Onan 25.0 DEH-53R, 30.0 DEH-3R, DEH, 25.0 DEH-515R, 30.0 DEH-15R Owner's Manual

...
Page 1
OPERATORS
AND
MANUAL
PARTS
ELECTRIC
CATALOO
FOR
GENERATING
SERIES
FORM NUMBER
976-0306
Pr.oted in
U.S.A.
ISSUE DATE
5-77
(SPEC H)
Page 2
TABLE
OF
CONTENTS
TITLE
Introduction
PAGE
1 Safety Precautions 2 Specifications Description
4
7 Installation 13 Operation 22 General Parts
The need for an international standard of measurement has been increased by today's improved communication and transportation between countries.
This has prompted formation of modernized metrics known as the International
System of Units, officially abbreviated SI. ONAN products appear on the world market, therefore both metric and the present
American system of units (CU) will be found in this manual. To assist in familiarization, refer to the following terms.
TERM
Length
Pressure
Mass (Weight) Volume (Liquid)
Power Frequency
Energy
Battery Capacity Revolutions per Minute Temperature
Maintenance 28
Catalog 33
METRIC
millimetre (mm)
kilopascals
.' (kPa)
kilogram (kg)
litre ^
kilowatt
hertz (Hz)
Joules (J)
Coulomb (C)
r/min
Celsius (0C)
pounds per square
horsepower (HP)
cycles per second
Ampere Hour (AH)
ENGLISH
Inch (in)
inch (PSI)
pound (Ib)
gallon (gal)
(CPS)
BTU
rpm
Fahrenheit (0F)
The customary unit of Brake Horsepower (BHP) becomes kilowatts (kW) when converted to S I metric units. This kW rating should not be confused with the kW
rating of the generator which will always be lower due to losses inherent with any electrical induction device.
WARNING
TO
AVOID EQUIPMENT CIAN OR AN AUTHORIZED REPRESENTATIVE STALLATION
POSSIBLE
DAMAGE, A
MUST
AND ALL
PERSONAL
QUALIFIED
PERfORM
SERVICE.'
INJURY
OR
ELECTRO
SERVICE
IN-
\ "
Page 3
INTRODUCTION
FOREWORD
This manual is applicable to the DEH Series electric generating set, consisting of an ONAN 30.0 kW, UR generator, driven by a Ford-Dorset, Diesel Engine.
The manual is divided into two sections. Section 1 provides information on installation, opera-
tion and troubleshooting. Section s is a Parts Catalog for ONAN optional and.
standard equipment. The.
manual should be used jn conjunction with the
Ford engine manual, for specif ic engine information.
WARNING | Onan
uses
this symbol
• throughout this manual to warn of
possible
personal injury.
MODEL
Identify your model by referring to the MODEL and SPECIFICATION NO. as shown on the Onan nameplate." Electrical characteristics are shown on the lower portion of the nameplate.
1.
Indicates Kilowatt rating.
2.
Factory code for SERIES identification.
3. 15 = 60 Hz Reconnectible
4.
Factory code fordesignating optional equipment.
5. Specification letter. (Advances when factory
When contacting a deialer orthe factory regarding the set, always mention the complete Model, Spec No. and Serial No. as given on the Onan nameplate. This nameplate information is necessary to properly iden­tify your unit among the many manufactured. Referto the engine nameplate when requesting information from its manufacturer. The ^nan nameplate is located on the right side of the generator; the Ford nameplate is on the upper left side, on flywheel housing.
IDENTIFICATION
30.0 DEH 15R / 1 G
1 2 3 4 5
515 = 50 Hz Reconnectible R—indicates remote starting feature.
makes production modifications.)
T
_ *
This
symbol refers to
equipment damage.
possible
: •. -1
Left side and. right side are considered when viewed from the engine or front end of the generating set.
Page 4
SAFETY
PRECAUTIONS
Throughout this manual you will find eye-catching flags containing Warnings and Cautions. These will alert you to conditions that could result in danger to you or the equipment, if the notice is ignored.
ONAN recommends that you read your manual and become thoroughly acquainted with it and your
equipment before you start your unit. The ac-
cumulated experience of ONAN engineers is available to-you, enabling you to operate your set in
the most efficient and safest manner possible. These
recommendations and the following safety precautions are for your protection. Study and know them!
REMEMBER. Most accidents are caused by failure to
follow simple and fundamental safety rules or
precautions.
Most accidents can be prevented!
KNOW MENT
personal injury. The suggested procedures should be adhered to.
YOUR
WARNING
MANUAL—KNOW
Set forth below are a number of potential hazards which could result in some degree of
YOUR
EQUIP-
Do not stand on a wet floor while working on electrical equipment. Use rubber insulative mats placed on dry wood platforms.
Fuel
System
• .DO NOT fill fuel tanks while engine is running, . unless tanks are outside engine compartment.
Fuel contact with hot engine or exhaust is a potential fire.hazard.
• DO NOT SMOKE OR USE AN OPEN FLAME in the vicinity of the generator set or fuel tank.
Internal combustion engine fuels are highlyflam­mable.
REMEMBER—IF YOU CAN SMELL FUMES—A POSSIBLE EXPLOSION AND FIRE CONDITION EXISTS!
• Make sure that oily rags are not left on or nearthe engine. Oil soaked rags are combustible and present hazardous walking conditions. •
General
» Keep your electric generating set and the sur-
rounding area clean and free from obstructions. Remove all oil deposits; keep the floor clean and dry.
• Provide appropriate fire extinguishers and install them in convenient locations. Consult your local fire department for the correct type of ex­tinguisher to use. Do not use foam on electrical fires.
Use extinguisher rated ABC by NFPA.
• Make sure that all fasteners on the generating set are secure. Tighten supports and clamps, keep guards in position over fans, driving belts, etc.
• Do not wear loose clothing in the vicinity of moving parts, or jewelry while working on elec­trical equipment. Loose clothing and jewelry can become caught in moving parts. Jewelry can short out electrical contacts; cause shock or burning.
» If necessary to make adjustments while the unit is.
running,
exhausts, moving parts, etc.
use extreme caution when close to hot
• Fuel lines must be of steel piping, adequately secured, should, copper piping on flexible lines as copper will work harden and become brittle.
• Your engine installation should be equipped with a means of positive fuel shutoff in applications
when fuel is conducted from a remote source.'
Fuels under pressure (e.g. natural gas or liquefied petroleum gas) should be controlled by a positive
shutoff valve, preferably automatic, in addition to
. any valve integral with the carburetor or gas
regulator equipment.
Exhaust
• Exhaust products df any internal combustion engine are toxic and can cause serious personal
injury, if inhaled. All engine installations, es-
pecially those within a confine, should be equipped with an exhaust system to discharge gases to the atmosphere. Do not use exhaust gases to heat a compartment.
• Inspect exhaust system regularly to assure that system is free of leaks.
and free from leaks. Piping at the engine
be approved flexible line. Do not use
System
Page 5
Coolant
• Coolants under pressure have a higher boiling
• Radiator fan belts are guarded for your protec-
Keep
Ventilation
• Check remote radiators frequently. Remove any
• Check ventilation louvres frequently. Make sure
Electrical
• The electrical installation exterior to your
System
point than that of water. DO NOT open a radiator or heat exchanger pressu re cap or break a system while the engine is running, and in rio case until the system pressure has been bled off.
tion.
DO NOT remove covers or guards.
your
hands
System
dirt, debris, bird nests, etc.
that free-fall louvres and motor operated louvres
open and close properly and that there, is no restriction in the free-air flow.
System
generator should have been performed by qualified licensed electricians. All local and state
away
from
moving parts.
codes should have been consulted and complied with.
It is essential that all load circuit breakers adequately protect electrical functions, a|l cir­cuits are properly grounded and wiring is correct capacity.
• Tag open switches.
• DON'T tamper with interlocks.
• Before starting work on the generating set, disconnect batteries. This will prevent inadver­tent starting of the set.
• Use extreme caution when making adjustments on the electrical components in the control cabinet while the engine is running. High voltages are present and could cause serious personal
injury.
• DO NOT SMOKE while servicing batteries. Verify correct polarity of battery cables before connec­ting.
Lead acid batteries give off a highly ex-
plosive hydrogen gas which can be ignited by
electrical arcing or by smoking. When connecting
batteries, connect the ground lead last.
Page 6
SPECIFICATIONS
r
ENGINE
Engine Manufacturer FORD Engine Series 2711 E Number of Cylinders 4 Displacement. 254-cubic inches (4.16 litres) BHP @ 1800 Compression Ratio 16.0:1
Bore .- 4.22-inches (107.19 mm) Stroke , > 4.52-inches (114.81 mm) Fuel ASTM No. 2 Diesel Battery Voltage 12 Volt Negative Ground Battery Group (Two 6-Volt, 135 A.H. [486 kC]) 2H Starting Method : Solenoid Shift Governor Regulation .. 5% Maximum
Battery Charging Current . ... 35-Ampere
GENERATOR DETAILS
Type UR 15 60 Hz Rating (Watts)
AC Voltage Regulation ±2%
Output Rating 0.8 PF
AC Frequency Regulation 3 Hz Max. No Load to Full Load
DETAILS
r/min
60 Hertz Continuous Standby 30 000 (37.5 kVA) 50 Hertz Continuous Standby 25 000 (31.25 kVA)
60 Hertz
50 Hertz r/min......... 1500
r/min
; 63 (47 kW)
UR 515 50 Hz
; 1800
CAPACITIES
Cooling System (Including Radiator) 1... 16 Quarts (15-litres)
Engine Oil Capacity (Filter, Lines, Crankcase)/ ' 9.5 Quarts (9.0-litres)
Exhaust Connection (inches pipe thread) 2 (Female) AIR REQUIREMENTS (1800 r/min)
Engine Combustion , 104-cfm (0.05 m3/s) Radiator Cooled Engine 6000-cfm (2.83 m3/s)
Total for Radiator Cooled Model 6104-cfm (2.88 m3/s)
Alternator Cooling Air (1800 r/min) , 1000-cfm (0.5 rnVsj Fuel Consumption at Rated Load ASTM No. 2 Diesel 2.6-gph (2.73 cm3/s)
GENERAL
Height 45.6-inches (1.16 m) Width 33.0-inches (0.84 m) Length Approximate Weight (Mass) 1-Phase.. 1700-lbs (771.1 kg).
;
AND
REQUIREMENTS
(1500 r/min) 833-cfm (0.4 m3/s)
66.0-inches (1.68 m)
3-Phase 1575-lbs (714.4 kg)
Page 7
VOLTS
TABLE
FREQ
I.
PHASE
UR GENERATOR VOLTAGE/CURRENT OPTIONS
AMPERES
DOUBLE
SERIES
DELTA DELTA
PARALLEL
WYE
SERIES
WYE
WIRE
REF
VOLTAGE
(W12) TAP
110/220 50 115/230 50 120/240 60
110/190 50 115/200 120/208 50 120/208 110/220 50 127/220 50
127/220 115/230 50 120/240 60
139/240 220/380 230/400 50 240/416 50 240/416
• 254/440 254/440 60 277/480 60
Hz 1 Hz 1 Hz 1
Hz
50
Hz Hz
60
Hz Hz Hz
60
Hz Hz
Hz
60
Hz
50
Hz Hz Hz
60
Hz
50
Hz. Hz Hz
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
3
9X
347/600 60
3
.
120/240 60
30
kW 37.5 kVA 60 Hz
25
kW 31.25 kVA 50 Hz
* - These current values are available only from special long stack units (Bl 25 option). When standard 3 phase unit is connected into Double Delta configuration, maximum current
Hz
Hz
3
1 '
142* 136* 156*
X
x x H5
95 90 87
104
82 x 82 98 78 90 90 47 45
43
52 41
49 45
36
L
156
is 2/3
that
of
value given.
X X X X
X X
x H6
X
X-
x' x H4 x x H3 x x
X
H5—Not
Reconnectible
H5—Not
Reconnectible
H6 H6
H3 H4 H4 H3 H6 H5 H4
H5 H5 H3
H4 H5
H4 H5
.
'
.
