Onan GRCA Service Manual

Page 1
Caution: This document contains mixed page sizes (8.5 x 11 or 11 x
17), which may affect printing. Please adjust your printer settings according to the size of each page you wish to print.
Page 2
Printed in U. S. A.
Installation Manual
184-0177
July, 2004
Service Manual
Page 3
Redistribution or publication of this document,
by any means, is strictly prohibited.
Page 4
Supplement 965−1081 Date: 12-2004 Insert with-
Titles: GRCA Installation Manual
GRCA Service Manual
Numbers: 184−0169, dated May, 2004
184−0177, dated July, 2004
This supplement updates the GRCA Installation Manual and GRCA Service Manual to include infor­mation on the RSZ transfer switch time delay relay.
TIME DELAY RELAY
Beginning in April of 2004, GRCA generator sets include a transfer switch time delay relay.
This relay eliminated a loss of start signal that sometimes occured on earlier models during transfer from normal to emergency power. Without this relay, the genset may not start as commanded during a loss of power or when testing the transfer switch.
If your genset does not include this relay, kit 307−3040 can be purchased separately.
NOTE: The wiring diagram provided with the
transfer switch shows connections of this relay to a genset, incorrectly indi­cating that terminals 1 and 5 are nor­mally open contacts. As shown in the illustrations, the normally open con­tacts are terminals 5 and 6.
CHANGES TO MANUALS
GRCA Installation Manual (184−0169) − Replace Figures 7-3, 7-4, 7-5, and 7-6 with the attached pages.
GRCA Service Manual (184−0177) − Replace page 11-2 with the attached page.
Page 1 of 7
Page 5
Page 2 of 7
Page 6
7-3
No. 306-4692 Sh 2 of 2 Rev. C Mod Sys: Pro-E Modified 7/2004
WITH TIME DELAY RELAY
FIGURE 7-3. RSZ 100-AMP NEMA-1 TRANSFER SWITCH
Page 7
7-4
No. 306-4693 Sh 2 of 2 Rev. C Mod Sys: Pro-E Modified 7/2004
WITH TIME DELAY RELAY
RSZ 200-AMP NEMA-1 TRANSFER SWITCH
Page 8
7-5
No. 306-4694 Sh 2 of 2 Rev. C Mod Sys: Pro-E Modified 7/2004
WITH TIME DELAY RELAY
RSZ 100-AMP NEMA-3R TRANSFER SWITCH
Page 9
7-6
No. 306-4695 Sh 2 of 2 Rev. C Mod Sys: Pro-E Modified 7/2004
WITH TIME DELAY RELAY
RSZ 200-AMP NEMA-3R TRANSFER SWITCH
Page 10
No. 630-2252 Sh 1 of 6 Rev. D Mod Sys: Pro-E Modified 6/2004
TIME DELAY RELAY
TIME DELAY RELAY
ADD
WIRE
5
NO Contacts To Genset Remote Start Terminals
6
Battery Positive (+)
Battery Negative (−)
Genset & Charger Battery Positive
(+)
Genset & Charger Battery Negative
(−)
TRANSFER SWITCH INTERCONNECTION WIRING DIAGRAM
11-2
Page 11
Table of Contents
i
SECTION TITLE PAGE
SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1–1
About this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1–1
2 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–1
3 OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–1
Engine Oil Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–1
Starting Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–1
Fuel Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–1
Fuel Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–1
Genset Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–2
Starting and Stopping the Genset . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–4
Powering Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–5
Varying Operating Conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–8
Genset Break–In. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–9
Genset Exercise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–9
Genset Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–9
4 PERIODIC MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–1
General Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–2
Checking Engine Oil Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–3
Changing Engine Oil and Oil Filter. . . . . . . . . . . . . . . . . . . . . . . . . . . 4–4
Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–5
Spark Plugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–6
Battery Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–7
5 PREPARATIONS FOR SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–1
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–1
Special Tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–2
Removing and Installing the Housing Panels. . . . . . . . . . . . . . . . . . . 5–3
Accessing the Engine for Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–5
Redistribution or publication of this document,
by any means, is strictly prohibited.
Page 12
Redistribution or publication of this document,
by any means, is strictly prohibited.
SECTION TITLE PAGE
6 ENGINE SUBSYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–1
Cylinder Compression Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–1
Valve Clearance (Lash) Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . 6–2
Exhaust System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–3
Ignition System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–4
Magnetic Pickup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–5
Governor Rod and Actuator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–6
Fuel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–8
7 GENERATOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–1
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–1
Servicing Brushes and Slip Rings . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–2
Generator Disassembly/Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–3
Testing the Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–8
8 GENSET CONTROL PCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8–1
9 GOVERNOR CONTROLLER BOARD (A12) . . . . . . . . . . . . . . . . . . . . 9–1
10 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10–1
Status/Diagnostics Light on the Genset Control Switch. . . . . . . . . . 10–1
Fault Code Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10–1
Displaying Level One/Two Fault Codes . . . . . . . . . . . . . . . . . . . . . . 10–1
11 WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11–1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11–1
ii
Page 13
Thoroughly read the OPERATOR’S MANUAL before operating the genset. Safe operation and top performance can be obtained only when equipment is operated and maintained properly.
The following symbols in this manual alert you to potential hazards to the operator, service person and equipment.
alerts you to an immediate hazard which will result in severe personal injury or death.
alerts you to a hazard or unsafe practice which can result in severe personal injury or death.
alerts you to a hazard or unsafe practice which can result in personal injury or equipment damage.
Electricity, fuel, exhaust, batteries and moving parts present hazards which can result in severe personal injury or death.
GENERAL PRECAUTIONS
• Keep ABC fire extinguishers handy.
• Make sure all fasteners are secure and torqued properly.
• Keep the genset and its compartment clean. Excess oil and oily rags can catch fire. Dirt and gear stowed in the compartment can restrict cooling air.
• Before working on the genset, disconnect the negative (–) battery cable at the battery to prevent starting.
• Use caution when making adjustments while the genset is running—hot, moving or electri­cally live parts can cause severe personal injury or death.
• Used engine oil has been identified by some state and federal agencies as causing cancer
or reproductive toxicity. Do not ingest, inhale, or contact used oil or its vapors.
• Do not work on the genset when mentally or physically fatigued or after consuming alco­hol or drugs.
• Carefully follow all applicable local, state and federal codes.
GENERATOR VOLTAGE IS DEADLY!
• Generator output connections must be made by a qualified electrician in accordance with applicable codes.
• The genset must not be connected to the public utility or any other source of electrical power. Connection could lead to electrocu­tion of utility workers and damage to equip­ment. An approved switching device must be used to prevent interconnections.
• Use caution when working on live electrical equipment. Remove jewelry, make sure clothing and shoes are dry and stand on a dry wooden platform.
FUEL IS FLAMMABLE AND EXPLOSIVE
• Keep flames, cigarettes, sparks, pilot lights, electrical arc-producing equipment and switches and all other sources of ignition well away from areas where fuel fumes are pres­ent and areas sharing ventilation.
• Fuel lines must be secured, free of leaks and separated or shielded from electrical wiring.
Leaks can lead to explosive accumulations of
gas. Natural gas rises when released and can accumulate under hoods and inside housings and buildings. LPG sinks when released and can accumulate inside hous­ings and basements and other below-grade spaces. Prevent leaks and the accumulation of gas.
iii
Redistribution or publication of this document,
by any means, is strictly prohibited.
DANGER
!
WARNING
!
CAUTION
!
Safety Precautions
Page 14
ENGINE EXHAUST IS DEADLY!
• Learn the symptoms of carbon monoxide poi­soning in this manual.
• The exhaust system must be installed in accordance with the genset Installation Manual.
• Do not use engine cooling air to heat a room or compartment.
• Make sure there is ample fresh air when operating the genset in a confined area.
BATTERY GAS IS EXPLOSIVE
Wear safety glasses and do not smoke while
servicing batteries.
When disconnecting the battery cables,
always check for a battery charger and dis­connect it first then disconnect the negative (–) battery cable.
When reconnecting battery cables, always
reconnect the negative (–) battery cable after the positive (+) cable, then reconnect the battery charger to reduce arcing.
MOVING PARTS CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH
• Do not wear loose clothing or jewelry near moving parts such as fans.
• Keep hands away from moving parts.
• Keep guards in place over fans.
iv
Redistribution or publication of this document,
by any means, is strictly prohibited.
HS-1
Page 15
ABOUT THIS MANUAL
This is the Service Manual for the Series GRCA generator set (genset). Read and carefully observe all of the instructions and precautions in this manual. For quick reference, this manual includes Operation and Periodic Maintenance, which are also covered in the Operator’s Manual.
See the Parts Catalog for part identification num­bers. Genuine Onan® replacement parts are rec­ommended for best results. When contacting Onan for parts, service or product information, be ready to provide the model number and the serial number, both of which appear on the genset nameplate (Figure 1-1). (The serial number is in the row marked “S/N”, just below the model num­ber. The last character of the model number is the specification letter, which is important for obtain­ing the right parts.)
Improper service or parts replace­ment can lead to severe personal injury or death and to damage to equipment and prop­erty. Service personnel must be qualified to perform electrical and mechanical service.
Unauthorized modifications or replacement of fuel, exhaust, air intake or speed control system components that affect engine emissions are prohibited by law in the State of California.
See the Installation Manual for important recom­mendations concerning the installation and for a list of the installation codes and standards for safety which may be applicable.
1-1
Redistribution or publication of this document,
by any means, is strictly prohibited.
1. Introduction
WARNING
!
WARNING
!
12GRCA-4229
Page 16
1-2
Redistribution or publication of this document,
by any means, is strictly prohibited.
THIS PAGE LEFT INTENTIONALLY BLANK
Page 17
2-1
Redistribution or publication of this document,
by any means, is strictly prohibited.
2. Specifications
GENERATOR SET GRCA:
Fuel Type Natural Gas LP Vapor Rated Power 9 kW 11 kW Frequency 60 Hertz Voltage 120/240 volts Circuit Breaker Rating 2-Pole, 50 amperes Speed 3600 RPM
FUEL CONSUMPTION: ft.
3
/ hr BTU/hr ft.3/ hr BTU/hr
Quarter load 72 74,736 38 97,166 Half-load 101 104,838 47 120,179 Threee Quarter Load 133 138,054 60 153,420 Full-load 184 190,992 73 186,661
Natural Gas Supply Pressure 7-11" WC (water column) (178–279 mm)
LP Supply Pressure (vapor) 9-13" WC (water column) (228-330 mm) Gas Supply Connection 3/4 inch NPT 3/4 inch NPT
ENGINE: Honda GX670 90 Degree V-Twin, 4 Stroke, OH Valve 2 Cylinder, Specifications available in your Honda Owners Manual
Bore 3.03 inch (77 mm) Stroke 2.83 inch (72 mm) Displacement 40.9 inch
3
(670 cc) Oil Capacity (with filter)* 1.48 Qt (1.4 Liter) Intake Valve Clearance (Cold) .006 + .001 inch (.15 +.02 mm) Exhaust Valve Clearance (Cold) .008 + .001 inch (.20 +.02 mm) Spark Gap .012 - .016 inch (.030 - .040 mm)
Cylinder compression pressure 85 - 114 lbf/in
2
(6.0 - 8.0 kg/cm2) at 500 rpm
CRANKING SYSTEM:
Nominal Battery Voltage (BCI, GP 26) 12 volts Battery Cranking Capacity 530 CCA @ 0° F (-17° C) Nominal Battery Charging Output 6 amperes Fuse F1 (control B+ input circuit) 10 amperes
ENCLOSURE:
Control Features Lighted Run-Off-Auto Switch, Running Time Meter, 50 Amp UL Listed Circuit
Breaker, DC Control Fuse. Large User Connection Area
Enclosure Features Sound Attenuated Drip-Proof Design, less than 70 dBA at 23 ft. (7M), Easy Service
Access, Internal Starting Battery Tray and Tie-Down, Heavy Duty Exterior High
Performance Fluoropolymer Finish Coat System Exhaust Silencer Exhaust Silencer, Insulated for Low Noise and heat Installation Features Pre-Mounted UV Resistant Plastic Installation Base, Convenient Electrical and
Gas Supply Connections, Ground Anchor System for Base Included Unit Dimensions 45 in (1143 mm) Length, 34 inch (864 mm) Width, 39 inch (986 mm) Height
(Including installation base) Weight 575 Pounds (261 kg) Sound Level at Full Load Less than 70 dBA at 23 ft. (7 m)
ENGINE PART TOLERANCES AND CLEARANCES
Refer to your Honda Owners Manual - Part # 0031-ZN1-6011
* See Periodic Maintenance for oil filling instructions.
-
-
-
-
Page 18
2-2
Redistribution or publication of this document,
by any means, is strictly prohibited.
