ui
[ZZl
C3SR9
eg,
n ,
CRS
K12
•
CRB
a "
CRB
C5
C7
KM KIG KIB
CB
Rl
U3
U5
I I
V RH"
WG
W7
Kea
CRM
F5I
W5
s
B
CRIB 7 P3
V2
K5
CRIP
CRIP
1
8 3 4 5 6 7 B 9 IB 11 IE 13 H 15 IB
OUT)
CRI3
K9 Kll
OUT 1 LAMP OC i OS HET LOP PREHET
1
TEST
*
RESET
K13 KIS
CD
cr
LJ
O"'
3 || 2 || 1 |
1
K17
GO
CR17
•I
PRELOP SU OFF LET
PE
Li
cr
LJ
K19
CR7
OUT| SHUT
LOU FUEL
Q
l3
o
i
a
3
5
il
12
9
IB
11
Q
P4
FIGURE
4-4.
ENGINE
TB2
MONITOR
4-7
BOARD
(ECM)
!_•
Page 21
AUXILIARY
The following describes the design/functional criteria forthe auxiliary relay board (ARB) with a Detec-
tor-? or -12 Genset control. When provided, the
board is mounted on the right wall of the control box.
See Figure 4-5. There are two versions of the ARB;
with and without the set of 12 Fault relays. Page
11-4 is a detailed connection diagram for the ARB.
RELAY
BOARD
(OPTIONAL)
• Jumper Position A (Run) - The relay operates as a Run relay, energizing when SW B+ is
applied from the engine monitor.
• Jumper Position B (Common Alarm) - The
relay operates as a Common Alarm relay. The
relay energizes any time there is an engine
shutdown.
gine.
This signal is provided from the en-
Terminal Blocks:
• TB1 - ARB TB1 and engine monitor
identically numbered and provide the same remote control connection points. Note that
tional terminals are provided for terminals 5,7,
and 10 of ARB TB1.
• TB2 through TBS - Connection points for re-
• lays Kl through K3. TB2 provides the N/O and
N/C connections (three form 'C contacts for
each relay). TB3 through TB5 provide the com-
mon connection points (TB3 for
and TB5 for K3).
• TB6 and TB7 - Connection points for fault relays K4 through K15. Three terminals are provided for each relay, which are labeled COM,
N/C, N/O.
Plug-In Relays (Kl, K2, K3): The ARB can be
equipped with one to three 3-pole, double-throw re-
lays.
These relays
plug-in relays for easy field addition and replacement.
Each relay can be operated as a RUN, COMMON
ALARM,
jumper.
The relay contact ratings are:
• 10 amps at 28 VDC or 120 VAC, 80% PF
• 6 amps at 240 VAC, 80% PF
• 3 amps at 480 VAC, 80% PF
Jumper Positions for Plug-In Relays: Jumpers
W1,
their respective relays,
K2,
of 3 positions (A, B, C) independently of each other.
or ISOLATED COIL with the changing of a
W2 and W3 perform the same functions for
and W3 for relay K3. They can be located in any
(K1,
K2, K3) are field changeable
W1
for relay
K1,
K1,
TB1
are
addi-
TB4 for K2
W2 for relay
• Jumper Position C (Isolated) - The relay operates as an Isolated relay. The relay coil is energized by a customer applied 6+ signal
through the terminal block; TB3-1 for relay K1,
TB4-1 for relay K2, and TB5-1 for relay K3.
Jumpers W11, W12, and W13 perform the same
functions for their respective relays; W11 for relay
K1,
Wl 2 for relay K2, and W13 for relay K3. They
can be located in two different positions (A, B) inde-
pendently of one another.
• Jumper Position A - The relay operates iso-
lated from the board. The customer provides
the circuit completion through terminal block;
TB3 for relay
for relay K3. The customer can operate the re-
lay with switched ground logic or use this relay
in the middle of more complex logic circuits if
needed.
• Jumper Position B - The relays operate with
the coils connected to ground through the
board connections. The coil will require a B+
signal to energize with the jumper in this
tion.
Fault Relays (K4 through K15):These optional relay modules are used to operate a remote alarm an-
nunciator that has an independent power source.
This allows the use of either AC or DC for alarm
drives. The relays are energized through the latching relays on the engine monitor and provided N/O
and N/C contacts for each extemal alarm connection.
The 12 relays with form 'C contacts are rated:
• 10 Amp, 120 VAC
• 10 Amp. 30 VDC
K1,
TB4-5 for relay
K2,
and TB5-5
posi-
4-8
Page 22
JUMPERS
RUN RELAY
MODULE(S)
JUMPERS
J1,
J2 WIRE
HARNESS PLUG
CONNECTIONS
FROM A11
Fl
K3
W13
O
K3
TBI
F2
F3
Kl
[KT
O
ua
•
o •—a ,
•
o-a • •
B
ca B
[_SW B+
o
l_B+
REMOTE
START
TB2
LGND
comDN
ALARM
RUN
Kl
N/C N/O
B
cm am
N/C
N/O N/C N/O
cdn
A
WC
B cAn
K2
N/O N/C N/O N/C N/O
cin
cAn
A
N/C N/O N/C N/O N/C N/O
TBT
con
N/C N/O
con
N/C N/O
con
N/C N/Q
con
N/C N/O
con
N/C N/Q
con
I
RUN | I PRELOP | I PREHET | I LOP | I «1 | I OS | I OC I
con
N/C N/O
con
N/C N/O
con
N/C N/O
con
TB7
I FLTl
| |
FLTC
| I LET I I
LO FUEI
K3
-
B con
cm
N/C N/O
N/C N/O cm N/C N/O
I I
con
con
SM OFF
F5
A
O
N/C N/O
|
TBS,
TB7 AND
RELAYS K4
THROUGH K15
ARE OPTIONAL
M
ICS KS t7
FIGURE
4-5.
AUXILIARY
RELAY
4-9
JCIB.
BOARD
O
J(I3_
(ARB)
ICK
Page 23
PREHEAT/TIME-DELAY
MODULE (A15)
Remote Control
Connections
The start delay/preheat is adjustable from 1/2 to 15
seconds and the stop delay from 1 to 30 minutes.
Turn the delay adjusting potentiometers clockwise
to increase delay and counterclockwise to de-
crease delay. Pre-heat occurs during the delayed
start period and continues through cranking.
START DELAY
POTENTIOMETER
o
Remote control connections are made at
the
terminal block (TB1) that is located on the preheat/timedelay module (Figure
4-6).
Connect
one
or more remote switches across the remote terminal (TBI-5).
ofthe preheat/time-delay module and the
B+
termi-
nal of the ECM (A11).
iSTOP DELAY
POTENTIOMETER
O-
•
IZZ]
O
A11-TB1-2
(DC DISCONNECT)
A11-TB1-3
A11-TB1-5
A11-TB1-7
(B+ OUT)
(RUN)
(GND)
I—I ,-, ,-,
r—i
TBI
4 5
i 1|
REMOTE
CONTROL RUN
SIGNAL
O
TB1-3
(SWITCHED B+)
K13-85
(PREHEAT)
A11-TB1-6
(RMT START)
A11-TB1-7
(B+ OUT)
HGURE
4-6.
PREHEAT/TIME-DELAY
4-10
MODULE
Page 24
BATTERY
CONNECTIONS
Starting the unit requires a 12 volt battery current.
Use one 12 volt battery for a nonnal installation
(Figure
4-7).
(Referto Section 2, Specifications tor
battery type.)
Necessary batteiy cables and rack are on the unit.
Service battery as necessary. Infrequent use (as in
emergency standby service), may allow battery to
self-discharge to the point where it cannot start the
unit. If installing an automatic transfer switch that
has no built-in charge circuit, connect a separate
trickle charger. Onan automatic transfer switches
can include an optional battery charging circuit.
IAWARNINGI Ignition of
can
cause severe personal Injury. Always
nect battery negative
IAWARNINGI Do not smoke while
batteries.
teries
cause
Explosive gases are emitted
In
operation. Ignition
severe
personal injury.
explosive battery gases
con-
(-) last
to
prevent arcing.
servicing
the
from bat-
of
these gases
can
STARTER SOLENOID
CONNECT NEGATIVE
CABLE TO CONVENIENT'
BOLT ON ENGINE
CONNECTION MUST
BE CLEAN AND
PAINT-FREE
RGURE
4-7.
BATTERY
POSITIVE (+)
CONNECTION
STARTER
MOTOR
TWO,
6 VOLT
BATTERIES
CONNECTIONS
ESI 693
4-11
Page 25
5. Control Description
GENERAL
The following describes the function and operation
ofthe standard Detector 7 and optional Detector 12
generator set control. All instruments and control
EMERGENCY STOP
PUSHBUTTON
PANEL LAMP
switches are located on the face of the control panel
as illustrated in Figures
5-1
through 5-3. The control
panel description is separated into a DC portion for
monitoring the engine and an AC portion for moni-
toring the generator.
PREHEAT
RUN/STOP/REMOTE
SWITCH
RESET/LAMP
TEST/ PANEL
LAMP SWITCH
COOLANT
TEMPERATURE
GAUGE
FIGURE
5-1.
OIL PRESSURE
GAUGE
RUNNING
TIME METER
DC CONTROLS (DETECTOR 12 SHOWN)
5-1
DC INDICATOR
VOLTMETER LAMPS
Page 26
DC CONTROLS
Preheat/Reset/Lamp Test/Panel Lamp Switch:
Panel Lamp: Illuminates control panel.