Page 8
120/240
NAMEPLATE VOLTAGE CODE
VOLT, 1 PHASE,
CONNECT LEAD
TERMINAL
63 TO HS
Tl
TO
T2
FROM
THIS
60
HERTZ
3
DIAGRAM
APPLIES
TO 12
347/600
VOLT, 3 PHASE,
NAMEPLATE VOLTAGE CODE
Tl
"
1
CONNECT LEAD
-
TERMINAL
raf
LEAD GENERATORS ONLY
60
HERTZ
9X -
TO
63 TO H5
FROM
15
515
15
515
15
515
IS
515
120/240
115/230
110/220
120/240
11'5/230
110/220
120/208 12^220 13^240 110/190 115/200 12(^208 127/220
240/»16 254/140 277/480 220/380
230/400
240/416
254/440
.60
60
HS
H6
H6
HS
H6
H6
H3 H4 H5 H3.
H4
H4
HS
H3 H4
HS
H3 H4
H4 H5
GENERATOR CONNECTION SCHEMATIC DIAGRAM
GENERATOR
(WITH
Tl
T2 T6T11 T8T12 T4 T9. f5 T7 TJ T10
10 11
CT21
Tl
T10 T6 T7 T2 Tll T4 T8 T3 T12 T5 T9 .
LO
11
T4
T6 Tll
TS
TIO T12
10 Ll
CT21
T10
Tll T12 Tl T7 T4
CONNECTION WIRING DIAGRAM
CURRENT TRANSFORMERS
L2
CT22
Tl
T7,
TT
T2
T8
L2
CT22_a_.
T2
T8 TS T3 T9 T6
WHEN
CT23^L|ir:
CT24
CT23
USED)
L3
>
TT
T3
T9
L3
_f"
FIGURE
1.
GENERATOR RECONNECTIONS
6
98C2193
Page 9
DESCRIPTION
GENERAL
An Onan DEH series electric generating set is a complete unit consisting of an engine driven AC generator, with standard and optional controls and accessories as ordered.
ENGINE
The engine on the DEH is a Ford-Dorset described in the engine manual. Basic measurements and requirements will be found under SPECIFICATIONS. For operation, maintenance and service information, consult the Ford-Dorset manual.
AC
GENERATOR
The generator is an ONAN Type UR, 12
revolving
main rotor is attached directly to the engine flywheel, therefore engine speed determines generator output frequency. The 60 Hz set operates at 1800 r/min, the 50 Hz at 1500 r/min. Excitation is achieved as foi
lows­Residual alternating durrent from the stator winding is applied to the voltage regulator, where it is
compared with a reference voltage, rectified- and
returned to the field winding of the exciter. Current
then induced in the exciter rotor is rectified and fed
into the generator rotor. This induces a current in
generator stator which is applied to the
CONTROL
The following is a brief description of each of the standard controls and instruments located on the face of the panel. See Figure 2.
DC
Panel Light and Switch: Illuminates control panel. Oil Pressure Gauge: Indicates pressure of lubricating
oil in engine (wired to a sensor unit located on the engine).
field,
Panel
reconnectible, brushless unit. The
PANEL
271
lead,
load.
IE as
4-pole
Warning Light: Indicates "Fault" in engine operation.
AC
Panel
AC Voltmeter Indicates ACgeneratoroutputvoltage.
Dual range instrument: measurement range in use
shown on indicator light. Voltage Regulator Rheostat, provides approximately
plus or minus 5% adjustment of the rated output voltage.
Exciter Circuit Breaker Provides generator" exciter and regulator protection from overheating, in the event of certain failure modes of the generator, exciter and voltage regulator.
Running Time Meter: Registers the total number of hours,
to
1/1
Oth,
that the unit has run. Use itto keepa record for periodic servicing. Time is accumulative, meter cannot be reset.
Voltmeter Phase Selector Switch: Selects phases of generator output to be measu red by the AC voltmeter.
OPTIONAL DC
Panel
Warning Lights: Eliminates the one "Fault" light and­substitutes five indicator (see Figure 3) lights to give warning of—
a. Overcrank b. Overspeed c. Low oil pressure d.
High.engine temperature
e. Low engine temperature
Operation of these lights will be discussed in junction with engine monitor panel.
Reset Switch: Manual reset for engine monitor after shut-down.
EQUIPMENT
con-
Water temperature Gauge: Indicates temperature of circulating coolant in engine. (Wired to a sensor unit
located on the engine.) Battery Charge Rate DC Ammeter: Indicates battery
charging current.
Run-Stop/Reset-Remote Switch: Starts and stops the unit locally or from a remote location. Resets engine monitor relay in Stop/Reset position.
Lamp Test: Press to test warning lamp bulbs (when engine is running only).
AC
Panel
AC Ammeter Indicates AC generatoroutput current.
Dual range in use shown on indicator lights.
Frequency Meter Indicates the frequency of the generator output in hertz. It can be used to check engine speed. (Each hertz equals 30 r/min.)
Page 10
INDICATE UPPER AND LOWER SCALE
PHASE SELECTOR SWITCH-
INDICATOR LAMPS
ON VOLTMETER AND AMMETER
DUAL RANGE
AC VOLTMETER
VOLTAGE ADJUSTING RHEOSTAT
FIELD CIRCUIT BREAKER FAULT LAMP
RUNNING TIME
METER
% TURN FASTENERS- TURN BOTH
SCREWS TO OPEN HINGED CONTROL
PANEL LIGHT AND SWITCH
PANEL DOORS
OIL PRESSURE
GAUGE
WATER TEMPERATURE
DC AMMETER
«UN-STOP-REMOTE SWITCH
(ALSO A RESET SWITCH FOR
GAUGE
ENGINE MONITOR)
FIGURE
DUAL RANGE AC AMMETER
INDICATE UPPER AND LOWER SCALE
INDICATOR LAMPS
O.N VOLTMETER AND AMMETER—.
DUAL RANGE
AC VOLTMETER
VOLTAGE
ADJUSTING
RHEOSTAT
FREQUENCY
METER
RUNNING TIME
METER
FIELD CIRCUIT BREAKER
PHASE SELECTOR SWITCH
2.
TYPICAL
CONTROL
PANEL
(ONE
FAULT
TEST LAMP BUTTON
ENGINE MONITOR RESET SWITCH USED ONLY ON CONTROL PANELS
LAMP)
% TURN FASTENERS- TURN BOTH
SCREWS TO OPEN HINGED CONTROL
PANEL LIGHT AND SWITCH
FAULT LAMPS
WITH FIVE FAULT LAMPS
PANEL DOORS
OIL PRESSURE
GAUGE
ATER TEMPERATURE
GAUGE
DC AMMETER
UN-STOP-REMOTE
(ALSO A RESET
ENGINE
SWITCH
SWITCH FOR
MONITOR)
FIGURE
3. OPTIONAL
CONTROL
PANEL
(FIVE
FAULT
LAMPS)
Page 11
CONTROL
PANEL
INTERIOR
The only equipments discussed in this section will be
those which the operator may have reason to adjust or
inspect for service. Terminal Board (TB) 21: Connection of wire W12 to
terminals H3, H4, H5, and H6 is made at this point, to change reference voltage when reconnecting generator for different voltages. Refer to Figure 1.
Voltage Regulator, Begin Spec G: Solid state unit,
consisting of printed circuit board VR21; an SCR bridge CR21, with a commutating reactor L21 are
located in the control panel as part of the voltage regulator system. AC output from generator is
trolled at predetermined level regardless of
con-
load; regulation is plus or minus 2% from no load to full load,
at 0.8 P.F.
Voltage Regulator, Prior to Spec G: Solid state unit consisting of printed circuit board VR21.
An exciter-regulator assembly designated VR22 containing an SCR
bridge circuit and commutating reactor is mounted on the
generator end bell (see Figure 4) and works in conjunction with VR21.
Engine Monitor: Printed circuit plug-in modules provide the following functions:
1.
A 75 second cranking period.
2.
Approximately a 12.5-second time delay for oil
pressure buildup.
3. An external alarm contact to light afault lamp and shut down the set for alarm conditions such as:
a. Overcrank (failed to start after cranking 75
seconds).
b. Overspeed (enginespeed reaches2100 r/min). c. Low oil pressure 14 psi (96.5 kPa). d.
High engine temperature 215° F (102°C).
On standard control panels, all four alarms are wired into one common fault lamp; on units with five fault lamps, four have shutdown alarms, the fifth (low engine temperature) lights a fault lamp only. Refer to Table 2.
Standard Cranking Module: Limits engine cranking time to 75 seconds. If engine fails to start after 75 seconds the engine monitor lights a fault lamp and opens the cranking circuit.
EXCI TER-REGULATOR CHASSIS ASSEMBLY
(PRIOR TO
SPEC Q)
OVERSPEED SWITCH
1
ROTATING EXCITER
WITH RECTIFIERS
FIGURE 4. GENERATOR (GRILLE REMOVED)
NDBELL
OPTIONAL
MODULES
Cycle Cranker Plug-in module replaces standard cranking circuit. Automatically provides a 15-second crank time and a 10-second rest time for three ON and two OFF cycles in 65 seconds. If engine fails to start, after 75 seconds the engine monitor lights a fault lamp and opens the cranking circuit. The ON and OFF cycle times are nominal and can be adjusted at potentiometers on the cranker module board.
Pre-Alarm:
Gives advance warning for low oil
pressure or high engine temperature. Requires two
sensors each for engine temperature and oil pressure.
Page 12
TABLE
2.
, FAULT
LAMP OPTIONS
SYSTEM FAULT
PENN STATE Overcrank -
SINGLE LIGHT
Overspeed
Low Oil Pressure
1 High Engine Temperature . x
STANDARD Overcrank
SINGLE LIGHT
Overspeed Low Oil Pressure x High Engine Temperature
5 LIGHT
Overcrank Overspeed Low Oil Pressure High Engine Temperature.
• Low Engine Temperature x
5 LIGHT Overcrank
PRE-ALARM; 1 Overspeed
• Low Oil Pressure
\ High Engine Temperature
Low Engine Temperature
FAULT
LAMP
X X
x
STOP
ENGINE
X X
x x
X X
X X
X X X X X X X X
X X X X
. *
X X
X X X X
X
X
X X
*
EXTERNAL
PRE-
ALARM ALARM
X
X
X
X A X
X X
1
X
* X X
X X
- With additional optional sensors.
10
Page 13
ENGINE
Resistance units temperature
SENSORS
and
and oil
pressure monitoring
switches
in the
and
engine
shut-
down systems are sealed units and are not repairable. For location, refer to Figures 5 and 6. When replacing
a sensor, Resistance units supply, actuation parts, made
do
not substitute, use recommended items.
are
and
cut-off switches
matched
for a
to the
are
gauge they
close-tolerance
specific application.
OIL PRESSURE
SENDER
^
FIGURE 5. OIL PRESSURE MONITORS
TEMPERATURE
SENDER
j (RESISTANCE
UNIT)
FIGURE 6. ENGINE TEMPERATURE MONITORS
s
WATER
HI-TEMPERATURE
CUT-OFF SWITCH
(HETCO
Page 14
COOLING AIR INLET MUST BE
AT LEAST IVJ TIMES LARGER THAN RADIATOR DUCT OUTLET AREA ON RADIATOR COOLED
MODELS.
FIGURE
7.
TYPICAL
MODEL DEH INSTALLATION
12
Page 15
INSTALLATION
GENERAL
Installations must be considered individually. Use these instructions as a general guide. All installations must meet regulations of state and local building codes, fire ordinances, etc., which may affect installa­tion details. See Figure 7.
Requirements to be considered prior to installation:
1.
Level mounting surface.
2.
Adequate cooling air.
3. Adequate fresh induction air.
4.
Discharge of circulated air.
5. Discharge of exhaust gases.
6. Electrical connections.
7. Fuel installation.
8. Water supply (city water cooling).
9. Accessibility for operation and servicing.
10.
Vibration isolation.
11.
Noise levels.
LOCATION
Provide a location that is protected from the weather
and is dry, clean, dust free and well ventilated. If
practical,
tion from extreme weather conditions.
install inside a heated building for protec-
Radiator set cooling air travels from the rearof the set and is removed by a pusher fan which blows out through the radiator. Locate the air inlet to the rear of the set. Make the inlet opening at least IVfe-times
larger than the radiator.
Locate the cooling air outlet directly in front of the
radiator and as close as possible. The opening size should be at least as large as the radiator and shape of the air outlet duct should offerminimum
restriction to air flow. Use a duct of canvas or sheet
metal between the radiator and the airoutlet opening. The duct prevents recirculation of heated air.
Provide a means of restricting the air flow in cold weather to keep the room or compartment temperature at a normal point.