THREAD TORQUES
Bolt torques are in lb-ft (N-m)* Rotor Through-Bolt 32.5 ± 2.5 (45 ± 3) Stator Feet to Base 16-20 (22-27) Adapter-Engine Mounting Screws 12 (16) Adapter-Generator Mounting Screws 25-35 (34-47) Rear Vibration Isolators
Center Screw 30-35 (41-47)
Flange to Drip Tray Screws 16-20 (22-27) Stator Studs to Engine Adaptor Finger tight Stator Nuts 30 (41)
Front Vibration Isolators
Center Screw 30-35 (41-47)
Flange to Drip Tray Screws 16-20 (22-27)
Engine to Mounting Plate 30-35 (41-47) Skidbase to Pallet 16-22 (22-27) Spark Plug 13 (18)
* - Use engine oil as a lubricant for all threads EXCEPT for spark plug and rotor through-bolt threads.
Page 19
3-1
Redistribution or publication of this document,
by any means, is strictly prohibited.
Engine Oil Recommendations
Oil is a major factor affecting performance and service life. Use 4-stroke automotive detergent oil that is designed for engines operating on LPG or NATURAL GAS.
(The table below are examples of oils that meet Honda’s requirements for LPG/NATURAL GAS­fueled engines.) SAE 30 (API service classifica­tion SJ) is recommended for general use. For operation in temperatures below 32
0
F (00C), 5W-30 sythetic oil may be used for easier starting. Do not use 5W-30 synthetic oil when the air tem­perature is above 32
0
F (00C). Units are shipped
with 10W-30 Oil.
STARTING BATTERY
This genset has a 12 VDC starting battery and control system. See Specifications in Section 2 for minimum battery requirements for genset cranking.
FUEL RECOMMENDATIONS
Fuels are flammable and explo­sive and can cause severe personal injury or death. Do not smoke if you smell gas or are near fuel tanks or fuel-burning equipment or are in an area sharing ventilation with such equipment. Keep flames, sparks, pilot lights,
arc-producing equipment, switches, and all other sources of ignition well away. Keep a type ABC fire extinguisher handy.
NFPA Standard No. 58 requires all persons handling and operating LP to be trained in proper handling and operating procedures.
When natural gas is the required fuel, use com­mercially available natural gas fuel having a methane content of at least 90 percent (by vol­ume).
When LP (liquified petroleum) is the required fuel, use grade HD–5 or equivalent consisting of at least 90 percent propane. Commercial LP may contain more than 2.5 percent butane, which can result in poor fuel vaporization and poor engine starting in ambient temperatures below 32° F (0° C).
Satisfactory performance requires that fuel be supplied at a pressure within the range indicated in Specifications.
High gas supply pressure can cause gas leaks which can lead to fire and severe personal injury or death. Gas supply pressure must be adjusted to Specifications in Section 2 by qualified personnel.
FUEL SELECTION
The natural gas/LP vapor genset leaves the fac­tory set up for natural gas. If the genset is to be run on LP vapor it must be converted for use with LP vapor. See NG/LP Vapor Fuel System in Installation Manual.
A genset purchased to use natural gas or LP vapor cannot be converted to use LP liquid.
Wrong fuel selection can result in hard starting, poor genset performance, and fault shutdown.
3. Operation
WARNING
!
CAUTION
!
WARNING
!
Page 20
GENSET CONTROL
Figure 3-1 shows the genset control panel. The control features are as follows:
Control Switch This is a three-position Run- Off-Auto switch with a status/diagnostics light.
The Run and Off positions are for manual start­ing and stopping of the genset. The Off position is also used for resetting the controller following a
fault shutdown. The Auto position is for remote start or transfer switch control.
Status/Diagnostics Light – This is an LED (light emitting diode) in the control switch. It blinks rap­idly during cranking. It blinks in a coded fashion to indicate the nature of a genset shut down. See Troubleshooting in Section 11.
Hour Meter – The hour meter records the total running time of the genset. It cannot be reset.
3-2
Redistribution or publication of this document,
by any means, is strictly prohibited.
20 A FUSE
CONTROL SWITCH
RUN
OFF
AUTO
CIRCUIT BREAKER
STATUS/DIAGNOSTIC
LIGHT
HOUR METER
FIGURE 3–1. GENSET CONTROL
Page 21
3-3
Redistribution or publication of this document,
by any means, is strictly prohibited.
FIGURE 3–2. GRCA GENSET
Page 22
3-4
Redistribution or publication of this document,
by any means, is strictly prohibited.
STARTING AND STOPPING THE GENSET
Pre-start Checks
Perform the maintenance checks instructed in General Inspection (See page 4-2). Service the genset and make repairs as required if a fault shutdown code displays (see Troubleshooting in Section 11). Also, see Genset Break-In and Genset Storage in this section before placing in service a new or rebuilt genset or one that has been in storage.
Manual Starting
Push the control switch to Run. The engine should crank, start, and run up to governed speed in approximately 15 seconds. The starter discon­nects automatically as the status light stops blink­ing.
If the engine does not start (after 20 seconds of cranking), the starter disengages. See Trouble- shooting in Section 11 if the engine does not start.
Check for fuel and exhaust leaks. Stop the genset immediately if there is a fuel or exhaust leak and have it repaired before continuing operation.
Whenever possible, allow the engine to warm up for a few minutes before connecting the electrical loads.
Manual Stopping
Push the control switch to Off. Whenever possi­ble, allow the engine to cool down with the elec­trical loads disconnected for a few minutes before stopping the genset.
Failure to push the control switch to AUTO before leaving the genset renders the genset unavailable for automatic standby service.
Automatic Starting and Stopping
Push the control switch to Auto for remote, auto­matic starting and stopping (transfer switch).
Automatic startup of the genset while performing maintenance or service can cause severe personal injury or death. Push the control switch to Off and disconnect the negative (–) battery cable from the battery to keep the genset from cranking and starting while working on it.
WARNING
!
EXHAUST GAS IS DEADLY!
All engine exhaust contains carbon monoxide, an odorless, colorless, poisonous gas that can cause unconsciousness and death. Symptoms of carbon monoxide poisoning include
Dizziness Nausea
Headache Vomiting
Weakness and Sleepiness Inability to Think Coherently
IF YOU EXPERIENCE ANY OF THESE SYMPTOMS, GET INTO FRESH AIR IMMEDIATELY. If symp­toms persist, seek medical attention. Shut down the genset and do not operate it until it has been inspected and repaired.
The exhaust system is an integral part of the genset. Do not modify the exhaust system. Make sure there is ample fresh air when operating the genset in a confined area.
WARNING
!
CAUTION
!
Page 23
3-5
Redistribution or publication of this document,
by any means, is strictly prohibited.
POWERING EQUIPMENT
Genset Loading
How much electrical equipment (system load) can be connected at one time depends upon how much power is available from the genset (See Specifications, Section 2) and the type of load being supplied. If the genset is “overloaded,” it’s circuit breaker trips or it’s controller shuts it down or both.
Determine how much equipment can be operated at one time by adding the power consumption rat­ings of the individual system loads that are likely to be used at the same time. Compare the sum of the loads to the kW (kilowatt) rating of the genset. Note that 1 kW = 1000 watts. See Table 3-2 for power consumption of typical residential appliances.
Note that when a genset is loaded nearly to full power and one of the large motor loads (such as
an air conditioner) “cycles on,” an undervoltage or under frequency fault shutdown (Code Numbers 13 and 15) could occur. The reason is that for a brief moment, at startup, motors can draw up to three or more times their rated power consump­tion. You may, therefore, have to consider shut­ting off some loads at times when large motor loads are “On.” When powering large motor loads (such as an air conditioner) it is recommended that the total load should not exceed 80% of the genset kW rating.
Operating at High Altitude or High Temperature
Air density is less at higher altitudes, resulting in less available engine power. Power decreases approximately 3.5 percent of rated power each 1000 feet (305 meters) of increase in elevation above sea level. Power also decreases approxi­mately 1.5 percent each 10°F (5.5°C) increase in ambient temperature above 77°F (25°C).
Page 24
3-6
Redistribution or publication of this document,
by any means, is strictly prohibited.
TABLE 3–2. TYPICAL APPLIANCE POWER CONSUMPTION
Appliance Typical Watts Basic Loads Loads Chosen
Basic Needs
Electric Lighting - N=Number of 100 W Bulbs N 100 W Bulbs N x 100 =
Furnace - Gas 750
Electric Heat (See Heater Nameplate) 2000-5000
Well Pump - 1/2 HP 1000
Well Pump - 1 HP 2000
Refrigerator - 20 Cu. Ft. 800
Heat Pump 5000
Electric Water Heater 5000
Security System 20
Freezer - 20 Cu. Ft. 550
Sump Pump 1/3 HP 500
Garage Door Opener - 1/3 HP 500
Garage Door Opener - 1/2 HP 720
Typical Discretionary Loads
Microwave Oven - 800 Watt 1200
Microwave Oven - 1000 Watt 1500
Coffee Maker 900
Dishwasher 1400
Toaster 900
Computer 250
Electric Range - Two Burners 2900
Electric Range - Oven 7500
TV - 13” Color 70
TV - 32" Color 170
VCR 60
Stereo System 140
Electric Iron 1100
Electric Clothes Dryer 6000
Gas Clothes Dryer 720
Washing Machine 1000
Electric Hair Dryer 1600
Air Conditioner - 1 Ton 2000
Air Conditioner - 2 Ton 3000
Window A/C - 17,800 BTU 2000
Ceiling Fan 100
Vacuum Cleaner 780
Central Vacuum 1750
Total Basic Loads:
Total Chosen Loads:
Total Power Requirement:
Page 25
How To Use the Table
Table 3-2 lists the typical power consumption of some common household appliances. The value in the table is a typical value, check the value on the nameplate of your appliance for the most accurate value. Also, you may want to use appli­ances that are not listed in the table. In that case, use the value on the nameplate of the appliance for its power consumption. For the most accurate genset loading, substitute the values from the nameplates on the appliances for all calculations.
Select the appliances that satisfy your basic needs and write the power consumption in the Basic Loads column. Add the power consumption of all Basic Loads and place it in the Total Basic Loads box at the bottom of the table.
Compare the Basic Loads Total with the rated output of the genset. If the genset still has addi­tional capacity (that is the Basic Loads Total is less than 80% of the genset capacity), you can select additional loads from the list. Write the power consumption of these additional loads in the Loads Chosen column. Add the power con­sumption of all Chosen Loads and place it in the Total Chosen Loads box at the bottom of the table. You can add loads to the Basic Loads until you reach 80% of the genset capacity.
Example
Using the chart on the previous page for a genset rated at 10 kW. Select a total load less than 8kW (8000 watts) in order to operate within the 80% limit.
Well Pump (1/2 HP) 1000
Refrigerator 800
Air Conditioner (2 ton) 2000
10 100 watt Bulbs 1000
Sump Pump (1/3 HP) 500
Microwave Oven (1000 W) 1500
Coffee Maker 900
Total 7700
This example uses 7700 watts. You could still safely use a TV, a small appliance, or even your computer before you exceed the 80% limit.
Remember that some loads are intermittent. For example your refrigerator does not run constantly. However, as it starts it requires considerably more current than when it is running. For the sake of the calculation from the table assume that all loads are constant. If total power consumption exceeds genset power output, the genset may shut down. In this case, you may have to operate some loads in sequence, one after another, rather than all at the same time.
If the load on the genset exceeds the rated capac­ity of the genset, the genset shuts down. If the genset shuts down under load, remove loads by turning off appliances, press the switch on the control to OFF and back to AUTO to allow auto­matic remote restarting.
3-7
Redistribution or publication of this document,
by any means, is strictly prohibited.
Page 26
3-8
Redistribution or publication of this document,
by any means, is strictly prohibited.
Restarting The Genset
If the genset shuts down because it is over­loaded, disconnect or turn off as many loads (appliances) as possible and try to restart the genset as instructed in Starting and Stopping in this section. Reconnect the loads one by one up to 80% of the genset rating.
Resetting Circuit Breakers
If a circuit breaker in the main power distribution panel or on the genset (see Figure 3-1) trips, there is either a short circuit or too many loads operating at the same time. Note that the genset continues to run after a circuit breaker trips.
If a circuit breaker trips, disconnect or turn off as many loads (appliances) as possible and reset the circuit breaker. If the circuit breaker trips right away, either the main distribution system has a short or the circuit breaker is faulty.
If the circuit breaker does not trip, reconnect the loads, one by one, up to 80% of the genset rating. If a circuit breaker trips right away when a load is connected, the load probably has a short.
Connecting The System To Utility Power
An approved device such as an automatic trans­fer switch must be provided to keep the genset and utility from being interconnected. The auto­matic transfer switch automatically reconnects the utility when service is restored.
Interconnecting the genset and the public utility (or any other power source) can lead to the electrocution of utility workers and damage to equipment and fire. An approved switching device must be used to prevent interconnections.