Oil Pressure Gauge: Indicates pressure of
cating oil in engine (wired to a sensor located on the
engine).
Coolant Temperature Gauge: Indicates temperature of circulating coolant in engine (wired to a
sor located on engine).
DC Voltmeter: Indicates the battery charging sys-
tem voltage.
Run/Stop/Remote Switch:
• Push the switch to the Run position to start and
run the generator set.
' • Push the switch to the Stop position to stop the
' set ( The switch must be in the Stop position
when the reset switch is used to restore generator set operation following a fault shutdown,)*
; • Push the switch to the Remote position to allow
a remote eontrollerto automatically run the set.
Running Time Meter: Registers the total number
of hours the unit has run. Use it to keep a record of
periodic servicing. Time is cumulative; meter
not be reset.
lubri-
sen-
can-
• Push the switch to the Preheat position (momentary contact) to manually preheat the en-
gine combustion chambers before starting.
(This is normally accomplished automatically
by the preheat module inside the control box.)
• Push the switch to the Reset, Lamp Test
tion (momentary contact) to reset the engine
control to restore operation following a fault
shutdown (the Run - Stop - Remote switch
must be in the Stop position for reset to occur)
and to test the indicator
has a light which lights following a fault or emer-
gency shutdown. The light remains lit until the
engine control has been reset.
' • Push the switch to the Panel Lamp position to
light the panel illumination lamp.
Emergency Stop Button (Optional): Push-in
switch for emergency shutdown of the engine. The
button lights up when it is pushed in. To reset, pull
switch out and move Run/Stop/Remote switch to
Stop position. Then push Preheat/Reset/Lamp
Test/ Panel Lamp switch to Reset/Lamp Test
tion.
lamps.
Also,
posi-
this switch
posi-
5-2
Page 27
Detector7 Indicator Lamps ;The standard control
panel has seven Indicator lamps which are described as follows:
• RUN (green) lamp comes on when starter circuit opens after set starting.
• PRE LO OIL PRES (yellow) indicates engine
oil pressure is marginally low.
• PRE HI ENG TEMP (yellow) indicates engine
temperature is marginally high (or coolant level
is low on optionally wired sets).
o
iemp
Tea*
• LO OIL PRES (red) indicates engine has shut
down because of critically low oil pressure.
• HI ENG TEMP (red) indicates engine has shut
down because of critically high engine
tem-
perature or low coolant level.
• OVERSPEED (red) indicates engine has shut
down because of excessive speed.
• OVERCRANK (red) indicates engine has failed
to start during the cranking period.
Detector 12 Indicator Lamps: Jhe optional twelve
lamp control includes all the features of the seven
lamp control plus the following:
• FAULT 1 (red) lamp indicates an undedicated
fault. May be field programmed as a shutdown
or non-shutdown, and as a timed or non-timed
fault. (Normally set fbr timed shutdown).
• FAULT 2 (red) lamp indicates same features as
Fault 1 (normally set for timed shutdown).
RUN
IfflEtOOLPflBl
jPBEHBMTBKj
OVBSIfED
MULTI
BMJLT2
UWBIQTHi'l
10
WB.
2>
• LOW ENG TEMP (yellow) lamp lights if engine
temperature is marginally low for starting. It
may indicate an inoperative coolant heater.
• LO FUEL (yellow) indicates fuel supply is marginally low.
. • SWITCH OFF (flashing red) indicates genera-
tor set is not in automatic start mode.
5-3
RGURE
5-2. INDICATOR
LAMPS
Page 28
EXCITATION-
FIELD BREAKER;
AC VOLTMETER AC AMMETER' FREQUENCY
METER
PHASE
SELECTOR
SWITCH
AC
CONTROLS
UPPER AND LOWER
SCALE INDICATOR
FIGURE
5-3.
AC Voltmeter (Optional): Dual range instrument
indicating AC voltage. Measurement range in use
shown on indicator lamp.
AC Ammeter (Optional): Dual range instrument
indicates AC generator line current.
Frequency Meter
(Optional):
Indicates generator
output frequency in hertz.
Voltage Adjusting Rheostat: Provides approximately plus or minus five percent adjustment of the
rated output.voltage.
VOLTAGE
ADJUST
AC
CONTROLS
Upper and Lower Scale Indicator Lamps (Optional):
Indicates
which
scale
to
use
on
meter and ammeter.
Phase Selector Switch: Selects phases of
erator output to be measured by AC voltmeter and
ammeter.
Excitation Field Breaker: Provides generator ex-
citer and regulator protection from overheating in
the event of certain failure modes of generator, ex-
citer and voltage regulator.
the
AC
gen-
volt-
5-4
Page 29
6.
Operation
Exhaust gases contain carbon monoxide, an odorless and colorless gas.
Carbon monoxide Is poisonous and can cause unconsciousness and
death. Symptoms of carbon monoxide poisoning can Include:
IAWARNINGI
EXHAUST GAS IS DEADLY!
• Dizziness
• Nausea
• Headache
•
Weakness
IF
YOU
GET OUT
medical attention. Shut down the unit and do not operate until It has been
Inspected and repaired.
Protection against carbon monoxide inhalation also Includes proper
stallation and regular, frequent visual and audible Inspections of the
complete exhaust sysfem.
This section describes generator set
cluding pre-start checks, starting, running, and
stopping the
before starting the set. Be completely familiar with
the set for safe operation.
IACAUTIONI Always disconnect a battery
charger from Its AC source before disconnect-
ing the battery cables. Otherwise, disconnecting the cables can result In voltage spikes high
enough to damage the DC control circuits ofthe
set
set.
Study this entire section carefully
OR ANYONE ELSE
INTO
GENERAL
and Sleepiness
EXPERIENCE
THE FRESH AIR
operation,
in-
IMMEDIATELY.
• Throbbing In Temples
• Muscular Twitching
• Vomiting
• Inability to Think Coherently
ANY OF THESE
If symptoms persist, seek
IAWARNINGI Accidental starting of the generator
set while working on It can cause severe per-
sonal Injury or death. Prevent accidental starting by disconnecting the starting battery cables
(negative [-] first).
Arcing can Ignite the explosive hydrogen gas
given off by batteries, causing severe personal
Injury. Arcing can occur If the negative (-) bat-
tery cable Is connected and a tool being used to
connect or disconnect the positive (+) battery
cable accidentally touches the frame or other
grounded metal part of the set
ing, always remove the negative (-) cable first,
and reconnect It last
SYMPTOMS,
In-
To
prevent arc-
6-1
Page 30
PRESTART
CHECKS
Lubrication
Before starting, be sure the following chiecks have
been made
to the Maintenance section for the recommended
procedures.
Ventilation
Verify all dir vents and ducts are open and free from
any obstructions. Verify dampers, if used, operate
properly.
Mechanical
Check for loose belts and fittings, leaking gaskets
and hoses, or any signs of mechanical damage. If
any problems are found, have them corrected im-
mediately. „ •
Coolant
Check
fhe recommended coolant if low.
the
and
the
Checks
coolant
unit is ready for
level.
Fill
the cooling system with
operation.
Refer
Checkthe engine
possible to
Fuel
Make sure the fuel tank has sufficient fuel and that
the fuel system is primed.
DC
Electrical
Check the terminals on the batteries for clean and
tight connections. Loose or corroded connections
create resistance which can hinder
and reconnect the battery cables if loose. Always
disconnect both ends ofthe negative battery cable.
Reconnect
tery terminal and the other
make
sure
teiy ahd least likely to ignite explosive battery
gases.
Fault Lamps: Push the Reset/Lamp switch on the
control
that
all
Replace any bulbs that are burned out.
the
one
that any
panel.
the
bulbs
oil
level.
Keep
dipstick
high
mark without Overfilling.
System
end
of the
arcing
All indicator lamps
are
on
cable
will
and
end
be
then
the
oil
level
near as
starting.
to
the
negative bat-
to
ground.
away
should
release the switch.
This will
from
light.
Clean
the
bat-
Verify
6-2
Page 31
STARTING
The following sections cover the three methods
used to start the generator set
IACAUTIONI Phase rotation of the genset and
utility must be the same. Equipment damage
can occur. Check and reconnect as necessary.
Check the rotation of 3-phase motors before
loading and reconnect If necessary.
IACAUTIONI Preheating the engine longer than
one minute before cranking the engine can de-
stroy the manifold heater and glow plugs, be-
cause there
is
no incoming airflow
to
cool them.
For this reason, do not exceed the one minute
preheat periods, to prevent heater burnout and
conserve the battery.
Preheat
The preheat circuit provides a signal during time
delayed start and during cranking to activate the
en-
gine glow plugs and the manifold heater.
Delayed Starting
The time delay start function precludes automatic
start-up of the genset for a determined amount of
time (1/2 to 15 seconds). It is used for installations
that might experience power interuptions of short
duration,
and not want the genset to start and also
for the preheat function noted above.
Starting at Control Panel
1.
Press the Preheat switch (Figure 6-1) to pre-
heat and hold it there for:
• One minute if the outdoor temperature is
belowSSoF^C)
• Thirty seconds if the outdoor temperature
is above 55° F (13° C)
In extreme cold (below 32° F [0° C]) it may be
necessary to maintain preheating for two
minutes after the engine starts, to obtain firing or
smooth out cylinders, especially at no load or
light loads.
2.
Release the Preheat switch and move the Run/
Stop/Remote switch to the RUN position. This
activates the engine control system and the
starting system. The starter will begin cranking,
and after a few
seconds,
the engine should
start. The starter will disconnect when the en-
gine speed reaches 450 to 570 r/min.