For operation outside a building, a shelter housing with electrically operated louvres is available as an option. output supply current to the motors.
When the generator is operating, current in the transformers actuate the motors and open the
louvres. The louvres are held open for the duration of the set operation, then are closed by return springs when the set is shut down.
Transformers connected across the generator
area.
Length
MOUNTING
Generator sets are mounted on a rigid skid base which provides proper support. The engine­generator assembly is isolated from the skid base by
rubber mounts which provide adequate vibration isolation for normal .installations. For installations where vibration control is critical, install additional spring-type isolators between skid base and founda­tion.
For convenience in general servicing and changing crankcase oil, mount set on raised pedestal at least 6­inches (150 mm) high. Refer to ONAN Technical Bulletin T-030 for further installation information.
VENTILATION
Generator sets create considerable heat which must be removed by proper ventilation. Outdoor in­stallations rely on natural air circulation but indoor installations need properly sized and positioned vents for the required air flow. See SPECIFICATIONS for the air required to operate with rated load under normal conditions at 1800 r/m.
City water cooled sets do not use the conventional radiator. A constantly changing water flow cools the engine. Ventilation is seldom a problem, but sufficient air movement and fresh air must be available to properly cool the generator, disperse heat convected off the engine and support combustion in the engine.
For small compartments, a duct of equal or larger area than generator outlet is recommended to remove the heated air from the generator air outlet to the outside atmosphere. Limit bends and use radius type elbows where needed. A larger, well ventilated compartment or room does not require a hot air duct.
Installations made in a small room may require installation of an auxiliary fan (connected to operate only when the unit is running) of sufficient size to
assure properaircirculation and evacuation of fumes.
13
Page 16
COOUNG
SYSTEM
Standard Radiator Cooling, uses a set mounted
radiator and engine driven pusher type fan to cool engine water jacket. Air travels from the generator end of the set, across the engine and but through the
radiator. An integral discharge duct adapter flange surrounds the radiator grille.
This system reduces set enclosure airflow re­quirements and noise levels. Proper operation is dependent on a constant supply of cooling water.The system cannot be protected from freezing. See Figure
9.
Heat Exchanger Cooling (optional), uses a shell and tube type heat exchanger instead of the standard
radiator and fan. Engine jacket coolant circulates through the shell side of the heat exchanger, while
raw cooling water is pumped through the tubes.
Engine coolant and raw water do not mix. This type of
cooling separation is necessary when the raw water
contains scale forming line and other impurities.
This system reduces set enclosure airflow ahd noise
levels.
Proper operation depends upon a constant supply of raw water for heat removal. The engine coolant side of the system may be protected from freezing the raw water side cannot. See Figure 8 for typical installation.
EXPANSION
'
TANK
c
^
HEAT
EXCHANGER
• ~ -rn ENGINE
FROM
ENGINE
ANTI-SIPHON —I
SOLENOID VALVE
(OPEN WHEN
SET IS RUNNING) -
N
WATER
IN
FIGURE
9.
TYPICAL
STAND
PIPE
STRAINER
STANDPIPE
DRAIN
: FROM
ENGINE
TO ENGINE
ADJUSTABLE VALVE
(RATE OF FLOW)
SYSTEM
SOLENOID
VALVE
(OPENS WHEN.
J
DRAIN
ADJUSTABLE
VALVE
(RATE OF FLOW) ex
FIGURE
8.
TYPICAL
SET IS RUNNING)
7"
Rev.
HEAT
STRAINER
EXCHANGER
JTwATER
IN
SYSTEM
Siandpipe Cooling (optional) substitutes a mixing (tempering) tank for the standard radiator and fan. Cooling watercirculating through theenginejacket is mixed with raw water in the tank. Because raw water
flows through tho engine jacket, it must not contain
scale forming .impurities or fouling of the engine, water will occur. Fouling results in engine overheating and ^ostiy repair bills.
Remote Radiator Cooling (optional), substitutes a remote mounted radiator and an electrically driven
fan,
for the set mounted components. Removal of the
radiator and fan from the set reduces set enclosure airflow requirements and noise levels without forcing dependence on a continuous cooling water supply. The remote radiator system can be completely
protected against freezing. This system must be designed to meet specific
requirements of the application. Water Jacket Heater (optional) may be installed to
keep engine coolant warm while engine is shutdown.
It heats and circulates the coolant within the engine, which reduces start-up time and engine wear caused
by cold starts. It is electrically operated and. ther-
mostatically controlled.
Page 17
COOLING
CONNECTIONS
The radiator cooled (standard) set does not require any external connections except as discussed under
Ventilation. Allow clearance around thesetforaccess
to service the radiator and fan belts. See Figure 7. Heat Exchanger and Standpipe cooled sets must be
connected to a pressurized supply of cold water. Make connections to the set with flexible pipe to absorb vibration. On the cool water line install a solenoid valve to shut off the flow when the set is shut down and a. rate of flow valve to control engine temperature. This valve can be either manual or automatic. Actual rate of flow will depend on inlet watertemperature.
Adjust the flow to maintain water temperature between 165° F and 195° F (73.9° C and 90.6° C) while viewing the water temperature gauge.
Before filling cooling system check all hardware for security. This includes hose clamps, capscrews, fittings and connections. Use flexible coolant lines with heat exchanger, standpipe or remote mounting radiator.
The regular formula can be used with plain water ahd selected antifreezes. The best protection results will
be gained by using the borate formula element with a
. permanent antifreeze.
ONAN recommends that shutoff valves be installed to the engine side of the inlet and outlet of the coolant filter, for ease in changing elements. Anothersugges­tion,
if so desired, a thick-walled pyrex tube can be
inserted and clamped into the line at a convenient
point to serve as a flow indicator. This flow indicator will act in the capacity of a sight gauge to observe general condition, possible air pockets and presence of contaminants in the coolant flow. See Figure 10for
installation recommendations-.
Remote radiator plumbing will vary with installation. All systems must comply with the following conditions—
1.
Make all connections to the set and to the
radiator, with flexible pipe.
2.
Install an auxiliary circulating pump if the
horizontal distance between the engine and pump exceeds 15-feet (4.65 m).
3. Install a hot-well system to relieve excess engine water jacket pressure if the top of the radiator is
more than 15-feet (4.65 m) above the center-line of the engine crankshaft.
GENERAL
WATER
FILTER
Electric generating sets can be equipped with an optional cooling system filter (corrosion resistor). This filter is a unit which directs coolant from the system through a filtering and treating device. It softens water, neutralizes acidity and protects against corrosion by the use of a replaceable chemically activated filtering element. In addition, the unit
con­tains a sacrificial metal plate which arrests pitting of metals in the system by electro-chemical action.
WATER OUTLET
FROM HEATER
WATER HEATER
FLOW
INDICATOR
WATER INLET LINE
FROM BLOCK
SHUT-OF
VALVE
. COOLING SYSTEM
FILTER
FIGURE 10. COOLING SYSTEM (RADIATOR)
Exact location of filter will vary because of other optional equipment which may also be installed.
Two types of elements are available from your Onan dealer or distributor.
1.
Regular formula (chromate).
2.
PAF formula (borate) year round type.
jCAUTION
or retard the flow through the filter, thereby eliminating the filtering process completely.
Do not use anti-freeze with an antMeak formula. The stop-leak element can prevent
WATER
JACKET HEATER
(Optional)
This heater is installed to maintain an elevated engine temperature in lower ambient temperature applications. It heats and circulates engine coolant, and is thermostatically controlled.
11
Page 18
EXHAUST
|
WARNING
Engine exhaust gas must be piped outside building enclosure. vents
(Figure
Do not
or
combustible materials. An approved thimble
11) through walls downward
or at the point where a rise in the exhaust system begins. Avoid sharp bends; use sweeping.long radiuselbows.
Provide adequate support pipes.
Refer
tion.
Shield orinsulate exhaust lines of personal contact. Allow of clearance wall
or
partition. Use a pipe
inch
(50 mm)
flexible portion between the engine and
Inhalation of exhaust gases can result in death.
terminate exhaust pipe near inlet
must
be
used where exhaust pipes pass
or
partitions. Pitch exhaust pipes
install a condensation trap {Figure
for
mufflers
to
Figure 7 for a typical exhaust installa-
at
least 9-inches (230
if the
pipes
run
at
pipe size outlet
close
least as large as the.2-
of the
and
exhaust
if
there isdanger
to a
combustible
engine with
the
muffler.-
or
12)
mm)
a
,
IF
EXHAUST LINE MUST
.CONSTRUCT A TRAP
FIGURE 12. EXHAUST CONDENSATION TRAP
POINT
DRAIN CONDENSATION TRAP
BE
OF
PIPE FITTINGS
OF
RISE
PERIODICALLY
PITCHED UPWARD,
AT
RAIN
CAP
HOLES
IN END OF
INNER SLEEVE
ROOF
WALL
OR
PARTITION-HjyMm11 V
NOTE:
VENTILATED THIMBLE DIAMETER
THAN EXHAUST LINE
DRIP
CAP
9" MINIMUM
(230
mm)
9-MINIMUM (230 mm)
m ,Y HOLES Jf
END OF
INNER SLEEVE
6"
LARGER
(152 mm)
IN
Do not connect a flexible line to the exhaust manifold. Minimum diameters
(with critical muffler[s])
and
maximum lengths
are as
follows:
of
pipe
Single Exhaust system:
2.5-inch
3.0-inch
(67 mm) (76 mm)
pipe
34
feet (10.5
pipe 166 feet .(50.5
m) m)
FIGURE 11. EXHAUST THIMBLE
Maximum permissible exhaust restriction - (back pressure)
is
20.4-inches H2O (5.1
kPa).
16
Page 19
FUELSYSTEM
Ford-Dorset engines used on DEH sets are designed for use with ASTM No. 2 Diesel fuel with a minimum Cetane rating of 43 and maximum Sulphur content of
0.40.
FUEL
CONNECTIONS
Check local regulations governing the installation of a fuel supply tank.
In any diesel engine Installation, fuel system cleanliness Is of utmost importance. Make every effort to prevent entrance of moisture or contaminants of any galvanized material.
kind.
Do not use lines or fittings of
A fuel lift in excess of 6feet (1.8 m) is not recommend­ed without a day tank installation, because of fuel
drainage. Horizontal run, if the supply tank is level with the fuel pump, should not exceed 12.5-feet (3.9 m). However, a day tank is again recommended. A fuel sediment trap should be installed between fuel transfer pump and supply tank.
The fuel inlet is to the transfer pump and is threaded for 3/8-inch pipe. Injectors' return line requires a 1/8­inch low pressure hose connection. Refer to Figure
13.
FUEL
LEAK-OFF
(TO TANK)
MAIN FUEL
SUPPLY LINE
OIL LEVEL
• PLUG
TWO
SECONDARY
FUEL FILTERS
FIGURE 13. FUEL SYSTEM
17
Page 20
DAY
TANK
Generator set installations may be equipped optional separate fuel day tank. A controls is
maintained to
necessary
fuel flow into the fuel tank. The correct level
assure
a constant
to install an overflow line between the day
float
operated valve
source
with
an
of fuel! It is
tank and the main fuel tank. Refertothe installations included of a day tank installation. Tank and
with
the tank. See Figure 14 for an example
lines
must be
below level of injector pump return outlet.
FUEL PUMP
RETURN LINE
FUEL
PUMP
'DAY' TANK:
5 GAL. (20 litre)
MINIMUM CAPACITY
FUEL TRANSFER
PUMP - ELECTRIC
MOTOR DRIVE
LARGER *n
OVERFLOW"^
LINE
i| ll 11 11 11
M
11 H 11 11 11 11
U
UNDERGROUND
FUEL TANK
FIGURE
14. DAY TANK
18
(TYPICAL)
Page 21
BATTERY
Starting the unit requires 12-volt battery current. Use two 6-volt (see SPECIFICATIONS) batteries for a
normal installation. Connect the batteries in series
(negative post of first battery to -positive post of second) as in Figure 15. Necessary battery cables are on unit. Service the batteries as necessary. Infrequent
unit use (as in emergency standby service) may allow the batteries to self-discharge to the point where they cannot start the unit. If installing an automatic transfer switch that has no built-in charge circuit, connect a separate trickle charger. Onan automatic transfer switches include such a battery charging circuit.
| WARNING
being charged.