VARYING OPERATING CONDITIONS
Cold Weather
Perform maintenance due according to Periodic Maintenance in Section 4. See Engine Oil Recommendations in this section.
An optional thermostatically controlled heater for the battery is recommended for more reliable starting in ambient temperatures down to -0° F (-17.6°C). Genset may crank longer before starting compared to warmer conditions. This is normal.
Hot Weather
Perform maintenance according to Table 4–1 of Periodic Maintenance. Make sure nothing blocks airflow to and from the genset. Keep the cooling fins clean.
High Altitude
See Powering Equipment in this section for infor- mation on how altitude affects the maximum power output of the genset.
Dusty Conditions
Keep the cooling fins clean. Perform air cleaner maintenance and change engine oil and oil filter more often than usual. See Periodic Maintenance in Section 4.
WARNING
!
Page 27
Redistribution or publication of this document,
by any means, is strictly prohibited.
3-9
GENSET BREAK-IN
Proper engine break-in on a new genset or on one with a rebuilt engine is essential for top engine performance and acceptable oil consump­tion. For proper break-in, run the genset at 1/2 rated power for the first 2 hours and then at 3/4 rated power for 2 more hours. Avoid light load or no load operation during break in. See Powering Equipment in this section.
Proper engine oil and oil level are especially criti­cal during break-in because of the higher engine temperatures that can be expected. See Engine Oil Recommendations in this section. Check the oil level twice a day or every 4 hours during the first 24 hours of operation and change the oil after the first 25 hours of operation.
GENSET EXERCISE
If genset use is infrequent, it is recommended that the genset be exercised at least 1/2 hour, once a month, without load. Exercising the genset drives off moisture, re-lubricates the engine, and removes oxide from electrical contacts and gener­ator slip rings, thereby promoting better starting, more reliable operation, and longer engine life.
An operator can exercise the genset by placing the control switch in the ON position. The genset would start and run at no load for a time deter­mined by the operator. When the exercise period is finished, return the control switch to the AUTO position.
Failure to push the control switch to AUTO before leaving the genset renders the genset unavailable for automatic standby service.
When a transfer switch with an exerciser clock is available, set the clock to exercise the genset once a month for 1/2 hour at no load.
See the transfer switch operator’s manual for instructions on how to adjust and activate the genset exerciser clock.
GENSET STORAGE
If the genset is to be stored for 120 days or longer, proper storage is essential for preserving top genset performance and reliability.
Storing the Genset
1. Push the genset line circuit breaker OFF
(Figure 3-1).
2. Remove the air filter and start the genset. While the genset is running, spray an engine fogger (OnaGard
TM
)1into the carburetor, fol­lowing the instructions on the container label, and then stop the genset. (A fogger coats the intake, cylinder and exhaust systems with a protective coat of oil.)
3. Change the engine oil and oil filter. Also, change the air filter if it is dirty.
4. Disconnect the battery cables (negative [–] cable first) from the starting battery and store the battery according to the battery manufac­turer’s recommendations.
5. Close the fuel supply valve. If the genset is being removed from the premises, cap or plug any unused fuel line to prevent gas leakage if a fuel shutoff valve is opened inadvertently.
Leaks can lead to explosive accu­mulations of gas. Natural gas rises when released and can accumulate under hoods and inside housings and buildings. LP vapor sinks when released and can accumulate inside housings and basements and other below-grade spaces. Prevent leaks and the accumulation of gas.
WARNING
!
CAUTION
!
Page 28
3-10
Redistribution or publication of this document,
by any means, is strictly prohibited.
Returning The Genset To Service
1. Reconnect the starting battery (negative [–]
cable last). See Battery Care in Section 4.
2. Open the fuel supply valve.
3. Inspect the genset. See General Inspection.
4. Start the genset at the genset control panel. The initial startup may be slow and there may be smoke and rough operation for a few min­utes until the oil in the cylinders from the fogger
burns off. If the engine does not start, clean or replace the spark plugs as they may have been fouled by the fogger.
5. Push the genset line circuit breaker to Run (Figure 3–1) and the control switch to Auto for remote, automatic starting and stopping (transfer switch).
Failure to push the control switch to AUTO before leaving the genset renders the genset unavailable for auto­matic standby service.
CAUTION
!
Page 29
4-1
Redistribution or publication of this document,
by any means, is strictly prohibited.
Automatic startup of the genset while performing maintenance or service can cause severe personal injury or death. Push the control switch to Off and disconnect the negative (–) battery cable from the battery to keep the genset from starting while working on it.
Periodic maintenance is essential for top per­formance and long genset life. Use Table 4-1 as a guide for normal periodic maintenance. Under hot or dusty operating conditions some maintenance
operations should be performed more frequently, as indicated by the footnotes in the table. Keep a log of maintenance performed and the hours run. Recording maintenance helps you keep it regular and provide a basis for supporting warranty claims.
Maintenance, replacement, or repair of emission control devices and systems may be performed by any engine repair establishment or individual. However, warranty work must be completed by an authorized Cummins/Onan dealer or distributor.
4. Periodic Maintenance
Refer to Your Honda Owners Manual for Maintenance Schedule
WARNING
!
* Emission-related items. (*) Replace the paper element type only. (1) Service more frequently when used in dusty areas. (2) These items should be serviced by your service dealer, unless you have the proper tools and are
mechanically proficient. Refer to Honda shop manual for service procedures.
Page 30
4-2
Redistribution or publication of this document,
by any means, is strictly prohibited.
GENERAL INSPECTION
Inspect the genset according to the genset Periodic Maintenance Schedule.
Oil Level
Check the engine oil level as explained under Checking Engine Oil Level in this section.
Exhaust System
Look and listen for exhaust system leaks while the genset is running. Shut down the genset if a leak is found and have it repaired before operat­ing the genset.
Fuel System
Check the fuel supply line and fittings for leaks while the genset is running. Check flexible fuel hose sections for cuts, cracks, and abrasions. Make sure the fuel line is not rubbing against other parts. Replace worn or damaged fuel line parts before leaks occur.
Gaseous fuels are highly flamma­ble and explosive and can cause severe per­sonal injury or death. Shut down and repair leaks immediately.
Battery Connections
Check the battery terminals for clean, tight con­nections. Loose or corroded connections have high electrical resistance which makes starting
harder. Shut the genset off and disconnect cor­roded or loose battery cables (negative [–] cable first) and clean and reconnect them as instructed under Battery Care in this section.
Batteries give off explosive gases that can cause severe personal injury. Do not smoke near batteries. Keep flames, sparks, pilot lights, electrical arcs and arc-producing equipment and all other ignition sources well away.
Do not disconnect the battery charger or bat­tery cables while the genset is cranking or running: the arcing can ignite the explosive battery gases.
Mechanical
Look for mechanical damage. Start the genset and look, listen, and feel for any unusual noises and vibrations.
Check to see that the genset air inlet and outlet openings are not blocked or clogged with debris.
Clean accumulated dust and dirt from the genset. Do not clean the genset while it is running or still hot. Always wear safety glasses when using com­pressed air.
Always wear safety glasses when using compressed air to avoid severe eye injury.
WARNING
!
WARNING
!
WARNING
!
Page 31
4-3
Redistribution or publication of this document,
by any means, is strictly prohibited.
CHECKING ENGINE OIL LEVEL
Set the genset control to the Off position before checking the engine oil level.
1. Remove the dipstick (see Figure 4-1), wipe it clean, screw the cap back on and then remove it again to check the oil level on the dipstick.
Crankcase pressure can blow hot engine oil out the fill opening causing severe burns. Always stop the genset before removing the oil fill cap or dipstick.
2. Add oil as necessary until the full mark is reached. See Engine Oil Recommendations in Section 3. Do Not Fill to a Level Above the Full Mark on the Dipstick. Drain the excess oil if too much has been added. It is not necessary to add oil between oil changes, if oil level is between upper and lower limits.
Too much oil can cause high oil consumption, high operating tempera­tures and oil foaming. Too little oil can cause severe engine damage. Keep the oil level between the Full and Add marks on the dipstick.
3. Secure the oil fill cap by turning clockwise until secure.
Return the genset control to Auto when finished performing maintenance.
WARNING
!
CAUTION
!
FIGURE 4–1. OIL LEVEL CHECK
Page 32
4-4
Redistribution or publication of this document,
by any means, is strictly prohibited.
CHANGING ENGINE OIL AND OIL FILTER
Refer to Table 4-1 for scheduled engine oil change. In hot weather and dusty conditions the oil should be changed more often.
Set the genset control to the Off position before changing engine oil.
State and federal agencies have determined that contact with used engine oil can cause cancer or reproductive toxicity. Take care to limit skin contact and breathing of vapors as much as possible. Use rubber gloves and wash exposed skin.
1. Place a pan under the oil drain hose. Run the engine until it is warm and then shut it off.
2. Remove the oil fill cap (see Figure 4-2), remove the hose plug, open the oil drain valve (see Figure 3-2), and allow all of the oil to drain from the engine.
3. Close the oil drain valve and replace the hose plug.
4. Spin off the oil filter canister (see Figure 3-2) and catch the oil in the canister. Discard the oil filter according to local regulations.
5. Thoroughly wipe off the filter mounting sur­face. Make sure that the mounting surface is clean and free of filter particles (gasket from old filter is not stuck to surface).
6. Make sure the gasket is in place on the new filter canister and apply a thin film of oil to the gasket.
7. Spin on the new filter canister by hand until the gasket just touches the mounting pad and then turn it an additional 1/2 to 3/4 turn. Do not over-tighten.
8. Refill with oil (see Engine Oil Recommenda- tions in Section 3 and Specifications in Sec­tion 2) for oil capacity. Check oil level.
9. Secure the oil fill cap by turning clockwise until secure.
10. Used oil is harmful to the environment if it is not disposed of properly. Pour used oil into a sealed container and deliver it to the nearest recycling center or automotive service station.
Return the genset control to Auto when finished performing maintenance.
WARNING
!
FIGURE 4-2. OIL FILL LOCATION
Page 33
4-5
Redistribution or publication of this document,
by any means, is strictly prohibited.
AIR FILTER
Refer to Table 4-1 for scheduled air filter replace­ment. In dusty conditions the air filter element and wrapper should be inspected and changed more frequently for best operation.
Set the genset control to the Off position before checking the air filter.
To change the air filter element and wrapper, loosen the 4 clips and remove the cover (Figure 4-3). Reassemble the air filter with a new air filter element foam filter element. Do not oil either the
paper or the foam filter elements.
Return the genset control to Auto when finished performing maintenance.
FIGURE 4-3. AIR FILTER ELEMENTS
Page 34
4-6
Redistribution or publication of this document,
by any means, is strictly prohibited.
SPARK PLUGS
Set the genset control to the Off position before checking the spark plugs.
See Table 4-1 for scheduled spark plug replace­ment. (The genset has two spark plugs: one on each side of the engine, see Figure 4-3.) The spark plugs must be in good condition for proper engine starting and performance. A spark plug that fouls frequently or has heavy soot deposits indicates the need for engine service. See Troubleshooting in Section 11.
To prevent crossthreading a spark plug, always thread it in by hand until it seats. If the spark plug is being reused, turn it with a wrench an addition­al 1/4 turn. If the spark plug is new, turn it an addi­tional 3/8 to 1/2 turn. If you have a torque wrench, tighten the spark plug to 8 lb-ft (10 N-m).
Return the genset control to Auto when finished performing maintenance.
FIGURE 4–3. SPARK PLUGS
Page 35
4-7
Redistribution or publication of this document,
by any means, is strictly prohibited.
BATTERY CARE
See Table 4–1 for scheduled battery maintenance and to the battery manufacturer’s recommenda­tions and instructions for battery care.
Set the genset control to the Off position before checking the battery.
Batteries give off explosive gases that can cause severe personal injury. Do not smoke near batteries. Keep flames, sparks, pilot lights, electrical arcs and arc–producing equipment and all other ignition sources well away.
Do not disconnect the battery charger or bat­tery cables while the genset is cranking or running: the arcing can ignite the explosive battery gases.
Battery electrolyte can cause severe eye damage and skin burns. Wear gog­gles, rubber gloves and a protective apron when working with batteries.
Maintain the battery as follows unless the battery manufacturer has other instructions and recom­mendations:
1. Keep the battery case clean and dry.
2. Make certain that the battery cable connec­tions are clean and tight. Use a terminal puller tool to remove the battery cables.
3. Identify the cable as positive (+) or negative (–) before making the battery connections. Always remove the negative (–) cable first and connect it last, to reduce the risk of arcing.
4. To remove corrosion from the battery termi­nals, wash the terminals with an ammonia solution or a solution consisting of 1/4 pound (about 100 grams) of baking soda in 1 quart (about 1 liter) of water. Be sure the vent plugs
are tight to prevent cleaning solution from entering the cells. After cleaning, flush the outside of the battery and the surrounding areas with clean water.