Ifthe engine does not start, the starter will disengage after a specified period of time and the
control will indicate an overcrank
fault.
Genera-
tor sets with the standard overcrank control will
crank continuously for up to 75 seconds before
disengaging the starter. Generator sets with
the cycle cranking option will crank for 15 seconds in each cycle until 3 cycles have been
completed.
To clear an overcrank fault, place the Run/
Stop/Remote switch in the STOP position and
momentarily depress the Reset switch. Wait
two minutes for the starter motor to
cool,
then
repeat the starting procedure. If the engine
does not run after a second attempt at starting,
refer to the Troubleshooting section.
IACAUTIONI Overvoltage will destroy the glow
plugs and air heater in 2 to 3 seconds. If extra
power Is needed to start the set, connect an ad-
ditional 12 volt battery In parallel to the starting
battery. Do not apply overvoltage to the starting
circuit at any time.
Starting From Remote Location
Move the Run/Stop/Remote switch on the genset
control panel to the REMOTE position. This allows
the generator set to be started from a remote
switch.
Closing the remote switch initiates the start-
ing sequence described.in the previous section.
Automatic Starting and Stopping
Place the Run/Stop/Remote switch on the genera-
tor set DC panel in the REMOTE position if an auto-
matic transfer switch is
used.
This allows the transfer switch to start the generator set if a power outage
occurs and stop it when the power returns.
6-3
Page 32
Cold
Starting
With
Loads
In addition to the following recommendations, the
RDJC generator set will require the installation of the
constant glow plug kit. This will enable the set to
start and accept a load within 10 seconds when am-
bient temperatures are above 40oF (40C).
In accordance with NFPA 110, Onan recommends
installing diesel standby generator sets (life safety
systems) equipped with coolant heaters in locations
where the minimum ambient temperature is above
40oF (40C). NFPA also requires that the engine
coolant be maintained at a minimum of 90oF (320C)
and for most applications, accept the emergency
load in 10 seconds or less. Although most Onan
generator sets will start in temperatures down to
-250F
(-320C)
when equipped with coolant heaters,
it might take some running time to warm the engine
up before a load can be applied when ambient
tem-
peratures are below 40oF (40C).
The Low Engine Temperature (LET) lamp on the
Onan Detector 12 control is provided to meet the requirements of NFPA 110. The LET sensor alarms
when the engine coolant temperature falls below
70oF (210C). In applications where the ambient
temperature falls below 40oF (40C), the LET may
be lit even though the coolant heaters are
nected.
Under these conditions, although the
con-
gen-
erator set may start, it may not be able to accept
load within 10 seconds. When this condition occurs,
check the coolant heaters for proper operation. If
the coolant heaters are operating properly, other
precautions might be necessary to warm the engine
before applying a
load.
AC VOLTMETER AC AMMETER
UPPER AND LOWER
SCALE INDICATOR
EXCITATION
RELD BREAKER
PHASE
SELECTOR
SWITCH
VOLTAGE
ADJUST
EMERGENCY STOP RUN/STOP/REMOTE PREHEAT
PUSH-BUTTON SWITCH RESET/LAMP
FREQUENCY V / TEST/PANEL
METER 1 PANEL LAMP / LAMP SWITCH
INDICATOR
LAMPS
RUNNING
TIME METER
COOLANT OILPRESSURE DC VOLTMETER
TEMPERATURE GAUGE
GAUGE
FIGURE
6-1.
CONTROL PANEL (DETECTOR 12 SHOWN)
6-4
Page 33
RUNNING
With the genset mnning, listen for any unusual
noises that may indicate mechanical problems and
check the oil pressure frequently. Investigate anything that indicates possible mechanical problems.
Oil Pressure
to 55 psi
Gauge:
(241
to 379 kPa) when the engine is at op-
The oil pressure should be 35
erating temperature.
Coolant Temperature Gauge: The coolant
temperature should be 170° to 216° F (77° to 102° C)
depending on the load and ambient temperature.
Before operating the genset under
load,
make certain the genset will perform correctly by checking
the following areas.
Exhaust
System
With the generator set operating, inspect the entire
exhaust system visually and audibly including the
exhaust
manifold,
mufflerand exhaust pipe and rain
cap (if equipped). Check for leaks at all connections,
welds, gaskets and joints and also make sure
that exhaust pipes are not heating surrounding ar-
eas excessively. If any leaks are detected, shut
down the genset and have leaks corrected immediately.
I AWARNING I Inhalation of exhaust gases can re-
sult In severe personal Injury or death. Be sure
deadly exhaust gas Is piped outside and away
from any windows, doors or other Inlets to
building.
Fuel
System
With the generator set operating, inspect the fuel
supply lines, return lines, filters and fittings for
cracks and abrasions and make sure they are not
rubbing against anything that could cause breakage.
If any leaks are
detected,
have them corrected
immediately.
IAWARNINGI Ignition of fuel can cause severe
personal Injury or death by fire or explosion. Do
not permit any flame, cigarette, spark, pilot
light, arcing equipment, switch or other Igniter
near the fuel system.
Engine
Gauges
Check the following while the genset is operating.
Refer to Figure 6-1 for location of engine gauges.
DC Voltmeter: This is a voltage reference gauge,
indicating condition of the batteries and also of battery charging circuit. Gauge should read approxi-
mately 12 to 14 volts while genset is running. If
reading is high or low, check batteries and the bat-
tery charging circuit.
Generator AC
Meters
(Optional)
Check the following meters while the genset is operating.
Refer to Figure 6-1 for location of the
gen-
erator AC meters.
Frequency Meter: The generator frequency
should be stable and the reading should be the
same as the nameplate rating (50 or 60 hz).
The generator frequency is a result of engine
speed,
which is automatically controlled. Ifthe
generator frequency is below specification, contact an
authorized service center.
AC Voltmeter: Tum the phase selector switch to
each line-to-line phase selection shown on the volts
scale (L1-L2 on single phase gensets: L1-L2,
L2-L3,
and L3-L1 on three phase gensets). Read
the AC voltmeter using the upper or lower scale as
indicated by the scale indicator
line-to-line voltage should be the same as the
light.
At no
load,
gen-
the
set nameplate rating. Ifthe reading is incorrect, refer to the Generator Voltage Adjustment procedure
at the end of this section.
AC Ammeter: Tum the phase selector switch to
each phase selection shown on the amperes scale
(L1 and L2 on single phase gensets;
L1,
L2 and L3
on three phase gensets). Read the ammeter using
the upper or lower scale as indicated by the scale
indicator light. At no
load,
the current readings
should be zero. With a load applied, each line cur-
rent should be approximately the same, and no line
current should exceed the genset nameplate rating.
6-5
Page 34
STOPPING
Emergency
Stop
(Optional)
Before Stopping
Run the genset at no load for three to five minutes
before stopping. This allows the lubricating oil and
engine coolant to carry heat away from the combustion chamber and bearings.
Normal
Ifthe genset was started atthe genset control panel
or at a remote control panel, move the Run/Stop/
Remote switch or remote starting switch to the
STOP position. If the stop circuit
ernor arm down to shut off fuel injection pump.
If the set was started by an automatic transfer
switch,
minutes after the normal power source returns. -
Time Delayed Stopping *
The time delay stop function (adjustable from 0.5 to
15 minutes) provides for automatic cool-down mnning of the genset for a preset amount of time
(approximately 3 to 5 minutes is recommended).
Stop
fails,
push the gov-
the genset will automatically stop about 15
An optional emergency stop button is located on the
right side of control panel. Push the button in for
emergency stop. Note that no fault indicators will
light when the emergency button is used. To reset
the fault circuitry, pull the emergency stop button
out and move the Run/Stop/Remote switch to the
Stop position. Then move the test switch to Reset/
Lamp Test position.
Engine
With the genset
switch in the Test position (see Figure 6-1). All
cator lamps should light. Verify all of the lamps are
on and then release the switch. Contact an Onan
distributor if any lamps require replacement.
Mechanical
With the genset stopped, check for loose belts and
fittings, leaking gaskets and hoses, or any signs of
mechanical damage. If any problems are found,
have them corrected immediately.
Monitor
stopped,
Checks
Indicator
hold the Reset/Lamp Test
Lamps
indi-
6-6
Page 35
BREAK-IN
Observe the following schedule for genset break-in:
1.
One half hour at 1/2
1.
One half hour at 3/4
3. Full
load.
During the first few hundred hours of
genset load should be at least 1/2 to full
load.
load.
operation,
load.
Con-
the
tinuous operation below this load recommendation,
can result in poor piston ring seating, causing high-
er-than-normal oil consumption and blowby.
• Condensation in the fuel and lubrication system,
causing contamination and/or corrosion
• Loss of protective oil film on moving engine
parts
• Loss of engine fuel prime due to drain-back
and/or evaporation
• Battery discharge due to internal and extemal
current leakage
• Breakdown of generator insulation due to
water absorption
Proper exercising does the following:
Drain and replace the crankcase oil afterthe first 50
hours of operation on new generator
sets.
Refer to
the Maintenance section ofthis manual forthe rec-
ommended procedures.
NO-LOAD
OPERATION
Periods of no-load operation should be held to a
minimum.
If it is necessary to keep the engine
running for long periods of time when no electric output
is required, best engine performance will be ob-
tained by connecting a "dummy" electrical
load.
Such a load could consist of a heater element, etc.
