Onan RDJC Operator's Manual

Page 1
»
Onon Operator's
RDJC
Manual
GENERATOR
SET
Printed U.S.A.
974-0127
Page 2
Table of Contents
SECTION TITLE PAGE
SAFETY
1 INTRODUCTION 1-1
About This Manual 1-1 Safety Considerations 1-1 How To Obtain Service 1-1
2 SPECIFICATIONS
3 INSTALLATION 3-1
General 3-1
Location 3-1 Mounting 3-2
Ventilation 3-3
Radiator Cooling 3-3
City Water Cooling (Opitional) 3-3
Exhaust 3-4 Fuel Tank And Unes 3-5
Oil Drain 3-6
4 ELECTRICAL PREPARATION 4-1
General 4-1
Transfer Switch 4-2
Generator Voltage Connections 4-3 Load Connection 4-4
DC Wiring 4-6
Battery Connections 4-6
5 CONTROL DESCRIPTION 5-1
PRECAUTIONS
2-1
iii, iv
General 5-1
DC Controls , 5-2
AC Controls.. 5-4
Page 3
SECTION
TITLE PAGE
6 OPERATION 6-1
General S'
1
Prestart Checks 6-2 Starting 6-3
Running 6-5 Stopping 6-6 Break-In 6-7 No-Load Operation 6-7
Exercising Period • • 6-7 High Temperatures 6-8
Low Temperatures •. • • 6-8
Dust And Dirt • • • 6-8
High Altitude .., 6-8
Power Rating Factors 6-8
7 ADJUSTMENTS 7-1
Generator Voltage Check and Adjustment 7-1
Governor - • • 7-2
Valve Clearance Adjustments 7-3
Centrifugal Switch 7-4
Charge Rate Adjustment 7-4
8 TROUBLESHOOTING .. . . 8-1
Safety Considerations 8-1
9 MAINTENANCE 9-1
General 9-
1
Generator Set Inspection 9-3
Lubrication System 9-3
Fuel System
• •
• 9-6 Air Cleaners - • 9-9 Contractor Model Air Cleaner 9-9 Governor Linkage 9-10
Batteries 9-11
Crankcase Breather 9-12
Crankcase Breather Tube 9-12
Torsional Washers 9-13 OuHaf-Service Protection 9-14
Returning a Unit to Service . • • 9-14
10 MAINTENANCE RECORD 10-1 11 WIRING DIAGRAMS 11-1
General 11-1
Page 4
Safety Precautions
Before operating the generator set, read the erator's Manual and become familiar with equipment. Safe achieved only ated
and
maintained. Many accidents are caused by failure tions.
The following symbols, found throughout this man­ual, the operator, seivice personnel,
rUJMtHil This symbol warns hazards which will result
jury
IAWARNINGI This symbol refers
safe practice which sonal Injury
to
alert you
or
death.
and
efficient operation
If
the equipment
follow fundamental rules
to
potentially dangerous conditions
In
can
or
death.
is
properly oper-
and
or
the equipment.
of
immediate
severe personal
to
a hazard or un-
result
in
severe per-
Op-
it
and
can be
precau-
in-
the
to
Be
sure all fuel supplies have a positive shutoff
valve.
Be
sure battery area
prior
to
servicing near emit a highly explosive hydrogen be ignited
EXHAUST
• Provide erly expel discharged gases away from closed dividuals are likely to congregate. Visually audibly inspect the maintenance schedule. Ensure that
haust manifolds Do
not use
ment.
Be
sure
by
arcing, sparking, smoking,
GASES
an
adequate exhaust system
or
sheltered areas
exhaust gases
the
unit
has
been well-ventilated
it.
Lead-acid batteries
ARE
DEADLY
and
the
exhaust daily
are
secured
is
well ventilated.
areas where
and not
to
heat a compart-
gas
for
that
can
etc..
to
prop-
en­ and
leaks
per
ex-
warped.
in-
IACAUTIONI This symbol refers
safe practice which can result In personal injury or product or property damage.
FUEL
AND
Fire,
explosion, and personal injury or
sult from improper practices.
DO NOT
unless tanks
ment. Fuel contact with
is a potential fire hazard.
• DO NOT permit any spark, arcing equipment, source near the generator
• Fuel lines must
free
should Do
copper will become brittle
brated
FUMES
fill fuel tanks while engine
of
leaks. Fuel connection be
made with
not use
or
repeatedly bent.
ARE
are
outside
flame,
be
adequately secured
an
copper piping
to
a hazard or un-
FLAMMABLE
death
the
engine compart-
hot
engine
cigarette, pilot light,
or
other ignition
set or
at the
approved flexible line.
on
flexible lines
if
continuously
can
is
running,
or
exhaust
fuel tank.
and
engine
re-
as
vi-
MOVING PERSONAL
• Keep your hands, clothing,
• Before starting work on
• Make sure that fasteners
Do
If
PARTS
from moving parts.
connect battery charger from then disconnect starting batteries, negative cable first. This
are secure. Tighten supports keep guards etc.
not wear loose clothing
cinity
of
moving trical equipment. Loose clothing can become caught can short
shock
or
adjustment must
running,
folds,
moving parts,
CAN
INJURY
in
out
electrical contacts
buming.
use extreme caution around hot mani-
CAUSE
OR
DEATH
the
will
prevent accidental starting.
position over fans, drive belts,
parts,
or while working on elec-
in
moving parts. Jewelry
be
made while
etc.
SEVERE
and
jewelry away
generator set, dis-
its AC
on the
or
generator
and
jewelry
source,
clamps,
in the
and
and
the
(-)
set
vi-
jewelry
cause
unit
is
in
LS-10
Page 5
ELECTRICAL SEVERE
• Remove electric power before removing pro­tective shields or touching electrical equip­ment. Use rubber insulative mats placed on dry wood platforms over floors that are metal or concrete when around electrical equipment. Do not wear damp clothing (particularly wet shoes) or allow skin surface to be damp when handling electrical equipment.
• Use extreme caution when working on electri­cal components. High voltages can cause in­jury or
• Follow all applicable state and local electrical codes. Have all electrical installations per­formed by a qualified licensed electrician. Tag open switches to avoid accidental closure.
• DO NOT CONNECT GENERATOR SET DI­RECTLY TO ANY BUILDING ELECTRICAL SYSTEM.
the generator set into the utility line. This cre­ates a potential for electrocution or property damage. Connect only through an approved isolation switch or an approved paralleling de­vice.
GENERAL SAFETY
• Coolants under pressure have a higher boiling point than water. DO NOT open a radiator or heat exchanger pressure cap while the engine is running. Allow the generator set to cool and
bleed the system pressure first.
SHOCK
PERSONAL
death.
DO NOT tamper with interlocks.
Hazardous voltages can flow from
CAN
INJURY
PRECAUTIONS
CAUSE
OR
DEATH
Benzene and
have been identified by some state and federal agencies as causing cancer or reproductive toxicity. When checking, draining or adding gasoline, take care not to ingest, breathe the fumes, or contact gasoline.
Used engine oils have been identified by some state or federal agencies as causing cancer or reproductive toxicity. When checking or changing engine oil, take care not to ingest, breathe the fumes, or contact used oil.
Provide appropriate fire extinguishers and in­stall them in convenient locations. Consult the local fire department for the correct type of ex-
tinguisher to fires.
Use extinguishers rated ABC by NFPA.
Make sure that rags are not left on or near the engine.
Remove all unnecessary grease and oil from
the unit. Accumulated grease and oil can cause overheating and engine damage which present a potential fire hazard.
Keep the generator set and the surrounding area clean and free from obstructions. Re­move any debris from the set clean and dry.
Do not work on this equipment when mentally or physically fatigued, or after consuming any alcohol or drug that makes the operation of equipment unsafe.
Substances in exhaust gases have been iden-
tified by some state or federal agencies as causing cancer or reproductive toxicity. Take care not to breath or ingest or come into contact with exhaust gases.
lead,
found in some gasoline,
use.
Do not use foam on electrical
and
keep the floor
KEEP
THIS MANUAL
NEAR
THE
GENSET
iv
FOR
EASY REFERENCE
Page 6
1.
Introduction
ABOUT
This manual provides installation instructions, and information on the Onan® RDJC generator set manual carefully and comply with each of its warn­ings and and performing regular maintenance can result in longer unit life, better performance, and safer op­eration.
The generator set has been carefully designed to provide safe and efficient service when properly in­stalled and operated. However, the overall safety and reliability of the complete system is dependent on many factors outside the control ofthe generator set manufacturer. To avoid possible safety haz­ards,
make all mechanical and electrical connec-
tions to the generator set exactly as specified in this
manual. exhaust, electrical, etc.) must comply with all appli­cable codes. Make certain all required inspections and tests have been completed and all code re­quirements have been satisfied before certifying the installation is complete and ready for service.
operating,
cautions.
SAFETY
All systems external to the generator (fuel,
THIS
Using the generator set properly
CONSIDERATIONS
MANUAL
maintaining and adjusting
(genset).
Study this
HOW TO OBTAIN
When the generator set requires your nearestl Cummins®/Onan® dealer or distribu­tor. Factory-trained Parts and Service representa­tives are ready to handle all your seivice needs.
If you are unable to locate a dealer or distributor, consultthe Yellow Pages. Typically, our distributors are listed under:
GENERATORS-ELECTRIC or
ELECTRICAL PRODUCTS
Forthe name of your local Cummins/Onan or Onan­only distributor in the United States or Canada, call
1-800-888-ONAN touch-tone phones only). By entering your area code and the first three digits ofyour local telephone
number, you will receive the name and telephone
number of the distributor nearest you.
For outside North America, call Onan Corporation,
1-612-574-5000, 7:30 AM to 4:00 PM, Central
Standard Time, Monday through Friday. Or, send a
fax to Onan using the fax number 1 -612-574-8087.
When contacting your distributor, always supply the
complete Model Number and Serial Number as
shown on the generator set nameplate.
(this automated service utilizes
SERVICE
servicing,
contact
IAWARNING
INCORRECT SERVICE OR PARTS REPLACEMENT CAN RESULT IN SEVERE PERSONAL IN­JURY, DEATH, AND/OR EQUIPMENTDAMAGE. SERVICE PERSONNEL MUST BE QUALIFIED
TO PERFORM ELECTRICAL AND/OR MECHANICAL SERVICE.
Onan is a registered trademark of Onan Corporation. Cummins is a registered trademark of Cummins Engine
Company,
Inc.
1-1
Page 7
2.
Specifications
DIMENSIONS
Height 40.12 inches (1019 mm) Width 27.00 inches (686 mm) Length 56.62 inches (1438 mm) Weight 940 lbs (426 kg)
ENGINE
Number of Cylinders 4 Engine Speed (50/60 Hz) 1500/1800 rpm Recommended Fuel #1 or #2 diesel Exhaust Connection (pipe tapped) 1.5 in. (38.1 mm)
Fuel Pump Maximum Lift 6 feet (1.8 mm) Oil Filter Full flow type Fuel Consumption (full load) 1.6 gallons/h (6 liters/h) (60 Hz)
1.4 gallons/h (5 liters/h) (50 Hz)
ELECTRICAL
Starting Voltage 12 Volts DC Cranking Current 225 amps at ambient temp, of 32° F (0° C) Battery 12 Volt, negative ground Battery Size 560 amps (cold cranking) at 32° F (0° C)
Battery Charge Rate 2 to 5 amps (adjustable)
GENERATOR
Power
15.0 RDJC 15kW(60Hz)
12.5 RDJC 12.5 kW (50 Hz)
Output Rating 1.0 power factor (single-phase)
CAPACITIES
Coolant System (Includes Radiator) 13 U.S. quarts (121) Oil Capacity 6.5 U.S. quarts (6.0 I)
TUNE-UP
Start-Disconnect Centrifugal Switch Point Gap Cylinder Head Bolt Torque 44 - 46 ft-lb (60 - 62 N»m) Glow Plug Torque 10-15 ft-lb (14 - 20 N»m) Valve Clearances
Intake 0.011 in. (0.28 mm) Exhaust 0.016 in. (0.41 mm)
Injector Firing Order 1, 2, 4, 3
SYSTEM
SPECIFICATIONS
800 amps (cold cranking) at 0° F (-18° C)
0.8 power factor (three-phase)
0.020
in. (0.51 mm)
2-1
Page 8
3. Installation
GENERAL
Most generator set installations must be designed
so that the generator set will function property under
all anticipated operating conditions. Use these
instructions as a general guide only. Follow the
instmctions of the consulting engineer when locat-
ing or installing any components.
Generator set installations must conform to local
building codes, fire ordinances, and other local,
state and federal regulation. For more detailed
installation instructions, consult Onan Application
Manual T-030, or contact an authorized Onan ser-
vice representative.
Requirements to be considered priorto installation:
• Level mounting surface
• Adequate cooling air
• Adequate fresh induction air
• Discharge of circulated air
• Discharge of exhaust gases
• Electrical connections
• Fuel connections
• Accessibility for operation and servicing
• Noise levels
• Vibration isolation
• Electrical connections
LOCATION
Provide a location for the genset that is dry, clean, dust-free, well-ventilated, and protected from the weather (see Figure 3-1). Generator set location is decided mainly by related systems such as ventila­tion,
wiring,
fuel,
and exhaust. The set should be lo-
cated as near as possible to the main power fuse
box.
Provide a location away from extreme ambient
tem­peratures and protect the generator set from ad­verse weather conditions. An optional housing is available for outside operation.
COOL AIR IN
GENERATOR SET
NOT LOCATE CLOSER
THAN 24"
[61
OMM] TO
ANY WALL)
AUTOMATIC LOAD
TRANSFER SWITCH
METER
CANVAS
SECTION
HEATED
AIR OUT
RETURN
LINE
TO FUEL TANK
G1079-1
FIGURE
3-1.
TYPICAL
3-1
INSTALLATION
Page 9
MOUNTING
Generator sets are mounted on a steel skid that pro­vides proper support. The engine-generator as­sembly is isolated from the skid frame by mbber mounts that provide adequate vibration isolation for normal installations. For critical installations, install vibration isolators between the skid base and foundation.
Mount the genset on a substantial and level base such as a concrete pad.
Use
3/4-inch
diameter, anchored mounting bolts to secure the generator set skid to the floor to prevent movement. Secure the skid using a flat washer and hex nut for each bolt (Figure 3-2).
FLATWASHER
HEX NUT
SKID
12 INCH
(305 mm)
MOUNTING BOLT
FIGURE
3-2.