5. If the battery is not of the “maintenance-free” type, maintain the electrolyte level by adding distilled water. Fill each cell to the split-level marker in the battery. The water component of the electrolyte evaporates, but the sulfuric acid component remains. For this reason, add water, not electrolyte to the battery.
6. Use a battery hydrometer to check the spe­cific gravity of the electrolyte in each battery cell (see Figure 4–4). Charge the battery if the specific gravity measures less than
1.215. Do not overcharge the battery. Stop charging the battery when the electrolyte specific gravity reaches 1.260, at approxi­mately 80
° F (27° C).
Return the genset control to Auto when finished performing maintenance.
FIGURE 4-4. BATTERY CHECK WITH
HYDROMETER
WARNING
!
WARNING
!
Page 36
4-8
Redistribution or publication of this document,
by any means, is strictly prohibited.
THIS PAGE LEFT INTENTIONALLY BLANK
Page 37
5-1
Redistribution or publication of this document,
by any means, is strictly prohibited.
SAFETY
There are hazards in servicing gensets. Study Safety Precautions and become familiar with the hazards listed in Table 5–1. Note the following safeguards and ways of avoiding hazards:
Reduce the hazard: A safe, orderly workshop
area and well-maintained equipment reduce the hazard potential. Keep guards and shields in place on machinery and maintain equip­ment in good working condition. Store flam­mable liquids in approved containers; away from fire, flame, spark, pilot light, switches, arc-producing equipment and other ignition sources. Keep the workshop clean and well lighted and provide adequate ventilation.
Develop safe work habits: Unsafe proce-
dures lead to accidents when using tools and machines. Be familiar with the equipment and its safe use. Use the correct tool for the
job and check its condition before using it. Observe the warnings in this manual. Take special precautions when working around electrical equipment. Do not work alone, if possible. Do not take risks.
Use personal protection: Wear appropriate
protective safety equipment, such as safety shoes and safety glasses. Do not wear rings or jewelry and do not wear loose or damp clothing that might get caught in equipment or conduct electricity.
Be prepared for an accident: Keep fire extin-
guishers and safety equipment nearby. Agencies such as the Red Cross and public safety departments offer courses in first aid, CPR and fire control. Take advantage of this information and be ready to respond to an acci­dent. Learn to be safety-conscious and make safety procedures part of the work routine.
5. Preparations for Service
TABLE 5–1. HAZARDS AND THEIR SOURCES
Leaking fuel
Fire and Explosion
Hydrogen gas from battery
Oily rags improperly stored
Flammable liquids improperly stored
Hot exhaust pipes
Burns
Hot engine and generator surfaces
Electrical shorts
Jewelry touching electrical components
Poisonous Gas Operating genset where exhaust gases can accumulate
Improper generator connections
Electrical Shock
Faulty wiring
Working in damp conditions
Jewelry touching electrical components
Rotating Machinery Fan and pulley guards not in place
Slippery Surfaces Leaking or spilled oil
Heavy Objects Mounting or removing genset
Page 38
5-2
Redistribution or publication of this document,
by any means, is strictly prohibited.
SPECIAL TOOLS
The following tools are necessary for servicing the genset:
Engine Tools
Torque wrench: 0-75 lb-ft (0-100 N-m)
Hole gauge: 0.300-0.400 inch (5-10 mm)
Outside micrometer set: 0-4 inch (0-100 mm)
Telescoping gauge set: up to 4 inch (100 mm)
Feeler gauge
Plasti–Gage bearing clearance guide
Spark plug gap gauge
Oil pressure gauge: 0–30 psi (0–200 kPa)
Manometer: 14 inch (350 mm) WC
Inclined Manometer: 1 inch (25 mm) WC range with 0.01 inch (0.1 mm) WC divisions
Cylinder compression tester
Flywheel puller
Crankshaft gear puller ring, bolts and puller (or special shoulder bolts and flywheel puller)
Snap ring pliers
Combination main and cam bearing remover
Oil seal loader and driver
Cylinder ridge reamer
Piston ring spreader
Piston groove cleaner
Piston ring compressor
Cylinder hone
Valve spring compressor
Valve lock replacer
Valve seat cutter kit
Valve guide driver
Slide hammer
Lead or dead–blow hammer
Generator and Control Tools
Rotor removal tool (headless bolt) (approximately 13 3/8 inches long)
Commutator stone
Battery hydrometer
Digital multi–meter
Load test panel and leads
Page 39
5-3
Redistribution or publication of this document,
by any means, is strictly prohibited.
REMOVING AND INSTALLING THE
HOUSING PANELS
Before removing housing panels (Figure 5–1) to access the genset for maintenance or service, perform the following steps.
Gaseous fuels are flammable and explosive and can cause severe personal injury or death. Do not smoke if you smell gas or are near fuel tanks or fuel–burning equip­ment or are in an area sharing ventilation with such equipment. Keep flames, sparks, pilot lights, electrical switches and arc–producing equipment and all other sources of ignition well away. Keep a type ABC fire extinguisher handy.
NFPA Standard No. 58 requires all persons handling and operating gaseous fuel to be trained in proper handling and operating pro­cedures.
1. Close the fuel supply shut off valve. If the genset can be started, purge the fuel supply line and genset as much as possible by run­ning the genset until it runs out of fuel with the shut off valve closed.
2. Press the control switch to Stop.
3. Remove the front access panel (Figure 5–1).
This unit can start automati­cally. Accidental starting of the generator set while working on it can cause severe personal injury or death. Prevent acciden­tal starting by disconnecting the negative (–) cable from the battery terminal.
4. Disconnect the negative (–) battery cable
from the battery to prevent accidental starting.
Do not operate the genset without the housing panels secured in place. The pan­els guard against rotating parts and bare live electrical parts that can cause severe person­al injury or death. The housing is also required for proper genset cooling.
The housing consists of removable side doors and panels. The two side doors are secured by latches and the remaining panels are secured by screws.
To open the side doors, lift handle up and out, then turn counter-clockwise, swing the side door down, and lift out.
Disassemble the housing in the following order
5. Remove the side doors.
6. Remove the roof panel by removing the fol­lowing screws. a. Two screws securing the top face of the roof to the engine divider panel. b. Seven screws securing the roof to the front panel. Note that one of these screws
has a toothed washer to provide a ground path between the roof and the front panel.
c. Seven screws securing the roof to the rear panel.
7. Remove the front panel, by removing the seven screws securing it to the base. Note
that one of these screws has a toothed washer to provide a ground path between the front panel and the base.
8. Remove the rear panel as follows. a. Working inside the unit, remove the two screws and the panel hole cover (see Figure 5-1), that is attached to the divider panel (located directly below the exhaust pipe) This must be removed to allow the exhaust pipe to clear the panel during removal. b. Inside the unit, remove the two screws located at the base of the divider panel (see Figure 5-1). c. Remove the seven external screws securing the rear panel to the base. Note
that one of these external screws has a toothed washer to provide a ground path between the front panel and the base.
Reassembly is the reverse of disassembly. To make sure that all of the panel screw holes will line up, wait to tighten the screws until all of the panels and screws are in place. Before fitting the roof panel, it is helpful to screw two M6 studs into the tapped holes on the top edge of the engine divider panel. These studs should then be guided through the holes in the roof panel as it is being fitted. This will ensure that, once the studs are removed, the tapped holes in the engine divider panel are aligned with the holes in the roof panel, so that the screws can be easily fitted. Pay par­ticular attention to the refitting of the toothed washers in steps 8,7 and 6, as these are neces­sary to meet the grounding requirements of UL
2200.
Lock the unit to prevent unauthorized access.
WARNING
!
WARNING
!
WARNING
!
Page 40
5-4
Redistribution or publication of this document,
by any means, is strictly prohibited.
PANEL
HOLE
COVER
ROOF
PANEL
FRONT PANEL
AIR INTAKE
SCREEN
ENGINE DIVIDER
PANEL MOUNTING
SCREWS
ACCESS
DOOR
REAR PANEL
ACCESS
DOOR
ALTERNATOR
DIVIDER PANEL
MOUNTING
SCREWS
FRONT
ACCESS
PANEL
FIGURE 5–1. GENSET HOUSING
Page 41
5-5
Redistribution or publication of this document,
by any means, is strictly prohibited.
ACCESSING THE ENGINE FOR SERVICE
In order to gain access to the engine to carry out adjustments and/or component replacements, proceed as follows.
Accidental starting of the genera­tor set while working on it can cause severe personal injury or death. Prevent accidental starting by disconnecting the starting battery cables (negative [-] first).
Ventilate battery area before disconnecting or connecting batteries. Arcing can ignite the explosive hydrogen gas given off by batteries, causing severe personal injury. Arcing can occur if the negative (-) battery is connected and a tool is being used to connect or discon­nect the positive (+) battery cable accidentally touches the frame or other grounded metal part of the set. To prevent arcing, always remove the negative (-) cable first, and recon­nect it last.
1. Run the unit out of fuel as described in steps
1 & 2 of Section 5-3
2 Disconnect both battery cables (Battery nega-
tive (B-) first) and remove the battery.
3. Remove the side doors, if not already
removed.
4. Remove the roof panel, as described in step 6
of Section 5-3.
5. Remove the front panel, as described in step 7 of Section 5-3.
6. Remove the battery tray.
7. Remove the bolts securing the gas inlet con­nection to the base.
8. Remove the two bolts that secure the engine divider panel to the base. Note that one of
these bolts has a toothed washer to provide a ground path between the engine divider panel and the base.
9. Carefully swing the engine divider panel, complete with the fuel inlet connection and piping, round to the right and lean it against the engine.
10. This will provide access to the flywheel end of the engine and the magnetic pick up, for adjustment and replacement as detailed elsewhere in this manual.
On completion of the engine work refit the panels and other components in the reverse order. Do not tighten the bolts securing the gas inlet con­nection to the base, until the screws securing the roof panel and the engine divider panel are tight­ened.
Pay particular attention to the refitting of the toothed washers in step 8 in this section, and in steps 7 & 6 in Section 5-3, as this is necessary to meet the grounding requirements of UL 2200.
FIGURE 5-2. ENGINE/GENERATOR ASSEMBLY
WARNING
!
Page 42
5-6
Redistribution or publication of this document,
by any means, is strictly prohibited.
THIS PAGE LEFT INTENTIONALLY BLANK
Page 43
6-1
Redistribution or publication of this document,
by any means, is strictly prohibited.
6. Engine Subsystems
These engine subsystems or service procedures do not require removal of the cylinder heads, gearcase or main bearings for access and may be serviceable without removing the engine from the cabinet.
CYLINDER COMPRESSION TEST
Examining the spark plugs and testing cylinder compression can tell much about the condition of the valves, piston rings and cylinders. Test cylin­der compression as follows:
1. Start the genset and let it warm up.
2. Stop the genset and remove and inspect the spark plugs. See Ignition System in this sec­tion.
3. Insert the compression gauge nozzle into one of the spark plug holes, hold the throttle open and crank the engine. Note the pres­sure indicated by the gauge.
4. Repeat the test on the other cylinder.
5. Compare the readings obtained with the Cylinder Compression Pressure Specifications given on Page 2-1.
Note: Do not operate the starter for more than 5 seconds at one try. If stable compres­sion is not obtained within 5 seconds, stop the starter motor and wait 10 - 20 seconds to allow the starter motor to cool, and repeat the operation again.
Page 44
6-2
Redistribution or publication of this document,
by any means, is strictly prohibited.
VALVE CLEARANCE (LASH) ADJUSTMENT
For Specifications, refer to Page 2-1
Valve clearance and inspection must be performed with the engine cold.
Accidental starting of the generator set while working on it can cause severe personal injury or death. Prevent accidental starting by dis­connecting the starting battery cables (negative [-] first).
The generator will be inoperable dur­ing this inspection and adjustment. Be sure to notify all potentially affected persons before beginning work
To access the flywheel and the timing marks on the fan cover, it is necessary to remove the 2 access doors, the roof panel, the rear panel and move the engine divider panel as described on page 5-5.
Inspection & Adjustment
1. Remove the Head Cover Bolt and the Cylinder
Head Cover from both Cylinder Heads.
2. Rotate the flywheel until the “T” mark on the
cooling fan aligns with the “T” mark on the right side of the fan cover. (This alignment point is Top Dead Center of No. 1 cylinder, See Figure 6-1.)
Be sure that No.1 cylinder is at TDC on the
compression stroke. This can be checked by “rocking” the flywheel an inch or so either side of the “T” mark and observing that both the valves remain closed. If either valve moves, the engine is at TDC on the exhaust stroke and must be rotated one complete rev­olution to reach TDC on the compression stroke.