EXERCISE
IACAUTIONI Improper exercising of the genera-
PERIOD
tor set may cause more damage than no exercising at all. Significant amounts of water and
raw fuel will remain In the lubrication oil If the
unit Is run at a low operating temperatuie. Also,
operating the engine at no load or at low tem-
peratures causes carbon buildup and exhaust
system fouling. Continued operation In this
manner may cause starting failure and/or engine damage. Exercising a generator set with-
out exercising Its associated controls and
switchgear does not test the operation of the
controls and switchgear. If the control systems
are not fully functional, the system may fall to
provide power when required.
Infrequent use of the generator set can cause it to
deteriorate. The following can occur
• Elevates engine
oil
temperature to at least 180°
F (82.2° C)
• Evaporates water from engine lubrication system
• Re-establishes a protective oil film on engine
parts
• Recharges battery to full normal potential
• Brings generatorto normal operating temperature through load application
The generator set
should
be exercised at least once
each week; the engine oil temperature should be
held at 180° F (82.2° C) for at least 30 minutes dur-
ing this exercise.
To exercise the generator set, do the following;
1.
Perform all required maintenance
checks,
start
the unit, and apply a load (50 percent or more)
by creating a simulated power
failure*.
This ex-
ercises the control and switchgear systems.
2.
Afterthe genset has reached its normal operat-
ing temperature, allow the genset to run an
additional 30 minutes.
3. Shut the unit down by simulating the retum of
normal power*. Run the set for approximately
three to five minutes with no load to allow the
engine to cool down.
• This applies to a standby genset only. Other units should
be started and loaded by control and load application sys-
tems normally associated with operation of the unit.
After each exercise period, refill the fuel tank and
checkthe engine for leaks and overall
condition.
Lo-
cate the cause of any leaks and correct.
6-7
Page 36
HIGH
1.
Make certain that nothing obstmcts air flow to
and from the set.
2.
Be sure that the set location is properly venti-
lated.
3. Check the level of battery electrolyte frequently, and add approved water when necessary to maintain the proper level.
4.
Keep the cooling system clean and the radiator
filled,
and see that the fan belt tension is prop-
erly adjusted.
LOW
1.
Use the correct viscosity oil for the prevailing
temperature. Change oil only when the engine
is warm. If an unexpected temperature drop
causes an emergency, move the set to a warm
location or apply externally heated air until the
oil flows freely (never use an open flame).
2.
Use fresh
condensation.
3. Keep the fuel system clean, and maintain the
batteries in a well-charged condition.
4.
Use additional preheating for cold starts.
TEMPERATURES
TEMPERATURES
fuel,
and protect against moisture
DUST
1.
Keep the generator set and the codling system
clean.
2.
Service the air cleaner as frequently as neces-
sary
3. Change the crankcase oil every 100 operating
hours.
Maximum power is reduced approximately 4 per-
cent for each 1000 feet (305 m) altitude.
The generator set power rating applies to sets used
in standby applications. The set will operate at the
stated rating forthe duration of normal utility power
interruptions. The rating was established for a standard radiator cooled set mnning on diesel fuel and
operating at an altitude of 300 feet (92 m) with an
ambient temperature of
relative to other applications, altitudes, cooling systems,
ized service center.
Keep the governor linkage clean.
HIGH
POWER
or ambient temperatures, contact an author-
AND DIRT
ALTITUDE
RATING
810 F
FACTORS
(27°^
C).
For a rating-
6-8
Page 37
7. Adjustments
GENERATOR
If the optional
control panel-mounted potentiometer
for adjusting the AC output (see Figure 7-1). Output
voltage
of nominal voltage
Call your distributor
be obtained
Move
control panel to the Run position. Check the following conditions while
IAWARNINGI Use extreme caution when working
on electrical components. High voltages
cause Injury
damp clothing (particularly
skln surface
cal equipment
can be
by
the
Run/Stop/Remote switch
to be
VOLTAGE
ADJUSTMENT
AC
meters
adjusted plus
this adjustment.
or
death.
are
by
turning this potentiometer.
if the
the
damp when handling electri-
required voltage cannot
genset
Do not
CHECK AND
installed,
or
minus five percent
is
wet
an
extemal
is
provided
on the
operating.
wear jewelry
shoes) or allow
engine
can
or
1.
Move
2.
Move the Phase Selector
the
Phase Selector switch
erator output current and voltage, and perform
the following steps:
A. Insert a screwdriver into
just potentiometer located
the genset control panel
wrench carefully loosen
B. While observing
the screwdriver clockwise to increase volt-
age
or
counterclockwise
age,
and
adjust
voltage.
If correct voltage cannot
this adjustment, contact
center
tion.
for
assistance.
C. After setting
the locking
change
the
the
voltmeter, slowly turn
to the
be
an
the
correct voltage, tighten
nut,
being careful
adjustment
switch
to
read
the
Voltage
on the
and
the
to
decrease volt-
rated nameplate
attained through
authorized service
to the Off
front
using
locking
not to
nut.
gen-
Ad-
of
a
posi-
Onon
FIGURE
o
2s
VOLTAGE
ADJUST
7-1.
CONTROL
PANEL
o
(DETECTOR
o
12
SHOWN)
7-1
Page 38
GOVERNOR
The governor controls engine speed. On a 4 pole
generator, engine speed equals frequency multiplied by
30.
Thus 1800
rpm
generates 60 hertz. Preferred engine speed does not vary more than 3
hertz from no-load to full-load operation. Be sure
that the throttle, linkage, and governor mechanism
operate smoothly.
Speed
Adjustment
To change the governor speed, change the spring
tension by turning the governor speed adjusting nut
(Figure 7-2). Turn the nut clockwise (more spring
tension) to increase rpm, or counterclockwise to reduce govemed speed. Use a stroboscope or a frequency meter to make this adjustment.
Sensitivity
If the governor is too sensitive, a rapid Hunting
Adjustment
condition occurs (alternate increasing and decreasing
speed).
Adjust the governor for maximum sensitiv-
ity without hunting. After making the sensitivity ad-
justment, readjust the speed.
To adjust governor sensitivity (no-load to full-load
speed droop), tum the sensitivity adjusting ratchet
as follows.
Radiator cooled Sets: Turning the ratchet clock-
wise provides more sensitivity (less speed drop
when full load is applied), and turning it counter-
clockwise provides less sensitivity (more speed
drop).
City Water Cooled Sets: Turning the ratchet counterclockwise provides more sensitivity (less speed
drop when full load is applied), and turning it clockwise provides less sensitivity (more speed drop).
GOVERNOR
SHAFT
DECREASE
SENSITIVITY
SPEED
ADJUSTING
NUT
GOVERNOR
ARM
SENSITIVITY
ADJUSTING
RATCHET ^
GOVERNOR ARM
SPEED ADJUSTING
NUT AND LOCK NUT
RADIATOR COOLED SETS
INCREASE RPM
(Hold spring stud in
GOVERNOR
SPRING STUD
(SENSITIVITY
ADJUSTMENT)
TURN FOR
MINIMUM SPEED
DROP,
THEN
ADJUST SPEED CUT
GOVERNOR
/ SPEED
GOVERNOR
STUD
INCREASE
SENSITIVITY
TURN TO
position)
STUD
DECREASE
7-2
DECREASE
SENSITIVITY
FIGURE
INCREASE
SENSiriVITY SPEED
ADJUSTING NUT
CrTY WATER COOLED SETS
7-2. ADJUSTING
GOVERNOR
INCREASE
SPEED
Page 39
VALVE
CLEARANCE
ADJUSTMENTS
Check the valve clearance when the engine is at
room temperature, about 70° F (21° C).
IACAUTIONI incorrect valve clearance adjust-
ment can lead to irrevocable damage to the generator set. Make certain that only qualified personnel perform this adjustment
1.
Tum the flywheel until the cylinder which is to
have its valve adjusted is on its compression
stroke. On engines without a hand crank, use a
socket wrench on the flywheel hex head screw.
To determine if the cylinder is in its compression stroke, observe the push rods as the engine is rotated in a clockwise
haust valve push rod will be in its lowest
tion,
and the intake valve push rod will be mov-
direction.
The ex-
posi-
ing downward. As the piston reaches top dead
center, the flywheel timing mark should be
aligned with the timing pointer, and the valve
push rods should be stationary.
2.
Tum the flywheel an additional 10 to 45 de-
grees clockwise (estimated). When the piston
is in this position, it is in its power stroke, with
both valves completely closed.
3. Check cylinder head-bolt torque prior to valve
clearance adjustment. Torque values are listed
in the Specifications section. Adjust valve
clearance with the locknut which secures the
rocker arm to the cylinder head (Rgure 7-3).
Loosen this locknut to increase clearance,
tighten it to reduce clearance.
4.
Using a feeler gauge, check the clearance be-
tween the rocker arm and the valve (Figure
7-4). Increase or decrease the clearance until
the proper gap is established. Valve clearances are listed in the Specifications section.
VALVE ADJUST VALVE
SPRING CLEARANCE HERE
RETAINER
VALVE
SPRING
RGURE 7-3. VALVE CLEARANCE
ADJUSTMENTS
EXHAUST VALVES
ROCKER
ARM
VALVE
PUSH ROD
VALVE SEAT
VT1044
PCV VALVE
7-3
INTAKE
VALVES
VT1045
RGURE 7-4. CHECK VALVE CLEARANCE
Page 40
CENTRIFUGAL
SWITCH
The start-disconnect centrifugal switch (Figure 7-5)
is located on the side ofthe
engine,
above the oil
fil-
ter. The switch opens when the engine stops, and
closes when engine speed reaches 900
essary, loosen the stationary contact
point gap to
0.020
inch
(51
mm). Replace burned or
rpm.
and
adjust the
If nec-
faulty points.