BOLT
in 627
DIAGRAM
3-2
Page 10
VENTILATION
Generator sets create a large amount of
heat,
which must be removed by ventilation. An outdoor instal­lation can rely on natural air circulation, but indoor
installations need enough properly sized vents in the correct positions to maintain the necessary air flow.
The presence or absence of a fan and radiator de­termines ventilation system design. With a radiator, engine-pusher fan size is large enough to remove
heat from the engine, generator, and a few feet (roughly a metre) of uninsulated exhaust pipe. Re-
strictive ducting or heat sources otherthan the
gen-
erator set require extra fans to increase airflow.
With other cooling options, ventilation fans are
needed.
Fan size must be large enough to remove the heat in the room given off by the generator set, uninsulated exhaust pipes and any other heat-pro­ducing equipment. A temperature differential of 20° to 30° F
(110 to 17° C) is usually satisfactory.
IACAUTIONI Operating the generator set with
any of the cooling system components re­moved can cause equipment damage. Do not
operate the generator set with any of the cool­ing system components removed.
RADIATOR
COOLING
Cooling air travels from the rear to the front of the set. Locate the room/compartment air inlet where it is most convenient, preferably to the rear of the set. The minimum inlet opening should be at least 1 -1/2 times the size ofthe radiator
area.
Increase the size of the opening if it will be restricted with louvers or filters (see Figure 3-1).
Engine heat is removed by a pusher fan which blows cooling air through the front of the radiator. The cooling air outlet should be directly in front of the radiator, and as close to it as is
practical.
The un-
restricted outlet opening must be at least as large as the radiator opening. A flexible section must
con-
nect the radiator and the air outlet opening, to pre­vent recirculation of heated air.
Generator cooling air is discharged through the en­gine-to-generator adapter on the left side of the en­gine.
3-3
Page 11
EXHAUST
Pipe exhaust gases outside the enclosure. The ex­haust outlet is 1 -1/2-inch pipe size. Locate the ex-
haust outlet far from the air inlet to avoid gases re­entering the enclosure. Use flexible seamless tub­ing to connect between the engine exhaust and any rigid pipe extension to prevent transmission of vi­bration.
IAWARNINGI Exhaust gas Is poisonous. Inhala-
tion .can result In severe personal Injury or death. Modifying the exhaust system can allow
poisonous exhaust gases to escape. Use only
original equipment replacement parts when servicing the exhaust system. Unauthorized modifications will also void the warranty and cancel the UL Listing/CSA Certification. Liabil­ity for injury or damages due to unauthorized modifications becomes the responsibility ofthe
person making the change.
Because an exhaust system is subjected to detri-
mental conditions such as extreme heat, infrequent operation,
and light operating
load,
inspect the ex-
haust system frequently to be sure that it remains fume-tight.
I AWARNING] Inhalation of exhaust gases can re-
sult In severe personal Injury or death. Do not use exhaust heat to warm a room, compartment or storage area.
An approved thimble must be used (Figure 3-3) to pass exhaust pipes through walls or partitions.
Build this thimble according to code (see National
Fire Protection Association bulletin, Volume 4, siec­tion 211 on "Standards for Chimneys, Fireplaces, and Vents").
As the exhaust pipe length and number of bends in­creases, a larger pipe is required to reduce exces­sive exhaust restriction and back pressure. Exces­sive exhaust back pressure will reduce the air-fuel ratio,
resulting in reduced output, smoke, wasted power, high exhaust temperatures and reduced en­gine life.
Total back pressure of ail system components must not exceed maximum back pressure limits. Note that any exhaust restriction, even if less than maxi­mum,
will affect performance.
AVOID SHARP BENDS
IF EXHAUST LINE MUST BE PITCHED
UPWARD CONSTRUCT A TRAP OF PIPE
FITTINGS AT POINT OF RISE
(228.60
mm)
h-9" —
INNER SLEEVE
9"^
DRAIN CONDENSATION TRAP
SINGLE THIMBLE DIAMETER
12 INCHES (305 MM)
LARGER THAN EXHAUST LINE
HOLES IN END
EXHAUST
THROUGH
PERIODICALLY
LINE
WALL
PASSING
OR PARTITION
EXS1175
FIGURE
3-3.
EXHAUST
PIPING
3-4
Page 12
FUEL
IAWARNINGI Fuel tanks present the risk of explo-
TANK AND
LINES
sion and fire, which can cause severe personal
Injury or death. Because fuel leaks create fire hazards, always use flexible tubing between the engine and the fuel supply,
to
avoid leaks due to vibration and/or fuel line fallure. Do not allow the fuel line to contact rough, sharp or hot sur­faces.
The top of the fuel tank must be lower than the fuel
pump to prevent siphoning if a system leak occurs. Install a shutoff valve at the icing.
If the fuel tank is shared, do not connect it to
an existing
line
at a point above the fuel supply level,
fuel
tank,
to enable serv-
to avoid starving either engine.
Use an approved flexible fuel line next to the en-
gine.
Diesel engines require a fuel supply line and a separate fuel return line. Install the fuel supply line from
the supply tankto the inverted flare male elbow
mounted in the inlet ofthe fuel pump. The pump is
threaded
7/16-24
NPTF (American Standard Inter-
nal Tapered Pipe Thread). Install fuel retum line from the
7/16-24
size opening in the overflow fitting located on injection pump (where nozzle fuel retum line is also connected) to
the top of the fuel supply tank. Shield the line with fire-retardant material if it passes through a com­bustible wall or partition.
IAWARNINGI Always use flexible tubing between
engine and fule supply to avoid line failure and teaks due to vibration.
IACAUTIONI Never use galvanized or copper fuel
lines, fittings or fuel tanks. Condensation In the tank and lines combines with the sulfur In diesel fuel to produce sulfuric acid. The molecular structure of the copper or galvanized lines or
tanks reacts with the acid and contaminates the fuel.
Carefully clean all fuel system components before putting the set into
operation.
Any dirt or contamina-
tion may cause major damage to the fuel injection
system.
IACAUTIONI Dirt In the system can severely dam-
age both the Injection pump and the Injection nozzles. Dirty fuel Is one of the major causes of engine fallure. Even a tiny particle of dirt In the Injection system may stop the engine. Because diesel Injection systems have extremely pre­cise tolerances, make certain that fuel Is kept clean.
FUEL RETURN
LINES
NOZZLES
CONNECT FUEL
RETURN LINE
HERE (FLEXIBLE)
INJECTION
PUMP
F8I111
FIGURE 3-4. FUEL LINE CONNECTIONS
3-5
Page 13
Separate
The fuel tank top must be lower
Fuel
Tanks
than
the fuel pump level to prevent putting a static head on the fuel pump
inlet.
Ifthe
fuel
tank
is
shared
gine,
use separate fuel lines for both engines tp
with
another
en-
avoid starving either one. The following restrictions apply to separate fuel
tank installation:
1.
The bottom of the fuel tank must not be more
than 6 feet (1.8
m)
below
the
fuel
transfer pump inlet, unless an auxiliary electric fuel pump is added. fer pump
The maximum lift capacity of
is
six
feet.
See
the
Wiring Diagram for
the
trans-
the connection.
2.
If the tank is installed above the fuel pump inlet
level without a supply line shutoff
tured pump diaphragm could cause
valve,
oil
dilution,
a rup-
fuel loss, and fuel leakage to the crankcase.
3. If the maximum fuel lift must be exceeded on any
installation,
ual
T-030
consult
Onan
Application Man-
for information on installing a day
tank and an electric solenoid shutoff valve.
4.
Use an electric or manual shutoff valve if the
minimum
fuel
level in the tank
is
higherthan the
pump inlet, to provide positive fuel shutoff
when the engine is stopped. This valve also prevents loss of fuel from possible leaks be-
tween the tank and the fuel pump.
IAWARNINGI Fuel
hazards which can
leaks create lire
result
In
severe
and
explosion
personal In-
jury or death. Always use flexible tubing be-
tween engine
ure and
must
Extend has a
IAWARNINGI Do notposltlon
leaks
meet applicable codes.
the
1/2-inch
drain
and fuel
due
OIL
to suit the
supply to
to vibration. The
DRAIN
installation.
pipe size tapped hole.
the
oil
avoid
fuel
The
drain
line fail-
system
oil
base
so
that
oil might drip onto the muffler, any exhaust components, fire
hazard.
personal
IAWARNINGI Fuel and oil must be
disposed of properly to avoid damage and state and local tanks
and secondary containment and disposal
or any other hot parts,
Fire
presents
Injury
or
death.
clean-up liability.
regulations
causing
the hazard of
severe
contained and
environmental
Check all federal,
regarding storage
requirements.
a
3-6
Page 14
4.
Preparation
GENERAL
The genset electrical system includes connecting the
load,
installing the control wiring and connecting the batteries. Connect the batteries last to avoid ac­cidental starting of the unit during installation.
IACAUTIONI Always disconnect a battery
charger from Its AC source before disconnect­ing the battery cables. Otherwise, disconnect­ing the cables can result In voltage spikes high enough to damage the DC control circuits ofthe set
IAWARNINGI Accidental starting of the generator
set while working on It can cause severe per­sonal Injury or death. Prevent accidental start­ing by disconnecting the starting battery cables
(negative [-] first). Arcing can Ignite the explosive hydrogen gas
given off by batteries, causing severe personal
Injury. Arcing can occur If the negative (-) bat-
tery cable Is connected and a tool being used to
connect or disconnect the positive (+) battery cable accidentally touches the frame or other
grounded metal part of the set To prevent arc-
ing, always remove the negative (-) cable first,
and reconnect It last.
The following paragraphs contain the procedures that are used to connect the electrical system ofthe genset.
Connecting the genset electrical system involves:
• Installation of transfer switch (standby service only)
• Generator voltage connections
• Load connection
• Control wiring
• Battery connection
Local regulations often require that wiring connec-
tions be made by a licensed electrician, and that the
installation be inspected and approved before op­eration. etc. must conform to the requirements of electrical codes in effect at the installation site.
IAWARNINGI Improper wiring can cause a fire or
electrocution, resulting In severe personal Inju­ry or death and/or property and equipment dam-
age.
Before starting the genset, verify that all electrical connections are secure, and that all wiring is com­plete. have been removed during installation. Check that the load cables from the genset are properly nected.
All connections, wire sizes, materials used,
Replace and secure any access panels that
con-
IAWARNINGI Each of the operations described In
this section should be done only by persons trained and experienced In electrical mainte­nance. Improper procedures may result In prop­erty damage, bodily Injury or death.
IAWARNINGI Backfeed to utility system can
cause electrocution or property damage. Do not connect to any building electrical system except through an approved device and after building main switch Is opened.
4-1
Page 15
TRANSFER
If the installation is for standby service, a transfer switch must be used for switching the load from the normal power source to the genset (see Figure 4-1). Either a manual or automatic transfer switch may be used.
Follow the installation instructions provided
with the transfer switch when connecting the load
and control Delay Module'"\n this section, for generator set re­mote start connections.
wiring.
Referto heading "Preheat/Time-
SWITCH
NORMAL SOURCE
1
•LOAD
GENSET
. - J
;8C-1101
(FIGURE
4^.1
.^PICAULOAD TRANSFER
^FUNdriON
4-2
Page 16
GENERATOR
IACAUTIONI Reconnecting factory connected
VOLTAGE
CONNECTIONS
generator sets to lower voltages may reduce set ratings, and also render line circuit breakers too small. Consult with your distributor before per-
forming reconnection for different voltage.
The generator output voltages and maximum cur­rent rating are specified on the generator name­plate.
Line-to-neutral voltage is always the lower voltage shown on the nameplate. Line-to-line volt­age is the higher rating.
The
factory panels the customer. Standard are shipped
separated
ships
especially
with
in the
special-order
wired
forthe
sets
sets
voltage
without the T1-T4 or T1-T12 output
box.
These
with
control
specified
by instruments output
leads
single-phase
and broad-range generators may be connected to
provide any connection check any
necessary
sired
voltage.
ofthe
output
voltages
Diagram. The Installer must
the stator lead
connections
reconnections to obtain the de-
shown
in
the Re-
always
and perfonn
Refer to the Reconnection Diagram when reviewing the voltage connection information, and use the
electrical schematic supplied with your genset
when actually performing load connections. (A re­connection diagram is located on the inside of the power output box cover.)
A DANGER
HAZARDOUS VOLTAGE! Touching
uninsulated live parts Inside the control and
power output boxes can result In severe per-
sonal Injury or death. Measurements and ad-
justments must be done with care to avoid
touching uninsulated live parts. For your protection, stand on a dry wooden plat-
form or rubber insulating mat, make sure your clothing and shoes are
dry,
remove jewelry from
your hands and use tools with Insulated
handles.
The genset control panel box contains the auto-
matic voltage regulator (AVR) printed circuit board. The AVR controls the output of the generator so that a constant voltage is maintained under varying load conditions. There are two types of AVR's available; one requiring jumper adjustments when connecting
or changing load connections. If the genset tains the AVR shown in Figure 4-2, be sure to
con-
con­nect jumper W10 between terminal V4 (common) and
V1,
V2, or V3 as listed on the reconnection dia-
gram.
AUTOMATIC VOLTAGE REGULATOR
(VR21)
V3 V1 W10 V2
O
V4
(COM)
FIGURE
4-2. AVR
SELECTION
4-3
JUMPERS
(P/N
300-1540)
Page 17
IAWARNINGI
LOAD
HAZARDOUS VOLTAGE! Touching
CONNECTION
uninsulated live parts Inside the AC power out-
put box can result In severe personal Injury or
death. Shut down the set and disconnect ALL power sources to the generator set before re­moving the cover of the AC power output box.
See Figure 4-3.
Load wires can be brought into the power output box through the holes that are shown in Figure 4-3.
Use flexible conduit and stranded load wires near
the set to isolate vibration and permit movement.
Use suitable size insulated wires forthe load rating applied.
When installing sets with AC meters.'the generator output leads must be routed through current trans­formers for proper meter operation. The transform­ers are labeled
CT21,
CT22and CT23. Referto
Fig­ure 4-3 and the reconnection diagram to identify the output leads that must be routed through each cur­rent transformer, and also appropriate transformer post selection for meter sensing leads.
Without optional main circuit breaker: Connect
each load wire to the proper generator output lead inside the output box. Insulate bare ends of un-
grounded wires. Use bolt provided on the output
box to connect the generator ground lead or earth
wire.