Do not smoke while servicing batteries. Lead
acid batteries give off explosive gases while
BATTERY,
HOT LOCATION
Batteries will self discharge very quickly when in­stalled where the ambienttemperature is consistently above 90° F (32.2°C) such as in a boiler room. To
lengthen battery life, dilute the electrolyte from its
normal 1.275 specific gravity.reading at full charge to a
1.2.25
reading. The cranking power is reduced
slightly when the electrolyte is so diluted, but if the temperature is above 90°F (32.2°C), this should not
be noticed. The lengthened battery life will be worth the effort.
1.
Fully charge the battery.
2.
With the battery still on charge, draw off the
electrolyte above the plates in each
cell.
DO NOT ATTEMPT TO POUR OFF; use a hydrometer or filler bulb and dispose of it in a safe manner. Avoid skin or clothing contact with the electrolyte.
3. Refill each cell with distilled water, to normal level.
4.
Continuechargingforl hourata4to6hourrate.
5. Test each
1.255, reduced to
cell.
If the specific gravity is still above
repeat steps 2, 3, and 4 until the reading is
1.225.
Usually, repeating steps twice is
sufficient.
TWO - 6 VOLT
I35AH (486 kc)
BATTERIES
REMOTE
CONTROL
CONNECTIONS
Provision is made foraddition of remote starting. This is accomplished on a 4 place terminal block situated within the control box. Connect one or more remote switches across remote terminal and B+ terminal as
shown in Figure 16. If the distance between the set and remote station is less than 1000-feet (305 m), use
No.
18 AWG wire; between 1000- and 2000-feet
(305 m and 610 m), use No. 16 AWG wire,
FIGURE 15. BATTERY CONNECTION
FIGURE 16. REMOTE START CONNECTION (TB12)
Page 22
WIRING CONNECTIONS
Most local regulations require that wiring connec-
tions be made by a licensed electrician and that the
installation be inspected and approved before opera­tion.
All connections, wire sizes, etc. must conform to requirements of electrical codes in effect at the installation site.
3. Open hinged control panel doors. Connect lead from terminal 63 to correct terminal for voltage desired.
These terminals are labeled H2, H3, H4,
H5 and H6. See Figure 19.
4.
Close front panel and secure with 1/4 turn
fasteners.
5. Connect load wires to generator leads.
Generator set grounding must be in accordance with National Electrical Code (NFPA 70-1975) Article 250.
If the installation is for standby service, a double throw transfer switch must always be used. Connect this switch (either automatic or manual) so that it is
impossible for commercial power and generator current to be connected to the load at the same time.
See Figure 17. Instructions for connecting an
automatic load transfer control are included with
such equipment.
LINE LOAD
NOTE:
SHOWN WITH LINE CONNECTED TO LOAD.
FIGURE 17. LOAD TRANSFER SWITCH
(TYPICAL FUNCTION)
GEN.
Control Box Connections: The factory ships these 12 lead generators with load connection wires NOT connected together in the control box. These.12 wires are labeled Tl through T12 and must be brought together before making load connections. Proceed as. follows: - -
1.
Remove either right, left or top panel from control
box. See Figure 18..
2.
Connect wires together as shown on panel draw-
ing and in Figure 1 according to voltage desired.
Preceding instructions do not apply to models designated Code 3 or 9X; this connection is made at the factory. The installer must only connect load wires.
(W12 WIRE)
CONNECT LOOSE WIRE
FROM TERMINAL #63
TO EITHER H3.H4.H5 OR
H6 DEPENDING ON VOLTAGE SELECTED.
FIGURE 19. REFERENCE VOLTAGE CONNECTION (TB21)
120/240 Volt, Single Phase, 12 Lead: Terminal
con-
nection LO can be grounded (neutral). For 120 volts, connect the hot load wires to either the Ll or L2 connection, Figure 20. Connect the neutral load wire to the grounded L0 connection. Two 120 volt circuits are thus available, with not more than 1/3 the rated capacity of the set available on either circuit. If using
bpth circuits, be sure to balance the load between them.
FIGURE 18. CONTROL BOX (SIDE PANEL REMOVED)
For 240 volts, connect one load wire to the Ll
connection and the second load wire to the L2
connection. Terminal connection L0 is not used for 240 volt service.
Only 2/3 ot rated current is available from this connection.
FIGURE 20. 120/240 V.
1-PHASE
DOUBLE DELTA
20
Page 23
120/240
Volt, 3
Phase,
Delta Connected Set; 12
Lead:
The 3 phase Delta connected set is designed to supply 120 and 240 volt, 1 phase current and 240 volt, 3 phase current, Figure 21. For 3 phase operation, connect the three load wires to generator terminals Ll,
L2 and L3—one wire to each terminal. For3 phase
operation the L0 terminal is not used. For 120/240 volt, 1 phase, 3 wire operation, terminals
Ll and L2 are the "hot" terminals. The L0 terminal is the neutral, which can be grounded if required. For 120 volt service, connect the black load wire to either theLl or L2 terminal. Connect the neutral (white) wire to the L0 terminal. Two 120 volt circuits are available. Connect between any two 3-phase terminals for 240 volt
1-phase
loads.
Any combination of 1 phase and 3 phase loading can be used at the same time as long as total current does ndt exceed the NAMEPLATE rating of thegenerator.
If no 3 phase output is used, usable 1 phase output is
2/3 of 3 phase kVA.
'L'X
240.
V L2—>-o £
L3^
2QL0
V-
"Z-OO NOT USE THIS
CONNECTION FOR ANY 120 VOLT LOADS.
•>
0)
FIGURE 22. 120/208 V. 3-PHASE WYE
120/240
Volt, 1
Phase, 3 Wire
Unit (3R Units):
Terminal post TO is the grounded (neutral) terminal.
For 120 volt current, connect the "hot" load wire to either theTI orT2terminal. Connect the neutral load wire to the TO terminal. Two 120 vo'lt circuits are thus available, with not more than 1/2 the rated capacity of the set available on each circuit. Balance the load as closely as possible (Figure 23).
For 240 volt current, connect one load wire to terminal Tl and the second load wire to terminal T2. Terminal TO is not used for 240 volt service.
FIGURE 21. 120/240 V. 3-PHASE DELTA
3 Phase, Wye Connected Set: The 3 phase, 4 wire set
produces line to neutral voltage and line to line
voltage. Line to neutral voltage is the lowervoltageas
noted on the unit nameplate, line to line voltage is the higher nameplate voltage.
For 3 phase loads, connect separate load wires to each of the set terminals Ll, L2 and L3. Single phase output of the higher nameplate voltage is obtained between any two 3 phase terminals as shown in Figure 22.
The terminal marked L0 can be grounded. For 1 phase loads,
connect the neutral (white) load wire to the L0
terminal.
Connect the black load wire to any one of
the other three terminals—Ll, L2 or L3. Three
separate 1 phase circuits are available, with not more
than 1/6 the rated capacity of the set from any one circuit.
If using 1 phase and 3 phase current atthesametime, use care to properly balancethe 1 phase
load,
and not
to exceed rated line current.
circuit.
Tl
o
TO
T2
If using both 120 and 240 volt current at the
same time, use care not to overload either
>
o
> 8
Figure 22 shows load connections for 120/208 voltage. Other voltages are available from' either parallei wye or series wye illustration in Figure 1.
21
o
FIGURE 23. 120/240 V.
1-PHASE
(CODE 3)
Page 24
OPERATION
GENERAL
Onan DEH Series electric generating sets are given a complete running test under various load conditions and are thoroughly checked before leaving the fac­tory. Inspect your unit closely for loosie or missing
parts and damage which may have occurred in transit. Tighten loose parts, replace missing parts and repair any damage before putting set into operation.-
PRESTART
Lubrication System: Engine oil was drained prior to shipment. Fill engine , to capacities'shown. After engine has been run, check dipstick, add oil to bring level to full mark. Record total capacity for future oil changes. For most operating conditions grade CC/DC lubricating oil is recommended. Do not mix
brands nor grades of lubricating oils.
Oil viscosity should be as follows:
SERVICING
ethylene glycol base. During initial engine run, check the coolant level several times and replenish if necessary to compensate for air pockets which may have formed during filling. Refer to Ford-Dorset engine manual for additional informatioh.
1.
Verify that the electric solenoid valve used
initial starting of unit to allow coolant chambers to and damage to the engine could result from noncompliance.
2.
If engine is equipped with a cooling system filter, do not use antifreeze with an anti-leak formula. The stop leak element can prevent or retard the coolant flow through the filter, thereby eliminating the filtering process completely.
WARNING I '^•^^HBBMHJ and bleed off pressure before removing pressure cap. Severe bums could result from contact with hot coolant.
with city water cooled sets is open before
Be
careful when checking coolant under
pressure. It is advisable to shut engine down
fill.
Overheating
USE
SAE
AMBIENT TEMPERATURE
Below -10oF (-23° C) -
-10° F to +40° F (-23° C to 4.5° C) 40° F to
70° F
(4.5° C to
70° F to 100° F (210 C to 38°
90° F and above (32° C)
21°
C)
C)
VISCOSITY
5W-20 ­10-10W 20-20W
30 40
Oil Capacities (nominal) Oil Pan and Filter—9.5-quarts (9.0 litres)
Cooling System: Cooling system was drained priorto shipment. Fill cooling system before starting. Nominal capacity is 16-quarts (15-litres). For units using either a radiator or heat exchanger (city water cooled),
fill the system with clean soft water. Use a good rust and scale inhibitor additive. If a possibility exists of a radiator cooled set being exposed to freezing temperatures use anti-freeze with an
Fuel System: Refer to the Ford-Dorset engine manual fpr fuel oil specifications. Check with fuel supplier and ensure that fuel supplied meets the
specifications. Filter or strain fuel when filling tank.
Fuel supply tanks should be kept as nearly full as
possible by topping up each time engine is used. Warm fuel returning from the injector pump heats the fuel in the supply tank. If the fuel level is low in cold weather, the upper portion of the tank not heated by
returning fuel tends to increase condensation. In warm weather both the supply tank and fuel are warm.
Cool nightairlowersthetemperatureof thetank more
rapidly than the temperature of the
fuel.
Again this
tends to increase condensation. Condensate mixing with the sulphur in the fuel forms
a sulphurous acid which will corrode and damagethe engine.. KEEP FUEL CLEAN.
WARNING
DO NOT SMOKE while handling
fuel is flammable.
fuel.
Diesel
22
Page 25
Priming Fuel System: Verify that
all
connections
in
the fuel system are secure and no leaks exist. Proceed
with priming
1.
.Open bleed screw
See Figure
2.
Actuate priming lever
transfer pump (Figure filter bleed screw without showing
3. Close filter inlet bleed screw.
4.
Open bleed screw
Figure
as
24.
follows:
24.
on the
inlet side
on the
13)
until fuel flows from
on
the outlet side
of
fuel filter.
side
of the
air
fuel
bubbles.
"
of
filter. See
5. Again, actuate priming lever until a bubble-free flow
of
fuel comes
out of the
bleed screw.
6. Close filter outlet bleed screw.
7. Open
one or two
bleed screws
on
fuel injection
pump.
8. Repeat priming lever actuation until bubble-free
fuel
is
emitted from bleed screws
on
injection
pump.
9. Close bleed screw(s).
10.
Torque
all the
bleed screws.
Filter—5-7 Ib-ft (6.88 Pump—3-5 Ib-ft (4.1
to 9.5 N.m)
to 6.8 N.m)
BATTERIES
Ensure that the cable.connections
secure. Coat connections with petroleum based
non-conductive grease
to
retard formation
rosive deposits.
Check level
Measure specific gravity 80°F (26.7°C). specific gravity
of
electrolyte
If
distilled water
is
less than
to be at
of
1.280, charge until desired reading charge.
to
the batteries are
split ring mark.
electrolyte:
has
been added
place batteries
is
reached. Do,
or
of
cor-
SG 1.280 at
or
on
not
over
STARTING
When
the
preceding service functions have been
performed,
1.
Crankcase filled.
2.
Cooling system filled—input solenoid valve open.
3. Batteries charged
4.
Fuel solenoid valve open.
To start, move the "run-stop/reset-remote" switch the "run" position. The engine should start after a few seconds the
oil
between
Check
1.
DC
2.
AC
3. Frequency Meter—AC generator output frequency.
recheck
of
cranking. Immediately after start, observe
pressure gauge. Normal
30 psi
the
following gauges.
Ammeter—10
to
verify unit
and
(207 kPa)
to 30
is
ready
connected.
oil
and 55 psi
amperes.
to
start.
