Onan Ensign 4500, Ensign 6500 Installation Manual

Page 1
Caution: This document contains mixed page sizes (8.5 x 11 or 11 x
17), which may affect printing. Please adjust your printer settings according to the size of each page you wish to print.
Page 2
MCE
Ensign
Series
4500/6500
in
U.S.A.
927-0600
8-93
Page 3
Safetv
Precautions
Before
operating
the
generator
set,
read the Operator's
Manualand become familiarwithitand your
unit.
Safe
andeffl-
cient operation
can
be
achieved only
if
the
unit
is
properly
operated
and
maintained.
Many accidents are caused
byfail-
ure
to
follow
fundamental
mles
and
precautions.
Thruugkout
this
manual you
will
notice symbolswhich alert
you
to
potenliaHy
dangerous conditions
to
the operator, service
per-
sonnel,
or
the
equipment
itself.
.
l'
This
symbd warns
of
immediate
haz-
ards which
wiil
result in
severe
personal
fnjury
or
death,
EWARtMG,
This
symbol
refers to a hazard or unsafe
practice which can resuit in severe personal injury
or
death.
l%~cAu-tror\l
Thls
symbol
refers
to
a
hazard
or
unsafe
practh?
which can result in personal Injuv
or
prod-
oct
or
property
damage.
FUEL,
ENGINE
OIL,
AND
FUMES
ARE
FLAMMABLE
AND
TOXIC.
Fire,
explosion, and personal injury can result from
im-
proper practices.
Benzene and lead, found
in
some gasoline,
have
been
identified
by
some state and federal agencies
as
causing
cancer
Or
reproductive toxicity. When checking, draining
or adding gasoline, take care not
to
ingest, breathe the
fumchs,
or
contact gasoline.
Used
engine
oils
have
been identified
by
some state or
federal
agencies
as
causing cancgr
or
reproductive toxic-
ity.
When
checkingor changing engine
oil,
take
care
not
to
ingest,
breathe
the
fumes,
or
contact used oil.
Do
not
fill
fueltankswith the engine
running.
Do
not smoke
around
the
generator set area. Wipe up
any
oil or gas
spills.
Do
not
leave
oily
rags
in
engine compartment or on
the
generator
set.
Keep
this
and surrounding area clean.
InsprxAfuel
system
before each operation and periodically
while
running.
Equip the engine
fuel
supply
with
a
positive fuel shutoff.
Always
disconnect
the
battery
ground
(-)
lead
first
and
re-
conmct
it
last. Make
sure
you connect
the
batlery
cor-
rectly.
A
direct short across the battery terminals
can
CPUSCI
an explosion.
Do
not smoke while servicing batter-
ies.
Hydrogen gas given
off
during charging
is
very
explo-
sive.
Keep a fire extinguisher available
in
or near the engine
cornpa-tment and
in
other areas throughout
tke
vessel.
Use the correct
ex?inguisher
for the area. For most
types
of
fires,
an
extinguisher rated
AB6
by
the
NFPA
is
avail-
able
ancl
suitable for
use
on
all
types
of
fires except alco-
hol.
EXHAUST
GASES
ARE
DEADLY
e
Provide adequate ventilation. Equipthe bilge
with
a
power
exhauster.
Be
sure propuhion
and
generator set engine exhaust
zys-
terns are
free
of
leaks. Perform
thorough,
pcriodrc
in:pec-
tions
of
the
exhaust
system
and
repair
leaks immedistsly.
E:<haust
gases
are deadly.
Never sleep
in
the
vessel
with
the
generator
set
running
unless
the
vessel
is
equipped
with
an operating carbon
monoxide detector.
,
HOT
COOLANT
CAN
CAUSE
SEVERE
PERSONAL
INJURY
Hot
coolant
is
under pressure.
Do
not
loossn
the
coolant
pressure
cap
while
the engine
is
hot.
Let
the
engina
coal
before
opening
the
pressure cap.
MOVING
PARTS
CAN
CAUSE SEVERE
PERSONAL
INJURY
OR
DEATH
Do
not
remove
any
belt guards or covers
with
the
genm-
tor set
running.
Keep hands and
loose
clothing away from moving
parts.
Do
not
wear jewelry while servicing
any
part
of
the
genera-
tor
set.
Never step
on
the gsnerator set (aswhen entering
or
leav-
ing
the engine compartment).
It
can stress and break
unit
components, possible resulting
in
dangerous operating
conditions.
.
from
leaking
fud,
leaking exhaust fumes,
etc.
Before performing any maintenance on the gerierator
cet,
disconnect
its
batteries to prevent accidental starting.
do
not disconnect or connect battery
cables
if
fuel vapors
are
present. Ventilate the generator
set
compartment or
bilge
thoroughly
with
the power exhauster.
ELECTRICAL
SHOCK WILL
CAUSE SEVERE
PERSONAL
INJURY
OR
BEATH
Do
not
make adjustments
in
the
control panel
or
on
engine
with
unit
running.
High voltages
are
present.
Work
that
must
be
done
while
unit
is
running
should be done only
by
qualified
service
personnel
standing
on
dry
surfaces
to
re-
duce shock hazard.
.
DO
NOT
CONNECT
THE
GEldEFWTOR
SET
TO
THE
PUBLIC
UTILllY
OR
TO
ANY
OTHER ELECTRICAL
POWER
SYSTEM.
Etectrocuti n or damage
to
property
can occur
at
a
sita
remote
from the
boat where
line
cor
equipment repairs are being
made
if
the
st
is
connected
tothe
power
system.
An
approved
bander
switch
mu3
be
used
if
more
than
one
power source
iz
to
be
made
avail-
able
to
service the
boat.
Do
not workon thisequiprnentwhen
~enfa:llyor
physically
fatigued,
or
after consuming
any
alcohol or
drug
that
makes
the
operation
of
equipmmt
unsafe.
bit
8
Copy
and
post
these
suggestloris
in
potential
hazard
areas
of
the
vessel.
Page 4
Table
of
Contents
SECTION
TITLE
PAGE
1
.
2
.
3
.
4
.
5
.
6
.
7
.
8
.
9
.
10
.
SAFETY PRECAUTIONS
...............................
Inside
Front
Cover
INTRODUCTION
...................................................
1-1
General
.........................................................
1-1
Installation Codes and Safety Recommendations
........................
1-1
Generator
Details
.................................................
2-1
Engine Details
...................................................
2-1
Location
........................................................
3-1
Mounting
........................................................
3-1
General
.........................................................
4-1
Requirements
....................................................
4-1
Coast
Guard
and
NFPA
Requirements
................................
4-1
General
.........................................................
5-1
Heat Exchanger Cooling
............................................
5-1
SPECIFICATIONS
..................................................
2-1
LOCATION AND MOUNTING
.........................................
3-1
VENTILATION
.....................................................
4-1
COOLING SYSTEM
.................................................
5-1
Sea Water Cooling
................................................
5.3
Combined Cooling Systems
.........................................
5.3
EXHAUST SYSTEM
................................................
6.1
General
.........................................................
6.
1
Below Load Waterline
Installation
....................................
6-3
Above
Load Waterline Installation
....................................