Install a fused main switch (or circuit breaker)
between the generator and
load.
If a test-run
indi­cates wrong rotation of 3 phase motors in the load circuit, switch the connections at any two ofthe
gen­erator terminals.
With optional main circuit breaker: To attach the
load wires to the optional circuit breaker, remove
the access plate that is located directly below the circuit breaker. Attach the load cables to the base of the circuit breaker and install the access panel. If a test-run indicates wrong rotation of 3 phase motors
in the load circuit, switch the connections at any two
of the generator terminals.
IAWARNINGI Backfeed to utility system can
cause electrocution or property damage. Do not connect to any building electrical system ex­cept through an approved device and after building main switch Is opened.
IACAUTIONI Phase rotation of the genset and
utility must be the same. Equipment damage
can occur. Check and reconnect as necessary.
Check the rotation of 3-phase motors before loading and reconnect If necessary.
Balancing
Loads
When connecting loads to the genset, balance the
loads so that the currentflowfrom each line terminal (L1,
L2 and L3) is about the same. This is especially
important if both single phase and three phase
loads are connected. Any combination of single
phase and three phase loading may be used as
long as all line currents are roughly the same (within
10 percent of median value) and no line current ex­ceeds the nameplate rating ofthe generator. Check the current flow from each load cable after connec­tions are made, by observing the control panel am-
meter.
Grounding
Grounding involves making a conducting connec­tion between the metal parts of the generator set or one of its electrical circuits and the earth. The de-
sign and installation of a grounding system is af­fected by many factors such as the use of multiple transformers, ground fault protection requirements, and physical location of the generator. Follow the
recommendations of the consulting engineer when
installing the grounding system.
IAWARNINGI Contact with electrical equipment
can result In severe personal Injury or death. It
Is extremely Important that bonding and equip-
ment grounding be properly done. All metallic parts that could become energized under ab-
normal conditions must be properly grounded.
4-4
Page 18
LINE CIRCUIT
BREAKERS (WHEN
PROVIDED)
TERMINALS FOR
CONNECTING GENERATOR
LEADS ON OPTIONAL
CIRCUIT BREAKER
CT22-I
PRP/BLK
AC CONTROL
WIRING HARNESS
GENERATOR LEAD
ENTRANCE
LOAD WIRING
ENTRANCE
Frem
Conlrol:
Gi-or/Blk
Loads
And OO
Grar/Blk
Bolo. Abovo
Aro CT.'
Loodo 300 VAC 300 VAC
To:
Coooon Connoct
-2 For
-3 For
LOAD TERMINALS ON
OPTIONAL CIRCUIT
BREAKER
FIGURE
4-3.
POWER
CURRENT
TRANSFORMERS CT21,
CT22 AND CT23 (WHEN
PROVIDED) THE POLARITY
DOTS MUST BE DOWN.
OUTPUT BOX
4-5
Page 19
CONTROL
The generator set control panel box contains
WIRING
con­nection points for remote control and monitor op­tions.
These connection points are located on the engine control monitor board (ECM), the preheat/ time-delay module and the optional auxiliary relay board (ARB). (Note that if the optional ARB is installed,
no remote monitor connections are at-
tached to the ECM. The ARB provides all remote
monitor connection points.)
If the distance between the genset and the remote station Is less than 1000 feet (305 m), use 18 gauge stranded copper
wire.
If the distance is 1000 to 2000
feet (305 to 610 m), use 16 gauge stranded copper
wire.
Always run control circuit wiring in a separate metal conduit from AC power cables to avoid Induc­ing currents that could cause problems within the control.
IAWARNINGI HAZARDOUS VOLTAGE Touching
uninsulated live parts Inside the control panel box can result In severe personal Injury or death. Control wire Installation must be done
with care to avoid touching uninsulated live
parts.
For your protection, stand on a dry wooden plat­form or rubber Insulating mat, make sure your
clothing and shoes are dry, remove jewelry from your hands and use tools with Insulated han­dles.
ENGINE
MONITOR
BOARD
(ECM-A11)
The heart of the engine control system is the engine
monitor (A11). It is a printed circuit board assembly mounted on the back wall ofthe control box (Figure
4-4).
It starts and stops the engine in response to
the control panel switches, engine sensors and re-
mote control signals.
Remote Monitor Connections
The optional Detector 12 Control (12 light panel)
provides the capability of attaching a remote moni-
tor panel. Connections are made on the terminal block (TB2) located on the ECM board. See Page
11-3 for typical connections at TB2 of the ECM
board.
(If the optional ARB is
installed,
remote mon-
itor connections attach to the ARB, not the ECM.)
4-6
Page 20
TB1
5.
Is
s
o
Ft
o
KE
U3
18
A
: V—\
15A TBI-7.B*
Cl
CRI
a
R5
[ZZ
Ri
EZZ
5
ll R in iii
TBI
O
W8
2 LilB
W9
I
8 | 7 | 6 |
Kl
51|
TBS
PI
FLT
4 ||
K4
LJ
g|lN
K3
CR2
5» CONTROL
F4
K7
Wl
CR3 IZI
CRI
a
RA
CRS
CREB
VR3
a
IC10
RB R7 RG
ui
[ZZl
C3SR9
eg,
n ,
CRS
K12
CRB
a "
CRB
C5
C7
KM KIG KIB
CB
Rl
U3
U5
I I
V RH"
WG
W7
Kea
CRM
F5I
W5
s
B
CRIB 7 P3
V2
K5
CRIP
CRIP
1
8 3 4 5 6 7 B 9 IB 11 IE 13 H 15 IB
OUT)
CRI3
K9 Kll
OUT 1 LAMP OC i OS HET LOP PREHET
1
TEST
*
RESET
K13 KIS
CD
cr
LJ
O"'
3 || 2 || 1 |
1
K17
GO
CR17
•I
PRELOP SU OFF LET
PE
Li
cr
LJ
K19
CR7
OUT| SHUT
LOU FUEL
Q
l3
o
i
a
3
5
il
12
9 IB 11
Q
P4
FIGURE
4-4.
ENGINE
TB2
MONITOR
4-7
BOARD
(ECM)
!_•
Page 21
AUXILIARY
The following describes the design/functional crite­ria forthe auxiliary relay board (ARB) with a Detec-
tor-? or -12 Genset control. When provided, the
board is mounted on the right wall of the control box. See Figure 4-5. There are two versions of the ARB;
with and without the set of 12 Fault relays. Page
11-4 is a detailed connection diagram for the ARB.
RELAY
BOARD
(OPTIONAL)
• Jumper Position A (Run) - The relay oper­ates as a Run relay, energizing when SW B+ is applied from the engine monitor.
• Jumper Position B (Common Alarm) - The
relay operates as a Common Alarm relay. The relay energizes any time there is an engine shutdown.
gine.
This signal is provided from the en-
Terminal Blocks:
• TB1 - ARB TB1 and engine monitor identically numbered and provide the same re­mote control connection points. Note that
tional terminals are provided for terminals 5,7, and 10 of ARB TB1.
• TB2 through TBS - Connection points for re-
• lays Kl through K3. TB2 provides the N/O and N/C connections (three form 'C contacts for
each relay). TB3 through TB5 provide the com-
mon connection points (TB3 for
and TB5 for K3).
• TB6 and TB7 - Connection points for fault re­lays K4 through K15. Three terminals are pro­vided for each relay, which are labeled COM, N/C, N/O.
Plug-In Relays (Kl, K2, K3): The ARB can be
equipped with one to three 3-pole, double-throw re-
lays.
These relays plug-in relays for easy field addition and replace­ment.
Each relay can be operated as a RUN, COMMON
ALARM, jumper.
The relay contact ratings are:
• 10 amps at 28 VDC or 120 VAC, 80% PF
• 6 amps at 240 VAC, 80% PF
• 3 amps at 480 VAC, 80% PF
Jumper Positions for Plug-In Relays: Jumpers W1,
their respective relays,
K2, of 3 positions (A, B, C) independently of each other.
or ISOLATED COIL with the changing of a
W2 and W3 perform the same functions for
and W3 for relay K3. They can be located in any
(K1,
K2, K3) are field changeable
W1
for relay
K1,
K1,
TB1
are
addi-
TB4 for K2
W2 for relay
• Jumper Position C (Isolated) - The relay op­erates as an Isolated relay. The relay coil is en­ergized by a customer applied 6+ signal through the terminal block; TB3-1 for relay K1, TB4-1 for relay K2, and TB5-1 for relay K3.
Jumpers W11, W12, and W13 perform the same functions for their respective relays; W11 for relay
K1,
Wl 2 for relay K2, and W13 for relay K3. They
can be located in two different positions (A, B) inde-
pendently of one another.
• Jumper Position A - The relay operates iso-
lated from the board. The customer provides the circuit completion through terminal block; TB3 for relay for relay K3. The customer can operate the re-
lay with switched ground logic or use this relay in the middle of more complex logic circuits if
needed.
• Jumper Position B - The relays operate with the coils connected to ground through the
board connections. The coil will require a B+ signal to energize with the jumper in this
tion.
Fault Relays (K4 through K15):These optional re­lay modules are used to operate a remote alarm an-
nunciator that has an independent power source. This allows the use of either AC or DC for alarm drives. The relays are energized through the latch­ing relays on the engine monitor and provided N/O and N/C contacts for each extemal alarm connec­tion.
The 12 relays with form 'C contacts are rated:
• 10 Amp, 120 VAC
• 10 Amp. 30 VDC
K1,
TB4-5 for relay
K2,
and TB5-5
posi-
4-8
Page 22
JUMPERS
RUN RELAY MODULE(S)
JUMPERS
J1,
J2 WIRE
HARNESS PLUG
CONNECTIONS
FROM A11
Fl
K3
W13
O
K3
TBI
F2
F3
Kl
[KT
O
ua
o •—a ,
o-a • •
B
ca B
[_SW B+
o
l_B+
REMOTE START
TB2
LGND
comDN ALARM RUN
Kl
N/C N/O
B
cm am
N/C
N/O N/C N/O
cdn
A
WC
B cAn
K2
N/O N/C N/O N/C N/O
cin
cAn
A
N/C N/O N/C N/O N/C N/O
TBT
con
N/C N/O
con
N/C N/O
con
N/C N/Q
con
N/C N/O
con
N/C N/Q
con
I
RUN | I PRELOP | I PREHET | I LOP | I «1 | I OS | I OC I
con
N/C N/O
con
N/C N/O
con
N/C N/O
con
TB7
I FLTl
| |
FLTC
| I LET I I
LO FUEI
K3
-
B con
cm
N/C N/O
N/C N/O cm N/C N/O
I I
con
con
SM OFF
F5
A
O
N/C N/O
|
TBS,
TB7 AND
RELAYS K4
THROUGH K15
ARE OPTIONAL
M
ICS KS t7
FIGURE
4-5.
AUXILIARY
RELAY
4-9
JCIB.
BOARD
O
J(I3_
(ARB)
ICK
Page 23
PREHEAT/TIME-DELAY
MODULE (A15)
Remote Control
Connections
The start delay/preheat is adjustable from 1/2 to 15 seconds and the stop delay from 1 to 30 minutes. Turn the delay adjusting potentiometers clockwise
to increase delay and counterclockwise to de-
crease delay. Pre-heat occurs during the delayed start period and continues through cranking.
START DELAY
POTENTIOMETER
o
Remote control connections are made at
the
termi­nal block (TB1) that is located on the preheat/time­delay module (Figure
4-6).
Connect
one
or more re­mote switches across the remote terminal (TBI-5). ofthe preheat/time-delay module and the
B+
termi-
nal of the ECM (A11).
iSTOP DELAY
POTENTIOMETER
O-
IZZ]
O
A11-TB1-2
(DC DISCONNECT)
A11-TB1-3
A11-TB1-5
A11-TB1-7
(B+ OUT)
(RUN)
(GND)
I—I ,-, ,-,
r—i
TBI
4 5
i 1|
REMOTE
CONTROL RUN
SIGNAL
O
TB1-3 (SWITCHED B+)
K13-85 (PREHEAT)
A11-TB1-6 (RMT START)
A11-TB1-7 (B+ OUT)
HGURE
4-6.
PREHEAT/TIME-DELAY
4-10
MODULE
Page 24
BATTERY
CONNECTIONS
Starting the unit requires a 12 volt battery current.
Use one 12 volt battery for a nonnal installation
(Figure
4-7).
(Referto Section 2, Specifications tor
battery type.) Necessary batteiy cables and rack are on the unit.
Service battery as necessary. Infrequent use (as in emergency standby service), may allow battery to self-discharge to the point where it cannot start the unit. If installing an automatic transfer switch that
has no built-in charge circuit, connect a separate trickle charger. Onan automatic transfer switches can include an optional battery charging circuit.
IAWARNINGI Ignition of
can
cause severe personal Injury. Always
nect battery negative
IAWARNINGI Do not smoke while
batteries.
teries cause
Explosive gases are emitted
In
operation. Ignition
severe
personal injury.
explosive battery gases
con-
(-) last
to
prevent arcing.
servicing
the
from bat-
of
these gases
can
STARTER SOLENOID
CONNECT NEGATIVE CABLE TO CONVENIENT' BOLT ON ENGINE
CONNECTION MUST BE CLEAN AND PAINT-FREE
RGURE
4-7.
BATTERY
POSITIVE (+)
CONNECTION
STARTER
MOTOR
TWO,
6 VOLT
BATTERIES
CONNECTIONS
ESI 693
4-11
Page 25
5. Control Description
GENERAL
The following describes the function and operation ofthe standard Detector 7 and optional Detector 12 generator set control. All instruments and control
EMERGENCY STOP
PUSHBUTTON
PANEL LAMP
switches are located on the face of the control panel as illustrated in Figures
5-1
through 5-3. The control
panel description is separated into a DC portion for
monitoring the engine and an AC portion for moni-
toring the generator.
PREHEAT
RUN/STOP/REMOTE
SWITCH
RESET/LAMP
TEST/ PANEL
LAMP SWITCH
COOLANT
TEMPERATURE
GAUGE
FIGURE
5-1.
OIL PRESSURE
GAUGE
RUNNING
TIME METER
DC CONTROLS (DETECTOR 12 SHOWN)
5-1
DC INDICATOR
VOLTMETER LAMPS
Page 26
DC CONTROLS
Preheat/Reset/Lamp Test/Panel Lamp Switch:
Panel Lamp: Illuminates control panel.