3. Check the intake and exhaust valve clearances for No.1 cylinder by inserting a feeler gauge between the valve stem and the valve rocker arm.
4. If the clearance of either valve does not fall within the specification given in Table 2-1, loosen the pivot adjusting nut and turn the rocker arm pivot to obtain the correct clearance.
5. Hold the rocker arm pivot using a wrench, and tighten the pivot adjusting nut to a torque of 6.5 lbf.ft (9Nm) (Figure 6-2)
6. Recheck the valve clearance after tightening the adjusting nut.
7. Rotate the flywheel 270
0
in a clockwise direction until the “T” mark on the cooling fan aligns with the “T” mark on the left hand side of the fan cover.
8. This will put No.2 cylinder at TDC of its compres­sion stroke.
9. Repeat steps 3,4,5 and 6 for No. 2 cylinder.
10. Replace the cylinder head covers and tighten the head cover bolts.
11. Refit the engine divider panel, the rear panel and the roof panel as described in 5-5.
WARNING
!
WARNING
!
FIGURE 6-1 FIGURE 6-2
Page 45
6-3
Redistribution or publication of this document,
by any means, is strictly prohibited.
EXHAUST SYSTEM
See Figure 6–3. The exhaust system is a welded assembly that consists of two exhaust manifolds, muffler, and exhaust pipe. This welded assembly is mounted inside the heat shield assembly.
Always service a leaking exhaust system before running a genset. Never try welding a broken or leaky tailpipe, muffler or manifold.
Exhaust gas is deadly. The exhaust system must not leak and must dis­charge all engine exhaust away from people, buildings and areas where exhaust can accu­mulate.
Liability for injury, death, damage and warran­ty expense due to the use of an unapproved muffler or due to modifications becomes the responsibility of the person installing the unapproved muffler or performing the modifi­cations. Use Onan approved exhaust system parts.
WARNING
!
FIGURE 6-3. EXHAUST SYSTEM
Page 46
6-4
Redistribution or publication of this document,
by any means, is strictly prohibited.
Spark Plugs
The genset has two spark plugs. The spark plugs must be in good condition and have the proper gap for top engine performance. See
Specifications.
To prevent crossthreading a spark plug, always thread it in by hand until it seats. Then tighten the spark plug according to Thread Torques (Page 2-2). Alternatively, if the spark plug is being reused, turn it with a wrench an additional 1/4 turn. If the spark plug is new, turn it an additional 3/8 to 1/2 turn.
If the engine misses or performance otherwise deteriorates, remove and examine the spark plugs for signs of the following problems:
Light tan, gray or reddish deposits - Normal
One spark plug fouled - Broken spark plug
cable, low cylinder compression
Soot fouled - Wrong spark plug heat range (too cold), duty cycle too short for engine to reach nor­mal operating temperature
Fuel fouled - Wrong spark plug heat range (too cold), faulty choke operation, overly rich fuel mix­ture, dirty air filter
Oil fouled - Malfunctioning crankcase breather, worn rings, worn valve guides or seals
Burned or overheated - Leaking intake manifold gaskets, lean fuel mixture
Worn - Spark plug service life used up.
Quick Ignition Test
If the engine misfires, test the ignition system as follows to quickly determine if the problem is in the ignition system. First recheck the spark plug cable connection to each spark plug.
.
Gaseous fuels are flammable and explosive and can cause severe personal injury or death. Conduct this test only in a well ventilated area and make sure you cannot smell gas. Keep a Type ABC fire extinguisher handy.
1. Open both access doors and wait several minutes and make sure you cannot smell gas before conducting this test.
2. Remove one of the spark plugs.
3. Reconnect the spark plug cable and lay the spark plug on bare engine metal to ground it.
HIGH VOLTAGE. To prevent electric shock do not touch the spark plug or wire during this test.
4. Crank the engine and observe the spark. A strong, consistent spark indicates that the igni­tion system probably is functioning properly and the problem is elsewhere. If no spark occurs or is weak or inconsistent, go to step 5.
5. Repeat step 4 using a new, or known good spark plug. If still no spark occurs, refer to the Honda Workshop Manual or your service dealer.
WARNING
!
WARNING
!
Page 47
6-5
Redistribution or publication of this document,
by any means, is strictly prohibited.
MAGNETIC PICK UP
The magnetic pick-up is situated directly below the engine flywheel and is mounted on a bracket that is secured with the engine mounting bolts at the flywheel end.
There is an aperture in the plastic fan cover which allows the tip of the magnetic pick up to be positioned in close proximity to the starter ring gear on the engine flywheel.
The red and black leads from the magnetic pick-up are terminated with “faston” connectors which are con­nected, respectively, to the blue (MAG PU+) and green (MAG PU -) leads on the Governor Controller Board situated at the top right corner of the engine divider panel.
The operation of the magnetic pick-up can be checked by disconnecting the leads and checking for AC volt­age while cranking the engine. The voltage at cranking speed should be approximately 5 VAC. Reconnect the leads after checking.
The voltage at running speed (with the leads connect­ed) should be approx. 22 VAC.
To access the magnetic pick-up, it is necessary to remove the roof panel, the rear panel and move the engine divider panel as described in Section 5-5.
The generator will be inoperable dur­ing this adjustment.. Be sure to notify all poten­tially affected persons before beginning work.
Incorrect installation, service, or replacement of parts can result in severe person­al injury or death, and/or equipment damage. Service personnel must be trained and qualified to perform electrical and mechanical work.
Magnetic Pick-up Adjustment
1. Remove the Air Filter Assembly and the Fan Cover.
2. Turn the flywheel until the crown of one of the teeth
on the flywheel ring gear is exactly opposite the tip of the magnetic pick up.
3. Slide a 0.012 inch feeler gauge between the crown of the tooth and tip of the magnetic pick up.
4. If necessary, adjust by loosening the locknut and rotating the magnetic pick-up until the correct clearance is obtained.
5. Retighten the lock nut and re-check the clearance.
6. Rotate engine one revolution by hand to make sure ring gear does not hit magnetic pick-up.
7. Refit the Fan Cover and the Air Filter Assembly.
8. Refit the engine divider panel, the rear panel and the roof panel as described in 5-5
Removal and replacement of the
magnetic pickup
9. Disconnect the magnetic pick-up leads from the governor controller board leads..
10. Cut the cable ties and remove the leads from the split conduit.
11. Loosen and remove the bolts which secure the fly­wheel end of the engine and the magnetic pick up bracket to the engine bracket.
12. Remove the magnetic pick-up bracket with the magnetic pick-up threaded into it.
13. The magnetic pick-up bracket is not reversible, so note that the top side is the side through which the tip of the pick up is protruding. Mark it as such if necessary.
14. Loosen the lock nut, and unscrew the pick up from the bracket.
15. Screw a new magnetic pick–up into the bracket, so that the tip of the pick up protrudes about 1/2 inch to 5/8 inch (about 13 to 15 mm) on the side marked top.
16. Fit the magnetic pick-up and bracket to the engine bracket, and refit the engine mounting bolts.
17. Make sure that the tip of the pick-up is positioned directly below the center line of the crankshaft, before tightening the engine mounting bolts.
18. Adjust the pick-up as described in steps 2) through
5) under “Magnetic Pick-up Adjustment” in this section.
19. Refit the Fan Cover and the Air Filter Assembly.
20. Refit the engine divider panel, the rear panel and the roof panel as described in Section 5-5.
WARNING
!
WARNING
!
Page 48
Redistribution or publication of this document,
by any means, is strictly prohibited.
6-6
GOVERNOR ROD AND ACTUATOR
See Figure 6–10. The genset controller operates the throttle by means of the governor rod and actuator to maintain a nearly constant engine speed (fre­quency) as the electrical load on the genset varies.
To determine if the governor actuator is defective or needs to be replaced, check the coil resistance
with the two leads disconnected. Coil resistance should be 1.5 to 3.0 ohms and open to ground. Also, with the leads disconnected, apply 12 VDC to the actuator. The actuator should open the car­buretor to full throttle.
If necessary, replace the governor actuator per governor actuator setting procedure located at section 6-5.
FIGURE 6–10. GOVERNOR ROD AND ACTUATOR
For Index of Components See Figure 6-11.
Page 49
6-7
Redistribution or publication of this document,
by any means, is strictly prohibited.
GOVERNOR ADJUSTMENT
The relationship between the Governor Actuator and the Carburetor has been carefully set during assembly, to give the required performance and should not require adjustment.
If either the Actuator or the Carburetor is replaced, then the settings should be checked and adjusted as follows.
1. To access the Carburetor and Governor Rod a. Remove the roof panel (Section 5-3). b. Remove the Air Cleaner assembly (Section 4-5).
2. To adjust the Carburetor a. Holding the butterfly closed by hand, adjust
the Idle Stop Screw (Figure 6-11 Item 23) until a 0.006” (0.15mm) feeler gauge is a snug fit between the Idle Stop Screw and the Carburetor Throttle Lever (Figure 6-11 Item 8).
b. Remove the feeler and turn the Idle Stop
Screw a further one and one quarter turns (1 1/4) clockwise.
3. To adjust the Actuator a. Check that the carburetor is correctly adjusted
as above.
b. Check that the distance from the actuator
housing to the shoulder at the end of the ground portion of the actuator shaft (Section 6-11 Item 24) is 0.500” (1/2 inch or 12.7mm).
c. If adjustment is required, loosen the clevis
lock nut (Figure 6-11 Item 11).
d. Holding the clevis (Figure 6-11 Item 10) from
turning, rotate the actuator shaft until the correct dimension is obtained.
e. Tighten the clevis locknut and recheck the
dimension.
f. Move the actuator through its range of motion
by hand, verifying that the linkage is free at both the idle and full throttle positions.
4. Refit the Air Cleaner (Section 6-8) and the roof panel (Section 5-3)
FIGURE 6–11
1 BEARING - BALL 2 10-32 x 3/4 FILHMS 3 10 - 32 HEXNUT 4 #10 LOCK WASHER 5 8-32 X 5/16 PHMS 6 8-32 HEXNUT 7 #8 LOCK WASHER 8 LEVER - THROTTLE 9 ROD - ACTUATOR 10 CLEVIS 11 JAM NUT (SUPPLIED WITH ACTUATOR) 12 ACTUATOR 13 M5 X 0.8 X 30 HHCS 14 M5 X 0.8 HEXNUT 15 CLAMP - GOVERNOR 16 M6 X 1.0 HEXNUT 17 BRACKET - THROTTLE 18 M8 LOCK WASHER 19 M8 X 1.25 X 20 HHCS 20 #10-32 NUT W / WASHER 21 M5 X 0.8 HEXNUT 23 IDLE STOP SCREW 24 ACTUATOR SHAFT 25 SLOTTED SHAFT
Page 50
Redistribution or publication of this document,
by any means, is strictly prohibited.
FIGURE 6–12. AIR CLEANER
6-8
FUEL SYSTEM
The engine is equipped with a fuel system that is designed to run on either natural gas or LP vapor.
A genset purchased to use natural gas or LP vapor can not be converted to use LP liquid.
The genset leaves the factory set up for natural gas. If the genset uses LP vapor, follow conver­sion instructions in the Installation Manual.
Gaseous fuels are flammable and explosive and can cause severe personal injury or death. Do not smoke if you smell gas or are near fuel tanks or fuel-burning equip­ment or are in an area sharing ventilation with such equipment. Keep flames, sparks, pilot lights, electrical switches and arc-producing equipment and all other sources of ignition well away. Keep a type ABC fire extinguisher handy.
NFPA Standard No. 58 requires all persons handling and operating gaseous fuel to be trained in proper handling and operating pro­cedures.
Gaseous fuel leaks into an inade­quately ventilated space can lead to explosive
accumulations of gas. Natural gas rises when released into the air and can accumulate under overhanging hoods and inside hous­ings and buildings. LPG sinks when released into the air and can accumulate inside hous­ings, basements and other below–grade spaces. Precautions must be taken to prevent gas leaks and the accumulation of gaseous fuel in the event of a leak.
Air Cleaner Assembly
Disassembly:
1. Open the side access doors. (See Removing and Installing the Housing Panels in Section 5.
2. Loosen the four spring clips (Figure 6–12).
3. Lift off the air cleaner element assembly.
4. Remove the five screws that secure air cleaner housing (two screws to the support bracket and the three screws to the carbure­tor) and remove housing.
Reassembly: Reassembly is the reverse of dis­assembly. Use a new gasket between the adapter and the carburetor.
Note: When replacing the air cleaner housing, take care to reattach the crankcase breather hose to the stub on the bottom face of this housing. A pair of long needle nose pliers will be helpful for this.
WARNING
!
WARNING
!
Page 51
Redistribution or publication of this document,
by any means, is strictly prohibited.