6-4
FUELSYSTEM
....................................................
7.1
General
.........................................................
7-1
Installation
......................................................
7.1
Fuelianks
......................................................
7.2
Fuel tines
........................................................
7.3
SiphonProtection
.................................................
7-3
FuelSystemTest
.................................................
7-3
ELECTRICAL SYSTEM
..............................................
8-1
General
.........................................................
8-1
Load
Connections
..................................................
8-1
Remote
Starting
Controls
...........................................
8-4
Batteries
........................................................
8-4
Installation
Checks
................................................
9.1
Initial Starting
and Checks
..........................................
9-1
FINAL INSTALLATION CHECKS
......................................
9.1
DC
WIRING
DIAGRAM
.............................................
10-1
i
Page 5
Page 6
Section
1.
Introduction
GENERAL
Each marine generator set must be installed properly
if
it
is
to
operate reliably, quietly, and most important
-
safely. Therefore, read this entire manual before starting the installation. The manual should be used only as a guide as each installation must be considered on an individual basis. For operation and maintenance proce­dures, refer to the MCE Operator‘s Manual
927-0124
which accompanies each unit
Proper installation is very important Requirements to
consider should include:
Adequate cooling air
a
Adequate combustion air
a
Discharge
of
exhaust gases
a
Discharge
of
circulated air Electrical connections and bonding Fuel connections Sea water connections
a
Accessibility for operation and servicing
a
Level mounting surface
a
Adequate support under mounting points
a
Noise levels
INSTALLATION
CODES AND SAFETY
RECOMMENDATIONS
The insthation must follow recommendations of the American Boat and Yacht Council (ABYC) and the National Fire Protection Association (NFPA).
The installer should be familiar with and follow the appropriate guidance found in the following publications:
ABYC
“Safety
Standards
for
Small
Craft”from:
ABYC
15
East
26th
St
New York, NY
10010
NFPA302
“Fire
Protection
Standard
for
Motor
Craif”from:
NFPA
470
Atlantic Avenue
Boston, MA
02210
USCG 33CFR183 from:
U.S.
Government Printing Office
Washington, D.C.
20404
~AWARNING
1
INCORRECT SERVICE
OR
REPLACEMENT OF PARTS CAN RESULT IN SEVERE
PERSONAL INJURY, DEATH, AND/OR EQUIPMENT DAMAGE. SERVICE PER-
SONNEL MUST BE QUALIFIED TO PERFORM ELECTRICAL AND/OR MECHANI-
CAL SERVICE.
1
=I
Page 7
Page 8
Section
2.
Specifications
GENERATOR
Type
................................................
Revolving Field, 4-Pole, Self-Excited
Standby Ratings:
60 Hertz, 6.5 MCE
...........................................
6.5
kW, (6.5 kVA
@
1.0
PF)
60 Hertz, 4.5 MCE
...........................................
4.5 kW, (4.5 kVA
@
1.0
PF)
50
Hertz,
5.0
MCE
...........................................
5.0
kW,
(5.0
kVA @ 1.0 PF)
AC Voltage Regulation
.............................................................
+5%
Frequency Regulation
......................................................
.5%
(3 Hertz)
ENGINE
Engine Type
............................................
Onan@ MCE, 2-Cylinder Opposed
Engine Speed (r/min)
.........................................................
I800/1500
Exhaust Outlet Hose Size
...............................................
.2.0 in. (50.8 mm)
Fuel..
..............................................................
Unleaded, 88 octane
Fuel Inlet Size..
............................................................
.1/4-18 NPT
Fuel Consumption, Average
@
Full Load:
60 Hertz, 6.5 MCE
....................................................
1.3 gph
(5.0
Lph)
60 Hertz, 4.5 MCE
....................................................
1.6 gph
(6.1
Lph)
50
Hertz,
5.0
MCE
....................................................
1.1 gph (4.2 Lph)
Fuel Inlet Size..
.........................................................
1/4-18 NPTF
Fuel Return Outlet Size
...................................................
.1/8-27 NPT
Minimum Cold Cranking Amps
@
0°F (-18°C).
......................................
360
Voltage
...........................................................................
12
Capacity, Heat Exchanger System..
....................................
.10 Quarts (9.4 L)
Heat Rejection:
60 Hertz
@
Load, Block & Exhaust Manifold..
............................
800 BTU/min
50
Hertz @ Load, Block & Exhaust Manifold..
............................
650 BTU/min
Heat Exchanger System, Thermostat Open
.........................
.2.2 gpm (8.3 L/min)
Sea Water, Heat Exchanger System
..............................
.3.0 gpm (1 1.4 L/min)
Sea Water Cooling System
......................................
-3.0
gpm
(1
1.4 L/min)
Heat Exchanger System, Thermostat Open
.........................
.2.2 gpm (8.3 L/min)
Sea Water, Heat Exchanger System
...............................
.2.5 gpm (9.5 L/min)
Sea Water Cooling System
.......................................
.2.5 gpm (9.5 L/min)
Sea Water Pump
Dry
Lift, Maximum
............................................
3
ft
(0.9 m)
Total Air Required (Generator Cooling and Combustion):
60 Hertz..
....................................................
.146 ft3/min (4.1 m3/min)
50
Hertz
....................................................
120 cu. ft./min (3.4 m3/min
Engine Oil Capacity with Filter
............................................
.3 Quarts
(2.8
L)
Battery Requirements:
Cooling System:
Cooling Flow Rate, 60 Hertz:
Cooling Flow Rate,
50
Hertz:
2-1
Page 9
Page 10
Section
3.
Location
and
Mounting
LO
CAT1
ON
Generator set location is preferable in the same room or compartment as the propulsion engine, as this is usually a
well
ventilated area, insulated, close to the fuel supply and isthe center of electrical load distribution. However, a generator set cannot be installed in the propulsion engine compartment unless specific conditions are met.
USCG
regulation
33CFR183
pertains to gasoline fuel systems, and requires a generator set operating in a gasoline fuel environment to be “ignition protected.”
This means a set capable of operating in an explosive environment without igniting that environment. Properly installed and operated, the
MCE
generator set can
operate in an explosive environment.
Gasoline fire or explosion can result in severe personal iniury or death.
Do
not installa gasoline generator set in the same room or compartment
of
a
diesel propulsion engine or generator set. The diesel unit may not be ignifion protected and may ignite gasoline fumes. Be sure
a
gasoline generator
set
is
insfalled in its own room or compartment.
MOUNT1
NG
The floor must be flat and givesupport directly underthe genset mounting points (Figures
3-1
and
3-2).
A
one
inch
(25
mm)
clearance around the unit is required to
permit rocking on its mounts without restraint; and
4.2
inches
(106
mm) for servicing the oil filter. Additional space must be allowed for proper ventilation for cooling and combustion, as well as service access.
Also
allow
access for periodic maintenancesuch as oil fill, coolant
fill,
spark plug replacement, etc. The entire exhaust
system must be accessible
so
a periodic visual and
audible check for leakage can be made by the operator. Install
two
hold-down clamps ortwo through boltsto the drip pan on both sides of the generator set. Tighten the clamps securely to the mounting base with bolts and
flatwas hers.