IAWARNINGI High
vere
personal Injury or
breaker point
voltage,
gap.
Disconnect the battery cable,
which can cause se-
death,
Is present at the
negative (-) terminal first, before setting the
breaker point
CHARGE RATE
gap.
ADJUSTMENT
The adjustable resistor slide tap (Figure 7-6) in the
charging circuit is set to produce a 2 ampere charg-
ing rate. This resistor is found in the generator air
outlet. For applications requiring frequent starts,
check the battery specific gravity periodically. If
necessary, increase the charging rate slightly
(move the slide tap up). Adjust this slide tap only
when the engine is stopped.
FIGURE
COOLING
OUTLET
CHARGING
RESISTOR"
SET GAP AT
7-5.
CENTRIFUGAL
ADJUSTMENT
AIR
CENTRIFUGAL
BREAKER
POINTS
0.020
SWITCH
SWITCH
INCH
(51 mm)'
ESI 808
IAWARNINGI
plosion,
jury. Because
do not
producing devices In
Batteries
which
smoke
present the hazard of
can result In severe personal In-
batteries
or allow any
produce explosive gas,
flame, sparks,
the
battery area.
or arc-
ex-
Avoid overcharging the battery. Make small increments of change until the proper rate has been de-
termined to keep the batteiy charged.
FIGURE
SLIDE
7-6.
CHARGING
TAP
ESI 971C
RESISTOR
Page 41
8. Troubleshooting
The generator set has sensors that continuously
monitorthe engine for abnormal conditions, such as
low oil pressure or high coolant temperature. If
these conditions occur, the engine monitor
vates a fault lamp, and may also stop the engine
(depending on the
stopped forthis
restart the set after making adjustments or correc-
tions.
This section describes the fault condition sys-
tem,
and suggests troubleshooting procedures.
fhe standard seven light control has a single green
light to indicate
fault lights. The optional twelve-light control has a
single green light to indicate
and seven red fault
terminal connection for a customer supplied
ble alarm, which sounds when a fault occurs.
SAFETY
High voltages are present inside the control box and
generator output box when the set is mnning. Do
not open the control box or generator output box
while the set is mnning.
IAWARNINGI Contacting high voltage components
can cause electrocution, resulting In severe personal Injury or
covers In place during troubleshooting.
Generator set installations are normally designed
for automatic starting or remote starting. When
troubleshooting a set that is shut down, make cer-
condition).
reason,
RUN,
death.
two amber lights and four red
lights.
CONSIDERATIONS
Keep control and output box
Ifthe generator set is
the operator may be able to
RUN,
Both controls also have a
four amber lights
acti-
audi-
tain the generator set cannot be accidentally restarted.
STOP position and remove the negative battery cable from the set starting battery.
IAWARNINGI Accidental starting of the generator set
during troubleshooting can cause severe personal
injury or death. Disable the generator set before
troubleshooting.
When a fault lamp tums on during operation, follow
the procedures listed below to locate and correct
the problem. For any symptom not listed, contact
an authorized service center for assistance.
Resetting the Control
The external alarm and fault lamp may be deacti-
vated by moving the Run/Stop/Remote switch to
the Stop position and pressing the Reset/Lamp
Test/Preheat switch. Locate the problem and correct it before restarting the set. While pressing the
Reset/Lamp Test/Preheat
all lamps light.
Line
The line circuit breaker mounts on the generator
output box. If the load exceeds the circuit breaker
current rating, the line circuit breaker
venting the generator from being overloaded. If the
circuit breaker trips, locate the source of the overload and correct as necessary. Manually reset the
breaker to reconnect the load to the generator.
Place the Run/Stop/Remote switch in the
Circuit
Breaker
switch,
(Optional)
make certain that
will
open, pre-
8-1
Page 42
TABLE
^WARNING: Many troubleshooting procedures present hazards which can result In severe personal
8-1.
TROUBLESHOOTING
Injuryordeath. Only qualified service personnel with knowledge of fuels, electricity, and machinery
SYMPTOM
1.
Green RUN lamp lights following engine
startup.
2.
PRE HI ENGINE TEMP lamp lights. En-
gine continues to operate.
3. HI ENG TEMP lamp lights. Engine
shuts down.
CORRECTIVE
1.
Indicates all engine systems are normal. No correc-
tive action required.
2.
Indicates engine is operating near its capacity and
temperature has risen to approximately 220oF (104°
C)
or coolant level is low on optionally wired sets. If
generator is powering non-critical and critical loads
and cannot be shut down, use the following:
a. Reduce load if possible by turning off non-critical
loads.
b. Check air inlets and outlets and remove any ob-
structions to airflow.
If engine can be stopped, follow procedure In
step 3.
3. Indicates engine has overheated (engine temperature has risen above 230oF/110oC) or coolant level is
low. Allow engine to cool down completely before
proceeding with the following checks:
a. Check coolant level and replenish if low. Look
for possible coolant leakage points and repair if
necessary.
ACTION
4.
PRE LO OIL PRES lamp lights. Engine
continues to operate.
5. LO OIL PRES lamp lights. Engine shuts
down.
NOTE: See also step 6.
b. Check for obstructions to cooling airflow and
correct as necessary.
c. Check for a slipping fan belt and tighten if loose.
d.
Reset control and restart after locating and cor-
recting problem. Contact an authorized service
center if none of the above.
4.
Indicates engine oil pressure has dropped to 20 psi
(138 kPa). If generator is powering critical loads and
cannot be shut
and then follow step 5 procedure. If engine can be
stopped,
5. Indicates engine oil pressure has dropped to 14 psi
(97kPa).
is OK but oil level is low, replenish. Reset control and
restart. Contact an authorized service center if oil
pressure is 20 psi (138 kPa) or lower.
follow procedures in step 5.
Check
down,
oil
level,
wait until next shutdown period
lines
and
filters.
If oil system
8-2
Page 43
TABLE
8-1.
TROUBLESHOOTING
(continued)
IAWARNINGI Many troubleshooting
procedures present hazards which
Injuryordeath. Only qualified service personnel with
hazards
6. OVERCRANK lamp lights and engine
7. Engine mns and then shuts down,
should perform
SYMPTOM
stops cranking.
or
Engine mns, shuts down, and LO OIL
PRES lamp lights..
OVERSPEED lamp lights.
service procedures. Review
6. Indicates possible fuel system problem.
a. Check for loss of engine prime, empty fuel tank,
fuel leaks, or plugged fuel lines and correct as
required.
b. Check for dirty fuel filter and replace if necessary
(see Maintenance section).
c. Check for dirty or plugged air filter and replace if
necessary (see Maintenance section).
d.
Reset the control and restart after correcting the
problem.
for service if none of the above.
7. Indicates engine has exceeded normal operating
speed.
service.
can
result
knowledge
safety
CORRECTIVE
Contact an authorized service center
Contact an authorized service center for
of
fuels, electricity,
precautions
ACTION
on
In
severe personal
and machinery
pages III and
iv.
*8.
SWITCH OFF lamp flashes.
*9.
LO FUEL lamp lights. Engine continues
to mn.
*10.LO FUEL LAMP lights. Engine shuts
down and LO OIL PRES lamp lights.
•11.
LO ENG TEMP lamp lights. Set is in
standby mode but is not operating.
(Lamp lights when engine coolant
perature is 70° F
the lamp goes out after the engine
warms up, there should be no cause for
alarm even during initial generator set
operation.)
*12-Ught Control Only.
(210 C) or lower. Since
tem-
8. Indicates Run/Stop/Remote switch is in the Stop position which will prevent automatic starting if
matic transfer switch is used. Move the Run/Stop/
Remote switch to the Remote position for automatic
starting.
9. Indicates diesel fuel supply is mnning low. Check
fuel supply and replenish as required.
10.
Indicates engine has mn out of
and replenish as required.
11.
Indicates engine coolant heater is not operating, is
not circulating coolant, or ambient temperature has
exceeded capability of heater. Check for the following conditions:
a. Coolant heater not connected to power supply.
Check for blown fuse or disconnected heater
cord and correct as required.
b. Check for low coolant level and replenish if re-
quired.
and repair as required.
c. Contact an authorized service center if none of
the above.
Look for possible coolant leakage points
fuel.
Check fuel level
an
auto-
8-3
Page 44
TABLE
iAWARNING] Many troubleshooting procedures present hazards which can result In severe personal
8-1.
TROUBLESHOOTING (continued)
injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery
hazards should perform service procedures. Review safety precautions on pages III and Iv.
SYMPTOM
*12.
The FAULT 1 or FAULT 2 fault lamp
lights.
engine runs for several seconds and
then shuts
run.
13.
Fault lamp lights but no fault exists. En-
gine gauges show oil pressure, engine
temperature, and frequency (speed) are ,
within normal limits.
14.
Engine starts from generator control
15.
Engine will not crank.
Engine shuts down immediately,
down,
panel but will not start automatically or
from a remote panel. (Note: The Run/
Stop/Remote switch must be in the Re-
mote position for automatic or remote
starting).
or engine continues to
CORRECTIVE
12.
The standard undesignated fault functions are pro-
grammed to shut down the set when a fault is sensed.
Fault 1 is time delayed while Fault 2 is immediate.
The nature of the fault is an optional selection that is
determined when the set installation is designed.