Oil Pressure Gauge: Indicates pressure of cating oil in engine (wired to a sensor located on the engine).
Coolant Temperature Gauge: Indicates tempera­ture of circulating coolant in engine (wired to a sor located on engine).
DC Voltmeter: Indicates the battery charging sys-
tem voltage.
Run/Stop/Remote Switch:
• Push the switch to the Run position to start and run the generator set.
' • Push the switch to the Stop position to stop the
' set ( The switch must be in the Stop position
when the reset switch is used to restore gener­ator set operation following a fault shutdown,)*
; • Push the switch to the Remote position to allow
a remote eontrollerto automatically run the set.
Running Time Meter: Registers the total number of hours the unit has run. Use it to keep a record of periodic servicing. Time is cumulative; meter not be reset.
lubri-
sen-
can-
• Push the switch to the Preheat position (mo­mentary contact) to manually preheat the en-
gine combustion chambers before starting.
(This is normally accomplished automatically
by the preheat module inside the control box.)
• Push the switch to the Reset, Lamp Test
tion (momentary contact) to reset the engine control to restore operation following a fault
shutdown (the Run - Stop - Remote switch must be in the Stop position for reset to occur)
and to test the indicator
has a light which lights following a fault or emer-
gency shutdown. The light remains lit until the engine control has been reset.
' • Push the switch to the Panel Lamp position to
light the panel illumination lamp.
Emergency Stop Button (Optional): Push-in switch for emergency shutdown of the engine. The button lights up when it is pushed in. To reset, pull switch out and move Run/Stop/Remote switch to Stop position. Then push Preheat/Reset/Lamp Test/ Panel Lamp switch to Reset/Lamp Test
tion.
lamps.
Also,
posi-
this switch
posi-
5-2
Page 27
Detector7 Indicator Lamps ;The standard control panel has seven Indicator lamps which are de­scribed as follows:
• RUN (green) lamp comes on when starter cir­cuit opens after set starting.
• PRE LO OIL PRES (yellow) indicates engine oil pressure is marginally low.
• PRE HI ENG TEMP (yellow) indicates engine temperature is marginally high (or coolant level is low on optionally wired sets).
o
iemp
Tea*
• LO OIL PRES (red) indicates engine has shut down because of critically low oil pressure.
• HI ENG TEMP (red) indicates engine has shut down because of critically high engine
tem-
perature or low coolant level.
• OVERSPEED (red) indicates engine has shut down because of excessive speed.
• OVERCRANK (red) indicates engine has failed to start during the cranking period.
Detector 12 Indicator Lamps: Jhe optional twelve lamp control includes all the features of the seven lamp control plus the following:
• FAULT 1 (red) lamp indicates an undedicated fault. May be field programmed as a shutdown or non-shutdown, and as a timed or non-timed fault. (Normally set fbr timed shutdown).
• FAULT 2 (red) lamp indicates same features as Fault 1 (normally set for timed shutdown).
RUN IfflEtOOLPflBl jPBEHBMTBKj
OVBSIfED
MULTI BMJLT2
UWBIQTHi'l
10
WB.
2>
• LOW ENG TEMP (yellow) lamp lights if engine temperature is marginally low for starting. It may indicate an inoperative coolant heater.
• LO FUEL (yellow) indicates fuel supply is mar­ginally low.
. • SWITCH OFF (flashing red) indicates genera-
tor set is not in automatic start mode.
5-3
RGURE
5-2. INDICATOR
LAMPS
Page 28
EXCITATION-
FIELD BREAKER;
AC VOLTMETER AC AMMETER' FREQUENCY
METER
PHASE
SELECTOR
SWITCH
AC
CONTROLS
UPPER AND LOWER
SCALE INDICATOR
FIGURE
5-3.
AC Voltmeter (Optional): Dual range instrument indicating AC voltage. Measurement range in use shown on indicator lamp.
AC Ammeter (Optional): Dual range instrument indicates AC generator line current.
Frequency Meter
(Optional):
Indicates generator
output frequency in hertz.
Voltage Adjusting Rheostat: Provides approxi­mately plus or minus five percent adjustment of the rated output.voltage.
VOLTAGE
ADJUST
AC
CONTROLS
Upper and Lower Scale Indicator Lamps (Op­tional):
Indicates
which
scale
to
use
on
meter and ammeter.
Phase Selector Switch: Selects phases of erator output to be measured by AC voltmeter and ammeter.
Excitation Field Breaker: Provides generator ex-
citer and regulator protection from overheating in the event of certain failure modes of generator, ex-
citer and voltage regulator.
the
AC
gen-
volt-
5-4
Page 29
6.
Operation
Exhaust gases contain carbon monoxide, an odorless and colorless gas. Carbon monoxide Is poisonous and can cause unconsciousness and death. Symptoms of carbon monoxide poisoning can Include:
IAWARNINGI
EXHAUST GAS IS DEADLY!
• Dizziness
• Nausea
• Headache
Weakness
IF
YOU
GET OUT medical attention. Shut down the unit and do not operate until It has been Inspected and repaired.
Protection against carbon monoxide inhalation also Includes proper stallation and regular, frequent visual and audible Inspections of the complete exhaust sysfem.
This section describes generator set cluding pre-start checks, starting, running, and stopping the before starting the set. Be completely familiar with the set for safe operation.
IACAUTIONI Always disconnect a battery
charger from Its AC source before disconnect-
ing the battery cables. Otherwise, disconnect­ing the cables can result In voltage spikes high enough to damage the DC control circuits ofthe set
set.
Study this entire section carefully
OR ANYONE ELSE
INTO
GENERAL
and Sleepiness
EXPERIENCE
THE FRESH AIR
operation,
in-
IMMEDIATELY.
• Throbbing In Temples
• Muscular Twitching
• Vomiting
• Inability to Think Coherently ANY OF THESE
If symptoms persist, seek
IAWARNINGI Accidental starting of the generator
set while working on It can cause severe per-
sonal Injury or death. Prevent accidental start­ing by disconnecting the starting battery cables (negative [-] first).
Arcing can Ignite the explosive hydrogen gas given off by batteries, causing severe personal Injury. Arcing can occur If the negative (-) bat-
tery cable Is connected and a tool being used to
connect or disconnect the positive (+) battery
cable accidentally touches the frame or other grounded metal part of the set ing, always remove the negative (-) cable first, and reconnect It last
SYMPTOMS,
In-
To
prevent arc-
6-1
Page 30
PRESTART
CHECKS
Lubrication
Before starting, be sure the following chiecks have been made to the Maintenance section for the recommended procedures.
Ventilation
Verify all dir vents and ducts are open and free from any obstructions. Verify dampers, if used, operate properly.
Mechanical
Check for loose belts and fittings, leaking gaskets
and hoses, or any signs of mechanical damage. If any problems are found, have them corrected im-
mediately. „ •
Coolant
Check
fhe recommended coolant if low.
the
and
the
Checks
coolant
unit is ready for
level.
Fill
the cooling system with
operation.
Refer
Checkthe engine
possible to
Fuel
Make sure the fuel tank has sufficient fuel and that
the fuel system is primed.
DC
Electrical
Check the terminals on the batteries for clean and
tight connections. Loose or corroded connections
create resistance which can hinder and reconnect the battery cables if loose. Always disconnect both ends ofthe negative battery cable.
Reconnect tery terminal and the other
make
sure teiy ahd least likely to ignite explosive battery gases.
Fault Lamps: Push the Reset/Lamp switch on the control that
all
Replace any bulbs that are burned out.
the
one
that any
panel.
the
bulbs
oil
level.
Keep
dipstick
high
mark without Overfilling.
System
end
of the
arcing
All indicator lamps
are
on
cable will
and
end
be
then
the
oil
level
near as
starting.
to
the
negative bat-
to
ground.
away
should
release the switch.
This will
from
light.
Clean
the
bat-
Verify
6-2
Page 31
STARTING
The following sections cover the three methods used to start the generator set
IACAUTIONI Phase rotation of the genset and
utility must be the same. Equipment damage can occur. Check and reconnect as necessary.
Check the rotation of 3-phase motors before loading and reconnect If necessary.
IACAUTIONI Preheating the engine longer than
one minute before cranking the engine can de-
stroy the manifold heater and glow plugs, be-
cause there
is
no incoming airflow
to
cool them.
For this reason, do not exceed the one minute
preheat periods, to prevent heater burnout and
conserve the battery.
Preheat
The preheat circuit provides a signal during time
delayed start and during cranking to activate the
en-
gine glow plugs and the manifold heater.
Delayed Starting
The time delay start function precludes automatic start-up of the genset for a determined amount of time (1/2 to 15 seconds). It is used for installations that might experience power interuptions of short duration,
and not want the genset to start and also
for the preheat function noted above.
Starting at Control Panel
1.
Press the Preheat switch (Figure 6-1) to pre-
heat and hold it there for:
• One minute if the outdoor temperature is belowSSoF^C)
• Thirty seconds if the outdoor temperature is above 55° F (13° C)
In extreme cold (below 32° F [0° C]) it may be necessary to maintain preheating for two
min­utes after the engine starts, to obtain firing or smooth out cylinders, especially at no load or light loads.
2.
Release the Preheat switch and move the Run/
Stop/Remote switch to the RUN position. This activates the engine control system and the starting system. The starter will begin crank­ing,
and after a few
seconds,
the engine should
start. The starter will disconnect when the en-
gine speed reaches 450 to 570 r/min.
Ifthe engine does not start, the starter will dis­engage after a specified period of time and the control will indicate an overcrank
fault.
Genera-
tor sets with the standard overcrank control will
crank continuously for up to 75 seconds before disengaging the starter. Generator sets with the cycle cranking option will crank for 15 se­conds in each cycle until 3 cycles have been completed.
To clear an overcrank fault, place the Run/
Stop/Remote switch in the STOP position and momentarily depress the Reset switch. Wait
two minutes for the starter motor to
cool,
then repeat the starting procedure. If the engine does not run after a second attempt at start­ing,
refer to the Troubleshooting section.
IACAUTIONI Overvoltage will destroy the glow
plugs and air heater in 2 to 3 seconds. If extra power Is needed to start the set, connect an ad-
ditional 12 volt battery In parallel to the starting battery. Do not apply overvoltage to the starting circuit at any time.
Starting From Remote Location
Move the Run/Stop/Remote switch on the genset control panel to the REMOTE position. This allows the generator set to be started from a remote
switch.
Closing the remote switch initiates the start-
ing sequence described.in the previous section.
Automatic Starting and Stopping
Place the Run/Stop/Remote switch on the genera-
tor set DC panel in the REMOTE position if an auto-
matic transfer switch is
used.
This allows the trans­fer switch to start the generator set if a power outage occurs and stop it when the power returns.
6-3
Page 32
Cold
Starting
With
Loads
In addition to the following recommendations, the
RDJC generator set will require the installation of the constant glow plug kit. This will enable the set to start and accept a load within 10 seconds when am-
bient temperatures are above 40oF (40C).
In accordance with NFPA 110, Onan recommends installing diesel standby generator sets (life safety systems) equipped with coolant heaters in locations where the minimum ambient temperature is above 40oF (40C). NFPA also requires that the engine coolant be maintained at a minimum of 90oF (320C) and for most applications, accept the emergency
load in 10 seconds or less. Although most Onan generator sets will start in temperatures down to
-250F
(-320C)
when equipped with coolant heaters,
it might take some running time to warm the engine
up before a load can be applied when ambient
tem-
peratures are below 40oF (40C). The Low Engine Temperature (LET) lamp on the
Onan Detector 12 control is provided to meet the re­quirements of NFPA 110. The LET sensor alarms when the engine coolant temperature falls below 70oF (210C). In applications where the ambient temperature falls below 40oF (40C), the LET may be lit even though the coolant heaters are
nected.
Under these conditions, although the
con-
gen-
erator set may start, it may not be able to accept
load within 10 seconds. When this condition occurs, check the coolant heaters for proper operation. If the coolant heaters are operating properly, other
precautions might be necessary to warm the engine
before applying a
load.
AC VOLTMETER AC AMMETER
UPPER AND LOWER
SCALE INDICATOR
EXCITATION
RELD BREAKER
PHASE
SELECTOR
SWITCH
VOLTAGE
ADJUST
EMERGENCY STOP RUN/STOP/REMOTE PREHEAT
PUSH-BUTTON SWITCH RESET/LAMP
FREQUENCY V / TEST/PANEL
METER 1 PANEL LAMP / LAMP SWITCH
INDICATOR
LAMPS
RUNNING
TIME METER
COOLANT OILPRESSURE DC VOLTMETER
TEMPERATURE GAUGE
GAUGE
FIGURE
6-1.
CONTROL PANEL (DETECTOR 12 SHOWN)
6-4
Page 33
RUNNING
With the genset mnning, listen for any unusual
noises that may indicate mechanical problems and check the oil pressure frequently. Investigate any­thing that indicates possible mechanical problems.
Oil Pressure to 55 psi
Gauge:
(241
to 379 kPa) when the engine is at op-
The oil pressure should be 35
erating temperature. Coolant Temperature Gauge: The coolant
tem­perature should be 170° to 216° F (77° to 102° C) depending on the load and ambient temperature.
Before operating the genset under
load,
make cer­tain the genset will perform correctly by checking the following areas.
Exhaust
System
With the generator set operating, inspect the entire exhaust system visually and audibly including the exhaust
manifold,
mufflerand exhaust pipe and rain cap (if equipped). Check for leaks at all connec­tions,
welds, gaskets and joints and also make sure
that exhaust pipes are not heating surrounding ar-
eas excessively. If any leaks are detected, shut down the genset and have leaks corrected immedi­ately.
I AWARNING I Inhalation of exhaust gases can re-
sult In severe personal Injury or death. Be sure deadly exhaust gas Is piped outside and away
from any windows, doors or other Inlets to
building.
Fuel
System
With the generator set operating, inspect the fuel supply lines, return lines, filters and fittings for cracks and abrasions and make sure they are not rubbing against anything that could cause break­age.
If any leaks are
detected,
have them corrected
immediately.
IAWARNINGI Ignition of fuel can cause severe
personal Injury or death by fire or explosion. Do
not permit any flame, cigarette, spark, pilot
light, arcing equipment, switch or other Igniter near the fuel system.
Engine
Gauges
Check the following while the genset is operating.
Refer to Figure 6-1 for location of engine gauges.