Select a location that will allow adequate space on all
sides for ventilation and servicing the set, preferably on and parallel with the keel or vessel center line. Keep the generator set away from living quarters, and away from bilge splash and vapors.
3-1
Page 11
2
(i
I
3
FIGURE
3-1.
DRIP
PAN
DIMENSIONS
DIMENSIONS
IN
(
4.k
"i"
)
ARE
METRIC
3-2
Page 12
(HEAT EXCI
SIDE
VIEW
NOTES
I
I
.DIMENSIONS IN
t
l
ARE
MILLIMETERS
2.DRY
WEIGHT! 335
LBS
(152
Kgl
COOLANT
FILL
iANGER
MODEL
ONLY)
C
CONNECTION
.I2
(d
HOLE(FARSIDE1
FRONl
IL
FILL
COOLANT FILL
(HEAT
EXCHANGER MODEL ONLY1
1.19
4
I
/WET
EXH!
1
18.04(30.2)
{
20.43
4
l518.9)
2.00
ID
HOSE 20.25
(50.8) (458.31
4.18 (106.2)
OIL
FILTER
REMOVAL
(514.3)
FIGURE
3-2.
OUTLINE DRAWINGS
3-3
Page 13
Page 14
Section
4.
Ventilation
GENERAL
The installation of boat ventilation systems must meet all Coast Guard and
NFPA
requirements. Establishing the
correct
air
flow quantity
is
particularly important with
small compartments under 1000 cubic feet
(28
m3), or installations in close quarters. Ventilation systems meet­ing Coast Guard requirements for gasoline engines in
passenger vessels (Table 4-1) will normally suffice, however special consideration must be given to com­partment conditions during operation.
TABLE
4-1.
PASSENGER VESSEL
VENTILATION REQUIREMENTS
SIZE
OF
MINUTES REQUIRED
COMPARTMENT TO EXCHANGE TOTAL
Cu.
Ft.
(m3)
AIR VOLUME
Less
than
500
(14)
2
500
to
1000 (14
to
28)
1000
to
1500 (28
to
42)
1500
and
Up
(42
and
Up)
3
4
5
REQUIREMENTS
Marine generator sets must have air ventilation for three
very important reasons:
1.
To remove flammableor other harmful gases.
Coast
Guard regulations require power blowers in the generator set and propulsion engine rooms be run at least four minutes priortostarting the engineand during operation. The operator must also inspect the engine room
for
the presence
of
fuel vapors prior to starting, especially when gasoline fueled equipment is used (see text under Coast Guard and
NFPA
Requirements).
2.
To
provide engine combustion
air
and generator
cooling air.
Coast Guard regulations require power exhausters in all installations, and one blower in each exhaust duct. Exhausters must have an air capacity
1-1
/2
to 2 times the minimum generator
set total air requirements. The
MCE
generator set
requiresa total operation minimum of 146 cubic feet
per minute
(4.2
m3/min).
3.
To
control compartment temperature during
genset operation.
This will avoid overheating which can result in shutdown from vapor lock, engine and related control component damage, and power loss.
As
a general rule, the operating environment
for a gasoline genset should not be higher than
14OOF (60OC) maximum. Lower temperatures are recommended. Often an operating power blower may be required to maintain temperature when the
genset is operating, especially when the boat is not
moving.
The compartment must have air inlets and outlets to provide this air. Inlet ducts should have cowls or equi­valent fittings of twice the area of the duct, larger if the opening
is
screened.
Do
not use recessed
or
flushed
inlets, or louvered transom outlets. If the gasoline fuel tank is in a separate compartment,
it
also must be ventilated.
COAST
GUARD
AND NFPA
REQUIREMENTS
Both organizations require at least
two
inlet ducts and
two
outlet ducts extending to the bilge for gasoline
generator set installations in
a
closed Compartment. When not in a closed compartment, at least one duct should be installed in the fore section of the boat and another aft. The
NFPA
recommends a vent size of at
least
two
square inches per foot
(42.3
cm2/m) of boat
beam for total inlet area and total outet area. Boats classified as pleasure vessels by the Coast Guard
must have sufficient ventilation to eliminate accumula­tion of flammable gases. Boats under
65
feet
(20
m) long classified as passenger vessels require ventilation be sufficient to change the compartment air within a given time interval (Table 4-1).
For passenger vessels, the Coast Guard recommends a mechanical exhausting system to meetthe requirement in Table 4-1. The exhaust blower motors should be outside the compartment.
If a gasoline fuel tank is in a separate compartment, it must be ventilated to the same requirements as the engine compartment.
4-1
Page 15
Page 16
Section
5.
Cooling
System
GENERAL
Throughout this manual, flotation water drawn into the boat for engine cooling iscalled sea water. Water recircu­lated through the engine closed system is called captive water. Thus, confusion is avoided with other generic terms describing water use.
The
two
types of marine cooling systems covered in this
manual are
heat exchanger
and
sea wafer
cooling. An
explanation
of
each system, and the advantages and disadvantages of each are covered in separate chapter headings. The heat exchanger system is ordered most often and is standard on the
MCE
generator set Sea
water cooling is an available option.
System
Plumbing
To adequately cool the generator set under all conditions, the plumbing system must be properly planned and
installed. Excess lengths of plumbing increases flow
resistance and results in reduced cooling. An air leak in the sea water intake will reduce cooling, cause corrosion, and can even destroy the neoprene impeller in the
sea
water pump. The neoprene impeller must never be run dry, and should be primed before initial start
The water line should have a minimum inside diameter of
0.75
inch
(1
9
mm). For runs over
20
feet
(5.2
m), increase
the line one pipe size for each additional
10
feet
(2.6
m) of length. Water lines can be either copper tubing or flexible hose. Be sure a length of flexible hose is used at the generator set connection to allow set movement and for noise abatement
Unless the sea water is very clean, Onan recommends a water strainer or filter to protect the sea water cooling system. See Figure
5-1.
Onan has a hull strainer (furnished with some muffler kits) that can be used with a flush through-hull fitting. The strainer (Figure
!SI),
installed with theslots parallel to the keel, helps prevent pressure or vacuum when the boat is underway. Always use a flush-type inlet with a hydrody­namic marine muffler.
The flush-fype through-hull wafer
inlef must have
an
opening at least as
lame as fhe wafer inlef line.
TO
GENERATOR
SET
RECOMMENDED
WATER
STRAINER
OR
FILTER
FLUSH
THRU-
HULL
FllllNG
STF
CROSS-SECTION
VlMl
HULL.
--WNER
CS-1312-1
FIGURE
5-1.
SEA
WATER
INLET
Stagger the generator set water inlet
so
it is not directly in
line with other inlets. Not doing
so
can reduce the amount of sea water available to the generator set when under­way and cause overheating. Never use scoop type water inlet fittings with a hydrodynamic muffler.
-1
Do
not use scoop
fype
wafer inlet
fit-
tings with a hydrodynamic muifler.
Forward
facing
scoops can develop suiiicienf
rampres-
sure
to force wafer
past
the
generator
sefs
sea
wafer
pump. This can floodfhe exhausfsystemandfhe engine
cylinders. This
happens
when the generator set
is
not
running and the boat
is
underway.