The undesignated fault functions may also be programmed for non-shutdown or non-time delay.
13.'
The monitor board or a sensor may be at fault.
tact an authorized service center for service.
14.
Remote circuit breaker is
restart. Contact an authorized service center if
breaker trips after resetting.
15.
Indicates possible fault with control or starting sys-
tem.
Check for the following conditions:
ACTION
tripped.
Reset breaker and
Con-
16.
No AC output voltage.
17.
Green RUN lamp does not light follow-
ing engine startup.
* 12-Light Panel Only.
a. Fault lamp on. Correct fault and reset control.
b. Poor battery cable connections. Clean the bat-
tery cable terminals and tighten all connections.
c. Discharged or defective battery. Recharge or
replace the battery.
d.
Emergency stop button (if equipped) pushed m.
To reset, pull switch put and move Run/Stop/Remote switch to Stop position. Then push test
switch to Reset/ Lamp position.
e. Contact an authorized service center if none of
the above.
16.
Reid breaker is tripped. Reset breaker. Contact an
authorized service center if voltage buildup causes
breaker to trip.
17.
Indicates possible Start/Disconnect relay failure.
Contact an authorized service center for assistance.
8-4
Page 45
9.
Maintenance
GENERAL
Establish a maintenance/service schedule based
on
the
type
of
application,
environment
service intervals. In extreme operating conditions,
reduce the service intervals accordingly. Factors
that affect the maintenance schedule include the
following:
• Use for continuous duty (prime power)
• Extremes in ambient temperature
• Exposure to elements
• Exposure to salt water
• Exposure to windblown dust or sand
Consult
is subject to extreme operating conditions, and determine a suitable maintenance
all service at the time period indicated, or after the
number of operating hours indicated, whichever
comes first. Use Table 9-1 to determine the required maintenance. Refer
tenance procedures.
The
Table
with
an authorized service center if the set
and
9-1
on the severity of the
lists
the
recommended
schedule.
to
this
section for
Perform
main-
IACAUTIONI Always disconnect a battery
charger
ing the battery
ing
enough to damage the
set.
IAWARNINGI Accidental
set while
sonal injury or
ing
(negative
Arcing can Ignite the explosive hydrogen gas
given off by
Injury.
tery cable Is
connect or
cable accidentally touches the frame or other
grounded
ing, always remove the
and
from
Its AC source before
cables. Otherwise,
the cables can result In voltage spikes
DC control
starting
working
by
disconnecting
[-]
first).
batteries, causing severe personal
Arcing can occur If
connected and a tool being
disconnect
metal part of
reconnect
on It can cause severe per-
death.
It last
Prevent
the starting battery cables
the
the positive (+) battery
the set. To
negative
disconnect-
disconnect-
circuits
of
the generator
accidental
negative (-) bat-
used to
prevent arc-
(-) cable first,
high
of the
start-
9-1
Page 46
TABLE
9-1. MAINTENANCE
SCHEDULE
HOURS OF OPERATION
8
50
too
200
500
MAINTENANCE TASK
• Inspect exhaust system
• Inspect generator set
• Check
• Check oil level
• See
• Check air cleaner; See
.. • Change crankcase oil
Clean
• Change crankcase oil (or annually); See
. • Clean sediment
pump; See
>
*r Replace oil
• Check
• Clean crankcase breather
• Check start-disconnect circuit
• Check valve
• Clean crankcase breather
fuel
supply; See
Note
2
governor linkage
bowl
Note
1
filter
battery
condition
clearances;
Note
1
Note
3
after
first 50 hours
and
filter
See
tube
on
Note
fuel
4
Note
3
transfer
600
1500
2000
3000
5000
1.
Water
2. Tighten head bolts and adjust valve clearance
3. Perform more
4. Contact an authorized
5. Check yearly on non-commercial
or
foreign
shows
water or
should
be replaced
overhauled
be
material
excessive
checked
following
engines,
often
arid
situation
correction of
and
in extremely dusty conditions.
service
• Change primary
• Check torsional washers for corrosion; See
NoteS
• Grind valves (if required); See
Ctiebk nozzle spray pattern; See
Cleian generator
• Change sedondary
• General overhaul (if required); See
in
fuel
can ruin the injection
dirt
in
then
adjust valve
center for
sediment
corrected:
fuel
sets.
bowl,
Primary
contamination problem.
clearance
service.
fuel
filter
Note
fuel
filter
system.
fuel
handling
and
after
first 50 hours on new and
each
If daily inspection
and
storing facilities
secondary
500
hours
fuel
4
Note
4
Note
4
filters
can
thereafter.
9-2
Page 47
GENERATOR
During operation,
that could create unsafe
Section
should
6 of
this manual covers
be
frequently inspected
be
SET
alert
INSPECTION
for
mechanical problems
or
hazardous conditions.
the
areas that
for
continued safe
operation.
LUBRICATION
The engine
oil was
drained from
fore shipment. Before the initial
system must
classification
section
be
filled with
and
for
the lubricating
viscosity. Referto Specifications
SYSTEM
the
start,
oil of the
oil
capacity.
crankcase
be-
the lubrication
recommended
Oil Recommendations
The
use of
with appropriate
are critical factors
ance
quality engine lubricating oils combined
oil
drain
and
filter change intervals
in
maintaining engine perform-
and
durability.
Use SAE 15W40 oil that meets the American Petroleum Institute
or
CE/SG.
(API)
Table
Classification CC/CD, CD/SG
9-2
shows the preferred
oil
grades
for ambient temperatures indicated.
climates, refer
mendations
IACAUTIONI Limited
such
as
10W-30 may be used
to
Table
for
extreme climates.
9-2 for oil
use of low
viscosity recom-
viscosity oils,
for
easier starting
and providing sufficient oil flow at ambient temperatures below
ous
use of low
gine life
due to
23>
Ff-P C).
viscosity oils
However, continu-
can
decrease
en-
wean Referto the accompanying
chart.
In extremely dusty
or
dirty conditions,
oil
should
be
changed more frequently. When adding oil between
changes,
gine.
use the
same brand
Various brands
as
already
of oil may not be
in the en-
compatible
when mixed.
TABLE 9-2.
OIL
VISCOSITY/TEMPERATURE
CHART
SOW
llllll
15W40
10W30,10W40
rrrr
CC/CD
where CE
interval must
given In
The use
found
or
CD/SG engine oils
oil Is not yet
be
reduced
the
Maintenance Schedule.
of a
multi-viscosity lubricating
to
improve
oil
consumption control
prove engine cranking
maintaining lubrication
tures.
While 15W-40
can be
available,
to one
used
but the oil
half
the
oil
in
cold temperatures while
at
high operating tempera-
oil is
recommended
in
areas
change
Interval
has been
and im-
for
most
0
F-30-20-10
0
C-34
-29
-23
TTT
5W30
0 10 20 30 40 50 60 70 80 90
-18
-12
32
-7 -1 4 10 16 21 27 32 38 43 48
* PREFERRED SUMMER
100110120
9-3
Page 48
Engine
L
oil level below
mark. Overfilling
of the oil while
Oil
CAUTION
Level
l
Do not
the
operation
operate
LOW
mark
the
engine
or above
can cause foaming
below the ADD mark
with the
the FULL
or aeration
can cause loss of oil pressure.
Check the engine oil level during engine shutdown
periods at the intervals specified in the Mainte-
nance Schedule. The oil dipstick and oil fill are located on the side of the engine (Figure 9-1). The
dipstick is stamped with FULL and LOW to indicate
the level of
ings,
shut off
minutes
oil
in the crankcase. For accurate read-
the
engine and wait approximately 10
before
checking
the
oil
level.
This
allows oil
in the upper portion of the engine to drain back into
the crankcase. • ,
ALWAYS REPLACE CAP
TIGHTLY OR OIL
LEAKAGE MAY OCCUR
CAP AND OIL
LEVEL INDICATOR
CRANKCASE OIL
FULL / AT THIS LEVEL
NEVER OPERATE
ENGINE WITH OIL
OIL FILL
TUBE
BELOW THIS LEVEL
KEEP
Keep the oil level as near as possible to the FULL
mark on the
dipstick.
Remove
the
oil
fill
cap
and
add
oil of the same quality and brand when necessary.
FIGURE
9-1. OIL
LEVEL
LS11S1
INDICATOR
9-4
Page 49
Oil
Change
IAWARNINGI Hot
If It
Is spilled
and hands clear
plug and wear
crankcase oil can cause burns
or
splashed on skln. Keep fingers
when
removing the oil drain
protective clothing.
Change the oil and filter at the intervals recom-
mended in the Maintenance Schedule.
IAWARNINGI Used
fied by
some state
engine
or
oils
federal agencies
have
been Identi-
as
causing cancer or reproductive toxicity. When
checking
to
Ingest, breathe the fumes,
or
changing
engine
oil,
take care not
or contact used oil.
Check the oil level indicator after every 8 hours of
operation,
and maintain the oil level at the FULL
mark (Rgure 9-3). Refer to the Specifications section for crankcase and filter capacity.
Oil Filter
Change
Stop the engine and drain the crankcase oil while
the engine is still hot. Place a pan under the drain
outlet and remove the oil drain plug or open the oil
drain valve. After the oil is completely drained, re-
place the drain plug or close the drain valve. Replace oil filter if necessary before adding oil.
Refill
with
oil
of
the
correct
API
designation
and
SAE
viscosity grade forthe temperature conditions (refer
to Table 9-2).