DC Voltmeter: This is a voltage reference gauge, indicating condition of the batteries and also of bat­tery charging circuit. Gauge should read approxi-
mately 12 to 14 volts while genset is running. If reading is high or low, check batteries and the bat-
tery charging circuit.
Generator AC
Meters
(Optional)
Check the following meters while the genset is op­erating.
Refer to Figure 6-1 for location of the
gen-
erator AC meters.
Frequency Meter: The generator frequency should be stable and the reading should be the same as the nameplate rating (50 or 60 hz).
The generator frequency is a result of engine speed,
which is automatically controlled. Ifthe
gen­erator frequency is below specification, contact an authorized service center.
AC Voltmeter: Tum the phase selector switch to each line-to-line phase selection shown on the volts scale (L1-L2 on single phase gensets: L1-L2,
L2-L3,
and L3-L1 on three phase gensets). Read
the AC voltmeter using the upper or lower scale as
indicated by the scale indicator line-to-line voltage should be the same as the
light.
At no
load,
gen-
the
set nameplate rating. Ifthe reading is incorrect, re­fer to the Generator Voltage Adjustment procedure at the end of this section.
AC Ammeter: Tum the phase selector switch to
each phase selection shown on the amperes scale (L1 and L2 on single phase gensets;
L1,
L2 and L3 on three phase gensets). Read the ammeter using the upper or lower scale as indicated by the scale indicator light. At no
load,
the current readings
should be zero. With a load applied, each line cur-
rent should be approximately the same, and no line
current should exceed the genset nameplate rating.
6-5
Page 34
STOPPING
Emergency
Stop
(Optional)
Before Stopping
Run the genset at no load for three to five minutes
before stopping. This allows the lubricating oil and engine coolant to carry heat away from the combus­tion chamber and bearings.
Normal
Ifthe genset was started atthe genset control panel or at a remote control panel, move the Run/Stop/
Remote switch or remote starting switch to the STOP position. If the stop circuit ernor arm down to shut off fuel injection pump.
If the set was started by an automatic transfer switch, minutes after the normal power source returns. -
Time Delayed Stopping * The time delay stop function (adjustable from 0.5 to
15 minutes) provides for automatic cool-down mn­ning of the genset for a preset amount of time (approximately 3 to 5 minutes is recommended).
Stop
fails,
push the gov-
the genset will automatically stop about 15
An optional emergency stop button is located on the right side of control panel. Push the button in for emergency stop. Note that no fault indicators will light when the emergency button is used. To reset
the fault circuitry, pull the emergency stop button
out and move the Run/Stop/Remote switch to the Stop position. Then move the test switch to Reset/ Lamp Test position.
Engine
With the genset
switch in the Test position (see Figure 6-1). All cator lamps should light. Verify all of the lamps are on and then release the switch. Contact an Onan distributor if any lamps require replacement.
Mechanical
With the genset stopped, check for loose belts and fittings, leaking gaskets and hoses, or any signs of
mechanical damage. If any problems are found,
have them corrected immediately.
Monitor
stopped,
Checks
Indicator
hold the Reset/Lamp Test
Lamps
indi-
6-6
Page 35
BREAK-IN
Observe the following schedule for genset break-in:
1.
One half hour at 1/2
1.
One half hour at 3/4
3. Full
load.
During the first few hundred hours of
genset load should be at least 1/2 to full
load. load.
operation,
load.
Con-
the
tinuous operation below this load recommendation, can result in poor piston ring seating, causing high-
er-than-normal oil consumption and blowby.
• Condensation in the fuel and lubrication sys­tem,
causing contamination and/or corrosion
• Loss of protective oil film on moving engine parts
• Loss of engine fuel prime due to drain-back and/or evaporation
• Battery discharge due to internal and extemal current leakage
• Breakdown of generator insulation due to water absorption
Proper exercising does the following:
Drain and replace the crankcase oil afterthe first 50
hours of operation on new generator
sets.
Refer to
the Maintenance section ofthis manual forthe rec-
ommended procedures.
NO-LOAD
OPERATION
Periods of no-load operation should be held to a minimum.
If it is necessary to keep the engine
run­ning for long periods of time when no electric output is required, best engine performance will be ob-
tained by connecting a "dummy" electrical
load.
Such a load could consist of a heater element, etc.
EXERCISE
IACAUTIONI Improper exercising of the genera-
PERIOD
tor set may cause more damage than no exer­cising at all. Significant amounts of water and raw fuel will remain In the lubrication oil If the
unit Is run at a low operating temperatuie. Also,
operating the engine at no load or at low tem-
peratures causes carbon buildup and exhaust
system fouling. Continued operation In this manner may cause starting failure and/or en­gine damage. Exercising a generator set with-
out exercising Its associated controls and
switchgear does not test the operation of the
controls and switchgear. If the control systems
are not fully functional, the system may fall to provide power when required.
Infrequent use of the generator set can cause it to
deteriorate. The following can occur
• Elevates engine
oil
temperature to at least 180°
F (82.2° C)
• Evaporates water from engine lubrication sys­tem
• Re-establishes a protective oil film on engine parts
• Recharges battery to full normal potential
• Brings generatorto normal operating tempera­ture through load application
The generator set
should
be exercised at least once
each week; the engine oil temperature should be
held at 180° F (82.2° C) for at least 30 minutes dur-
ing this exercise. To exercise the generator set, do the following;
1.
Perform all required maintenance
checks,
start the unit, and apply a load (50 percent or more) by creating a simulated power
failure*.
This ex-
ercises the control and switchgear systems.
2.
Afterthe genset has reached its normal operat-
ing temperature, allow the genset to run an additional 30 minutes.
3. Shut the unit down by simulating the retum of normal power*. Run the set for approximately
three to five minutes with no load to allow the engine to cool down.
• This applies to a standby genset only. Other units should be started and loaded by control and load application sys-
tems normally associated with operation of the unit.
After each exercise period, refill the fuel tank and checkthe engine for leaks and overall
condition.
Lo-
cate the cause of any leaks and correct.
6-7
Page 36
HIGH
1.
Make certain that nothing obstmcts air flow to
and from the set.
2.
Be sure that the set location is properly venti-
lated.
3. Check the level of battery electrolyte fre­quently, and add approved water when neces­sary to maintain the proper level.
4.
Keep the cooling system clean and the radiator
filled,
and see that the fan belt tension is prop-
erly adjusted.
LOW
1.
Use the correct viscosity oil for the prevailing
temperature. Change oil only when the engine is warm. If an unexpected temperature drop causes an emergency, move the set to a warm location or apply externally heated air until the
oil flows freely (never use an open flame).
2.
Use fresh
condensation.
3. Keep the fuel system clean, and maintain the batteries in a well-charged condition.
4.
Use additional preheating for cold starts.
TEMPERATURES
TEMPERATURES
fuel,
and protect against moisture
DUST
1.
Keep the generator set and the codling system
clean.
2.
Service the air cleaner as frequently as neces-
sary
3. Change the crankcase oil every 100 operating hours.
Maximum power is reduced approximately 4 per-
cent for each 1000 feet (305 m) altitude.
The generator set power rating applies to sets used
in standby applications. The set will operate at the stated rating forthe duration of normal utility power
interruptions. The rating was established for a stan­dard radiator cooled set mnning on diesel fuel and operating at an altitude of 300 feet (92 m) with an ambient temperature of
relative to other applications, altitudes, cooling sys­tems, ized service center.
Keep the governor linkage clean.
HIGH
POWER
or ambient temperatures, contact an author-
AND DIRT
ALTITUDE
RATING
810 F
FACTORS
(27°^
C).
For a rating-
6-8
Page 37
7. Adjustments
GENERATOR
If the optional control panel-mounted potentiometer for adjusting the AC output (see Figure 7-1). Output voltage of nominal voltage Call your distributor be obtained
Move control panel to the Run position. Check the follow­ing conditions while
IAWARNINGI Use extreme caution when working
on electrical components. High voltages
cause Injury
damp clothing (particularly
skln surface
cal equipment
can be
by
the
Run/Stop/Remote switch
to be
VOLTAGE
ADJUSTMENT
AC
meters
adjusted plus
this adjustment.
or
death.
are
by
turning this potentiometer.
if the
the
damp when handling electri-
required voltage cannot
genset
Do not
CHECK AND
installed,
or
minus five percent
is
wet
an
extemal
is
provided
on the
operating.
wear jewelry
shoes) or allow
engine
can
or
1.
Move
2.
Move the Phase Selector
the
Phase Selector switch erator output current and voltage, and perform the following steps:
A. Insert a screwdriver into
just potentiometer located the genset control panel wrench carefully loosen
B. While observing
the screwdriver clockwise to increase volt-
age
or
counterclockwise
age,
and
adjust
voltage.
If correct voltage cannot
this adjustment, contact
center
tion.
for
assistance.
C. After setting
the locking change
the
the
voltmeter, slowly turn
to the
be
an
the
correct voltage, tighten
nut,
being careful
adjustment
switch
to
read
the
Voltage
on the
and
the
to
decrease volt-
rated nameplate
attained through
authorized service
to the Off
front
using
locking
not to
nut.
gen-
Ad-
of a
posi-
Onon
FIGURE
o
2s
VOLTAGE
ADJUST
7-1.
CONTROL
PANEL
o
(DETECTOR
o
12
SHOWN)
7-1
Page 38
GOVERNOR
The governor controls engine speed. On a 4 pole generator, engine speed equals frequency multi­plied by
30.
Thus 1800
rpm
generates 60 hertz. Pre­ferred engine speed does not vary more than 3 hertz from no-load to full-load operation. Be sure
that the throttle, linkage, and governor mechanism operate smoothly.
Speed
Adjustment
To change the governor speed, change the spring tension by turning the governor speed adjusting nut
(Figure 7-2). Turn the nut clockwise (more spring
tension) to increase rpm, or counterclockwise to re­duce govemed speed. Use a stroboscope or a fre­quency meter to make this adjustment.
Sensitivity
If the governor is too sensitive, a rapid Hunting
Adjustment
con­dition occurs (alternate increasing and decreasing speed).
Adjust the governor for maximum sensitiv-
ity without hunting. After making the sensitivity ad-
justment, readjust the speed. To adjust governor sensitivity (no-load to full-load
speed droop), tum the sensitivity adjusting ratchet as follows.
Radiator cooled Sets: Turning the ratchet clock-
wise provides more sensitivity (less speed drop
when full load is applied), and turning it counter-
clockwise provides less sensitivity (more speed drop).
City Water Cooled Sets: Turning the ratchet coun­terclockwise provides more sensitivity (less speed drop when full load is applied), and turning it clock­wise provides less sensitivity (more speed drop).
GOVERNOR
SHAFT
DECREASE
SENSITIVITY
SPEED
ADJUSTING
NUT
GOVERNOR
ARM
SENSITIVITY
ADJUSTING
RATCHET ^
GOVERNOR ARM
SPEED ADJUSTING
NUT AND LOCK NUT
RADIATOR COOLED SETS
INCREASE RPM
(Hold spring stud in
GOVERNOR
SPRING STUD
(SENSITIVITY
ADJUSTMENT)
TURN FOR
MINIMUM SPEED
DROP,
THEN
ADJUST SPEED CUT
GOVERNOR
/ SPEED
GOVERNOR
STUD
INCREASE
SENSITIVITY
TURN TO
position)
STUD
DECREASE
7-2
DECREASE
SENSITIVITY
FIGURE
INCREASE
SENSiriVITY SPEED
ADJUSTING NUT
CrTY WATER COOLED SETS
7-2. ADJUSTING
GOVERNOR
INCREASE
SPEED
Page 39
VALVE
CLEARANCE
ADJUSTMENTS
Check the valve clearance when the engine is at room temperature, about 70° F (21° C).
IACAUTIONI incorrect valve clearance adjust-
ment can lead to irrevocable damage to the gen­erator set. Make certain that only qualified per­sonnel perform this adjustment
1.
Tum the flywheel until the cylinder which is to
have its valve adjusted is on its compression stroke. On engines without a hand crank, use a socket wrench on the flywheel hex head screw. To determine if the cylinder is in its compres­sion stroke, observe the push rods as the en­gine is rotated in a clockwise haust valve push rod will be in its lowest tion,
and the intake valve push rod will be mov-
direction.
The ex-
posi-
ing downward. As the piston reaches top dead center, the flywheel timing mark should be aligned with the timing pointer, and the valve push rods should be stationary.
2.
Tum the flywheel an additional 10 to 45 de-
grees clockwise (estimated). When the piston
is in this position, it is in its power stroke, with both valves completely closed.
3. Check cylinder head-bolt torque prior to valve clearance adjustment. Torque values are listed in the Specifications section. Adjust valve clearance with the locknut which secures the rocker arm to the cylinder head (Rgure 7-3).
Loosen this locknut to increase clearance,
tighten it to reduce clearance.
4.
Using a feeler gauge, check the clearance be-
tween the rocker arm and the valve (Figure 7-4). Increase or decrease the clearance until the proper gap is established. Valve clear­ances are listed in the Specifications section.
VALVE ADJUST VALVE
SPRING CLEARANCE HERE
RETAINER
VALVE
SPRING
RGURE 7-3. VALVE CLEARANCE
ADJUSTMENTS
EXHAUST VALVES
ROCKER
ARM
VALVE
PUSH ROD
VALVE SEAT
VT1044
PCV VALVE
7-3
INTAKE
VALVES
VT1045
RGURE 7-4. CHECK VALVE CLEARANCE
Page 40
CENTRIFUGAL
SWITCH
The start-disconnect centrifugal switch (Figure 7-5) is located on the side ofthe
engine,
above the oil
fil-
ter. The switch opens when the engine stops, and
closes when engine speed reaches 900 essary, loosen the stationary contact point gap to
0.020
inch
(51
mm). Replace burned or
rpm.
and
adjust the
If nec-
faulty points.
IAWARNINGI High
vere
personal Injury or
breaker point
voltage,
gap.
Disconnect the battery cable,
which can cause se-
death,
Is present at the
negative (-) terminal first, before setting the
breaker point
CHARGE RATE
gap.
ADJUSTMENT
The adjustable resistor slide tap (Figure 7-6) in the charging circuit is set to produce a 2 ampere charg-
ing rate. This resistor is found in the generator air outlet. For applications requiring frequent starts, check the battery specific gravity periodically. If
necessary, increase the charging rate slightly
(move the slide tap up). Adjust this slide tap only when the engine is stopped.
FIGURE
COOLING
OUTLET
CHARGING
RESISTOR"
SET GAP AT
7-5.