6-9
FIGURE 6–13. LP VAPOR/NATURAL GAS FUEL SYSTEM
NG / LP Vapor Fuel System
The fuel system for NG or LP vapor consists of a 3/4” NPT female gas supply connection (located toward the bottom right hand side of the front access panel), supplying fuel through a pair of fuel shut off solenoids (plumbed in series, wired in parallel) to a gas pressure regulator (located at the top left hand corner of the engine divider panel). A vent tube from the regulator protrudes through the engine divider panel to ensure that the atmospheric pressure at the regulator and at the carburetor is balanced.
The gas pressure regulator fitted to the unit pro­vides constant gas pressure to the carburetor under varying load conditions. It is pre-set and sealed to comply with EPA and CARB regula­tions.
The change of gas supply between NG and LP vapor is accommodated simply by fitting the engine hose to the appropriate outlet on the tee­piece at the regulator (refer to Figure 6-13). No
adjustment to the regulator is necessary or possi­ble.
Adjusting Inlet Gas Supply Pressure:
There is a pressure test port on the inlet side of the regulator. To access this test port it is neces­sary to remove the roof panel (Section 5-3). The pressures given in the Specifications (Section 2-
1) are taken at this point, which is after the fuel shut off solenoids.
A more practical and convenient method of checking and adjusting the inlet pressure is to connect a manometer, by means of a suitable tee piece, between the gas supply and the Fuel Inlet fitting on the unit (Figure 3-2). The manometer should have a scale range of at least 14 inches (350 mm)
The pressure at this point, on either NG or LP vapor, should be 2 inches (25mm) WC greater than the pressure given in the Specifications (Section 2-1) to allow for the pressure drop through the fuel solenoid valves.
Page 52
Redistribution or publication of this document,
by any means, is strictly prohibited.
6-10
Adjust the supply pressure as follows:
1.Close the gas supply shut off valve.
2. Disconnect the gas supply pipe, and fit a tee-piece and the manometer.
3. Reconnect the gas supply pipe.
4. Test for leakage by performing a soap
bubble test.
5. Open the gas shut off valve.
6. With the genset at rest, adjust the gas supply pressure regulator to obtain between 7 and 13 inches (178-330mm) WC.
7. Start the unit, and while running at no load, note the gas supply pressure.
Adjust if necessary.
8. If the genset is operable, check the gas supply pressure under full load. If gas pressure drops below the required mini mum of 7 inches (178mm) WC, the gas supply piping may be too small. On an LP vapor supply system, the tank may be
too small to provide the required rate of vaporization, or it may not contain enough fuel.
NOTE: Be sure to have all other gas appliances running during this test, to place full demand on the gas supply.
9. Close the gas supply shut off valve
10. Disconnect the manometer, and remove or plug off the tee piece.
11. Open the gas shut off valve
12. Before returning the unit to service, test for leakage, by performing a soap bubble test at any connection point that has
been disturbed.
Fuel Solenoid Valve Tests
To access the fuel solenoid valves, remove the
roof panel (Section 5-3) Replace a leaky fuel solenoid valve or one that fails to open.
To test for leakage, use a test pressure of at least 11 inches (279mm) WC and perform a soap bubble test.
To test for opening, jumper both solenoids across the battery cable connections at the genset. A manometer connected to the test port on the regulator can be used to indicate whether both valves are opening.
Gaseous fuels are flammable and explosive and can cause severe personal injury or death. Do not smoke if you smell gas or are near fuel tanks or fuel-burning equip­ment or are in an area sharing ventilation with such equipment. Keep flames, sparks, pilot lights, electrical switches and arc-producing equipment and all other sources of ignition well away. Keep a type ABC fire extinguisher handy.
NFPA Standard No. 58 requires all persons handling and operating gaseous fuel to be trained in proper handling and operating pro­cedures.
Gaseous fuel leaks into an inade­quately ventilated space can lead to explosive accumulations of gas. Natural gas rises when released into the air and can accumulate under overhanging hoods and inside hous­ings and buildings. LPG sinks when released into the air and can accumulate inside hous­ings, basements and other below–grade spaces. Precautions must be taken to prevent gas leaks and the accumulation of gaseous fuel in the event of a leak.
WARNING
!
WARNING
!
Page 53
Redistribution or publication of this document,
by any means, is strictly prohibited.
7-1
7. Generator
GENERAL DESCRIPTION
The YVB generator (Figure 7–1) is a two-pole, revolving field, brush-type design with drip-proof construction. It is regulated by the microproces­sor-based genset controller.
The generator rotor and engine crankshaft have a tapered coupling secured by the rotor through­bolt. The other end of the rotor is supported in a sealed, pre-lubricated ball bearing assembly. The cooling blower wheel is bolted to the rotor assem­bly
ROTOR
STATOR
ASSEMBLY
WRAPPER
ASSEMBLY
ROTOR
WINDINGS
COLLECTOR
RING
END
BEARING
GENERATOR
FAN
FAN MOUNTING
DISC
ROTOR
HUB
END BELL ASSEMBLY (SEE FIGURE 8–2
FOR BRUSH CONFIGURATION)
MOUNTING
FOOT
FIGURE 7-1 YVB GENERATOR
Page 54
Redistribution or publication of this document,
by any means, is strictly prohibited.
7-2
SERVICING BRUSHES AND SLIP RINGS
Remove the rear panel to access the generator brushes. See Removing and Installing the Housing Panels in Section 5.
Remove the brush block and inspect for burned brushes and grooved or pitted slip rings and other damage. (Turn the rotor to inspect all the way around the slip rings.)
If everything looks good, check brush wear with a piece of wire marked off as shown in Figure 8–2. Replace the brushes and brush springs if the wire can be inserted more than 1 inch (25 mm) into the hole in the brush holder. (Make sure the wire rests on top of the brush and not on part of the brush spring.)
If the slip rings are grooved or pitted try cleaning them up with a commutator stone. If the slip rings need to be replaced, see Removing and Replacing the Slip Ring Assembly under Generator Assembly/ Disassembly in this section.
To replace the brushes or to clean up the slip rings:
1. Disconnect the leads marked F1 and F2 from
the brush block terminals.
2. Remove the brush block mounting screws (2) and lift out the brush block assembly.
Incorrect installation, service, or replacement of parts can result in severe per­sonal injury or death, and/or equipment dam­age. Service personnel must be trained and qualified to perform electrical and mechanical work. When carrying out the following proce­dure, be aware of the dangers of working with rotating parts. Take care to keep body parts, hair and loose clothing from coming into con­tact with rotating parts.
3. If the slip rings need to be cleaned up, insu-
late the ends of leads F1 and F2, disconnect all leads from the positive (+) terminal of the ignition coil to keep the engine from starting, hold the commutator stone lightly against the slip rings and crank the engine for 3 to 6 sec­onds. Check the slip rings and repeat the procedure as necessary until the pits and groves have been removed. Clean any resulting debris from the inside of the gener­ator, using compressed air, if available, or a small brush.
4. Replace the brushes and brush springs with
new parts. Connect each brush pigtail to the terminal on its side of the insulating divide (Figure 7–3).
5. Remount the brush block. Center the brush­es on the slip rings before tightening the mounting screws.
6. Reconnect the lead marked F1 to the out­board brush terminal and the lead marked F2 to the inboard brush terminal and secure.
7. Reassemble Housing as detailed in Section 5.
BRUSH BLOCK
ASSEMBLY
MEASURING
WIRE
GENERATOR
BEARING
1 INCH
BRUSH
SPRING
BRUSH
LEAD
TERMINALS
BRUSH
PIG TAILS
FIGURE 7-2 CHECKING BRUSH WEAR
FIGURE 7-3 BRUSH BLOCK ASSEMBLY
WARNING
!
Page 55
Redistribution or publication of this document,
by any means, is strictly prohibited.
7-3
GENERATOR DISASSEMBLY/ASSEMBLY
The following sections describe the disassembly and reassembly procedures for the generator. Figure 7–4 illustrates generator assembly.
Generator components are heavy and can cause severe personal injury if dropped or lifted during service. Be careful, use appropriate lifting techniques, keep hands and feet clear during service, and use the recommended service procedures.
Disassembly
1. Remove the rear panel. See Removing and Installing the Housing Panels in Section 5.
Check lead markings before disconnecting a lead. If the lead makings do not clearly identi­fy reconnection, mark the leads with tape.
2. Remove the two harness clamps that secure the harness to the outside of the generator (Figure 7–4).
3. Remove the cover from the control box and disconnect stator leads T1 and T4 from the circuit breaker and T2 and T3 from the neu­tral terminal. Cut necessary cable ties to remove these leads from the harness sleev­ing up to the rear of the generator.
4. Disconnect leads Q1 and Q2. Connectors are located in the harness sleeving at the rear of the generator (Figure 7–4).
5. Disconnect leads F1 and F2 from the brush block terminals (Figure 7–3).
6. Remove the bonding strap from the genera­tor mounting foot.
7. Remove the exhaust assembly (see Exhaust System in Section 6).
WARNING
!
FIGURE 7-4 ALTERNATOR HARNESS
Page 56
Redistribution or publication of this document,
by any means, is strictly prohibited.
7-4
8. To keep from damaging the brushes and to keep them from interfering when remounting the stator, either:
A. Remove the brush block assembly by
disconnecting the leads marked F1 and F2 from the brush block terminals (Figure 7–3) and then removing the two mounting screws, or
B. Insert a stiff wire through the small hole
in the end of the stator housing and into the brush block, to hold the brushes up and out of the way (Figure 7–5). To do this, first pull both brush pigtails to lift the brushes off the slip rings.
9. Remove the two generator vibration isolator center-bolts.
10. Place a piece of “two-by-four” lumber under the rear of the engine mounting plate to sup­port the engine.
11. Remove the four nuts(Figure 7-6 item 20) and lock washers (Item 21) from the genera­tor studs (Item 22). Pry the end bell free of the rotor bearing. Be careful not to damage the brush holder. (Figure 7–6).
12. Pull the stator/wrapper assembly off the rotor and away from the engine, taking care not to scrape stator windings. Set it aside.
INSERT A RETAINING
WIRE TO KEEP THE
BRUSHES OUT OF THE
WAY WHEN ASSEMBLING
AND DISASSEMBLING
THE GENERATOR
RETAINING
WIRE
FIGURE 7-5 BRUSH BLOCK ASSEMBLY
Page 57
Redistribution or publication of this document,
by any means, is strictly prohibited.
7-5
FIGURE 7-6 GENERATOR DISASSEMBLY/REASSEMBLY
Page 58
Redistribution or publication of this document,
by any means, is strictly prohibited.
7-6
Removing the Rotor
1. Remove the rotor through stud. (Use two nuts locked together at the end of the rotor through stud to loosen and remove stud from crankshaft.)
2. Thread in a rotor removal rod (Figure 7–7) and turn it with a screwdriver until it bottoms in crankshaft. Thread in and tighten a 9/16­12 x 1-3/4 inch bolt against the rod until the rotor breaks loose from the crankshaft. A tap with a lead hammer on the rotor assy. May be required. Be careful not to hit the windings.
3. If necessary, replace the bearing and the slip ring assembly as instructed in this subsection.
Remounting the Rotor
Replace the bearing and the slip ring assembly, if necessary, as instructed in this section. Use the rotor removal tool to guide the rotor on. Torque the through bolt to torque indicated in Section 2-2 Thread Torques.
APPROXIMATELY 13 3/8
INCHES LONG
SCREWDRIVER
SLOT
REMOVAL BOLT
FIGURE 7-7 ROTOR REMOVAL TOOL
Page 59
Redistribution or publication of this document,
by any means, is strictly prohibited.
7-7
Remounting the Stator Housing
Remounting is the reverse of removal. Note the following:
1. Mount the rotor.
2. Make sure the brush block assembly has been removed or that the wire is holding both brushes up and out of the way.
3. Make sure the bearing O-ring is in place in the housing bearing bore.
4. Torque the stator housing nuts, the rotor through stud nut and vibration isolator center bolts to Thread Torques in Section 2.
5. Make sure to secure the bonding strap to the generator mounting foot using one EIT (external and internal toothed) lock washer on each side of the strap terminal for a good electrical connection.
6. Reconnect or reassemble all other parts that were disconnected or removed.
7. Install the brush block assembly if it was removed. If it was left in place, pull the brush pig tails and remove the retaining wire. If nec­essary, loosen the brush block mounting screws, align the brush block so that the brushes are centered on the slip rings and retighten the mounting screws.
8. Connect the lead marked F1 to the outboard brush terminal and the lead marked F2 to the inboard brush terminal.
9. Replace all cable ties that were removed dur­ing this procedure.
Removing and Replacing the Rotor Bearing with the Rotor already removed.
Use a gear puller to remove the bearing from the rotor shaft if it or the slip ring assembly is to be replaced, otherwise leave it in place. If the bearing is to be reused, make sure the fingers of the gear puller bear on the inner race of the bearing only.