.pressure
(380 kPa).
Voltmeter—AC generator output voltage.
to
is
1.
SECURING BOLT
2.
BLEED SCREWS
3. SEAL
4.
FILTER ELEMENT
5. BOWL
6. DRAIN
7. SEAL
CAP
FIGURE 24. FUEL FILTER
After running temperature gauge should have stabilized
195° F (82° C adjustable valve Adjust
the that will keep within the range
10
minutes under load
the
at
to
90.6° C). On city watercooled units an is
connected in the water supply line.
hand wheel valve
the
water temperature gauge reading
of
170° F to 200° F (76.7° C to 93.3° C).
to
provide a water flow
water
180° Fto
Break-in Note: Run set at 50 percent rated load forthe
first half-hour
of
initial operation after reaching
operating temperature. Non-Start:
fails
to
lamp lights, refer
chart, Table
If
start,
after or
3 or
a few
starts
to
Table
seconds
and
of
cranking engine
runs then stops and fault
appropriate troubleshooting
4.
STOPPING
To reduce and stabilize the engine temperatures,
the engine
at no
load
for
three
to
five minutes before
shutting down.
Move
the
tion
run-stop/reset-remote switch
to
shut down
the set.
to
stop
run
posi-
23
Page 26
TROUBLESHOOTING
(Engines
with
TABLE
3.
ENGINE
only one
SHUTDOWN
fault
lamp)
SYSTEM
SYMPTOM
1.
1.
Engine stops cranking-and fault
lamp lights, after cranking approximately 75 seconds.
2.
Fault lamp lights immediately
after engine starts.
3. Fault lamp lights and engine . shuts down after running for a period. _
See engine service manual for
troubleshooting fuel system. After correcting problem, reset engine
monitor relay by placing Run-Stop/ Reset-Remote switch to Stop/Reset, then back to the required running position.
2.
Check for:
Overspeed condition as engine starts.
3. Check the following: a. Oil level. Engine will shut down
if sensor is closed.
b. Check engine manual for
troubleshooting oil system.
c. High engine temperature. Check
coolant level; check water flow check radiator for free air flow,
and fan belts for tightness. See engine manual for troubleshooting cooling system.
d.
Check for faulty oil pressure
sensor or faulty high engine temperature sensor.
CORRECTIVE
(city water cooled systems);
ACTION
4.
Engine runs, shuts down and
cranks for 75-seconds. Cranking cycle stops; fault lamp lights.
5. Fault lamp lights, no fault exists.
- ' 4. Check fuel supply.
5. To check a no-fault condition, disconnect leads from TB11 terminals 29,
30 and 31. If fault lamp lights with leads disconnected, replace, engine monitor board. Reconnect leads.
24
Page 27
TROUBLESHOOTING
(Units
with
TABLE
4.
ENGINE
five
fault
SHUTDOWN
lamps)
SYSTEM
SYMPTOM
1.
Overcrank fault lamp lights and
engine stops cranking after approximately 75-seconds.
2.
Engine runs, shuts down, cranks
for 75-seconds, cranking cycle stops, overcrank light ON.
3. *Low oil pressure shutdown.
4.
"High engine temperature shutdown.
CORRECTIVE
.1.
See engine service manual for
troubleshooting fuel system. After correcting fault, reset engine
monitor relay by placing Run-Stop/ ResetTRemote switch to Stop/Reset position, then to the required running position.
2.
Check fuel supply.
3. Check— a. Oil level. Replenish if necessary. b. Sensor. Faulty sensor will shut
c. Refer to engine service manual for
.4.
Check—
a. Coolant level. Replenish if
b. City water cooled sets. Check
c. Check sensor; check thermostat. d.
Radiator model, check fan belts,
depressing Reset button,
down engine.
troubleshooting guide for oil system.
necessary.
water flow, valves, etc.
radiator for obstructions, etc.
ACTION
5. Overspeed shutdown.
6. Overspeed light on, no shutdown.
7. *Low oil pressure light ON. No shutdown.
8. "High engine temperature light ON. No shutdown.
*NOTE:
Not applicable on Pennsylvania State models.
5. Check governor and throttle linkages for freedom of movement.
Check overspeed switch.
6. Disconnect wire at TB11-29. Light on after reset; replace engine monitor board.
7. Disconnect wire at TB11-30. Light ON after relay reset. Replace engine monitor board.
8. Disconnect wire at ON after relay reset. Replace engine monitor board.
TB11-31.
25
Light
Page 28
EXERCISE
Generator sets on continuous standby service are required to be operative at essential loads from a cold start in a short period of time in the event of a power outage.
This imposes severe conditions on the engine. Fric­tion of drypiston rings upon dry cylinderwallscauses scuffing and rapid wearing. These can be relieved by exercising thei set at least once a week for a minimum time of 30-minutes per exercise period. Preferably,
run the set under at least 50 percent load to allow the engine to reach normal operating temperature. This will keep engine parts lubricated, maintain fuel prime,
prevent electrical relay contacts from oxidizing and
insure easy emergency starts. Onan automatic transfer switches contain an optional exercise switch which,
period and shut down a set on a weekly frequency.
For example, the switch can be set for time of start,
length of run, A.M: or P.M. and day of week.
After each exercise period, top off fuel.tank, check
engine for leaks and unit for general condition.
by pre-selection, wMl start, determine run
Locate cause of leaks (if any) and correct.
PERIOD
2.
Run set until thoroughly warm; generator under
at least 50%
3. Shut down engine and drain oil base while still warm.
Refill and attach a warning tag indicating
viscosity of oil used.
4.
Service air cleaner.
5. Clean throttle and governor linkage and protect
by wrapping with a clean cloth.
6. Plug exhaust outlets to prevent entrance of
moisture, bugs, dirt, etc.
7: Clean off dirt and dry entire unit. Coat parts likely
to rust with a light coat of grease or oil.
8. Disconnect battery and follow standard battery storage procedure. Apply a film of non-
conductive grease lugs.
9. Fill fuel tank to prevent condensation contamina­tion.
10.
Provide a suitable cover for the entire unit.
load.
(e.g.,
vaseline) to battery cable
NO
LOAD
Periods of no load operation should be held to-a minimum:
for long periods of time when no electric output is
required, by connecting a."dummy" electrical could consist of heater elements, etc.
OUT-OF-SERVICE
Generator sets removed from service for extended periods of time should be protected from rust and corrosion. No.
2 Diesel fuel should protect a diesel engine for at least 30-days when unit is not in service. Tb protect a unit that will be out of service over 30 days, Onan recommends the following procedure:
1.
Check coo.'ant, top up
recommended anti-freeze.
OPERATION
If it is necessary to keep theengine running
best engine performance will be obtained
load.
Such a load
PROTECTION
The natural lubrication qualities of ASTM
if necessary using
RETURNING A UNIT
1.
Remove cover and all protective wrapping.
Remove plug from exhaust outlet.
2.
Check warning tag on oil base and verify that oil
viscosity is still correct for existing ambient temperature.
3. Clean and check battery. Measure specific gravity (1.260 at 77° F [25° C]) and verify level to be at split ring.
If specific gravity is low, charge until correct value is obtained. If level is low, add distilled water and charge until specific gravity is correct. DO
NOT OVERCHARGE.
WARNING
batteries in operation. Ignition of these gases can cause severe personal injury.
4.
Check coolant level, adjust if necessary.
5. Connect batteries.
6. Verify that no loads are connected to generator.
7. Start engine.
8. After start, apply load to at least 50 percent of rated capacity.
9. Check all gauges to be reading correctly. Unit is ready for service.
TO
SERVICE
Do not smoke while servicing batteries. Explosive gases are emitted from
26
Page 29
HIGH
standard cooling, normal ambients and with No. 2 Onan distributor for operating characteristics under
other conditions.
Engine horsepower loss is approximately 3 percent for each 1000 feet (305 m) of altitude above sea level. Use lower power require­ment at high altitudes to prevent smoke, over-fueling and high temperatures.
HIGH
ALTITUDE
Ratings apply to altitudes up to 1000-feet (305 m), Diesel
fuel.
Consult factory or nearest authorized
TEMPERATURES
1.
See that nothing obstructs air flow to-and-from
the set.
2.
Keep cooling system clean.
3. Use correct SAE No. oil for temperature ditions.
con-
LOW
TEMPERATURES
1.
Use correct SAE No. oil for : jmperature
ditions. Change oil only when engine is warm.
2.
Use fresh
sation.
3. Keep fuel system clean and batteries in a well charged condition.
4.
Partially, restrict cool airflowbutusecaretoavoid
overheating.
5. Connect water jacket heater when set is not
running.
6. Refer to Ford-Dorset manual for further informa­tion.
Water Jacket Heater: The function of this optional heater is to keep the engine warm enough to assure starting under adverse weather conditions. Connect the heater to a source of power that will be on during the time the engine is not running. Be sure the voltage rating is correct for the heater element rating.
fuel.
Protect again; . moisture conden-
con-
27
Page 30
GENERAL
MAINTENANCE
GENERAL
Follow a definite schedule of inspection and ser­vicing, accurate logbook, of maintenance, servicing, and operating time. Use the running time meter to keep a record of operation and servicing. Service periods outlined are recommended for normal service and operating conditions. For continuous duty, extreme temperature, etc., service more frequently. For in­frequent use, light duty, etc., service periods can be lengthened accordingly. Refer to Ford^Dorset engine manual for details of engine service and maintenance procedures.
based on operating hours (Table 5). Keep an
CONTROL
LEVER
WARNING
automatic transfer switch or associated wiring, disconnect batteries. Failure to do so could result in damage to the unit or serious personal injury in the event of inadvertent starting.
ENGINE
SPEED
Before performing any maintenance work on
the engine, generator, control panel,
Generator frequency is in direct ratio to enginespeed which is controlled by the governor. The governor controlling the DEH set is integral with the injector pump.
High and low speed limit stops are set at the ONAN testing facility and normally do not require further adjustment, therefore if your set is ori
con-
tinuous standby service, the governor may never
need to be touched. If however the unit is removed for repair or the set is
used frequently, adjustment may be necessary due to
wear of internal components.
IDLING
STOP
SCREW
MAXIMUM SPEED
STOP SCREW
FIGURE 25. GOVERNOR SPEED ADJUSTMENT
3. - Back off maximum speed stop screw (screwdriver slot).
4.
Turn'idle speed stop screw clockwise until fre-
quency meter indicates 60 Hz. (Counterclockwise
reduces rpm.)
5. Turn maximum speed stop until it bottoms on governor control lever. .
6. Secure lock nuts.
To adjust governor, proceed as follows:
1.
Loosen lock nuts on idle stop screw and max-
imum speed stop screw. Refer to Figure 25.
2.
Start engine; apply full
If governor se'' 'g is considerably out of adjustment, adjust low speed stop .crew until frequency meter indicates ap­proximately 63 >:z before applying
load.
load.
DUST
AND DIRT
1.
Keep set clean. Keep cooling system free of dirt,
etc,
2.
Service air cleaners frequently.
3. Store oil and fuel in dust-tight containers.
4.
See engine operation, and maintenance manual.
28
Page 31
COOLANT (Water
CORROSION
Filter)
RESISTOR
The PAF formula elements can be used with most
permanent antifreezes, but is not recommended for
use with plain water. It is necessary to drain and flush the system thoroughly when changing from one element formula to the other if a non-compatible antifreeze is in use. See Figure 10 for view of the system.
At each 300 to-500 hour interval of operation, depending on conditions, service the coolant filter as follows:
1.
Thoroughly clean filter body and surrounding
area.
2.
Close coolant inlet and outlet shutoff valves.
3. Remove drain plug from bottom of filter body and drain coolant.
4.
Remove capscrews attaching filter cover to body
and remove cover (Figure 26).
5. Lift upper plate and filter element out of filter body. Discard filter element.
6. Remove lower corrosion resistor plate and spring
from filter body.
7. Inspect and clean lower corrosion resistor plate, buffing it to a bright finish. If plate is thin and
pliable, or has developed holes, replace it.
8. Remove and clean sump plate. Clean sump area in filter body.
9. Install sump plate, spring, and lower corrosion resistor plate.
10.
Install new filter element. '
11.
Position upper plate in filter body.
12.
Make certain gasket is ih good condition, then
install cover and secure with attaching
capscrews.
13.
Replace drain plug and open inlet and outlet
shutoff valves.