IAWARNINGI Hot
If It
Is spilled
crankcase
or
splashed
oil
can cause
on
skln.
Keep
burns
fingers
and hands clear when removing the oil drain
plug and wear protective
Place
a container under the
clothing.
oil
filter and remove the
filter by turning it counterclockwise. Clean the filter
mounting area. Coat the oil filter gasket with clean
oil.
To install the new
filter,
turn the fitter on clockwise until the gasket touches the mounting base,
then tighten 1/2 tum.
9-5
Page 50
FUEL
SYSTEM
Use only high-quality fuel in this generatorset. Fuel
quality is important in obtaining dependable performance and satisfactory engine
clean,
completely distilled, well refined, and non-
life.
Fuel must be
corrosive to fuel system parts.
IAWARNINGI Ignition of fuel can cause severe
personal Injury or death by fire or explosion. Do
not permit any flame, cigarette, spark, pilot
light, arcing equipment or other Igniter near the
fuel system.
Fuel Recommendations
Use ASTM 2-D (No. 2 Diesel) or ASTM 1 -D (No. 1
Diesel) fuel with a minimum Cetane number of 45.
Number 2 diesel fuel gives the best economy and
performance under most operating conditions. Use
number 1 diesel fuel when ambient temperatures
are below 0° C (32°
engine
load.
F),
or during long periods of light
The fuel's viscosity must be kept above 1.3 cSt to
provide adequate fuel system lubrication.
temperature. (Cloud point is the temperature at
which wax crystals begin to form in diesel fuel.)
Fuel
Handling Precautions
Take appropriate precautions to prevent the en-
trance of dirt, water or other contaminants into the
fuel system. Filter or strain the fuel as the tank is
filled.
IACAUTIONI Due to the precise tolerances of die-
sel Injection systems, dirt or water In the fuel
can cause severe damage to both the Injection
pump and Injector nozzles. Take special pre-
cautions
to
keep the fuel clean and free of water.
To avoid condensation problems, keep fuel tanks as
full as possible. In cold weather,>warm fuel return-
ing from the engine heats the fuel in the supply tank,
If the fuel level is low, condensation tends to form in
the upper portion of the tank. In warm weather, the
fuel and the tank will both be warm during the daytime.
At night, cool air lowers the temperature of the
tank more rapidly than the temperature ofthe
fuel.
If
the fuel level is low, the upper portion of the tank will
cool more rapidly and condensation will tend to
form.
Fuels with Cetane numbers higher than 45 may be
needed In higher altitudes or when extremely low
ambient temperatures are encountered to prevent
misfires and resultant excessive smoke.
Use low-sulfur-content fuel with a cloud point at
least 10 degrees below the lowest expected fuel
Condensation (water) can clog fuel filters as well as
causing freezing problems. Also, water mixing with
the sulfur in the ftiel forms acid which can corrode
and damage engine parts.
9-6
Page 51
Fuel
Filters
The filters are
drain is situated at the bottom ofthe filter case
spin-off,
throw-away units. A water
(Fig-
ure 9-2). This should be used to drain off moisture
either daily or at the end of every exercise period,
depending on unit application.
The drain plug on the fuel filter can tolerate only a
limited amount of torque.
Use
two wrenches in com-
bination for breaking the plug loose and for final
tightening.
Change the primary and secondary fuel filters at the
intervals recommended in the Maintenance Schedule.
Change the fuel filters by removing the washer
and capscrew on top of the fuel filter body.
CONNECTOR
(FROM FUEL
TRANSFER PUMP)
PRIMARY
FILTER
DRAIN
ELBOW (TO
INJECTION PUMP)
SECONDARY
FILTER
DRAIN
FS1113
Fuel
Pump Sediment Bowl
Remove the sediment bowl from the fuel filter body
(Figure
9-3).
Clean out any contaminants from
sediment bowl. When re-installing the sediment bowl,
make sure that gasket and screen are in place.
FIGURE
FUEL PUMP AND
FILTER BODY
GASKET-
9-2. DUAL
FILTER
BOWL.
FUEL FILTERS
9-7
FIGURE
9-3.
FUEL
PUMP
SEDIMENT
FS1115
BOWL
Page 52
Priming the
Fuel
System
4.
Tighten the fuel line at the injection pump inlet.
The fuel system must be primed before initial
startup or afterthe engine has run out of
fuel.
Prime
the fuel system as follows.
1.
Check fuel level in fuel tank and open shutoff
valve.
2.
Loosen the fuel filter-to-injection pump line at
the injection pump fuel inlet fitting (Figure 9-4).
3. Actuate the hand priming lever on the fuel
transfer pump until the fuel flows from the fitting.
If the pump lobe of the camshaft is up (no restriction can be felt when moving priming lever),
crank the engine one revolution to permit
hand priming:
ALWAYS RETURN
PRIMER LEVER TO
LOWEST POSITION
5. Actuate the hand priming lever several more
times to prime the injection pump.
6. When finished, retum priming lever inward
(disengaged position) to permit normal pump
operation.
WORK TRANSFER PUMP PRIMING
LEVER UNTIL FUEL FLOWS FROM
FUEL INLET FITTING
FIGURE
9-4.
FUEL
SYSTEM
FUEL INLET FITTING
TO INJECTION PUMP
FUEL
RETURN;
LINE
FS1777
9-8
Page 53
AIR CLEANERS
IACAUTIONI
to prevent
Filters should
damage.
If the filter
be
handled with
does
care
become
damaged. Install recommended replacement
part
After every
50
hours of
operation,
remove
and
clean
the filter element (Figure 9-5). After washing the
element
in
solvent,
dip the
element
in
engine
oil
and
squeeze it as dry as possible.
CONTRACTOR
1.
Remove
pre-cleaner
MODEL AIR
(Figure
9-6)
CLEANER
and
wash
out
dirt. Dry and reinstall.
2.
Loosen clamp and remove end cover.
3. Remove thumbscrew and take out element.
Wash
element
element after 6
4.
Remove
in
detergent
washings).
air cleaner
baffle
and
water
(use
Dry and reinstall.
from
cover,
wash
new
out
dirt, and reinstall in cover.
5. Install cover
with
"TOP" up and tighten clamp.
ELEMENT
HGURE
COVER
9-5.
POLYURETHANE
CLEANER
DUST
THUMBSCREW
\_
CLAMP
RETAINER
FOAM
(PRE-CLEANER)
^
AIR
CUP
HI 770
9-9
HGURE
FS18S3C
9-6. CONTRACTOR MODEL AIR
CLEANER
Page 54
GOVERNOR
LINKAGE
Every 100
nor ball joints apart
these
IACAUTIONI Some solvents can damage the
neoprene governor ball joints. Read the
facturer's
lubricants or
hours,
carefully
and
joints.
See Figure 9-7.
recommendations
solvents
pull
clean
near
the neoprene gover-
them.
Do not lubricate
manu-
before using any
the
ball joints.
FIGURE
9-7. GOVERNOR
CLEAN
BALL
BALL
JOINT
*FS1114
JOINT
Page 55
BATTERIES
IAWARNINGI Ignition of explosive battery gases
can cause severe personal Injury. Do not
smoke or allow any source of Ignition while
servicing batteries.
Check the condition ofthe starting battery at the interval specified in the maintenance schedule. To
prevent dangerous arcing, always disconnect the
negative ground strap from the battery before working on any part of the electrical system or the engine.
Disregard the sections on Checking Specific
Gravity and Checking Electrolyte Level if using a
"maintenance-free" battery.
Be sure the vent plugs are tight to prevent cleaning
solution from entering the cells.
After cleaning, flush the outside of the battery and
surrounding areas with clean water.
Keep the battery terminals clean and tight. After
making connections, coat the terminals with a light
application of petroleum jelly or non-conductive
grease to retard corrosion.
Checking
Specific
Gravity
Use a battery hydrometer to check the specific
gravity of the electrolyte in each battery
cell.
IAWARNINGI Arcing can Ignite the explosive hy-
drogen gas given off by batteries, causing se-
vere personal Injury. Arcing can occur If the
negative (-) battery cable Is connected and a
tool being used to connect or disconnect the
positive (+) battery cable accidentally touches
the frame or other grounded metal part of the
set. To prevent arcing, always remove the negative (-) cable first, and reconnect It last.
IACAUTIONI Always disconnect a battery
charger from Its AC source before disconnecting the battery cables. Otherwise, disconnecting the cables can result In voltage spikes high
enough to damage the DC control circuits ofthe
set.
Cleaning
Batteries
Keep the batteries clean by wiping them with a
damp cloth whenever dirt appears excessive.
If corrosion is present around the terminal connec-
tions,
remove battery cables and wash the terminals with an ammonia solution or a solution consisting of 1/4 pound of baking soda added to 1 quart of
water.
Hold the hydrometer vertical and take the reading.
Correct the reading by adding four gravity points
(0.004) for every ten degrees the electrolyte
perature is above 80° F (27°
C).
A fully charged battery will have a corrected specific gravity of
Charge the battery if the reading is below
Checking
IACAUTIONI DO not add water In freezing
Electrolyte
Level
tem-
1.260.
1.215.
weather unless the engine will run long enough
(two to three hours) to assure a thorough mix-
ing of water and electrolyte.
Check the level of the electrolyte (acid and water
solution) in the batteries at least every 200 hours of
operation.
Fill
the battery cells to the bottom ofthe filler neck, if
cells are low on water, add distilled water and recharge. If one cell is low, check case for leaks.