CENTRIFUGAL
ADJUSTMENT
AIR
CENTRIFUGAL
BREAKER
POINTS
0.020
SWITCH
SWITCH
INCH
(51 mm)'
ESI 808
IAWARNINGI
plosion,
jury. Because
do not
producing devices In
Batteries
which
smoke
present the hazard of
can result In severe personal In-
batteries
or allow any
produce explosive gas,
flame, sparks,
the
battery area.
or arc-
ex-
Avoid overcharging the battery. Make small incre­ments of change until the proper rate has been de-
termined to keep the batteiy charged.
FIGURE
SLIDE
7-6.
CHARGING
TAP
ESI 971C
RESISTOR
Page 41
8. Troubleshooting
The generator set has sensors that continuously monitorthe engine for abnormal conditions, such as
low oil pressure or high coolant temperature. If these conditions occur, the engine monitor vates a fault lamp, and may also stop the engine
(depending on the
stopped forthis
restart the set after making adjustments or correc-
tions.
This section describes the fault condition sys-
tem,
and suggests troubleshooting procedures.
fhe standard seven light control has a single green
light to indicate
fault lights. The optional twelve-light control has a
single green light to indicate and seven red fault terminal connection for a customer supplied ble alarm, which sounds when a fault occurs.
SAFETY
High voltages are present inside the control box and generator output box when the set is mnning. Do not open the control box or generator output box while the set is mnning.
IAWARNINGI Contacting high voltage components
can cause electrocution, resulting In severe per­sonal Injury or covers In place during troubleshooting.
Generator set installations are normally designed for automatic starting or remote starting. When
troubleshooting a set that is shut down, make cer-
condition).
reason,
RUN,
death.
two amber lights and four red
lights.
CONSIDERATIONS
Keep control and output box
Ifthe generator set is
the operator may be able to
RUN,
Both controls also have a
four amber lights
acti-
audi-
tain the generator set cannot be accidentally re­started. STOP position and remove the negative battery ca­ble from the set starting battery.
IAWARNINGI Accidental starting of the generator set
during troubleshooting can cause severe personal injury or death. Disable the generator set before
troubleshooting.
When a fault lamp tums on during operation, follow the procedures listed below to locate and correct the problem. For any symptom not listed, contact
an authorized service center for assistance.
Resetting the Control
The external alarm and fault lamp may be deacti-
vated by moving the Run/Stop/Remote switch to
the Stop position and pressing the Reset/Lamp
Test/Preheat switch. Locate the problem and cor­rect it before restarting the set. While pressing the
Reset/Lamp Test/Preheat
all lamps light.
Line
The line circuit breaker mounts on the generator output box. If the load exceeds the circuit breaker current rating, the line circuit breaker venting the generator from being overloaded. If the circuit breaker trips, locate the source of the over­load and correct as necessary. Manually reset the breaker to reconnect the load to the generator.
Place the Run/Stop/Remote switch in the
Circuit
Breaker
switch,
(Optional)
make certain that
will
open, pre-
8-1
Page 42
TABLE
^WARNING: Many troubleshooting procedures present hazards which can result In severe personal
8-1.
TROUBLESHOOTING
Injuryordeath. Only qualified service personnel with knowledge of fuels, electricity, and machinery
SYMPTOM
1.
Green RUN lamp lights following engine
startup.
2.
PRE HI ENGINE TEMP lamp lights. En-
gine continues to operate.
3. HI ENG TEMP lamp lights. Engine shuts down.
CORRECTIVE
1.
Indicates all engine systems are normal. No correc-
tive action required.
2.
Indicates engine is operating near its capacity and
temperature has risen to approximately 220oF (104°
C)
or coolant level is low on optionally wired sets. If generator is powering non-critical and critical loads and cannot be shut down, use the following:
a. Reduce load if possible by turning off non-critical
loads.
b. Check air inlets and outlets and remove any ob-
structions to airflow. If engine can be stopped, follow procedure In
step 3.
3. Indicates engine has overheated (engine tempera­ture has risen above 230oF/110oC) or coolant level is
low. Allow engine to cool down completely before proceeding with the following checks:
a. Check coolant level and replenish if low. Look
for possible coolant leakage points and repair if necessary.
ACTION
4.
PRE LO OIL PRES lamp lights. Engine
continues to operate.
5. LO OIL PRES lamp lights. Engine shuts down.
NOTE: See also step 6.
b. Check for obstructions to cooling airflow and
correct as necessary.
c. Check for a slipping fan belt and tighten if loose.
d.
Reset control and restart after locating and cor-
recting problem. Contact an authorized service
center if none of the above.
4.
Indicates engine oil pressure has dropped to 20 psi
(138 kPa). If generator is powering critical loads and cannot be shut and then follow step 5 procedure. If engine can be stopped,
5. Indicates engine oil pressure has dropped to 14 psi (97kPa). is OK but oil level is low, replenish. Reset control and restart. Contact an authorized service center if oil pressure is 20 psi (138 kPa) or lower.
follow procedures in step 5.
Check
down,
oil
level,
wait until next shutdown period
lines
and
filters.
If oil system
8-2
Page 43
TABLE
8-1.
TROUBLESHOOTING
(continued)
IAWARNINGI Many troubleshooting
procedures present hazards which
Injuryordeath. Only qualified service personnel with
hazards
6. OVERCRANK lamp lights and engine
7. Engine mns and then shuts down,
should perform
SYMPTOM
stops cranking. or
Engine mns, shuts down, and LO OIL PRES lamp lights..
OVERSPEED lamp lights.
service procedures. Review
6. Indicates possible fuel system problem. a. Check for loss of engine prime, empty fuel tank,
fuel leaks, or plugged fuel lines and correct as
required.
b. Check for dirty fuel filter and replace if necessary
(see Maintenance section).
c. Check for dirty or plugged air filter and replace if
necessary (see Maintenance section).
d.
Reset the control and restart after correcting the
problem.
for service if none of the above.
7. Indicates engine has exceeded normal operating speed. service.
can
result
knowledge
safety
CORRECTIVE
Contact an authorized service center
Contact an authorized service center for
of
fuels, electricity,
precautions
ACTION
on
In
severe personal
and machinery
pages III and
iv.
*8.
SWITCH OFF lamp flashes.
*9.
LO FUEL lamp lights. Engine continues
to mn.
*10.LO FUEL LAMP lights. Engine shuts
down and LO OIL PRES lamp lights.
•11.
LO ENG TEMP lamp lights. Set is in
standby mode but is not operating. (Lamp lights when engine coolant
perature is 70° F the lamp goes out after the engine warms up, there should be no cause for
alarm even during initial generator set
operation.)
*12-Ught Control Only.
(210 C) or lower. Since
tem-
8. Indicates Run/Stop/Remote switch is in the Stop po­sition which will prevent automatic starting if matic transfer switch is used. Move the Run/Stop/ Remote switch to the Remote position for automatic starting.
9. Indicates diesel fuel supply is mnning low. Check fuel supply and replenish as required.
10.
Indicates engine has mn out of
and replenish as required.
11.
Indicates engine coolant heater is not operating, is
not circulating coolant, or ambient temperature has exceeded capability of heater. Check for the follow­ing conditions:
a. Coolant heater not connected to power supply.
Check for blown fuse or disconnected heater
cord and correct as required.
b. Check for low coolant level and replenish if re-
quired. and repair as required.
c. Contact an authorized service center if none of
the above.
Look for possible coolant leakage points
fuel.
Check fuel level
an
auto-
8-3
Page 44
TABLE
iAWARNING] Many troubleshooting procedures present hazards which can result In severe personal
8-1.
TROUBLESHOOTING (continued)
injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages III and Iv.
SYMPTOM
*12.
The FAULT 1 or FAULT 2 fault lamp
lights. engine runs for several seconds and then shuts run.
13.
Fault lamp lights but no fault exists. En-
gine gauges show oil pressure, engine temperature, and frequency (speed) are , within normal limits.
14.
Engine starts from generator control
15.
Engine will not crank.
Engine shuts down immediately,
down,
panel but will not start automatically or from a remote panel. (Note: The Run/ Stop/Remote switch must be in the Re-
mote position for automatic or remote
starting).
or engine continues to
CORRECTIVE
12.
The standard undesignated fault functions are pro-
grammed to shut down the set when a fault is sensed.
Fault 1 is time delayed while Fault 2 is immediate. The nature of the fault is an optional selection that is determined when the set installation is designed. The undesignated fault functions may also be pro­grammed for non-shutdown or non-time delay.
13.'
The monitor board or a sensor may be at fault.
tact an authorized service center for service.
14.
Remote circuit breaker is
restart. Contact an authorized service center if breaker trips after resetting.
15.
Indicates possible fault with control or starting sys-
tem.
Check for the following conditions:
ACTION
tripped.
Reset breaker and
Con-
16.
No AC output voltage.
17.
Green RUN lamp does not light follow-
ing engine startup.
* 12-Light Panel Only.
a. Fault lamp on. Correct fault and reset control. b. Poor battery cable connections. Clean the bat-
tery cable terminals and tighten all connections.
c. Discharged or defective battery. Recharge or
replace the battery.
d.
Emergency stop button (if equipped) pushed m.
To reset, pull switch put and move Run/Stop/Re­mote switch to Stop position. Then push test switch to Reset/ Lamp position.
e. Contact an authorized service center if none of
the above.
16.
Reid breaker is tripped. Reset breaker. Contact an
authorized service center if voltage buildup causes
breaker to trip.
17.
Indicates possible Start/Disconnect relay failure.
Contact an authorized service center for assistance.
8-4
Page 45
9.
Maintenance
GENERAL
Establish a maintenance/service schedule based on
the
type
of
application,
environment
service intervals. In extreme operating conditions, reduce the service intervals accordingly. Factors
that affect the maintenance schedule include the
following:
• Use for continuous duty (prime power)
• Extremes in ambient temperature
• Exposure to elements
• Exposure to salt water
• Exposure to windblown dust or sand
Consult is subject to extreme operating conditions, and de­termine a suitable maintenance
all service at the time period indicated, or after the number of operating hours indicated, whichever comes first. Use Table 9-1 to determine the re­quired maintenance. Refer tenance procedures.
The
Table
with
an authorized service center if the set
and
9-1
on the severity of the
lists
the
recommended
schedule.
to
this
section for
Perform
main-
IACAUTIONI Always disconnect a battery
charger ing the battery ing enough to damage the
set.
IAWARNINGI Accidental
set while sonal injury or ing (negative
Arcing can Ignite the explosive hydrogen gas
given off by Injury.
tery cable Is
connect or
cable accidentally touches the frame or other
grounded
ing, always remove the and
from
Its AC source before
cables. Otherwise,
the cables can result In voltage spikes
DC control
starting
working
by
disconnecting
[-]
first).
batteries, causing severe personal
Arcing can occur If
connected and a tool being
disconnect
metal part of
reconnect
on It can cause severe per-
death.
It last
Prevent
the starting battery cables
the
the positive (+) battery
the set. To
negative
disconnect-
disconnect-
circuits
of
the generator
accidental
negative (-) bat-
used to
prevent arc-
(-) cable first,
high
of the
start-
9-1
Page 46
TABLE
9-1. MAINTENANCE
SCHEDULE
HOURS OF OPERATION
8
50
too
200 500
MAINTENANCE TASK
• Inspect exhaust system
• Inspect generator set
• Check
• Check oil level
• See
• Check air cleaner; See
.. • Change crankcase oil
Clean
• Change crankcase oil (or annually); See
. • Clean sediment
pump; See
>
*r Replace oil
• Check
• Clean crankcase breather
• Check start-disconnect circuit
• Check valve
• Clean crankcase breather
fuel
supply; See
Note
2
governor linkage
bowl
Note
1
filter
battery
condition
clearances;
Note
1
Note
3
after
first 50 hours
and
filter
See
tube
on
Note
fuel
4
Note
3
transfer
600
1500
2000
3000
5000
1.
Water
2. Tighten head bolts and adjust valve clearance
3. Perform more
4. Contact an authorized
5. Check yearly on non-commercial
or
foreign
shows
water or should be replaced
overhauled
be
material
excessive
checked
following
engines,
often
arid
situation
correction of
and
in extremely dusty conditions.
service
• Change primary
• Check torsional washers for corrosion; See NoteS
• Grind valves (if required); See Ctiebk nozzle spray pattern; See Cleian generator
• Change sedondary
• General overhaul (if required); See
in
fuel
can ruin the injection
dirt
in
then
adjust valve
center for
sediment
corrected:
fuel
sets.
bowl,
Primary
contamination problem.
clearance
service.
fuel
filter
Note
fuel
filter
system.
fuel
handling
and
after
first 50 hours on new and
each
If daily inspection
and
storing facilities
secondary
500
hours
fuel
4
Note
4
Note
4
filters
can
thereafter.
9-2
Page 47
GENERATOR
During operation,
that could create unsafe
Section should
6 of
this manual covers
be
frequently inspected
be
SET
alert
INSPECTION
for
mechanical problems
or
hazardous conditions.
the
areas that
for
continued safe
operation.
LUBRICATION
The engine
oil was
drained from fore shipment. Before the initial system must classification
section
be
filled with
and
for
the lubricating
viscosity. Referto Specifications
SYSTEM
the
start,
oil of the
oil
capacity.
crankcase
be-
the lubrication
recommended
Oil Recommendations The
use of
with appropriate
are critical factors ance
quality engine lubricating oils combined
oil
drain
and
filter change intervals
in
maintaining engine perform-
and
durability.
Use SAE 15W40 oil that meets the American Petro­leum Institute
or
CE/SG.
(API)
Table
Classification CC/CD, CD/SG
9-2
shows the preferred
oil
grades
for ambient temperatures indicated.
climates, refer
mendations
IACAUTIONI Limited
such
as
10W-30 may be used
to
Table
for
extreme climates.
9-2 for oil
use of low
viscosity recom-
viscosity oils,
for
easier starting and providing sufficient oil flow at ambient tem­peratures below
ous
use of low
gine life
due to
23>
Ff-P C).
viscosity oils
However, continu-
can
decrease
en-
wean Referto the accompanying
chart.
In extremely dusty
or
dirty conditions,
oil
should
be changed more frequently. When adding oil between changes, gine.
use the
same brand
Various brands
as
already
of oil may not be
in the en-
compatible
when mixed.
TABLE 9-2.