Rear
iacing scoops
develop vacuum which can impede
ding
wafer flow.
HEAT EXCHANGER COOLING
This cooling system, standard on the genset, keeps sea water and the resulting sediment deposits
(salt,
silt, etc.),
from the engine cooling jacket It also provides more
uniform cooling and temperature control in the engine.
Sea water and captive water are kept separated, and the engine water jacket stays clean for optimum heat transfer.
5-1
Page 17
Figure
5-2
shows the flow direction of sea water and
captive water. The sea water pump constantly renews the cool water bath in the heat exchanger and exhaust system. The captive water is circulated by a pump through the engine block, heat exchanger, and the exhaust manifold. The captive water temperature and flow rate are controlled
by
thermostats.
Each genset has a recoverytank kit to be installed in the
captive cooling system. The tank (similar to automotive application) is connected to the overflow fitting below the pressure cap. It keeps the captive system filled with coolant which helps prevent corrosion and sediment. The tankshould be locatedforeasychecking
of
coolant level, and for serviceability. lnstallation instructions are furnished with the kit.
BELT-DRIVEN
SEA
WATER PUMP HEAT EXCHANGER
r-
I
FROM
SEA
WATER INLET
The captive cooling system should always use a
50-50
mixture of ethylene glycol and distilled water to help prevent corrosion. See the
lnstallation Checkout
sec-
tion for filling instructions. If a heat exchanger other than the Onan standard is
installed, several precautions are required as follows:
The heat exchanger must properly cool thegenera-
tor set under all load conditions.The Onan system is
designed to cool the set at full load with sea water inlet temperatures up
to
1
OOOF
(38OC).
Extra margin
(10%)
must be allowed for varying conditions of
pumps, coolant and scale build up. Minimum captive water and sea water flow required
by the generator set must be met. The heat exchanger will also have minimum and maximum flow requirements which must be met for cooling at
its capacity. The generator set requirements are
listed in the
Specificafion
section.
r*
I
I
t
I
I
I
I
.-*----
t
MANIFOLD
(MIXER)
EXHAUST AND
SEA
WATER OUTLET
TO
MUFFLER
by Separate Pump
--P
Captive Cooling Water Circulated by
cs1369
....
FIGURE
5-2.
COOLANT
FLOW, HEAT EXCHANGER COOLING SYSTEM
5-2
Page 18
SEA WATER
COOLING
The sea water cooling system is shown in Figure
5-3.
This
system
uses
the belt-driven
sea
water pump to direct water through the engine cooling system and out the exhaust system. The electric circulating pump
is
not used on this system. The engine blocks have a drilled coolant bypass hole to allow some coolantflow regard­less of thermostat opening. This allows for exhaust cool-
ing and protection of the pump. The sea water and exhaust is disposed
of
similarly as described in Heat
Exchanger Cooling with a hydrodynamic muffler (above
or
below water line installation).
The sea water comes into direct contact with the engine cooling jacket, and this system should be avoided for
use
in salt
or
contaminated water. Such water can cause engine block corrosion and/or plugging; there­fore, heat exchanger systems are recommended.
.
COMBINED
COOLING
SYSTEMS
Onan does not recommend combining the generator set cooling system with the propulsion engine cooling sys-
tem. This involves a great amount of experience and
knowledge for the installer, as well as complete know­ledge
of
characteristics of both the generator set and
propulsion engines.
Propulsion engines use scoop-type water inlet fittings which must not be
used for a generator set with a hydrodynamic muffler.
When not operating, ram pressure can force waferpast
the generator set’s sea water pump and flood the exhaust system. From here it can flow back, flooding the engine cylinders and possibly the engine com-
partment.
BELT-DRIVEN
SEA
WATER
PUMP
EXHAUST
MANIFOU)
I
,-
I
EXHAUSTMANIFOLD
/I\
FROM
SEA
I
(MIXER)
/I\
+
WATER
INLET
I
re
I
EXHAUST AND
SEA
WATER OUTLET
TO
MUFFLER
I
I
+
I
I
I
FIGURE
5-3.
COOLANT
FLOW.
SEA
WATER
COOLING
5-3
Page 19
Page 20
Section
6.
Exhaust
System
GENERAL
The installation of
two
water-cooled exhaust systems are covered in this section. They are below-load waterline and above-load waterline, and are covered under separ­ate headings.
All
exhaust systems for water-cooled marine installations must meet each of the following requirements. Failure to meet these requirements could result in severe property damage, personal injury or
death.
b
The entire exhaust system must be accessible
so
a
periodic visual and audible check for leakage can be
made by the operator.
0
The exhaust system must be water cooled, and the water injected as near to the generator set as possible.
0
All
exhaust system sections preceding the point of
water injection must be water jacketed or effectively
insulated or shielded.
0
The exhaust line must be installed to prevent back flow of water to the engine under any conditions; and the exhaust outlet must be above the load waterline.
Water backflow into the engine will damage
it
The generator set exhaust system
must
not
be com-
bined with the exhaust system of another
engine.
0
A
flexible section of marine exhaust hose must be used near the engine to allow for engine movement and vibration during operation.
All
exhaust system
hoses must be CERTIFIED for marine use.
0
The exhaust system must be of sufficient size to pre­vent excessive back pressure. See Back Pressure data in this section.
Install exhaust through hull fitting aft of sink, shower or other cabin drains to prevent backflow of exhaust gases into the vessel.
Material
Use material recommended by ABYC in
“Safety
Standard
for
Small
Crafi,
”Section P1. The exhaust line must be at
least as large as the engine exhaust manifold outlet
See
following section on Back Pressure.
Exhaust gas contains carbon monox-
ide, an odorless, colorless, highly
poisonous gas that presents the hazard of severe
per-
sonal injuw
or
death. Place special emphasis on the
following:
0
Be
sure
the flexible exhaust hose
is
designed and
certified
for
marine exhaust line use.
Use
two
clamps at each end
of
all flexible exhaust
hose connections.
Do
not make shatp bends in the exhaust hose.
0
Position exhaust outlet
to
prevent backflow of
Use flexible hose designed and CERTIFIED for marine exhaust line use. The muffler must be at the lowest point of the entire exhaust system. The muffler top should be at least 12 inches
(305
mm) below the exhaust manifold outlet If it is higher, backflow of water toward the manifold is more likely.
Make sure the hose drains toward the muffler at
a
grade
of
1
/2
inch per lineal foot
(42
mm/m). An uphill section between the exhaust manifold and muffler can cause backflow of water and is not permissible
-
NO
EXCEPTIONS.
exhaust gases info the vessel.
Be
sure that the vertical rise
of
the exhaust hose mea­sured fromthe bottom of the muffler to its peak is not more than
48
inches (1.2
m)
as shown in Figure 6-1.
The exhaust tubing (on both above and below load water-
line installations) must be pitched downward to the
through-hull outletfitting ata minimum downgrade of 112
inch per lineal foot
(42
mm/m). There must also be a
12-inch
(305
mm) minimum drop from this peak to the
through-hull outlet fitting as shown in Figures 6-1 and
6-2.