Initially the element should be changed after 150 hours of operation for borate (PAF) formula filter elements.
Do not use soluble oil or other conditioners in the cooling system. However, filter efficiency is not affected by use of permanent type antifreeze in the system.
UPPER PLATE
FILTER ELEMENT
CORROSION
RESISTOR PLATE
SPRING
FILTER BODY
MODEL OS
FIGURE 26. CHANGING CORROSION RESISTOR
ELEMENT ANO PLATE
PcAUTION^
valves are provided in inlet and outlet lines for isolating the filter from remainder of cooling system.
Whenever coolant supply is changed (spring and must be drained and flushed.
If a stop-leak is added to the coolant, do not
allow it to circulate through the filter. Shutoff
fall),
the system
On an extremely dirty system, the coolant should be drained and flushed before a new element is installed.
In a few rare cases, additional flushing and change of filter may be necessary in order to completely purge the system. Generator sets subject to excessive idling or frequent start and stop cycles, or units located in areas with dust, air contaminants, or other noxious atmospheric conditions, will require more frequent servicing.
After maintenance has been completed, check flow indicator if one has been installed to see if air bubbles
(which can cause pump cavitation) are in the system. If air is present, bleed the system by disconnecting the filter outlet line momentarily until the coolant flows in a solid stream.
GENERAL
ENGINE
MAINTENANCE
Refer to the engine manual furnished with the
generating set for additional details on servicing
procedures not covered by this manual. Refer to Table 5 for general information on clearing the electric generating set of any malfunctions which
have developed during the period of operation.
29
Page 32
START-STOP (Failure
to Shut Down)
SOLENOID
In case the set does not shut down when moving Run­Stop/Reset-Remote switch to Sfop position, the stop solenoid linkage may be out of adjustment. See Figure 27. Adjust as follows:
1.
Remove the joint that attaches the stop solenoid
rod to injection pump arm.
2.
With the engine running, move the lever arm on
the injection pump back slowly towards radiator just until engine stops.
3. Hold lever in this same position and adjust linkage accordingly.
4.
Snap rod joint back on injection pump arm.
START-STOP
SOLENOID
GOVERNOR LUBRICATING OIL-
FILLER PLUG
OIL LEVEL PLUG
DRAIN PLUG
(GOV.LUBE OIL)
FIGURE 27. STOP-SOLENOID LINKAGE ADJUSTMENT
SPEED- CONTROL
LEVER
_ v
A
(^DISCONNECT JOINT HERE •
fti
(2)PULL BACK LEVER'IN THIS DIRECTION
(3)READJUST ROD ACCORDINGLY
JUST UNTIL ENGINE STOPS
AND SNAP BACK ON
AC
GENERATOR
There are no brushes, brush springsorcollector rings on these generators, therefore they require very little servicing.
Periodic inspections, to coincide with
engine oil changes, will ensure good performance.
Generator Bearing: Inspect the bearing every 1000 hours with the unit running. Apply light smear of Molykote grease if unit appears dry.
If using the unit for "prime power," replace the bearing every 10,000 hours or two years. If using the set for "standby," replace the bearing every five years.
Check generator voltage. It may be necessary to make a slight readjustment of the voltage rheostat to obtain the preferred voltage at average
load.
30
\
Page 33
INSPECTION
AND
CLEANING
When inspecting the rotating rectifier assembly,
make sure diodes are free of dust, dirt and grease.
Excessive foreign matter on these diodes and heat
sinks will cause the diodes to overheat and will result
in their failure. Blow out the assembly periodically, with filtered, low pressure air. Also check to see that diodes and leadwires are properly torqued. The diodes should be torqued to 30 in. Ib. (3.4 N*m) or finger tight plus a-quarter
turn.
Blow dust out of
control panel.
BATTERIES
Check the condition of the starting batteries at least
every two weeks. See that connections are clean and
tight. A light coating of non-conductive grease will
retard corrosion at terminals. Keep the electrolyte at the proper level above the plates by adding distilled water. Check specif ic gravity, recharge if below
1.280.
CONNECTIONS
(Fuel,
Exhaust,
etc.)
Operator should periodically make a complete visual inspection of the set while running at rated
load.
Some of the things to check for are as follows:
1.
Check all fuel and oil lines for possible leakage.
2.
Inspect exhaust lines and mufflers for possible
leakage and cracks.
3. Periodicallyordaily, drain moisture from conden­sation traps.
4.
Inspect water lines and connections for leaks and
security.
5. Inspect electrical wires and connections for security and fray damage.
If generator requires major repair or servicing, contact an authoriz-
ed Onan dealer or distributor.
TABLE
5.
OPERATOR
MAINTENANCE ITEMS
MAINTENANCE ITEMS 10 50
Inspect Complete Set Check Engine Oil Level Check Radiator Coolant Level Check Fuel Check Governor Oil Level Check Air Cleaner (Clean if
Required)
Check Electrolyte Level of
Battery Stop-Solenoid Linkage Adjust Fan Belt Tension x3 Change Governor Oil Change Engine Oil & Filter Clean Fuel Lift Pump Clean Sediment Bowl & Filter Check Starter Clean & Inspect Battery
Charging (DC) Alternator Check AC Generator
Replace Fuel Filter Element x2 Replace Air Cleaner Element x2 Remove & Service Injectors
Adjust Valve Clearances
Examine Water Filter Element X
MAINTENANCE
OPERATIONAL HOURS
X X
X
xl
X
x2
x
x2
SCHEDULE
200 400
X
x2
X X
x5
X
x6
ft
•4
x4
X
xl - After every run. x2 - Perform more often in extremely dusty conditions. x3 - Adjust to
Refer to Ford engine manual. x4 - Check for proper spray pattern, etc. Refer to the Ford manual. x5 - Oil front bearing sparingly; check brushes.
x6 - Check brushes (if installed), replace if worn to 5/8-inch
(15.9 mm) or if damaged. DO NOT LUBRICATE.
1/2-inch
(12.5 mm) depression between pulleys.
31
Page 34
TABLE
TITLE PAGE Parts Catalog 33
Replacement Engine 33 Set Data Table 33 General Information 34 Cooling System Group 35
Electric Fuel Pump Parts Group - Optional 35
Miscellaneous Engine Parts Group 36,37
Stopping Solenoid Group 38
Oil Drain Group 38
Voltage Regulator Filter Group - Optional 39
Mounted Fuel Tank Group - Optional 39
Generator Group •
Voltage Regulator Group - Spec B Through F... 42*43
Exciter Rotor Group . 44 Mounting and Housing Group (Housed Sets) 45 Mounting and Housing Group (Unhoused Sets) 46,47 Control Group (AC Portion) • 48,49 Control Group (Engine Portion) 50,51
Voltage Regulator Group (Spec B Through G) .. .52
Voltage Regulator Group (Begin Spec H) 53 Cranker Control Group - Standard 54 Cranker Cycle Control Group - Optional 54
Engine Control Monitor Group 55 Wattmeter Group - Optional 56 Circuit Breaker Group - Optional 56
179-0441 Installation Day Fuel Tank - Optional 57
179-0368 Installation Exhaust Muffler - Spec B
Through Serial #K760188585 58 179-0264 Installation Water Cooled Exhaust ManifoldOptional 58 179-0368 Installation Exhaust Muffler - Begin Serial #K760188586 During Spec G .59 179-0388 Heat Exchanger Cooling with Regulator - Optional 60 179-0371 Installation Heat Exchanger Cooling - Optional 61 179-0180 Installation Water Jacket Heater - 120 Volt - Optional 62 179-0256 Installation City Water Cooling with Water Cooled Manifold
Optional 63 179-0319 Installation City Water Cooling - Optional 64 179-0376 Installation Water Jacket Heater - 240 Volt - Optional 65
OF
CONTENTS
• •
• 40,41
32
Page 35
PARTS
This catalog applies to the standard DEH Generator Sets as listed below. Parts are arranged in groups of related
items.
Each illustrated part is identified by a reference number corresponding to the same reference number in the parts list for that group. Parts illustrations are parts from this catalog that apply to your set. Unless otherwise mentioned in the description, parts are
interchangeable between models. Right and left sides are determined by facing the engine end (front) of the set.
typical.
SET
CATALOG
Using the Model and Spec No. from the nameplate, select the
DATA
TABLE
MODEL
MODEL
* - The Specification Letter advances (A to B, B to C, ...Z to AA, etc.) with manufacturing changes.
A Specification Number, other than 1, designates customer option(s).
£ - These sets are reconnectible, refer to Specifications (Generator Details) in Operator's Manual
for Electrical Data.
NOTE:
Hertz is a unit of frequency equal to one cycle per second.
AND
SPEC
AND
SPEC
25.0 DEH-53R/*
25.0 DEH-515R/*
30.0 DEH-3R/* 30,000
30.0 DEH-15R/*
30.0 DEH-9XR/*
NO.
NO.
WATTS
25,000 120/240 25,000 £
30,000 £
• 30,000
VOLTS
120/240 60
347/600 60
REPLACEMENT
100-0993
Engine, Replacement (Ford Motor Company Model 2711E
General Description: Includes—Complete Cylinder Block, Fuel Pump, Fuel
Filter, Oil Filter, Starter Motor, Governor, Fan Blades
(pusher type), Flywheel, Water Pump, Oil Pan, Exhaust
Manifold.
Excludes—Alternator, Alternator Mounting Brackets, Alternator Belt, Temperature Sender, Oil Pressure Sender, Air Cleaner, Radiator, Fan Belt and Front Moun-
ting Brackets.
ELECTRICAL
HERTZ
ENGINE
DAI
50
50
60
FA
WIRE
3
12 1 or 3
3
12 1 or 3
4
PHASE
1 1 ­3
ENGINE
Engine parts modified oradded by Onan will be in this parts list and have Onan part numbers. These supersede similar parts listed in the Ford Engine manual.
All Ford engine parts must be ordered from your nearest authorized Ford distributor. When ordering parts, complete engine TYPE, SERIAL and OPTIONS number.
_ I
refer to the engine nameplate giving the
PARTS
< ' ^petrel': : ^.•••^
REG.
U.S. PAT. OFF.". . > • 1 • -
INDUSTRIAL
SERIAL
TYPE
ENGINE
OPTIONS
NOTICE!
ITEMS REFERENCED AS OPTIONAL INDICATE PART IS FACTORY INSTALLED AND MAY NOT BE
APPLICABLETO ALL MODELS. FOR FIELD CONVERSIONS ADDITIONAL PARTS ARE USUALLY REQUIRED.
33
Page 36
For parts
or
service, contact
Authorized Onan Parts
INSTRUCTIONS
the
dealer from whom
and
Service Center.
FOR
ORDERING O^^S!* REPAIR PARTS
you
purchased this equipment
or
refer
to
your Nearest
To avoid errors Always refer
1.
Always give
to
or
delay
the
nameplate
the
MODEL
in
filling your parts order, please furnish
on
your unit:
and
SPEC
NO. and
SERIAL
NO.
Qnan
r ELECTRICGEN
Yll D D D T A'U'T
.IWIT U_K
... ONAN
„ DIVISION Ej-^P . MINN E AKOL IS. MINN. 55432,
'
fOR
VAIWAYS
I ATI I
I.WH'EN 'ORDERING
M'ANUF
GIVE ABOVE NO"V
ACTUI
EP ' BY
^- :
Of
ONAN COSPOli AIION,
ElECI EOUtPMtNI^.ONl
SET
"PAius
U S A^
Y
all
information requested.
For handy reference, insert "YOUR"
2.
Do
3 Give
return
nameplate information
not
order
by
reference number
the
part number, description and quantity needed
the
part prepaid
to
your dealer
or
group number: always
or
nearest AUTHORIZED SERVICE STATION. Print your name and
in
the spaces above.
of
each item.
address plainly on the package. Write a letter to the same address stating
4.
State definite shipping instructions.
promptly against packing list indicates items
Prices
are
purposely omitted from this Parts Catalog
the
transportation company making
are
import duties, sales taxes, exchange rates, For current parts prices, consult your Onan Dealer, Distributor
"En esta lista
de
los
Consiga
de
partes
los
precios se omiten de proposito, ya que bastante confusion resulto de fluctuaciones
precios, derechos aduanales, impuestos
los
precios vigentes
de
su
Any
claim
back ordered.
etc.
de
distribuidor
de
for
loss
or
damage
the
delivery. Shipments
due
to
the
or
venta, cambios extranjeros,
productos "ONAN".