OIL
VISCOSITY/TEMPERATURE
CHART
SOW
llllll
15W40
10W30,10W40
rrrr
CC/CD where CE
interval must given In
The use found
or
CD/SG engine oils
oil Is not yet
be
reduced
the
Maintenance Schedule.
of a
multi-viscosity lubricating
to
improve
oil
consumption control
prove engine cranking
maintaining lubrication
tures.
While 15W-40
can be
available,
to one
used
but the oil
half
the
oil
in
cold temperatures while
at
high operating tempera-
oil is
recommended
in
areas
change
Interval
has been
and im-
for
most
0
F-30-20-10
0
C-34
-29
-23
TTT
5W30
0 10 20 30 40 50 60 70 80 90
-18
-12
32
-7 -1 4 10 16 21 27 32 38 43 48
* PREFERRED SUMMER
100110120
9-3
Page 48
Engine
L
oil level below
mark. Overfilling
of the oil while
Oil
CAUTION
Level
l
Do not
the
operation
operate
LOW
mark
the
engine
or above
can cause foaming
below the ADD mark
with the
the FULL
or aeration
can cause loss of oil pressure.
Check the engine oil level during engine shutdown
periods at the intervals specified in the Mainte-
nance Schedule. The oil dipstick and oil fill are lo­cated on the side of the engine (Figure 9-1). The dipstick is stamped with FULL and LOW to indicate the level of
ings,
shut off
minutes
oil
in the crankcase. For accurate read-
the
engine and wait approximately 10
before
checking
the
oil
level.
This
allows oil
in the upper portion of the engine to drain back into
the crankcase. • ,
ALWAYS REPLACE CAP
TIGHTLY OR OIL
LEAKAGE MAY OCCUR
CAP AND OIL
LEVEL INDICATOR
CRANKCASE OIL
FULL / AT THIS LEVEL
NEVER OPERATE ENGINE WITH OIL
OIL FILL
TUBE
BELOW THIS LEVEL
KEEP
Keep the oil level as near as possible to the FULL mark on the
dipstick.
Remove
the
oil
fill
cap
and
add
oil of the same quality and brand when necessary.
FIGURE
9-1. OIL
LEVEL
LS11S1
INDICATOR
9-4
Page 49
Oil
Change
IAWARNINGI Hot
If It
Is spilled
and hands clear
plug and wear
crankcase oil can cause burns
or
splashed on skln. Keep fingers
when
removing the oil drain
protective clothing.
Change the oil and filter at the intervals recom-
mended in the Maintenance Schedule.
IAWARNINGI Used
fied by
some state
engine
or
oils
federal agencies
have
been Identi-
as
caus­ing cancer or reproductive toxicity. When checking
to
Ingest, breathe the fumes,
or
changing
engine
oil,
take care not
or contact used oil.
Check the oil level indicator after every 8 hours of
operation,
and maintain the oil level at the FULL mark (Rgure 9-3). Refer to the Specifications sec­tion for crankcase and filter capacity.
Oil Filter
Change
Stop the engine and drain the crankcase oil while
the engine is still hot. Place a pan under the drain
outlet and remove the oil drain plug or open the oil drain valve. After the oil is completely drained, re-
place the drain plug or close the drain valve. Re­place oil filter if necessary before adding oil.
Refill
with
oil
of
the
correct
API
designation
and
SAE viscosity grade forthe temperature conditions (refer to Table 9-2).
IAWARNINGI Hot
If It
Is spilled
crankcase
or
splashed
oil
can cause
on
skln.
Keep
burns
fingers and hands clear when removing the oil drain plug and wear protective
Place
a container under the
clothing.
oil
filter and remove the
filter by turning it counterclockwise. Clean the filter
mounting area. Coat the oil filter gasket with clean
oil.
To install the new
filter,
turn the fitter on clock­wise until the gasket touches the mounting base, then tighten 1/2 tum.
9-5
Page 50
FUEL
SYSTEM
Use only high-quality fuel in this generatorset. Fuel quality is important in obtaining dependable per­formance and satisfactory engine clean,
completely distilled, well refined, and non-
life.
Fuel must be
corrosive to fuel system parts.
IAWARNINGI Ignition of fuel can cause severe
personal Injury or death by fire or explosion. Do not permit any flame, cigarette, spark, pilot light, arcing equipment or other Igniter near the fuel system.
Fuel Recommendations Use ASTM 2-D (No. 2 Diesel) or ASTM 1 -D (No. 1
Diesel) fuel with a minimum Cetane number of 45. Number 2 diesel fuel gives the best economy and performance under most operating conditions. Use number 1 diesel fuel when ambient temperatures
are below 0° C (32° engine
load.
F),
or during long periods of light
The fuel's viscosity must be kept above 1.3 cSt to provide adequate fuel system lubrication.
temperature. (Cloud point is the temperature at
which wax crystals begin to form in diesel fuel.)
Fuel
Handling Precautions
Take appropriate precautions to prevent the en-
trance of dirt, water or other contaminants into the
fuel system. Filter or strain the fuel as the tank is
filled.
IACAUTIONI Due to the precise tolerances of die-
sel Injection systems, dirt or water In the fuel can cause severe damage to both the Injection
pump and Injector nozzles. Take special pre-
cautions
to
keep the fuel clean and free of water.
To avoid condensation problems, keep fuel tanks as full as possible. In cold weather,>warm fuel return-
ing from the engine heats the fuel in the supply tank,
If the fuel level is low, condensation tends to form in the upper portion of the tank. In warm weather, the fuel and the tank will both be warm during the day­time.
At night, cool air lowers the temperature of the
tank more rapidly than the temperature ofthe
fuel.
If the fuel level is low, the upper portion of the tank will cool more rapidly and condensation will tend to form.
Fuels with Cetane numbers higher than 45 may be needed In higher altitudes or when extremely low ambient temperatures are encountered to prevent misfires and resultant excessive smoke.
Use low-sulfur-content fuel with a cloud point at least 10 degrees below the lowest expected fuel
Condensation (water) can clog fuel filters as well as causing freezing problems. Also, water mixing with the sulfur in the ftiel forms acid which can corrode and damage engine parts.
9-6
Page 51
Fuel
Filters
The filters are drain is situated at the bottom ofthe filter case
spin-off,
throw-away units. A water
(Fig-
ure 9-2). This should be used to drain off moisture
either daily or at the end of every exercise period,
depending on unit application. The drain plug on the fuel filter can tolerate only a
limited amount of torque.
Use
two wrenches in com-
bination for breaking the plug loose and for final
tightening.
Change the primary and secondary fuel filters at the intervals recommended in the Maintenance Sched­ule.
Change the fuel filters by removing the washer
and capscrew on top of the fuel filter body.
CONNECTOR
(FROM FUEL
TRANSFER PUMP)
PRIMARY
FILTER
DRAIN
ELBOW (TO
INJECTION PUMP)
SECONDARY
FILTER
DRAIN
FS1113
Fuel
Pump Sediment Bowl
Remove the sediment bowl from the fuel filter body (Figure
9-3).
Clean out any contaminants from
sedi­ment bowl. When re-installing the sediment bowl, make sure that gasket and screen are in place.
FIGURE
FUEL PUMP AND
FILTER BODY
GASKET-
9-2. DUAL
FILTER
BOWL.
FUEL FILTERS
9-7
FIGURE
9-3.
FUEL
PUMP
SEDIMENT
FS1115
BOWL
Page 52
Priming the
Fuel
System
4.
Tighten the fuel line at the injection pump inlet.
The fuel system must be primed before initial startup or afterthe engine has run out of
fuel.
Prime
the fuel system as follows.
1.
Check fuel level in fuel tank and open shutoff
valve.
2.
Loosen the fuel filter-to-injection pump line at
the injection pump fuel inlet fitting (Figure 9-4).
3. Actuate the hand priming lever on the fuel transfer pump until the fuel flows from the fit­ting.
If the pump lobe of the camshaft is up (no re­striction can be felt when moving priming le­ver),
crank the engine one revolution to permit
hand priming:
ALWAYS RETURN
PRIMER LEVER TO
LOWEST POSITION
5. Actuate the hand priming lever several more times to prime the injection pump.
6. When finished, retum priming lever inward (disengaged position) to permit normal pump
operation.
WORK TRANSFER PUMP PRIMING
LEVER UNTIL FUEL FLOWS FROM
FUEL INLET FITTING
FIGURE
9-4.
FUEL
SYSTEM
FUEL INLET FITTING
TO INJECTION PUMP
FUEL
RETURN;
LINE
FS1777
9-8
Page 53
AIR CLEANERS
IACAUTIONI
to prevent
Filters should
damage.
If the filter
be
handled with
does
care
become
damaged. Install recommended replacement
part
After every
50
hours of
operation,
remove
and
clean the filter element (Figure 9-5). After washing the element
in
solvent,
dip the
element
in
engine
oil
and
squeeze it as dry as possible.
CONTRACTOR
1.
Remove
pre-cleaner
MODEL AIR
(Figure
9-6)
CLEANER
and
wash
out
dirt. Dry and reinstall.
2.
Loosen clamp and remove end cover.
3. Remove thumbscrew and take out element. Wash
element
element after 6
4.
Remove
in
detergent
washings).
air cleaner
baffle
and
water
(use
Dry and reinstall.
from
cover,
wash
new
out
dirt, and reinstall in cover.
5. Install cover
with
"TOP" up and tighten clamp.
ELEMENT
HGURE
COVER
9-5.
POLYURETHANE
CLEANER
DUST
THUMBSCREW
\_
CLAMP
RETAINER
FOAM
(PRE-CLEANER)
^
AIR
CUP
HI 770
9-9
HGURE
FS18S3C
9-6. CONTRACTOR MODEL AIR
CLEANER
Page 54
GOVERNOR
LINKAGE
Every 100 nor ball joints apart
these
IACAUTIONI Some solvents can damage the
neoprene governor ball joints. Read the facturer's lubricants or
hours,
carefully
and
joints.
See Figure 9-7.
recommendations
solvents
pull
clean
near
the neoprene gover-
them.
Do not lubricate
manu-
before using any
the
ball joints.
FIGURE
9-7. GOVERNOR
CLEAN
BALL
BALL
JOINT
*FS1114
JOINT
Page 55
BATTERIES
IAWARNINGI Ignition of explosive battery gases
can cause severe personal Injury. Do not smoke or allow any source of Ignition while servicing batteries.
Check the condition ofthe starting battery at the in­terval specified in the maintenance schedule. To prevent dangerous arcing, always disconnect the negative ground strap from the battery before work­ing on any part of the electrical system or the en­gine.
Disregard the sections on Checking Specific Gravity and Checking Electrolyte Level if using a "maintenance-free" battery.
Be sure the vent plugs are tight to prevent cleaning solution from entering the cells.
After cleaning, flush the outside of the battery and surrounding areas with clean water.
Keep the battery terminals clean and tight. After making connections, coat the terminals with a light application of petroleum jelly or non-conductive grease to retard corrosion.
Checking
Specific
Gravity
Use a battery hydrometer to check the specific
gravity of the electrolyte in each battery
cell.
IAWARNINGI Arcing can Ignite the explosive hy-
drogen gas given off by batteries, causing se-
vere personal Injury. Arcing can occur If the negative (-) battery cable Is connected and a tool being used to connect or disconnect the
positive (+) battery cable accidentally touches
the frame or other grounded metal part of the set. To prevent arcing, always remove the nega­tive (-) cable first, and reconnect It last.
IACAUTIONI Always disconnect a battery
charger from Its AC source before disconnect­ing the battery cables. Otherwise, disconnect­ing the cables can result In voltage spikes high enough to damage the DC control circuits ofthe set.
Cleaning
Batteries
Keep the batteries clean by wiping them with a
damp cloth whenever dirt appears excessive.
If corrosion is present around the terminal connec-
tions,
remove battery cables and wash the termi­nals with an ammonia solution or a solution consist­ing of 1/4 pound of baking soda added to 1 quart of water.
Hold the hydrometer vertical and take the reading. Correct the reading by adding four gravity points (0.004) for every ten degrees the electrolyte perature is above 80° F (27°
C).
A fully charged bat­tery will have a corrected specific gravity of Charge the battery if the reading is below
Checking
IACAUTIONI DO not add water In freezing
Electrolyte
Level
tem-
1.260.
1.215.
weather unless the engine will run long enough
(two to three hours) to assure a thorough mix-
ing of water and electrolyte.
Check the level of the electrolyte (acid and water solution) in the batteries at least every 200 hours of operation.
Fill
the battery cells to the bottom ofthe filler neck, if cells are low on water, add distilled water and re­charge. If one cell is low, check case for leaks. Keep the battery case clean and dry. An accumula­tion of moisture will lead to a more rapid discharge and battery failure.
9-11
Page 56
CRANKCASE BREATHER
Clean the crankcase breather at the intervals rec-
ommended in the Maintenance Schedule.
BREATHER
HOSE
To clean the crankcase breather, remove hose clamp, breather
hose,
breather
cap
clamp
and
insu-
lator halves to release breather cap and valve as-
sembly (Figure
9-8).
Wash
cap,
valve assembly and
baffle in suitable solvent. Dry and reinstall.
CRANKCASE BREATHER TUBE
Clean the crankcase breather tube at the intervals recommended in the Maintenance Schedule.
To
clean the crankcase breather rocker covers (Figure is installed with a sealant
9-9).
on
tube,
remove both
The breather tube itself
the threads to prevent
oil leakage into the intake manifold; it should NOT
be removed. A small wire, nail or drill bit inserted
through from the top can be used to clean out the breather hole. The breather hole seldom needs cleaning.
A 500 hour interval coincides with the valve lash adjustments, because the rocker box covers must also be removed at that time.
c
HOSE CLAMP_
CAP AND VALVE.
O-RING
FILTER
BREATHER
TUBE
FIGURE 9-8. CRANKCASE BREATHER
CLEAN CRANKCASE
BREATHER PIPE
EVERY 500 HOURS
SCREEN
RETAINER
CLAMP
OIL BAFFLE
ASSEMBLY
LS1206C
CRANKCASE
BREATHER
TUBE
9-42
cion
FIGURE 9-9. CLEANING BREATHER
Page 57
Four
TORSIONAL
torsional
washer assemblies are bolted inside
WASHERS
the flywheel pulley hub (Figure 9-10). When func­tioning properly, they react to relieve torsion
stresses on the crankshaft. Inspect the assemblies periodically for movement of washers and freedom from corrosion (1500 hours commercial, yearly non-commercial): If condition is questionable,
con-
tact an Onan service center or distributor.