Allow space between the marine muffler and
its
mounting surface by use of spacers under the mounting flanges. This allows air circulation under the muffler and discour­ages condensation build-up.
6-1
Page 21
Usetwo clamps at each end of hoseasshown in Figures
6-1
and
6-2.
The clamps must be
Of
corrosion resistant
metal, a minimum Of% inch
(12.7
mm) wide. They should
be spaced at kist one clamp width apart, and at least one
clamp widthfromtheend ofthe hose. Clamps depending
solely on spring tension must not be used.
Provide adequate support for hose lengths to prevent sagging, bending, and fOrmation
Of
water Pockets- The
use ofautomotive@Pe Pipe hangers
Will
help stop tms-
mission of vibration or noise to the boat hull.
Back
Pressure
Exhaust back pressure is an important criteria of an a&­quate exhaust system.
If
the exhaust installation requires
a long run of pipe (more than
30
feet
[9
m] overall), back pressure should be checked. Exhaust back pressure for the
MCE
generator set should not exceed
3.0
inches (76
rnm) of mercury
(10
kPa).
Increase theexhaust pipe diameter from the mufflertothe hull outlet one standard pipe size for every
10
feet
(3
m)
beyond
30
feet
(9
m) of overall length.
"\
TO GENERATOR
SET
SEA
c
RECOMMENDED FLUSH-TYPE, THROUGH-HULL FliTlNG
AND WATER STRAlNER (NOTSUPPUED
BY
ONAN)
.
FLUSH THRU-HULL Sk/VNER
CS-1312-1
FllTING
FIGURE
6-1.
BELOW
LOAD
WATERLINE
INSTAWTlON
6-2
Page 22
Exhaust
Cooling
Water
Injection
The neoprene impeller pump moves the
sea
water
through the
cooling
system and into the exhaust manifold. The injected water cools the exhaust and prevents exhaust system damage from heat
A
temperature oper­ated switch on theexhaust manifold shu tsthe unit down if overheating occurs. The switch closes if temperature reaches
175'
to
185°F
(79'
to
85'C)
and actuates the
Fault Reset breaker on the control panel.
If
high exhaust
temperature shutdown occurs, the entire exhaust system
should be checked for any signs
of
overheating, espe­cially the exhaust hoses. Replace defective components immediately, and do not operate the generator set until
Inhalation of exhaust gas
can
cause
jawnR"Gl
severe personal
injury
or
death.
Do
not operate the generator set after a high exhaust temperature shufdown until the entire exhaust system
has been checked
and
serviced as mquimd.
.
system is repaired.
DO
NOT
USE
SCOOP
TYPE
WATER
-1
INLET FITTINGS. Forward
facing
scoops
can
develop suificient ram
pressure
to
torce
wafer
past
the
generator set's
sea
waferpump. Thiscan
flood
the
exhaust system and the engine cylinders. This
happens when the generafor set
is
not running and the
boat
is
underway. Rear facing scoops develop vacuum
which
can
impede
cooling
water flow.
BELOW
LOAD
WATERLINE
INSTALLATION
Figure
6-1
shows details
of
a
recommended below load
waterline installation. Review and apply
data
from
the
preceding
G€N€ML
section, plus the following.
Siphon
Break
Install a siphon break (anti-siphon)
if
the
sea
water injec-
tion port on
the
exhaust manifold
is
at or below
the
load
waterline. The siphon break is a vacuum operated vent valve that opens the exhaust water discharge line to the atmosphere when the engine
is
not operating. The open
vent valve prevents
sea
water (flotation water) from being siphoned into the exhaust manifold and cylinders on engines installed below load waterline.
The siphon break hoses connect between the exhaust
manifold water injection port and the water tube from the heat exchanger. Connect the siphon break hose ends to
these connectors. Remove plug from top panel and route
hoses through the hole. Locate the siphon break in a vertical position at least
12
inches
(305
mm) above the load waterline.
See
Figure
6-1.
Remote mounting is permissible within a 5 foot
(1.5
m) radius
of
the injection port The vertical position and
height of the valve must be maintained.
HIGH EXHAUST TEMPERATURE
CUTOUT,SWITCH
TWO
HANGER
MINIMUM
DOWNGRADE
112
INlLlNEAL
FT
-------------------------------------------------------
LOAD WATERLINE
FIGURE
6-2.
ABOVE
LOAD
WATERLINE
INSTALIATION
6-3
Page 23
The siphon break must be mounted vertically with the threaded end pointed down. Use pipe strap material to secure the assembly to the frame or bulkhead. Be sure
the slotted opening in the siphon break valve is open to
atmospheric pressure. The valve will not function if the
slot
is closed in any way.
1-1
Failure to use a siphon break when the exhaust manifold injection port
is
at
or
below the load waterline will result in sea water
damage to the engineandpossible flooding of tbe boat.
ABOVE LOAD WATERLINE
INSTALLATION
Figure
6-2
shows detailsof a recommended above load
waterline installation.
A
siphon break valve is not required with this installation. Review and apply data from the preceding GENERALsection. Be sure the min­imum drop and downward pitch of exhaust runs are applied, and that all hose end connections have
two
clamps as shown.
6-4
Page 24
.
Section
7.
Fuel
System
GENERAL
Fuel leakage in boats presents fire
-1
and explosion hazards that can
result in severe personal injury
or
death.
For
this rea-
son,
it is important that the material, design, consfruc­tion and installation of all fuel system components meet the highest possible standards. Use only pro­ducts specified
for
marine application.
Make sure all fuel lines are properly supported and
connections tightened securely. Use an approved pipe joint compound acceptable for use with gasoline fuel at all thread fittings.
Fuel distribution lines must have as few connections as practicable, and be protected against mechanical injury and vibration. In all fuel system installations, cleanliness is very important. Take precautions to prevent the entrance of moisture, dirt or contaminants of any kind during installation.
If
possible, avoid the use of fuels composed of blends of gasoline and alcohol. Methanol notably can cause cor­rosion of metals and damage to plastic and rubber. Some blended fuels may have cosolvents in them to prevent damage, but the suitability of these fuels is not fully known at thistime. Fuel containing alcohol can also cause external paint damage
if
spilled during refueling. Some states require the use of labels on pumps to indi­cate alcohol content If unsure, ask the fuel station operator.
INSTALLATION
Any flexible fuel line installed between the fuel tank and the generator set must meet USCG requirement 33CFR183.558 and be stamped
“USCG
TYPEA”.
There cannot be an electrical connection between the hose end fittings. A bad ground in the cranking circuit will cause a wire reinforced hose to become hot and ignite the fuel during cranking. If a metallic fuel line is run into the generator set compartment, a length of flexible hose meeting the above specifications must be installed to absorb vibration from the generator set.
Ignition
of
fuel can cause fire and
severe personal injury or death. Be sure any flexible fuel line used between the fuel tank and the generator
set
meets
USCG
requirement
33CFR183.558
and
is
stamped
“USCG
TYPE
A”.
SERVICE
SHUT-OFF
VALVE
PROPULSION
ENGINE
GENERATOR
FUEL
TANK
FIGURE
7-1.
I
I
M-1679
INSTALLATION ABOVE TANK LEVEL
Leakage
of
gasoline in
or
around the
generator
set compartment presents
a hazard
of
fire
or
explosion and can cause severe
personal injury
or
death.