34
use
part number
If
an older part cannot
the
to
your unit
and
reason
in
are
description.
be
identified,
for
returning tfie part.
transit should
complete unless
be
filed
the
confusion resulting from fluctuating costs,
Parts
and
Service Center.
etc."
Page 37
COOLING
^EF. NO. NO.
1
130-0352
2
815-0181 4
3
130-0351 1
4 815-0181 4 Screw, Tapping, Thread
5
503-0365 1
6- 503-0441 1 7 503-0311 8 503-0441 1 9 504-0028 1
10 130-0449 11 821-0014
12 870-0113 8 13 130-0815 1 14 405-1054 15 KIT, REPLACEMENT-
130-0769 130-0772 1
16 GASKET, COVER
130-0777 130-0778 1
17 ELEMENT, FILTER
130-0773 130-0776 1
18
PLATE,
130-0779 1 •Regular Element 130-0780 1 +PAF Element
Contained i n the original element.
Contained in the #130-0772 Element Replacement Kit for Permanent Anti-Freeze.
SYSTEM
PART
FILTER ELEMENT (Lower)
QTY.
USED
the #130-0769 Element Replacement Kit for
GROUP
1
Guard, Screw, Tapping, Thread
Guard,
Clamp, Hose Hose,
3
Clamp, Hose Hose,
Valve - Drain
1
Cap - Radiator
8
Screw, Self-Locking - Hex
Nut, Clinch (5/16-18) Radiator
1
Flange, Duct - Optional '
-WATER FILTER
1
Regular (Includes Parts Special (Includes Parts
1
•Regular Element +PAF Element
1
•Regular Element +PAF Element
(Radiator Cooled Generator
PART
DESCRIPTION
Fan - Right Side
Cutting - Hex Head with
External Tooth Washer (#10-32 x 1/2")
Fan - Left Side
Cutting - Hex Head with External Tooth Washer (#10-32 x 1/2")
Rubber - Upper Rubber - Lower
Head (5/16-18 x 1/2")
Marked *) Marked +)
Marked +)
1
Sets)
ELECTRIC
FUEL
PUMP
PARTS
35
GROUP
REF.
NO. NO.
1 2 3 4 5 6 7 8 9 149-1449 1
10
- OPTIONAL EQUIPMENT
PART
149-0554
149-1445 149-1447 . 1 149-1446 149-1453 149-1452
1.49-0705 149-1451 149-1450
149-1448
QTY.
USED
!
1 1
1 1 1 1
"1
1
PART
DESCRIPTION
Pump. Fuel
Filter Magnet Gasket, Cover Cover Plunger
Spring,
Plunger Return
Spring Cup & Valve
Gasket. Spring Cup
Washer, Cup Gasket
Retainer. Cup & Plunger
Page 38
MISCELLANEOUS ENGINE PARTS GROUP
22 '?
36
Page 39
MISCELLANEOUS
ENGINE
PARTS
GROUP
REF.
NO.
10 309-0269 1 11 502-0193 1 12 502-0051 1
13 140-1089 1 14 15 503-0597 16 503-0354 17 18 800-0030
19 850-0045 2 20 862-0015 2 Nut, 21 191-0725 1 22 23
24 850-0045 1 Washer, Lock - Spring (5/16) 55 25 1191-0101 26 27 191-0781 1 28 800-0095
29 850-0060 1 30 31 191-0665
32 312-0058 1
PART
NO.
SENDER,
193-0108'
193-0244 309-0169 309-0064
SENDER
193-0202 193-0249 502-0361 505-0763
SENDER, WATER TEMPERATURE 193-0104 193-0246 1 Begin Spec
8 309-0179 1 9 309-0178 1
140-1091
155-0863
191-0619 800-0025
1191-0101
'511-0084
'511-0084
862-0016
QTY.
USED
OIL PRESSURE
OIL TEMPERATURE
1 Spec B Through 1 Begin Spec 1 Switch, 1 Switch,
1 Spec B Through 1 Begin Spec 1
. Tee,
1 Cross,
1
Spec B Through Switch,
Switch, Switch, Connector, Pipe - Fuel Coupling,
Element, 1 Cleaner, 1
Hose,
2
Clamp, Hose
1
Adapter, Exhaust Tube
2
Screw, Washer, Lock - Spring (5/16) Guard,
1
Shield, Screw,
1
1
Bracket, Adjusting - Alternator
1
Belt, Driye - Alternator Pulley, Drive - Alternator Screw,
1
Washer, Lock - Spring
1
Nut,
"Alternator (Includes Regulator
1
Capacitor
PART
DESCRIPTION
G .
H Low Oil Low Oil
Shutdown - Optional
Pipe -1/8")
F'ipe - (1/8")
Optional
High Water Temperature 41 High WaterTemperature
Alarm - Optional
Low Engine Temperature-
Optional Line (1/8")
Air
Air
Cap - Hex
(5/16-18 x 1-1/4")
Hex
Belt Heat - Alternator Cap - Hex
(5/16-18
Cap - Hex
(1/2-13x2-1/4")
Hex
&
Fan) -
Pressure Pressure
G
H
-
G
H
Pipe - (1/8")
Air
Cleaner
Cleaner
- Air
Cleaner
Head
(5/16-18)
Head
x 5/8")
Head
(1/2-13)
Motorola #7D44039B
(.10
MFD) +
(1/2)
REF.
NO.
33 34 35
36 37
38 39
40
40 815-0104
41
42 43
44 45
46
46 47
48 49 50
51 52
53
.
54
PART
NO.
191-0732 1 800-0048 2 850-0045
191-0786 1 800-0047
856-0010 332-1292
VERNIER THROTTLE Parts Marked
+)
526-0052
QTY.
USED
•Regulator, Voltage (Part Alternator)
Screw,
2
1 1 1
(5/16-18
Washer, Lock - Spring (5/16) Bracket, Mounting - Alternator Screw,
(3/8-16x5/8")
Washer, Lock - External/
Internal Tooth (3/8")
Bracket, Terminal
ASSEMBLY-OPTIONAL (Includes
+Screw, Machine - Fillister
Head (#8-32 x 5/16")
+Washer, Flat - Brass
(17/64" +Clamp, Cable +Swivel +Cable, Throttle +Bracket, Angle - Throttle
Mounting
Harness, Engine Control Tang,
Drive - Optional
(Tach Sender)
Sender, Tach - Optional Cover, Plate - Starter Hole Screw,
(7/16-14x3/4")
Washer, Lock - Spring (7/16") Screw,
(1/2-13
Washer, Lock - External/
Internal Tooth
Cable, Electrical - Battery
PART
DESCRIPTION
Cap - Hex
x 7/8")
Cap - Hex
IDx9/16"ODx
Cap - Hex
Cap - Hex
x 1")
(1/2)
Head
Head
Head
Head
(16")
Cable, Electrical - Battery 56 57
58
- For components, contact you r nearest Motorola Dealer or
Motorola Automotive Products, Inc., Franklin Park, Illinois60131.
- Included
in
Optional Vernier Throttle Assembly.
(24")
Cable, Electrical - Battery
Jumper
Line,
Fuel - Begin Spec
Line,
Fuel - Begin Spec
9401
W.Grand Ave.,
of
1/32"Thk)
H H
37
Page 40
STOPPING
18
1112
SOLENOID
GROUP
REF.
NO.
10 812-0151
PART
NO.
1 115-0025 1 2
150-0638
3
115-0025 1 .
4 516-0103 .1 5
306-0215 ' 1
6
518-0218
7 306-0193 8 518-0203 1 9
306-0161
QTY.
USED
1
2 1
1 2
PART
DESCRIPTION
Nut. Hex - Hardened (1/4-28) Joint, Ball - Rod to
Injection Pump Nut, Hex - Hardened (1/4-28) Pin,
Roll (1/8 x 1/2")
Rod,
Connecting - Solenoid '
to Injector Pump
Ring,
Retaining Cover, Plunger - Solenoid Ring,
Retaining Spring,
Plunger - Solenoid
Screw, Machine - Round
Head (1/4-20 x 3/4")
OIL
DRAIN
REF.
NO. NO.
11 850-0040 12 862-000.1 2 Nut, Hex (1/4-20) 13 307-0628 1 14 306-0222 1 15 306-0162 1 16 800-0069 2
17 850-0050 2 18 306-0214 1 Bracket, Mounting - Solenoid 19 306-0226 • 1
PART
QTY.
USED
2
PART
DESCRIPTION
Washer, Lock - Spring (1/4)
Solenoid (12 Volt)
Plunger, Solenoid Spacer, Mounting - Solenoid Screw, Cap - Hex Head
(7/16-14x3/4")
Washer, Lock - Spring (7/16)
Brace - Solenoid Mounting
GROUP
REF.
PART
NO. NO-
1 503-0131 1 Clamp, Hose 2 503-0484 1 Hose, Rubber - Drain 3 . 505-0135 1 Nipple, Pipe - Half 4 504-0030 1 Valve, Bail - Oil Drain 5 505-0101 1 Nipple, Pipe - Close 6 505-0119 1 Elbow, Pipe - Street (45°) 7 102-0619 1 Reducer, Pipe - Oil Drain 8 102-0532 - 1 Gasket, "O" Ring - Oil Drain
QTY.
USED
PART
DESCRIPTION
38
Page 41
VOLTAGE REGULATOR FILTER
Optional
GROUP
REF.
NO.
. 5 312-0188
10 304-0427 4 Washer, Shoulder - Centering 11 12 13 862-0001 2 Nut, Hex (1/4-20)
14 354-0025 2 Resistor, Wirewound 15 232-2218 1 Bracket, Angle - Mounting
PART QTY.
NO.
232-2219
1
812-0061 .
2
850-0020
3
860-0006
4
312-0189
6"
815-0001
7
853-0003
8 860-0006 4 Nut, Hex (#6-32)
812-0165 2 Screw, Machine - Round Head
9
304-0292
850-0040 2 Washer, Lock - Spring (1/4)
USED
Filter,
1
- .
4 5 Washer, Lock - Spring (#6)
4 Nut, Hex (#6-32)
2 1
4 Screw, Machine - Binding
4 Washer, Lock - External Tooth
2
Voltage Regulator -
(Complete)
Screw, Machine - Round Head
(#6-32 x 3/8")
Bracket, Hold-down - Capacitor Capacitor, Plastic Dielectric,
Metal Case (15 MFD, 440 VAC) Head, (#6)
(1/4-20x4-1/2")
Insulator, Disk
(10-Ohm,
PART
DESCRIPTION
Brass (#6-32 x 1/4")
100 Watts, 5%)
MOUNTED OPTIONAL
REF.
NO.
10 11 501-0009 1 12 504-0007 1 13 159-0490 1 14 502-0002 1 Elbow, Pipe - 90°
PART QTY.
NO.
1
159-0512
2
159-0751
3 812-0158 . 2 4 850-0040 2 Washer, Lock - Spring (1/4)
5 821-0010 8 6 159-0489 1
7 505-0057 1 8 504-0013 1 9 501-0007 1
503-0685
USED
1 Cap and Indicator 1
Gasket, Gas Cap Screw, Machine - Round
Head (1/4-20 x 2")
Screw, Self-Locking - Hex
Head (1/4-20 x 1/2") Strap Assembly, Mounting Plug,
Pipe - Square Head
Valve,
Globe
Hose,
. 1
Rubber Clamp, Hose Hose,
Rubber
Valve,
Globe
Tank, Fuel (20 gallon)
FUEL
EQUIPMENT
PART
DESCRIPTION
TANK
GROUP
(Housed
Sets
Only) -
39
Page 42
63
GENERATOR
GROUP
50 51
44
14543
42 4,1 38
40 39
40
Page 43
GENERATOR
GROUP
REF.
NO.
4 5
6 7
10
11
12 305-0481 2 13
14 15 16 17
18 19
20
21.
22 23
24 25
26 27 28
29 30 31
32 33 850-0050
34
PART
NO.
1
800-0003
2
850-0040
3
150-1456
150-0723 1 870-0250 1
862-0001 853-0013 1
150-1356
VOLTAGE REGULATOR ASSEMBLY Spec B Though F
(See Separate Group for Complete Breakdown) 305-0491 305-0489 1 800-0009 2
853-0013 4
/
862-0011 850-0050
211-0185 509-0125 800-0009 4
850-0040 4
220-2353 1 114-0023 4
850-0040 526-0018 4
212-1225 4 526-0016 4
212-0342
212-1105 4 214-0046 800-0008 2
850-0040 2 862-0001 234-0368 1
800-0051
520-0718 4
QTY.