FIGURE
9-10. TORSION
WASHER
ASSEMBLY
9-13
Page 58
OUT-OF-SERVICE
The inherent lubricating qualities of normally should protect the cylinders of a diesel en­gine for at least 30 days when the unit is not in serv­ice.
To protect an engine that will be out of service
for more than 30 days, proceed as follows:
1.
Exercise the generator set as described in the
Operation section until the engine is up to oper-
ating temperature.
2.
Shut down the engine. Disconnect battery and
store in a charger every 30 days to maintain it at full charge.
3. Drain the oil base while it is still warm. Refill and attach a waming tag indicating the viscos-, ity of oil used. - ' „
4. Service the-air cleaner.' ' , -
5. Clean throttle and governor linkage and protect by wrapping with a clean cloth.
6. Plug the intake and exhaust outlets to prevent entrance of moisture, bugs, dirt, etc.
7. Clean and wipe the entire unit. Coat parts sus­ceptible to rust with a light coat of grease or
8. Provide a suitable cover for the enti re unit after unit has cooled down.
cool,
dry place. Connect battery to a
PROTECTION
No.
2 diesei fuel
oil.
RETURNING A UNIT
1.
Remove the cover and all protective wrapping.
Remove the plug from the intake and exhaust
outlet.
2.
Check the warning tag on the oil base and ver-
ify that the oil viscosity is still correct for the ex­isting ambient temperature.
3. Clean cooling fin areas.
4.
Clean and check the battery. Measure the spe-
cific gravity (1.260 at 80° F [27° C]) and verify that the level is at the split gravity is low, charge until the correct value is obtained. and charge until the specific gravity is correct.
DO NOT OVERCHARGE.
- IAWARNINGI Ignition of explosive battery gases can cause severe personal Injury. Do
^ pot smoke or allow any Ignition source
while servicing batteries.
5. Connect the starting battery (ground terminal last).
6. Prime the fuel system.
7. Remove all loads before starting the engine.
8. Start engine and observe oil pressure gauge and charge rate ammeter.
9. After start, apply load to at least 50 percent of rated capacity.
10.
Unit is ready for service and load may be ap-
plied.
Ifthe level is low, add distilled water
TO
SERVICE
ring.
If the specific
,
Page 59
10.
Maintenance
Record
Keep a record of all periodic and unscheduled maintenance. Record the service date and the number of operating hours from the hour
DATE
HOUR
METER
READING
meter.
Referto the Maintenance Schedule in Section 8 for
the
time
interval between maintenance procedures.
Record
center and keep all of your service receipts.
SERVICE
the
name
PERFORMED / NOTES
and
address of your Onan service
Record the name, address, and phone number of
your authorized Onan service center.
10-1
Page 60
Page 61
11.
Wiring
GENERAL • Page 11-3-Customer Connections at the En-
Diagrams
gine Monitor Board.
This section consists ofthe schematic
tion
wiring diagrams
lowing drawings are
referenced
included.
in the
• Page 11-5-Generator Reconnection Diagram
and
connec- • Page
text. The
fol- •
11
-4-Customer Connections at the Aux-
liary Relay Board
-
11-1
Page 62
TB1-10 (SWfTCHED B+ OUTPUT) OUTPUT TO RELAY K12, FUSED AT 20 AMPS, ENERGIZED WHEN THE
START SIGNAL IS APPLIED AND DE-ENERGIZED AT SHUTDOWN (NORMAL AND FAULT)
TBI-9 (B+ INPUT) BATTERY POSITIVE (+) CONNECTION
TB1-8 (START SOLENOID) OUTPUT TO RELAY
K11,
FUSED AT 20 AMPS
TBI-7 (B+ OUTPUT) OUTPUT TO TIME DELAY START/STOP MODULE Al 5,
FUSED AT 15 AMPS, AVAILABLE WHEN THE STARTING BATTERIES ARE CONNECTED
TB1-6 (REMOTE START) CONNECTED TO TIME DELAY START/STOP MODULE A15. CONNECT REMOTE START
CONTACT OF THE AUTOMATIC TRANSFER SWITCH TO TERMINAL
TB1
-5 OF MODULE A15.
TB1-5
(GROUND)
TB1-4 (COMMON ALARM B+ OUTPUT) 4 AMP RATED DEVICE MAXIMUM
TBI-3 (RUN) CONNECTED TO TIME DELAY START/STOP MODULE A15
TBI-2 (DC DISCONNECT) CONNECTED TO TIME DELAY START/STOP MODULE Al
5
5*
COKTROL
R
Ul
C8
C3
• R9 I
1
U3
U5
VR2
KB
K7
R10
cne
-
CR17
•1
U2
DBD
iq
CR9
C5
C7
Kll
a
CRB
CRG
+
ID
5:
LJ
H
(Zl
a CRIB
KIG
W4
rj
n
CRI a
um um
Wl
Kl K5
CRI?
CRI?
LJ
"l
g 3 1 5 6 7 8 ~9~ IB 15 H H 15 IB
CR3
^
™ I
CR5
CREB
VR3
KIB
KB Kll K13 K15
L_l
I
CR13
dl
K]2
RB R7 RG
_n_
I
3
W
WG
W7
Dffl
KIB
K17
15 13
K22
•1
CRII CRIE
K19
CD
LJ
Lu
F5
A
US
9 IB II 12
1 5 3 4 5 6
7
P3
8 9
IB li
15
PA
THIS
IS A
REPRESENTATIVE SCHEMATIC/WIRING TROUBLESHOOTING,
IWIRING
•NCLUDED
DIAGRAM
WITH
PACKAGE
YOUR
TB2-10 (PRE-HIGH ENGINE TEMPERATURE WARNING) GROUND OUTPUT TO LIGHT/RELAY*
(GENERIC)
DIAGRAM. FOR
REFER
TO
THE
THAT WAS
GENSET.
TB2-1 (FAULT 2) GROUND INPUT FROM SENDER
TB2-2 (FAULT 2) GROUND OUTPUT TO LIGHT/RELAY*
TB2-3 (FAULT 1) GROUND INPUT FROM SENDER
TB2-4 (FAULT 1) GROUND OUTPUT TO LIGHT/RELAY*
TB2-5 (REMOTE RESET) MOMENTARY CONTACT TO GROUND
TB2-6 (OVERCRANK FAULT) GROUND OUTPUT TO LIGHT/RELAY*
TB2-7 (OVERSPEED FAULT) GROUND OUTPUT TO LIGHT/RELAY*
TB2-8 (HIGH ENGINE TEMPERATURE FAULT) GROUND OUTPUT TO LIGHT/RELAY*
TB2-9 (LOW OIL PRESSURE FAULT) GROUND OUTPUT TO LIGHT/RELAY*
TB2-11 (PRE-LOW OIL PRESSURE WARNING) GROUND OUTPUT TO LIGHT/RELAY*
TB2-12 (SWITCH OFF WARNING) GROUND OUTPUT TO LIGHT/RELAY*
TB2-13 (LOW ENGINE TEMPERATURE WARNING) GROUND OUTPUT TO LIGHT/RELAY*
TB2-14 (LOW FUEL WARNING) GROUND INPUT FROM SENDER
CUSTOMER
* 0.5 AMP
SUPPLIED
FACTORY
RATED
DEVICE
P2
WIRING
WIRING
MAXIMUM
TB2-16 (EMERGENCY SHUT DOWN) MOMENTARY CONTACT TO GROUND
CUSTOMER
TB2-15 (LOW FUEL WARNING) GROUND OUTPUT TO LIGHT/RELAY*
CONNECTIONS AT THE
ENGINE
MONITOR
BOARD
11-3
Page 63
TB2
9
RUN
3
N/C
_
j_
<2
N/O
N/C
._L.
9
COMMON ALARM
N/O I N/C N/O
9 9
9
H/O
NA:
._3..
9 9
N/O
H/C
._L.
._L.
9 9 9
p
3
ISOLATED
N/C N/O
._3..
N/O
._3._.
9 i
mi-TBi-io
All-TBI-4
AII-IBI-5
HII-IBI-7
Aii-iai-6
AU-1B1-3
All-TBZ-11 AII-TB2-10
a b*
COn
cm
ISA B«
mr
START
HH
PIOLOP
PRETCT
SPflRE
J2r.
I I
n
TB!
r 1
94 I
su
I
con
ALMHI
RUN
1
isn Bt
RNT
START
TBG con N/C N/O
r ! 9 9 9
K4.2
K<.
ttl — .
4
2
1
TB3
6 o
con
i
9
K5.2
K5.
I
4^
con
2
o 9 9
KS.2
K6.
con
3
1
O
N/O
9-
9
Wl 1
K7. SfLL
4^
k'2
1
/Ts /T\
f
COM
3
9
O
Q
N/C
o
_
6
con
2
o o
om
i
N/C
:
Q
9
Cil
o
9
W12
T
o i
TB7 con
7
r
sa*-
K9.2
2
9
2
W3
/T\
/t\ /K
• o
t
TBS
G
4J"
COM
I
0. 9
8 _t
con
Q
-lie
B
O
cm
3
9 9
con O
W13
i4
• t
9
Q
2
K15.2
Q
9
4¥P
K9.
1
1
L
CH-
4>
4}
1
A1I-TB2-3 All-TBZ-B A1I-TB2-7 AII-TB2-6 AII-TB2-1 AII-IB2-2 AI1-TB2-I3 AII-TB2-IS AII-TB2-I2
LOP ICT OS OC
FLT I
TLT 2
LET LO FUL SM OFF
Jl
I 1 I
THE
TERMINALS
IN THE SHADED
BOXES
ARE
FOR CUSTOMER CONNECTIONS
CUSTOMER
CONNECTIONS AT THE AUXILIARY
11-4
RELAY
THIS
IS A
REPRESENTATIVE SCHEMATIC/WIRING TROUBLESHOOTING,
WIRING
INCLUDED
DIAGRAM
WITH
PACKAGE
YOUR
BOARD
(GENERIC)
DIAGRAM.
REFER
TO THE
THAT
GENSET.
FOR
WAS
Page 64
3 PHASE RECONNECTABLE,
12
LEAD
YD
GENERATORS
I PHASE RECONNECTABLE,
12
LEAD
THIS
IS A REPRESENTATIVE SCHEMATIC/WIRING TROUBLESHOOTING, WIRING DIAGRAM INCLUDED
WITH
PACKAGE
YOUR
(GENERIC)
DIAGRAM. FOR
REFER
TO THE THAT WAS
GENSET.
60HZ
•SOHZ
60HZ
SOHZ
SECONDARY CURRENT TRANSFORMER CONN.
I20/240V.
IP0/200V, V4-VI II0/220V, V4-VI II5/230V. V4-V2 I20/240V, V4-V3
120V, V4-VI
V4-VI
I
PHASE
SECONDARY CURRENT TRANSFORMER CONN.
L
T3
8
L4
IOOV. V4-VI IIOV, V4-VI I
15V.
V4-V2
120V. V4-V3
RECONNECTABLE, 4 LEAD
1-3
I20/240V.
I
ttJl
tfl
I00/200V, V4-VI II0/220V. V4-VI II5/230V. V4-V2 I20/240V, V4-V3
1-3
I20/208V, I27/220V. I39/240V,
I IO/l90V, V4-VI II5/220V, V4-V2 I20/208V. V4-V3 I27/220V, V4-V4
V4-VI
V4-VI V4-V2 V4-V/t
CT2I
Ll
LO
L4
60HZ
- SOHZ
SECONDARY CURRENT TRANSFORMER CONN.
240/416V, V4-VI 254/440V, V4-V2 277/480V, V4-V4
220/380V, V4-VI 230/400V, V4-V2 240/416V. V4-V3 254/440V, V4-V4
VOLTAGE CONTROL
1-2
INPUT
TB2I
-21
-23
-24
-25
-26
SENSING
GENERATOR
SENSING
LEADS
8 7 4 6 6 5 5
CONTINUITY
347/600 CONNECT SENSING
LEADS
TO 8 7
:-
"
SECONDARY CURRENT
TRANSFORMER CONN.
I20/240V, V4-VI
:I0/220V, V4-VI II5/230V. V4-V2 I20/240V. V4-V3
1-3
— 60HZ
- 50HZ
NOTES:
1.
CURRENT TRANSFORMER SECONDARY
ABOVE 300 VOLTS AC, BELOW
300 VOLTS AC,
TERMINALS
2.
DESIGNATIONS
WIRE IN
ACCORDANCE LEAD VR2I-5 REGULATOR
3.
WHEN
INSTALLED JUMPER
4.
GENERATOR VOLTAGE
CONNECTED
2/3
ARE COMMON AND
V4-VI.-V2
ON
VOLTAGE REGULATOR,
FROM
FOR
WITH
XI-I
OUTPUT VOLTAGE
MUST
SOHZ. THESE
ONLY.
300-0688
IS REMOVED
SWITCHING
ON
VR2I
BETWEEN
FOR 60 HZ.
SENSING
TO
GENERATOR OUTPUT LEADS AND VOLTAGE REGUALATOR LIEU
OF
MARKING
AS
FOLLOWS: GEN-4 GEN-5 GEN-6 RED/BLK GEN-7 GEN-8
INSULATE
AND
347/600V
SECONDARY CURRENT TRANSFORMER CONN, i-2
MUST
BE TERMINALS I & 2 TERMINALS I &,
CONNECTED
OR -V3
BE
RECONNECTED
INDICATE
VR2I.
JUMPER
INSTRUCTIONS
MANUALLY
;
3. TO
CONNECTION
AND
FREQUENCY.
TO
VR2I-6
APPLY
GROUND.
MUST
TO
REGUALTOR IS USED. A JUMPER
TBI-7
LEADS
AND
TBI-8
FOR
GEN-4,-5,-6,-7, &,
AS SHOWN FOR
OPERATION.
LT
GRN/BLK
LEADS
MAY BE
TAN/BLK YEL/BLK
DK
BLU/BLK
TIE
BACK
ANY
UNUSED
LEADS.
V4-VI
60HZ
SELECTED:
OF
BE
JUMPER
CONNECTED
ALSO.
FOR
60HZ
300-1540
IS
SOHZ.
THIS
-8
MUST
PROPER
COLOR CODED IN
NO. REV. MODIFIED 12/1/93
THE
OR
BE
METERING
625-2758 1 ot 1
A
RECONNECTION
11-5
DIAGRAMS
Page 65
Loading...