Do
not
permit
any flame,
spark, cigarette, pilot light, arcing equipment,
or
other ignition source near fhe generator set. The ventilation system must provide a constant flow
of
air
to
safely
expel all fuel vapors.
The fuel line should be run at
or
above level of the tank
top to a point close to the engine connection whenever
possible to prevent siphoning. See Figure 7-1.The line
should be supported throughout its length with clips
or
straps spaced at no more than 14-inch (355 mm)
intervals.
A
separate fuel line is recommended for the genset. If a fuel tank is shared, afuel linetee isnotrecommended-A tee can cause erratic set operation due to fuel starva­tion. The generator set’s fuel pump has neither the
capacity nor the power to overcome the draw of the propulsion engine fuel pump.
If the fuel tank fitting is large enough, a second, shorter
dip tube may be installed as shown in Figure
7-2.
The
required fittings can be built by a machine shop. Install
an anti-siphon device at the tank fitting as shown.
Page 25
FUEL LINE TO
PROPULSION ANTI-SIPHON FUEL UNE TO
ENGINE DEVICE GENERATOR
SET
HEX
HEAD
CAP
FTTTING
FIGURE
7-2.
TWO
FUEL LINES IN
TANK
FllllNG
1-1679.2
If
the tank does not have an unused outlet, a new outlet can be installed. The metal tank must be removed to braze
or
weld a new outlet fitting. This procedure
.
requires the service of a welder familiar with the essen-
tial safety measures.
1-1
Ignition
of
fuel vapors can cause
severe personal injury
or
death.
Welding a
fuel
tank, empty
or
not, is extremely danger-
ous!
Vapors can ignite causing an explosion and fire.
Another consideration is the generator set fuel pump
lift
capacity. The vertical height must not exceed 4 feet
(1.2
m), minus the requirement
of
an anti-siphon valve when
used,
or
the generator set operation can be adversely
affected.
FUEL
TANKS
Avalve must be installed directly at the tank connection to shut
off
fuel flow. This valve may be electrically
or
manually operated. If electrical1,y operated, it must be energized only during engine operation, and have a manual override to comply with
USCG
regulations. This electric valve can be purchased from Onan and is listed in the parts manual.
The manual valve must have an arrangement for operat­ing
it
outside the compartment in which the tank is
located, preferable from above deck. A USCG approved service shutoff valve must be
installed at the engine end of the fuel line under condi­tions listed below. This valve stops fuel flow when the genset is serviced.
0
When fueltanksare located in a compartment other
When the engine and fuel tanks are separated more
than the engine.
than
12
feet
(3.7
m).
If the propulsion engines and generator set usedifferent fuels, a separate fuel tank will be required. Use only an approved fuel tank designed
for
marine application. Be
sure thatthe Compartment is well ventilated (see
Ventila-
tion
System
section). Fuel consumption data in the
Specificafionssection is useful for determining the tank
size. When installing a separate tank, locate it as close as
possible to the generator set Compartment. Be sure it is accessible and can be removed for inspection.
Fuel starvation can cause marginal operation of the generator
set.
Fiber-
glass
fuel
tanks can present a problem if the fuel pick-
up tube is too.close
to
the tank bottom. Fiberglass
fibers can seftle and
form
a
mat
wifh
time.
Make
a
diagonal cut
on
the bottom
of
the pick-up tube and
install
35
to Pinches
(73
to
51
mm) from the fankbottom.
Mount the fuel tank and secure into position. The
NFPA
recommends that flat bottom tanks be installed on slat­ted wooden platforms to help prevent moisture conden­sation. Cylindrical tanks should be set in chocks
or
cradles and securely fastened. Small fuel tanks can be suspended from deck beams.
Support and brace the tank to prevent any movement.
Line up braces with the tank internal baffle plates. Insu-
late all wood
or
metal surfaces from the tank surface
with a non-abrasiveand nonabsorbent material. Heavy
rubber-impregnated cotton fabric or oil and acid-
resistant plastics work well.
Ignition of fuel
when
filling the tank
l&lZ@l
can result in
seuere
personal injury
or
death. All metallic fuel tanks
MUST
be
electrically
bonded to
the
boat common ground. Also bond the
filler neck
or
opening
to
the tank if a hose is used
between them. This helps prevent static spark when
filling that can ignite the fuel.
Position the tank
fill
and vent pipes
so
fuel
or
vapor
cannot escape into the bilge. Run the vent and
fill
pipes
from separate openings in the tank.
If
the
fill
pipe has a
flexible section of fuel hose, install aseparate grounding
wire between the deck fuel plate and tank. Install the
vent opening as far from any other hull opening as
possible and with a gooseneck
so
water cannot enter.
Install a flame arrester on the vent opening.
7-2
Page 26
FUEL LINES
The proper installation of fuel lines is very important Give special attention to the following requirements.
0
All
fuel line materials must meetthe requirementsof
both the USCG and the ABYC.
0
Solid fuel lines must be seamless annealed, double­flared, and approved for marine installations.
0
Run fuel lines at the top level of tank to a point as close to the engine as possible to reduce danger of fuel siphoning should the line break.
areas. This reduces chance of vapor lock.
I
.
0
Keep fuel lines away from hot engine or exhaust
0
Any locked-in torsional stresses must be avoided in
the fuel line.
0
Install a flexiblefuel line meeting USCG requirement 33CFR183.558, and stamped
“USCG
TYPE
A”
between the solid fuel line and engine to absorb vibration. The line length must be sufficient to pre­vent binding or stretching due to generator set movement.
,
FUEL LINE
I
TO
BOAT
I
COMMON BONDING
METALLIC
FUEL
CONDUCTOR
LINE FROM TANK
ES-1891
FIGURE 7-3. FUEL LINE BONDING
Install fuel lines
so
they
are
accessible and pro-
tected from damage.
Use non-ferrous metal straps without sharp edges
to secure the fuel lines every
14
inches
(355
mm).
Electrically bond a metallic fuel line to the vessel with a suitable bonding strap. The drip pan must also be bonded to thissame conductor asshown in Figure 7-3.
SIPHON
PROTECTION
A carburetor float valve cannot be trusted to stop fuel flow if there is gravity feed from the fuel tank. When the tank is installed above the engine level an anti-siphon device is needed to prevent
the
fuel from emptying into the carburetor if the float valve doesn’t close.
It
also prevents siphoning if the line
breaks at a point below the fuel level. Mandatory siphon protection must be provided by
installing a
U.S.
Coast Guard approved anti-siphon
device. See Figure
7-4.
This device can be installed at the tank withdrawal fitting, or at a location where the line from the fuel tank will no longer remain above the fuel tank top level. The device can be either a mechanical check valve
(1
f0.5
psi
[6.9
53.5
kPa]), or an electric valve with mechanical
override. The electricvalve must be connected
so
it
operates only when the engine ignition is on.
ANTISYPHON VALVE OR ELECTRICALLY
OPERATED FUEL STOP VALVE
M-1679
FIGURE
7-4.