The bearing will be damaged and become unusable if force is applied to the outer race either when pulling it off or press­ing it on.
Replace the bearing as follows:
1. Replace the slip ring assembly first, if neces­sary.
2. Bearing is glued on. Follow the instructions in the Bearing Replacement Kit.
Removing and Replacing the Slip Ring Assembly
Unsolder the two rotor leads from the slip ring assembly and pull the slip ring assembly off with a gear puller. Tape the key to the shaft to keep from loosing it if a new assembly is not going to be installed right away.
Press on a new slip ring assembly with a press, making sure the key is in place and the assembly is aligned with the key. Solder the two rotor leads to the solder terminals on the slip ring assembly.
CAUTION
!
Page 60
Redistribution or publication of this document,
by any means, is strictly prohibited.
7-8
TESTING THE GENERATOR
The following tests and adjustments can be per­formed without disassembly of the generator.
Many troubleshooting procedures present hazards that can result in severe per­sonal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery hazards should perform serv­ice procedures. Review safety precautions on inside cover page.
Testing Field Flash Voltage
Incorrect installation, service, or replacement of parts can result in severe personal injury or death, and/or equipment damage. Service personnel must be trained and qualified to perform electrical and mechanical work. When carrying out the following procedure, be aware of the dangers of working with rotating parts. Take care to keep body parts, hair and loose clothing from coming into contact with rotating parts.
Field flash voltage can be tested at the brush holder terminals with a DC voltmeter (Figure 7-8). With the engine cranking, check for 12 VDC. If present, check for open windings in the rotor. If not present, alternator harness or genset control (A11) PCB is defective.
WARNING
!
BRUSH BLOCK
ASSEMBLY
LEAD (F2
TO A11-F2)
LEAD (F1
TO A11-F1)
TEST POINTS
FIGURE 7-8 FIELD VOLTAGE TEST POINTS
WARNING
!
Page 61
Redistribution or publication of this document,
by any means, is strictly prohibited.
7-9
Testing the Rotor
The generator circuits can be tested without hav­ing to disassemble the generator. It is recom­mended that an ohmmeter be used to check for open circuits and an insulation resistance meter for grounded circuits. An ohmmeter can be used to check for grounded circuits, but it may not be able to detect marginal insulation breakdown.
Testing for Grounds: Check for grounds between each slip ring and the rotor shaft, Figure 7–9. Use a Megger or insulation resistance meter which applies 500 VDC at the test leads. Perform test as follows:
1. Isolate the rotor windings by disconnecting the two leads to the brush holder.
2. Connect test leads between each ring and the rotor shaft in turn. Meter should register 100,000 ohms or greater.
3. If less than 100,000 ohms, rotor is question­able. Thoroughly dry the rotor and retest.
4. Replace a grounded rotor with a new identi­cal part.
Testing for Open or Shorted Windings: Perform this test with an accurate meter such as a digital ohmmeter.
1. Isolate the rotor windings by disconnecting the two leads to the brush holder.
2. Using ohmmeter, check resistance between F1 and F2 collector rings (25.47 ohms
±
10%), Figure 8–10.
If there is a large difference, replace the defective rotor with new, identical part.
MEGGER OR
INSULATION
RESISTANCE
METER
CONNECT LEADS
BETWEEN EACH RING
AND ROTOR SHAFT
FIGURE 8-9 TESTING ROTOR FOR GROUNDS
CONNECT LEADS
BETWEEN F1, F2
SLIP RINGS
DIGITAL
OHMMETER
FIGURE 7-9 TESTING ROTOR FOR GROUNDS
FIGURE 7-10 TESTING ROTOR FOR AN OPEN
Page 62
Redistribution or publication of this document,
by any means, is strictly prohibited.
7-10
Testing Generator Stator
Using proper test equipment, check the stator for grounds, opens, and shorts in the windings. Isolate the stator windings by disconnecting all six stator leads. Test each winding T1-T2, T3-T4, Q1­Q2.
Testing for Grounds: Some generators have ground connections to the frame. Check wiring dia­gram. All stator leads must be isolated for testing.
Use a megger or insulation resistance meter which applies not more than 500VDC to the test leads (Figure 7–11). Test each stator winding for short to laminations. A reading of less than 100,000 ohms indicates a questionable stator. Thoroughly dry the stator and retest. T1,T2,T3,T4,Q1,Q2 : be open to ground.
Testing for Open or Shorted Windings: Test for continuity between coil leads as shown in Figure 7–12. Use an accurate instrument for this test such as a Wheatstone Bridge. Resistance should correspond to the values shown below.
Resistance values (± 5%):
T1-T2: 0.095 ohms T3-T4: 0.095 ohms Q1-Q2: 1.185 ohms T1-T3: open T1-T4: open T2-T3: open T2-T4: open T1,T2,T3,T4-Q1: open T1,T2,T3,T4-Q2: open
If a winding is shorted, open or grounded, replace the stator assembly. Before replacing the assem­bly, check the leads for broken wires or insulation.
CONNECT LEADS BETWEEN
EACH WINDING AND GROUND
FIGURE 8–11. TESTING STATOR WINDIN G FOR
GROUNDS
CONNECT LEADS
BETWEEN PAIRS
OF STATOR
WINDING LEADS
FIGURE 7-11 TESTING STATOR WINDING FOR
GROUNDS
FIGURE 7-12 TESTING STATOR WINDING
RESISTANCE
Page 63
Redistribution or publication of this document,
by any means, is strictly prohibited.
8-1
8. Genset Control PCB (A11)
The genset control PCB (A11) is a fully potted assembly with one connector (P1) and is mounted by one screw to the generator control assembly. A bracket is also used at the top of the control PCB for additional bracing for removing and installing the P1 connector. To remove the control PCB, perform the following steps.
3. Remove the side access doors, top and front access panel. (See Removing and Installing the Housing Panels in Section 5 for instruc­tions and important safety precautions.)
4. Remove connector P1 from the control PCB (Figure 8–1). To remove connector, insert small blade screwdriver into slot of connector
retainer tab. Move tab downward to release and remove connector.
5. Remove retainer screw from the base of the control PCB.
6. Loosen the lower two screws and remove the upper four screws that secure the control assembly panel to the engine divider panel.
7. Lightly pull back on the top of the control assembly until the connector on the back of the control PCB clears the cutout in the back of the engine divider panel.
8. With the control assembly tilted back, lift up on the control PCB to release the bracket from the control assembly and remove the control PCB.
SMALL BLADE
SCREWDRIVER
REMOVE
(FOUR SCREWS)
CONNECTOR
P1
ENGINE DIVIDER
PANEL
LOOSEN
(TWO SCREWS)
CONTROL
PCB (A11)
CONTROL
ASSEMBLY
CONTROL PCB
RETAINER
SCREW
RETAINER
TAB SLOT
BRACKET
CUTOUT
FIGURE 8-1 REMOVING CONTROL PCB
Page 64
Redistribution or publication of this document,
by any means, is strictly prohibited.
8-2
The control PCB uses a microprocessor with embedded software. The micro–controller supports the traditional functions of genset control along with
voltage regulation and extensive diagnostics (see Troubleshooting, Section 11). Figure 8–2 is a block diagram of control PCB inputs and outputs.
+-
OUTPUT VOLTAGE SENSE
AC POWER OUTPUT
FIELD CURRENT
BRUSHES/
SLIP RINGS
ROTATING
MECHANICAL
POWER INPUT
OF ENGINE
FUEL
IGN
START
MAIN STATOR (G1)
MAIN ROTOR
(FIELD)
RUN-OFF-AUTO SWITCH AND STATUS/DIAGNOSTICS LED
AUTOMATIC TRANSFER SWITCH
ENGINE SENSOR (LOP)
+
-
GENSET
CONTROL
PCB (A11)
Q1/Q2 (FIELD POWER AND FREQUENCY SENSE)
FIGURE 8-2 GENSET CONTROLLER INPUTS AND OUTPUTS
Page 65
Redistribution or publication of this document,
by any means, is strictly prohibited.
9-1
9. Governor Controller Board (A12)
The genset governor controller board (A12) is mounted on the engine divider panel, directly above the control PCB. It receives the governing control (tachometer) signal from the magnetic pick-up and B+ from the control PCB.
THIS CONTROLLER IS PROGRAMMED SPECIFICALLY FOR THE 12GRCA. IN ORDER TO ENSURE CORRECT OPERATION OF THE 12GRCA UNIT, THIS CONTROL MUST BE ORDERED FROM AN AUTHORIZED DEALER.
The governor controller board outputs a DC volt­age that drives the governor actuator, which in turn moves the carburetor throttle to maintain an engine speed of 3600 RPM (60 Hz). The input from the magnetic pick-up and B+ from the con­trol PCB can signal the governor controller board to shut the engine off under the following adverse conditions:
If power (B+) is lost to the control PCB
Any control PCB shutdown fault
If signal from the magnetic pick-up stops
Under all these circumstances, governor con­troller board shuts down the genset. The governor controller board is a non-serviceable component.
Note: This controller possesses a warm up fea­ture to assist with low ambient start up. As part of
the warm up sequence, the genset will climb to 2600 rpm and maintain this speed for up to 8 sec­onds. After 8 seconds, the unit will then ramp up until it reaches its running speed of 3600 rpm. The total time for the start up sequence to occur can be as long as 18 seconds.
GOVERNOR CONTROLLER BOARD
TROUBLESHOOTING
When starting the genset, the actuator should open the carburetor to approximately 1/2 throttle. If not, first check the operation of the actuator and linkage (see Governor Rod and Actuator in Section 6) and also the ignition system (see Ignition System in Section 6) and then check the following to determine if the governor controller board is defective.
The status indicator on the governor controller board should light for 1 second, then off for 1 sec­ond and then remain on during cranking and genset operation. If the indicator flashes more than once, the governor controller board is defective.
If the indicator does not light, check all connec­tions before replacing the governor controller board. Also check for +12 VDC at the ignition coil. If not present the controller PCB may be defective.
Page 66
Redistribution or publication of this document,
by any means, is strictly prohibited.
9-2
FIGURE 9–1. GOVERNOR CONTROLLER BOARD A12
Page 67
Redistribution or publication of this document,
by any means, is strictly prohibited.
10-1
10. Troubleshooting
Table 10–1 provides troubleshooting guidance for a genset that fails to start or that shuts down. The genset controller has an extensive diagnostic capability and its fault codes are covered in numerical sequence in Table 110–1. Gaps in the
code numbers are for codes that do not apply to this genset.
Most shutdowns can be prevented by proper maintenance and use of the genset—maintaining oil levels, keeping battery connections clean and tight, and not overloading the genset.
STATUS/DIAGNOSTICS LIGHT ON THE
GENSET CONTROL SWITCH
The genset controller causes the status/diagnos­tics LED to indicate a fault code if there is a fault shutdown that requires maintenance or service. There are distinct (longer) pauses between repe­titions of the code blink transmissions.
Single-Digit Fault Code – A single-digit fault code is indicated by a corresponding number of blinks. For example:
Code No. 4: blink-blink-blink-blink-long pause repeat code
Two-Digit Fault Code – A two-digit fault code is indicated by two sets of blinks separated by a short pause. The first set corresponds to the tens digit and second to the ones digit. For example:
Code No. 32: blink-blink-blink-pause-blink-blink- long pause-repeat code
FAULT CODE LEVEL
There are two levels of fault codes. Level One is a “single digit” fault code that indicates engine faults (possibly correctable by customer) or that there is a level two fault.
Level Two fault is a “two digit” fault code that requires repair by an authorized service repre­sentative.
DISPLAYING LEVEL ONE/TWO FAULT
CODES
Immediately following a fault shutdown, the indi­cator light will blink a Level One fault code and will stop after five minutes. To restore and read this fault, perform the following:
9. Disconnect the remote start wire from the ter­minal block of the control assembly (TB1-5). This will prevent accidental starting of the genset by the transfer switch while perform­ing this procedure.
10. Grasp the side of the Run/Off/Auto switch and toggle the switch three times between Off and Auto within five seconds.
11. The Level One fault code will be displayed. If a Level One fault code “3” is displayed, a Level Two fault has occurred. To display the Level Two code, toggle the switch one more time between Off and Auto.
12. See Table 10–1 for troubleshooting guidance of indicated fault code.
Note: The fault displayed is the last fault logged and will remain in memory even though the condi­tion has been corrected and the genset is running normally.
Automatic startup of the genset while performing maintenance or service can cause severe personal injury or death. Push the control switch to Off and disconnect the negative (–) battery cable from the battery to keep the genset from starting up while work­ing on it.
Hot engine parts can cause severe burns. Always allow the engine time to cool before performing any maintenance or service.
WARNING
!
WARNING
!
Page 68
Redistribution or publication of this document,
by any means, is strictly prohibited.