Keep the battery case clean and dry. An accumulation of moisture will lead to a more rapid discharge
and battery failure.
9-11
Page 56
CRANKCASE BREATHER
Clean the crankcase breather at the intervals rec-
ommended in the Maintenance Schedule.
BREATHER
HOSE
To clean the crankcase breather, remove hose
clamp, breather
hose,
breather
cap
clamp
and
insu-
lator halves to release breather cap and valve as-
sembly (Figure
9-8).
Wash
cap,
valve assembly and
baffle in suitable solvent. Dry and reinstall.
CRANKCASE BREATHER TUBE
Clean the crankcase breather tube at the intervals
recommended in the Maintenance Schedule.
To
clean the crankcase breather
rocker covers (Figure
is installed with a sealant
9-9).
on
tube,
remove both
The breather tube itself
the threads to prevent
oil leakage into the intake manifold; it should NOT
be removed. A small wire, nail or drill bit inserted
through from the top can be used to clean out the
breather hole. The breather hole seldom needs
cleaning.
A 500 hour interval coincides with the
valve lash adjustments, because the rocker box
covers must also be removed at that time.
c
HOSE CLAMP_
CAP AND VALVE.
O-RING
FILTER
BREATHER
TUBE
FIGURE 9-8. CRANKCASE BREATHER
CLEAN CRANKCASE
BREATHER PIPE
EVERY 500 HOURS
SCREEN
RETAINER
CLAMP
OIL BAFFLE
ASSEMBLY
LS1206C
CRANKCASE
BREATHER
TUBE
9-42
cion
FIGURE 9-9. CLEANING BREATHER
Page 57
Four
TORSIONAL
torsional
washer assemblies are bolted inside
WASHERS
the flywheel pulley hub (Figure 9-10). When functioning properly, they react to relieve torsion
stresses on the crankshaft. Inspect the assemblies
periodically for movement of washers and freedom
from corrosion (1500 hours commercial, yearly
non-commercial): If condition is questionable,
con-
tact an Onan service center or distributor.
FIGURE
9-10. TORSION
WASHER
ASSEMBLY
9-13
Page 58
OUT-OF-SERVICE
The inherent lubricating qualities of
normally should protect the cylinders of a diesel engine for at least 30 days when the unit is not in service.
To protect an engine that will be out of service
for more than 30 days, proceed as follows:
1.
Exercise the generator set as described in the
Operation section until the engine is up to oper-
ating temperature.
2.
Shut down the engine. Disconnect battery and
store in a
charger every 30 days to maintain it at full
charge.
3. Drain the oil base while it is still warm. Refill
and attach a waming tag indicating the viscos-,
ity of oil used. - ' „
•
4. Service the-air cleaner.' ' , -
5. Clean throttle and governor linkage and protect
by wrapping with a clean cloth.
6. Plug the intake and exhaust outlets to prevent
entrance of moisture, bugs, dirt, etc.
7. Clean and wipe the entire unit. Coat parts susceptible to rust with a light coat of grease or
8. Provide a suitable cover for the enti re unit after
unit has cooled down.
cool,
dry place. Connect battery to a
PROTECTION
No.
2 diesei fuel
oil.
RETURNING A UNIT
1.
Remove the cover and all protective wrapping.
Remove the plug from the intake and exhaust
outlet.
2.
Check the warning tag on the oil base and ver-
ify that the oil viscosity is still correct for the existing ambient temperature.
3. Clean cooling fin areas.
4.
Clean and check the battery. Measure the spe-
cific gravity (1.260 at 80° F [27° C]) and verify
that the level is at the split
gravity is low, charge until the correct value is
obtained.
and charge until the specific gravity is correct.
DO NOT OVERCHARGE.
- IAWARNINGI Ignition of explosive battery
gases can cause severe personal Injury. Do
^ pot smoke or allow any Ignition source
while servicing batteries.
5. Connect the starting battery (ground terminal
last).
6. Prime the fuel system.
7. Remove all loads before starting the engine.
8. Start engine and observe oil pressure gauge
and charge rate ammeter.
9. After start, apply load to at least 50 percent of
rated capacity.
10.
Unit is ready for service and load may be ap-
plied.
Ifthe level is low, add distilled water
TO
SERVICE
ring.
If the specific
,
Page 59
10.
Maintenance
Record
Keep a record of all periodic and unscheduled
maintenance. Record the service date and the
number of operating hours from the hour
DATE
HOUR
METER
READING
meter.
Referto the Maintenance Schedule in Section 8 for
the
time
interval between maintenance procedures.
Record
center and keep all of your service receipts.
SERVICE
the
name
PERFORMED / NOTES
and
address of your Onan service
Record the name, address, and phone number of
your authorized Onan service center.
10-1
Page 60
Page 61
11.
Wiring
GENERAL • Page 11-3-Customer Connections at the En-
Diagrams
gine Monitor Board.
This section consists ofthe schematic
tion
wiring diagrams
lowing drawings are
referenced
included.
in the
• Page 11-5-Generator Reconnection Diagram
and
connec- • Page
text. The
fol- •
11
-4-Customer Connections at the Aux-
liary Relay Board
-
11-1
Page 62
TB1-10 (SWfTCHED B+ OUTPUT) OUTPUT TO RELAY K12, FUSED AT 20 AMPS, ENERGIZED WHEN THE
START SIGNAL IS APPLIED AND DE-ENERGIZED AT SHUTDOWN (NORMAL AND FAULT)
TBI-9 (B+ INPUT) BATTERY POSITIVE (+) CONNECTION
TB1-8 (START SOLENOID) OUTPUT TO RELAY
K11,
FUSED AT 20 AMPS
TBI-7 (B+ OUTPUT) OUTPUT TO TIME DELAY START/STOP MODULE Al 5,
FUSED AT 15 AMPS, AVAILABLE WHEN THE STARTING BATTERIES ARE CONNECTED
TB1-6 (REMOTE START) CONNECTED TO TIME DELAY START/STOP MODULE A15. CONNECT REMOTE START
CONTACT OF THE AUTOMATIC TRANSFER SWITCH TO TERMINAL
TB1
-5 OF MODULE A15.
TB1-5
(GROUND)
TB1-4 (COMMON ALARM B+ OUTPUT) 4 AMP RATED DEVICE MAXIMUM
TBI-3 (RUN) CONNECTED TO TIME DELAY START/STOP MODULE A15
TBI-2 (DC DISCONNECT) CONNECTED TO TIME DELAY START/STOP MODULE Al
5
5*
COKTROL
R
Ul
C8
C3
• R9
I
1
U3
U5
—
VR2
KB
K7
R10
cne
-
CR17
•1
U2
DBD
iq
CR9
C5
C7
Kll
a
CRB
CRG
+
ID
5:
LJ
H
(Zl
a CRIB
KIG
W4
rj
n
CRI a
um um
Wl
Kl K5
CRI?
CRI?
LJ
"l
g 3 1 5 6 7 8 ~9~ IB 15 H H 15 IB
CR3
^
™ I
CR5
CREB
VR3
KIB
KB Kll K13 K15
L_l
I
CR13
dl
K]2
RB
R7
RG
_n_
I
3
W
WG
W7
Dffl
KIB
K17
15 13
K22
•1
CRII CRIE
K19
CD
LJ
Lu
F5
A
•
US
9
IB
II
12
1
5
3
4
5
6
7
P3
8
9
IB
li
15
PA
THIS
IS A
REPRESENTATIVE
SCHEMATIC/WIRING
TROUBLESHOOTING,
IWIRING
•NCLUDED
DIAGRAM
WITH
PACKAGE
YOUR
TB2-10 (PRE-HIGH ENGINE TEMPERATURE WARNING) GROUND OUTPUT TO LIGHT/RELAY*
(GENERIC)
DIAGRAM. FOR
REFER
TO
THE
THAT WAS
GENSET.
TB2-1 (FAULT 2) GROUND INPUT FROM SENDER
TB2-2 (FAULT 2) GROUND OUTPUT TO LIGHT/RELAY*
TB2-3 (FAULT 1) GROUND INPUT FROM SENDER
TB2-4 (FAULT 1) GROUND OUTPUT TO LIGHT/RELAY*
TB2-5 (REMOTE RESET) MOMENTARY CONTACT TO GROUND
TB2-6 (OVERCRANK FAULT) GROUND OUTPUT TO LIGHT/RELAY*
TB2-7 (OVERSPEED FAULT) GROUND OUTPUT TO LIGHT/RELAY*
TB2-8 (HIGH ENGINE TEMPERATURE FAULT) GROUND OUTPUT TO LIGHT/RELAY*
TB2-9 (LOW OIL PRESSURE FAULT) GROUND OUTPUT TO LIGHT/RELAY*
TB2-11 (PRE-LOW OIL PRESSURE WARNING) GROUND OUTPUT TO LIGHT/RELAY*
TB2-12 (SWITCH OFF WARNING) GROUND OUTPUT TO LIGHT/RELAY*
TB2-13 (LOW ENGINE TEMPERATURE WARNING) GROUND OUTPUT TO LIGHT/RELAY*
TB2-14 (LOW FUEL WARNING) GROUND INPUT FROM SENDER
CUSTOMER
* 0.5 AMP
SUPPLIED
FACTORY
RATED
DEVICE
P2
WIRING
WIRING
MAXIMUM
TB2-16 (EMERGENCY SHUT DOWN) MOMENTARY CONTACT TO GROUND
CUSTOMER
TB2-15 (LOW FUEL WARNING) GROUND OUTPUT TO LIGHT/RELAY*