SIPHON PROTECTION
FUEL SYSTEM TEST
After installation, test thefuel system fortightness by pumping air into the tank to a pressure Of
4
to 5 psi (28 to 35 kPa). Pressure must remain steady. If not, the leak must be found before putting the system into service.
7-3
Page 27
.
Page 28
Section
8.
Electrical
System
GENERAL
All
wiring &meet Coast Guard,
NFPA,
and
all
other applicable codes. Have all wiring installed by a qualified electrician. Onan wiring diagrams do not include com­ponents added by customers.
Faulty electrical equipment can
cause shock and severe personal
injury or
deafh.
Use
only approved power supply
the power cord. lncorrect
or
no ground may cause the
vessel to be electrically
"hot".
I
assemblies, and never remove the grounding pin from
LOAD
CONNECTIONS
While at dock, most boats have a dockside connection for use of commercial power. These installations must have a transfer switch to isolate the generator set and the commercial power. The
two
power sources never be connected together. A manual transfer switch is available from Onan for this function. See Figure
8-1.
Ignifion
of
explosive fumes can
IiEFi%I
cause severe personal injury
or
death. The load fransfer switch cannot
be
used
in
a
gasoline fueled environment unless certified
for
such
use. Separation
by
a bulkhead
or
deck is necessary.
Use a section of flexible conduit at the generator set to absorb vibration. Flexible, multistrand wire must be used throughout
to
reduce the danger
of
breakage due
to boat movement or vibration. The generator set
is
available in either 120-volt
(two-
wire) or 120/240-volt (three-wire) as shown in Figures 8-2 and
8-3.
The three-wire
(1
20/240-volt) genset must have the 120-volt loads balanced across thetwo gener­ator windings. Taking full load from only one winding can cause damage to the generator.
A
240-volt load is
connected across both windings. The 120-volt genset will haveasingle-pole breaker; the
120/240-volt genset will have a two-pole breaker.
ONAN
SWITCH
TO BRANCH CIRCUIT
PROTECTIVE DEVICES
300-0269
2-POLE,
120
VOLT
SYSTEMS
300-0270
3-POLE,
1201240
VOLT
SYSTEMS
OBSERVE
NEGATIVE
GENERATOR
SET
GROUND
'EQUIPMENT GROUNDING CONDUCTOR '(GREEN)
L
GROUNDED NEUTRAL CONDUCTOR (WHITE)
UNGROUNDED CONDUCTOR (BLACK)
UNGROUNDED CONDUCTOR WHEN USED
(BUCK)
-
GENEGATOR
---------------
SHORE-POWER DISCONNECT
/
CIRCUIT BREAKER
FROM
DOCKSIDE
POWER SOURCE
'Equipment ground
is
not part
of
generator
wiring:
must be customer installed
if
required.
FIGURE
8-1.
TYPICAL
MANUAL
TRANSFER
SWITCH
CIRCUIT
c
Page 29
I
A1
1
CB22 CR21
G21 T21
RV21
TB1,2
ROHT
PANEL
(REAR
VIEW)
PCB ASSY, ENGINE MONITOR CIRCUIT BREAKER,
LOAD
BRIDGE RECTIFIER GENERATOR, AC TRANSFORMER ASSY
SUPPRESSOR ASSY
STAND-OFF INSULATOR
CONNECTION
SEE
NOTE
2
I
I
I
I
RV2
I
i
.
FIGURE
8-2.
GENERATOR AC WIRING DIAGRAM
8-2
Page 30
COMPONENT IDENTIFICATION
1
CRZI-AC
A1 1
CB22
cR21
621
TB1,2
RV21
T21
PCB ASSY, ENGINE MONITOR CIRCUIT BREAKER, LOAD BRIDGE RECTIFIER
.
GENERATOR, AC TRANSFORMER ASSY
SUPPRESSOR ASSY
STAND-OFF INSULATOR
x
NOMINAL NOLOADVAC
127.5?4.5
LEADS
TOMCRUSE HOYWAL
NO
VAC
x3
x4
TO
ADJUST
WlRlT
VOLTAOL,MOVE TAPSONT21
ACCDRDINB
TD
TABLES. I.IN ALL WLTAQECOmECTKmS
LEAVETIAHIT4
t.FOR6DHz:VSE?%LUDONTIPSXI-2
3.
IF
CS.22
IS
NOT
USED
CWNECr
LEADS
DlPEClLY
4.UNLESS
UlHfRWlSE
&,ALL
COMWNCMS
AESHOWN
IN
5.
MSND
LINESINC4CATEWHEN~
Lo
L2
LI
CONNECTED
TOHI
ANDIH
REspEcnvw.
(4
TApSlW
W%. [ FROM
OENl
WD
ONTAPS
x5.4
TO
%E
LOAD.
THEDE-D(CRGIZEDPOS~ON
FIGURE
8-3.
GENERATOR AC SCHEMATIC DIAGRAM
8-3
Page 31
REMOTE STARTING CONTROLS
Onan has control panel kits available for remotestarting and stopping of the genset The kits vary from a basic single-pole, double-throw, momentary-on switch on up to remote-gauge controls with running time meter, bat­tery condition meter, and engine monitors. The kits come with installation instructions and wiring diagrams for connection.
The control panels are prewired and terminate with a plug connector. See Figure 8-4. Onan has prewired harness assemblies in
15,25,
and 45 foot lengths (4.6,
7.6,
and
13.7
m) with plug connectors that connect to the generator set control boxand the remote panel. Multiple remote stations are possible with parallel hard-wiring. The genset can be started and stopped from any station, including the set itself. Engine monitor gauges can be used on only one panel (generator set or remote).
If prewired harnesses are not used, number 16-gauge
wire is acceptable if runs do not exceed
25
feet (7.6 m)
between the remote switch and the genset. Use number
14-gauge wire for longer runs.
-1
lnterchanging connections other ihan shown on the generator set wir-
ing
diagrams can cause equipment damage.
BATTERIES
General
Always use a battery at least as large as specified. The battery should be installed close to the generator set, preferably in a separate compartment The compart­ment must be well ventilated to preventaccumulation of explosive battery gases.
Mount the battery in an acid resistant tray on a platform above the floor. It must be secured to prevent shifting. If mounted in an engine compartment, always install a non-metallic cover to prevent battery damage and arc­ing from accidentally dropped tools. Figure 8-5 shows a typical battery tray and cover.
Maintenance free batteries definitely should be consi­dered for marine application. New technology of these batteries make them completely sealed and mainte­nance free. They usually offer higher output
(CCA),
bet­ter durability and vibration resistance than other equally priced batteries.
PCB
ASSY
-
ENGINE
MONITOR
I
TB12
I
11"
K12
n
0
GND
1
ES-167c2
FIGURE
8-4.
REMOTE
CONTROL CONNECTIONS
Page 32
ESHW
CaMeSize
Lengwl
FIGURE
8-5.
TYPICAL BAllERY TRAY
AND
COVER
Leakage of fuel in
or
around the
l3iESl
generatorset compartmentpresents
a
hazard
of
fire
or
explosion that can cause severe per-
sonal injury
or
death.
Do
not disconnect
or
connect
battety
cables if fuel
vapors
are present. Ventilate the comparfment thoroughly with the bilge blowers orpower exhausters.