10-2
TABLE 10–1. TROUBLESHOOTING
Some genset service procedures present hazards that can result in severe per­sonal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery hazards should perform genset service. See Safety Precautions.
NO RESPONSE WHEN THE CONTROL SWITCH IN THE RUN POSITION
(Marginal batteries, connections, or charging system)
Corrective Action:
1. Replace Fuse F1 (B+) if blown.
2. Clean and tighten the positive (+) and negative (–) battery cable connections at the battery and
genset.
3. Recharge or replace the battery. Refer to the battery manufacturer’s recommendations.
4. Test the battery charging system and service as necessary. See Flywheel Alternator - Section 6.
5. Push the control switch to Auto and try starting the genset through the transfer switch control. Replace control switch S2 if the genset can be operated remotely but not locally.
6. Resettable fuse on genset control PCB is open. Check for short to ground in the starter, fuel sole­noid, ignition, field flash circuits.
7. Replace the genset control PCB (see Section 8).
NO POWER—GENSET RUNNING, RUN LIGHT ON
(Line circuit breaker OFF or tripped or faulty wiring)
Corrective Action:
1. Turn on or reset the line circuit breaker on the genset.
2. Turn on or reset the line circuit breakers on the main distribution panel.
3. Check for proper transfer switch function.
4. Check genset AC output connections at the equipment (transfer switch) and reconnect as nec­essary.
5. Attempt to reset the circuit breakers and measure electrical continuity across terminals. Replace a circuit breaker that does not close or that has measurable resistance across the contacts.
6. Check all AC wiring connections in genset.
LOW OIL FAULT—CODE NO. 2
(The controller sensed that the low oil pressure cutoff did not open within 10 seconds of starting or
closed during operation)
Corrective Action:
1. Check engine oil level and add oil as necessary. Repair oil leaks.
2. Drain excess oil. (Excess oil leads to foaming and a consequent loss of oil pressure.)
3. Repair the low oil pressure cutoff switch (S1) wiring or replace defective switch.
4. Service a worn lubricating system and/or engine according to Engine Subsystems (Section 5) and/or Honda recommendations).
WARNING
!
Page 69
Redistribution or publication of this document,
by any means, is strictly prohibited.
10-3
TABLE 10–1. TROUBLESHOOTING (CONT.)
Some genset service procedures present hazards that can result in severe per­sonal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery hazards should perform genset service. See Safety Precautions.
SERVICE CHECK FAULT—CODE NO. 3
(A Level Two fault occurred)
Corrective Action: Check the second–level fault code. See Displaying Level One/Two Fault Codes in this section.
OVERCRANK FAULT—CODE NO. 4
(Cranking exceeded 20 seconds without engine starting)
Corrective Action:
1. Open any closed fuel shutoff valves.
2. Check the governor linkage for binding and service as necessary (see Governor Linkage and Actuator in Section 6).
3. Check magnetic pick-up for proper operation (See Section 6-5).
4. Fill the LPG fuel tank if less than half full. On cold days the LPG container may have to be kept at least half full to provide the rate of vaporization required to keep up with genset fuel demand. LPG with more than 2.5 percent butane will not vaporize below 32
° F (0° C). Use HD-5 grade LPG.
5. Inspect/secure the spark plug cable on the spark plugs.
6. Service the air cleaner.
7. Check for a blocked exhaust system and service as necessary.
8. Check fuel solenoid valve operation (see Fuel System in Section 6).
9. Check the gas supply pressure and adjust as necessary (see Fuel System in Section 6).
10. Conduct the ignition system tests and service as necessary (see Ignition System in Section 6).
11. Check the governor controller board (see Section 9).
12. Conduct a cylinder compression test and service the engine if it is worn or malfunctioning.
OVERVOLTAGE FAULT—CODE NO. 12
(Controller not able to regulate to rated voltage)
Corrective Action:
1. Service the brushes and slip rings as necessary (see Servicing Brushes and Slip Rings in Section 8).
2. Replace the genset control PCB (see Section 8).
UNDERVOLTAGE FAULT—CODE NO. 13
(Controller not able to regulate to rated voltage)
Corrective Action:
1. Turn the genset line circuit breaker OFF. If the genset runs without shutting down, run the genset with fewer connected loads.
2. Check power factor. Disconnect loads that cause a power factor of 0.5 or less.
3. Service the brushes and slip rings as necessary (see Servicing Brushes and Slip Rings in Section 7).
4. Test the generator field, stator and guadrature windings for opens or shorts. Replace the gener­ator rotor or stator assembly if winding resistance is not as specified in Section 7.
5. Replace the genset control PCB (see Section 8).
WARNING
!
Page 70
Redistribution or publication of this document,
by any means, is strictly prohibited.
10-4
TABLE 10–1. TROUBLESHOOTING (CONT.)
Some genset service procedures present hazards that can result in severe per-
sonal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery hazards should perform genset service. See Safety Precautions.
OVERFREQUENCY FAULT—CODE NO. 14
(Controller not able to regulate to rated frequency)
Corrective Action:
1. Check the governor linkage for binding and service as necessary (see Governor Linkage and Actuator in Section 6).
2. Check the governor controller board (see Section 9).
UNDERFREQUENCY FAULT—CODE NO. 15
(Controller not able to regulate to rated frequency)
Corrective Action:
1. Turn the genset line circuit breaker OFF. If the genset runs without shutting down, run the genset with fewer connected loads.
2. Fill the LPG fuel tank if less than half full. On cold days the LPG container may have to be kept at least half full to provide the rate of vaporization required to keep up with genset fuel demand. LPG with more than 2.5 percent butane will not vaporize below 32
° F (0° C). Use HD-5 grade LPG.
3. Inspect/secure the spark plug cable on the spark plugs.
4. Service the air cleaner.
5. Check fuel solenoid valve operation (see Fuel System in Section 6).
6. Check the gas supply pressure and adjust as necessary (see Fuel System in Section 6).
7. Conduct the ignition system tests and service as necessary (see Ignition System in Section 6).
8. Check for a blocked exhaust system and service as necessary.
9. Check the governor linkage for binding and service as necessary (see Governor Linkage and Actuator in Section 6).
10. Check magnetic pick-up for proper operation (See Section 6-5).
11. Check the governor controller board (see Section 9).
12. Conduct a cylinder compression test and service the engine if it is worn or malfunctioning.
13. Replace the genset control PCB (see Section 8).
AC OUTPUT SENSE FAULT—CODE NO. 27
(Controller unable to sense output voltage)
Corrective Action:
1. Check AC sense circuitry (Voltage Sense Input signal to genset control PCB) for continuity. See Wiring Diagram in Section 11.
2. Check resistance of AC sense transformer:
H1 to H2 - 309 ohms
±10%
X1 to X2 - 391 ohms
±10%
3. Replace the genset control PCB (see Section 8).
WARNING
!
Page 71
Redistribution or publication of this document,
by any means, is strictly prohibited.
10-5
TABLE 10–1. TROUBLESHOOTING (CONT.)
Some genset service procedures present hazards that can result in severe per­sonal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery hazards should perform genset service. See Safety Precautions.
HIGH BATTERY VOLTAGE FAULT—CODE NO. 29
(Voltage across battery system greater than 17.5 volts)
Corrective Action:
1. Test the battery charging system and service as necessary.
LOW CRANKING SPEED FAULT—CODE NO. 32
(Cranking speed less than 180 rpm for more than 2 seconds)
Corrective Action (When engine is cranking slowly):
1. Clean and tighten the positive (+) and negative (–) battery cable connections at the battery and
at the genset.
2. Recharge or replace the battery. See the battery manufacturer’s recommendations.
3. Replace the engine oil with oil of proper viscosity for the ambient temperature (p. 2–1). (High oil viscosity can slow cranking speed.)
4. Test the battery charging system and service as necessary.
Corrective Action (When engine appears to be cranking normally):
1. Disconnect genset control connector P1 (refer to Section 8 to remove connector P1) and check for electrical continuity across pins P1-1 and P1-10 (field windings). If the circuit is open, service the generator brush block and slip rings and repeat the test. Service or replace the generator rotor if the circuit is still open (Section 7). (Speed sense signal is generated from this circuit.)
2. Disconnect genset control connector P1 and check for electrical continuity across pins P1-3 and P1-9 (quadrature windings). Replace the generator stator assembly if the circuit is open (Section 7).
3. Replace the genset control PCB (see Section 8).
CONTROL CARD FAILURE FAULT—CODE NO. 35
(Microprocessor EEPROM error during self-test)
Corrective Action: Replace the genset control PCB (See Section 8).
WARNING
!
Page 72
Redistribution or publication of this document,
by any means, is strictly prohibited.
10-6
TABLE 10–1. TROUBLESHOOTING (CONT.)
Some genset service procedures present hazards that can result in severe per-
sonal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery hazards should perform genset service. See Safety Precautions.
MECHANICAL FAULT—CODE NO. 36
(Engine stopped without command by controller)
Corrective Action:
1. Fill the LPG fuel tank if less than half full. On cold days the LPG container may have to be kept at least half full to provide the rate of vaporization required to keep up with genset fuel demand. LPG with more than 2.5 percent butane will not vaporize below 32
° F (0° C). Use HD-5 grade LPG.
2. Inspect/secure the spark plug cable on the spark plugs.
3. Service the air cleaner.
4. Check continuity through S5 switch at idle and during operation.
5. Check fuel solenoid valve operation (see Fuel System in Section 6).
6. Check the gas supply pressure and adjust as necessary (see Fuel System in Section 6).
7. Disconnect genset control connector P1 (refer to Section 8 to remove connector P1) and check for electrical continuity across pins P1-1 and P1-10 (field windings). If the circuit is open, service the generator brush block and slip rings and repeat the test. Service or replace the generator rotor if the circuit is still open (Section 7). (Speed sense signal is generated from Q1 - Q2 circuit.)
8. Check pin connections to controller.
9. Conduct the ignition system tests and service as necessary (see Ignition System in Section 6).
10. Check magnetic pick-up for proper operation (see Section 6).
11. Conduct a cylinder compression test and service the engine if it is worn or malfunctioning.
12. Replace the genset control PCB (see Section 8).
FIELD OVERLOAD FAULT—CODE NO. 38
(To many low power factor loads)
Corrective Action:
1. Reduce the number of appliances running at the same time, especially those with high motor starting loads such as air conditioners.
2. Have air conditioners and other appliances checked for proper operation. (A locked compressor rotor can cause very low power factor.)
3. Check pin connections.
4. Check brushes (see Section 7).
5. Test Rotor (see Section 7).
GENERATOR ROTOR FAULT—CODE NO. 41
(Controller failed to sense field voltage)
Corrective Action:
1. Check brushes (see Section 7).
2. Test rotor (see Testing the Generator in Section 7).
PROCESSOR FAULT—CODE NO. 42
(Microprocessor ROM error during self-test)
Corrective Action: Replace the genset control PCB (see Section 8).
WARNING
!
Page 73
Redistribution or publication of this document,
by any means, is strictly prohibited.
10-7
TABLE 10–1. TROUBLESHOOTING (CONT.)
Some genset service procedures present hazards that can result in severe per­sonal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery hazards should perform genset service. See Safety Precautions.
PROCESSOR FAULT—CODE NO. 43
(Microprocessor RAM error during self-test)
Corrective Action: Replace the genset control PCB (see Section 8).
SPEED SENSE FAULT—CODE NO. 45
(Controller failed to sense quadrature frequency)
Corrective Action:
1. Check all pin connections and pin condition. Replace as necessary.
2. Disconnect genset control connector P1 (see Section 8 to remove connector P1) and check for electrical continuity across pins P1-1 and P1-10 (field windings). If the circuit is open, service the generator brush block and slip rings and repeat the test. Service or replace the generator rotor if the circuit is still open (Section 7).
3. Disconnect genset control connector P1 and check for electrical continuity across pins P1-3 and P1-9 (quadrature windings). Replace the generator stator assembly if the circuit is open (Section 7).
4. Replace the genset control PCB (see Section 8).
FIELD SENSE LOST FAULT—CODE NO. 48
(Controller failed to sense field voltage)
Corrective Action: Replace the genset control PCB (see Section 8).
WARNING
!
Page 74
Redistribution or publication of this document,
by any means, is strictly prohibited.
10-8
THIS PAGE LEFT INTENTIONALLY BLANK
Page 75
Redistribution or publication of this document,
by any means, is strictly prohibited.
11-1
11. Wiring Diagrams
GENERAL
This section consists of the schematic and wiring diagrams referenced in the text. the following drawings are included:
Page 11–2, Transfer Switch
Page 11–3, Schematic Diagram
Page 11–4, Genset Harness
Page 11–5, Control Harness
Page 76
11- 2
Page 77
11- 3
Page 78
11- 4
Page 79
11- 5
Page 80
Redistribution or publication of this document,
by any means, is strictly prohibited.
Loading...