2
1
0
00
0oooooO
4ft
5ft 7ft
(12
m)
(1.5
m)
(21
m)
(27
m)
(3.4171)
(4.3m)
9ft
11ft
14ft
Connectthe battery cablesasshown
in
Figure
8-6.
Use
cable sizes specified
in
Table
8-1.
Be
sure the battery
connections are clean and
tight;
then cover the battery
terminals
with
a dielectric grease
to
retard corrosion.
Connect the battery negative lead to the generator set at
the location shown
in
Figure
8-6.
Failure
to
do
so
can
cause arcing
or
resistance
in
the cranking circuit
The ignfion
of
gasoline fuel or fumes
lZEHEl
can result in severe personal injury
or
death. Connect fhe generafor set battery ground
lead only
af
the Iocation shown.
TABLE
8-1.
BAlTERY CABLE
SIZE
REQUIREMENTS
(Maximum
Length
of
One
Cable)
Eli
WASHERS
LOCKWASHER
a+-
B-
VlEWA
VIEW
B
HARDWARE
ASSEMBLY
ES-1672-2
FIGURE
8-6.
BATTERY CABLE CONNECTIONS
Page 33
Grounding
Onan marine generator sets require the batteries con­nected negative ground. Most propulsion engines and vessel electrical equipment have negative ground systems.
BATTERY ACCEPTABLE BATTERY
+
f
7
w-
0--
The generator set and propulsion engineh must be
grounded in accordance with
USCG
regulation
33CFR183.415. The regulation requires a common ground
conductor connected between the generator set and pro­pulsion engine cranking motor circuits. The conductor must be the same size as the largest battery cable. See Figure
8-7.
COMMON CONDUCTOR SAME
SIZE
AS BATTERY CABLE
d
\
The conductor prevents accidental passage of cranking current through the
fuel
systems and smaller electrical
conductors common to
the
engines. This can happen if
a
cranking motor ground circuit becomes resistive or opens
from corrosion, vibration, bad cable, etc.
GENERATOR SET
rmpmper
gtwnd
can cause seven?
l3BHSl
persona/ iniury
or
death
trom
fire
or
explosion.
Besun,
to
installa commongrrxrndconductor
hiween
all
on
bead
cranking
circuiis.
Do
not connect the
battery
negative
lead
to
the
generator
set at a location other than shown in Figure
8-6.
PROPULSION ENGINE
I
FIGURE
8-7.
COMMON GROUND CONDUCTOR
Bonding
The generator set must
be
bonded to
the
vessel
common bonding conductor with a bonding strap as shown in Fig­ure 8-8.
If
a metallic fuel line
is
installed between the fuel
tank
and the generator set shutoff valve, it too must be
bonded to the same vessel common conductor.
COMMON
BONDING
CONDUCTOR
Es.1891-I
FIGURE
8-8.
BONDING CONNECTlONS
8-6
Page 34
Section
9.
Final Installation
Checks
INSTALLATION
CHECKS
Before trying to start the generator set, determine that the installation is complete by answering affirmatively the following questions:
Is
the exhaust system secure and all connections
tight?
Is
a flexible section of exhaust hose used between
the genset and muffler?
Is
all exhaust hose certified for marine exhaust application, and adequately supported and pro­tected?
Is the exhaust outlet terminated away from win­dows, vents or other openings that might allow exhaust gases to enter the vessel, or be pulled into the vessel when in motion?
Does the fuel system have a flexible section at the generator set to allow for.movement
of
the genset
when the vessel pitches?
0
Are the AC generator and load wires securely and
0
0
correctly connected to the circuit breaker? Are the battery cables connected correctly and
securely at the generator set and battery? Has crankcase oil and coolant been added to the
engine, and are they at correct levels? See the
Main-
tenance section of the Operator’s Manual.
Oil, fuel and coolant have been
drained from the engine prior
to
shipping from the factory. Operation wifhouf oil or coolant MI damage fhe engine.
INITIAL STARTING
AND
CHECKS
Refer to the Operator’s Manualbefore trying to
start
the generator set Make sure the fuel shutoff valve and sea water cock are open. Operating the sea water pump
without water will ruin the neoprene impeller.
Gasoline vapors
can
cause an explo-
sion and fire resulting in severe per­sonal injury or death. Before starting thegenerator set, operate the bilge blower for a minimum ofrlminutes. If fuel fumes are present, locate the source and correct
prior
to
generafor
set
operation.
1.
2.
3.
4.
5.
Start the genset by holding the StartIStop switch in the Start position. The
genset
should
start
within a few seconds. If not, check fuel supply and shutoff valve/s.
Check the hull exhaust outlet for water flow and the genset operation. Monitor the remote control panel gauges (if equipped) for normal range of readings. Refer
to
Operator’s
Manual
for proper values.
Check the exhaust system for leaks, visually and audibly. Note the security of the exhaust system supports. If any leaks are found, shut down the genset immediately and repair.
Exhaust gas is deadly. For this
AWARNING
reason, shutdown fhegenerafor
set
immediatelyifan exhaust leakor exhaustcom-
ponent needs repair.
Do
not
run
the generator set
until the exhaust system is repaired.
Check the genset for fuel,
oil
or coolant leaks.
If
any are found, shut down the genset and repair the leak before making any more checks.
Connect an accurate AC voltmeter and frequency meter across
two
line terminals. Apply load to the
generator and check output voltage and frequency.
Output frequency
is
determined by engine speed and
normally does not require adjustment Verify that fre­quency is correct before making any voltage adjust­ments. Call an authorized Onan distributor or dealer for assistance if needed.
If the voltage is not within specs, it can be adjusted for the generator connection used as shown in the Figure
8-3
table. Before making any adjustments, disable the
genset
by
removing the negative
(-)
cable at the battery.
Accidenial starting
of
the generafor
-1
set can cause severe personal injury
or
death. Disconnect the negative
(-)
baffery cable
before adjusting fhe regulator transformer taps.
9-1
Page 35
.
Page 36
Section
10.
DC
Wiring Diagram
This section contains
DC
wiring diagram number
612-6539
forthe
MCE
generator set.
Use
this dia­gram in conjunction with the wiring information in Section
8
of
this manual
to
make the electrical con-
nections necessary
to
operate the set.
*
10-1
Page 37
SCHEIUTIC
-
TI
I.
-
AI
I
K16
K14
dk5
AI
I
K15
-
MTE
I
I.
UNLESS
DWRYISE
MTEO NL CDPCNNTS
ARE
SWYN
IN
TH
OE-ENhZW
p(IsITICN.
2.
DASHED
LIKS IMICATE
WKN
EEO.
AC
Kl4
U
I
I
I
GM
I
?A
-I
,
t-2
AI
I-R
KII
nl
Y
E3.E
cBI2
BT
I
81
AI
I
ENOIN
10-2
Page 38
Page 39
Onan Corporation 1400
73rd
Avenue N.E.
Minneapolis, MN 55432 612-574-5000 International Use
Telex:
275477
Fax:
612-574-8087
Onan
is
a
registered
trademark
of
Onan
Corporation
1
-800-888-ONAN
Loading...