USED
2
Screw, Cap - Hex Head
2
Washer, Lock - Spring (1/4") Contact Assembly - Overspeed
1
tPoint, Overspeed Switch tNut, Insulated - Overspeed
2
tNut, Hex (1/4-20) tWasher, Lock - External
1
tBracket, Overspeed Switch
1
Brushless Generator Brush Type Generator Screw, Cap - Hex Head
Washer, Lock - External
Spacer, Sleeve
4
Nut, Hex - Special, Grade 8
4
Washer, Lock - Spring (3/8")
1
End Bell - Generator
1
. Seal, Oil - "O" Ring
Screw, Cap - Hex Head Washer, Lock - Spring (1/4")
Stator, Exciter - Brushless Screw, Cap - Hex Head,
4
Washer, Lock - Spring (1/4"). Washer, Flat (17/64" ID x
Spacer, Sleeve Washer, Flat (17/64" ID x
1
Rig Assembly.Brush (Includes
+Spring,
4
•Brush, Screw, Cap - Hex Head
Washer, Lock - Spring (1/4")
2
Nut, Hex (1/4-20) Screen,
8
Screw, Cap - Hex Head
8
Washer, Lock - Spring (3/8") Stud (3/8-16 x
DESCRIPTION
(1/4-20 x 1/2")
Switch (Includes Parts Marked t) - Begin Spec G
Switch
Tooth (1/4")
(1/4-20 x
Through F Tooth (1/4") Spec B
Through F
(3/8-16).
(1/4-20 x
Generator Special - Heat Treated
(1/4-20 x
5/8" OD x 1/16" Thk)
9/16" OD x 1/32" Thk)
Brush and Springs Marked +) ­Brush Type Generators
(1/4-20 x
Generator (3/8-16x1-1/4")
Used on Single Phase Sets
1-1/2")
1-1/2")
1-1/4")
Brush
Generator
1-1/4")
Air Outlet -
PART
3/8-16
Spec B
x 14-11/16")
REF.
NO.
35
36 503-0611 4 37
38
•39 40 41 800-0513 1
42 850-0079 1 •Washer, Lock - Spring (3/4") 43 526-0238 1
44 510-0101 • 1 45 232-2102 1 •Spacer, Sleeve 46 515-0145 1 47
48 204-0083 1 49 805-0018. 8 Bolt, Hex Head - Grade 8 50 805-0033 8 •Bolt, Hex Head - Grade 8 51 526-0259 8 •Washer, Flat - Special 52 232-2078 1
53 54 ROTOR, WOUND
55 56 850-0040 2 57 232-2210 2 58 59 508-0001 1
60 800-0072 9 Screw, Cap - Hex Head 61 850-0055 9
62 516-0152 2 63 231-0149 1
t - lncludedinOverspeedContactAssemblyNo.150-1456. + - Included in Brush Rig Assembly No. 212-0342.
* - Included in Generator Rotor Assembly.
PART
NO.
520-0721 •
STATOR, WOUND 220-1552 . 220-1994 220-1552 1 220-1451 1 220-1599 812-0189
856-0010 150-0717
ROTOR ASSEMBLY, GENERATOR (Includes Parts Marked *)
201-1739
QTY.
USED
4 Stud (3/8-16 x
1 25.0DEH-53R Sets 1
1 1
1 1
1
Used on Three Phase Sets
Hose,
Rubber
25.0DEH-515R Sets
30.0DEH-3R Sets
30.0DEH-15R Sets
30.0DEH-9XR Sets Screw, Machine - Round Head
(3/8-16x3/4")
Washer, Lock - External/
Internal Tooth (3/8")
Switch,
'Screw, Cap - Hex Head,
Special Heat Treated, Unplated (3/4-10 x
•Washer, Flat - Steel Alloy (13/16"
•Bearing,
•Key, Machine (1/4" x 1/4" x 7/8
•Rotor Assembly, Exciter ­Brushless Generators Only (See Separate Group for Components)
•Ring,
Collector - Brush
Type Generators Only (3/8-16 x 1") (5/8-11x1")
PART
DESCRIPTION
3/8-16
Overspeed
IDx 2" ODx 3/16" Th
Ball
x 16-11/32")
1-1/2")
•'•
Hardened Steel 5/8"
•Disk, Drive - Generator
205-0089
201-1714 1 201-1716 201-1719 201-1716 201-1716 862-0001 2
232-2211 2
1
•Fan,
Centrifugal - Generator
•Fan,
Centrifugal - Generator
25.0DEH-53R Sets
1
25.bDEH-515R Sets
1
30.0DEH-3R Sets
1
30.0DEH-15R Sets
1
30.0DEH-9XR Sets Nut, Hex (1/4-20)
Washer, Lock - Spring (1/4") Cover, Adapter Slot Catch,
Adapter Slot Cover
Grommet, Rubber - Generator
Adapter
(7/16-14 x Washer, Lock - Spring (7/16") Pin,
Straight, Headless
Adapter - Engine to Generator
1-1/4")
41
Page 44
22
VOLTAGE REGULATOR GROUP - SPEC B THROUGH
M-15-16-17
F
7-8
18-19-20 14-15-16-17
42
32
32 34
Page 45
VOLTAGE REGULATOR GROUP - SPEC B THROUGH
F
REF.
NO.
PART OTY,
NO. USED
CHASSIS
(Complete)
305-0491
305-0489 305^0482
358-0029
RECTIFIER, SILICON 364-0014 364-0012
RECTIFIER, SILICON
358-0035
358-0031 5 363-0048 6 332-1265 7 812-0077
8 853-0005 9 812-0077
10 853-0005 11 871-0010 12 526-0009
13 850-0030 14 812-0079
15 526-0048 16 853-0005
PART
DESCRIPTION
ASSEMBLY,
1 1
1 2
2 .
2 2
3 6 6
6 6 ;tScrew, Machine Roundhead
6
3 3
3 2
2 2
VOLTAGE REGULATOR
Brushless Generator (Includes
Parts Marked
Brush Type Generator (Includes
Parts Marked
•fChassis, Voltage Regulator
•fRectifier, Silicon CONTROLLED
•Brushless Generator tBrush Type Generator
*
Brushless Generator thrush Type Generator *tHeat Sink, Rectifier
'tlnsulator, Stand *tScrew, Roundhead - Heat Sink
Mtg.
'tWasher, Lock
"tWasher, Lock "tNut, "tWasher, Flat (7/32" l.D. xl/2"
"tWasher, Lock - Spring - Rectifier "tScrew, Machine - Roundhead
"tWasher, Flat (Brass) (.172" "tWasher, Lock
(8-32 x 3/8")
Sink
Mtg. (#8)
Stand
(#8-32 Stand
Hex -
(CRI,
x
1/16"
(CRI, Mtg.
(CRI, CR2
Rectifier Lead
(#8-32 x
3/8" O.D. x 1/32"
Lead
*)
t)
(CR3)
(Q4 & Q5)
(Q4 & Q5)
(CR1
(CR1
off
- ET -
Heat
off
Insulator
x 3/8")
off
Insulator Mtg.
Rectifier Mounting
CR2 & CR3)
Thick) - Rectifier
CR2 &
x 1/2")
to
Heat Sink
Mtg.
- ET
(#10-32)
CRS)
& CR3) (#10)
to
Heat Sink
- ET -
Thick)
Rectifier
(#8)
&CR2)
&CR2)
-
(#8)
O.D.
Mtg.
-
l.D.
REF.
NO. NO.
17 18 812-0079
19 853-0005
.20 871-0007
21 508-0002 22 332-1415 23
24 812-0081
25 26 860-0008 27
28 29 30
31 150-0723 32 862-0001
33 853-0013
34
35 332-1043
* - Parts included
t - Parts included
PART QTY.
871-0007
332-1266
853-0005
REACTOR ASSEMBLY, COMMUTATOR 315-0343 315-0341 812-0077
853-0005 860-0008
870-0250
USED
2
"tNut,
1
"tScrew, Machine Roundhead
1
'
"tWasher, Lock
1
"tNut,
2
"tGrommet, Rubber
1
"tClamp, Cable
1
"tBIock, Terminal
2
"tScrew Machine - Roundhead
2
"tWasher, Lock
2
"tNut,
1
"Brushless Generator
1
tBrush Type Generator
2
"tScrew, Machine - Roundhead
• Reactor
2
"tWasher, Lock
2
"tNut,
1
"tPoint, Contact - Overspeed
2
"tNut,
.1
"tWasher, Lock
2
"tNut, Insulator - Contact Point
2
.
"tJumper - Terminal Block
in
305-0491 Voltage Regulator,
in
305-0489 Voltage Regulator.
DESCRIPTION
Hex -
Heat Sink (#8-32)
Terminal Block Lead
Heatsink (#8-32
Terminal Block
Sink to Heat Sink (#8-32)
Terminal Block Mounting
(#8-32 Block Mounting Mounting (#8-32)
Reactor Mounting
Switch
(1/4-20)
Contact Point
(1/4)
Rectifier Lead
(#8)
Hex -
Terminal Block Lead
x 5/8")
Hex -
Terminal Block
Mtg.
Hex -
Reactor
Hex -
Contact Point
PART
x 1/2")
- ET ­ to
Heat
- ET -
Terminal
(#8)
(#8-32
- ET ­ (#8)
Mtg.
- ET .
(1/4)
to
-
to
-
-
x 3/8")
(#8-32)
43
Page 46
EXCITER
ROTOR
GROUP
-19
REF.
NO.
4
7 8
9
10
PART
NO.
1
358-0016
2
358-0015 3
3
870-0053 850-0030 6
5
508-0093 2
6
813-0100 2 526-0008 850-0030 2
870-0053 • 2 813-0110 4
QTY.
USED
3 6
2
PART
DESCRIPTION
Rectifier, Diode - Positive Rectifier, Diode - Negative
Nut, Hex (#10-32)
•Washer, Lock - Spring (#10) Grommet, Rubber Screw, Machine - Round Head
(#10-32.x 1/2")
Washer, Flat (13/64" ID x
7/16" OD x 1/32" THK) Washer, Lock - Spring (#10) Nut, Hex (#10-32) Screw, Machine - Round Head
(#10-32 x 2")
44
REF.
NO.
•.. 11
526-0009
12
332-0050 13 508-0124 14
508-0156 15
850-0030 16
870-0053 4 17 .
363-0054 18
363-0055 1
19
201-1737
PART
NO.
QTY.
USED
4 2
• 4 4
5 1
1
PART
DESCRIPTION ' "
Washer, Flat (7/32" ID x
1/2" OD x 1/16" THK) Clamp, Loop . Spacer, Stepped Washer, Flat - Fiber
(19/64"
IDx
1-7/8"
ODx Washer, Lock - Spring (#10) Nut, Hex (#10-32) Heat Sink, Rectifier -
Positive
Heat Sink, Rectifier -
• Negative Rotor,
Exciter
1/8"THK)
Page 47
MOUNTING
AND HOUSING
GROUP
-8
-12-13
(Housed
Sets)
REF.
NO.
.9
10 11
12 405-1831
13
14 406-0157 15 406-0089 16 809-0059
17 870-0106 ' 18 19
PART
NO.
HOUSED SETS - OPTIONAL (Includes following parts and unhoused set items indicated in previous group)
813-0098
1
2
850-0030 870-0053
3 4
406-0105
5 405-1808 6 405-1832
7 821-0014 8 821-0016
870-0113 821-0014 6
405-1814
.405-1844
405-1777 1 821-0014
QTY.
USED
"16
16 16
8 2
2 4
6 6
2 1
1
1 1
3 3 2
DESCRIPTION
Screw, Machine - Round
Head (#10-32 x 3/8") Washer, Lock - Spring (#10) Nut, Hex (#10-32) Clamp, Door Door,
Louvered - Engine
Section
Door,
Louvered - Generator
Section Screw, Self-locking - Hex
Head (5/16-18 x 1/2") .
Screw, Self-locking - Hex
Head (5/16-18 x 3/4")
Nut, Clinch (5/16-18)
Screw, Self-locking - Hex
Head (5/16-18 x 1/2")
Support, Housing - Center
Panel,
Housing - Top (Used with standard exhaust manifold)
Panel,
Housing - Top (Used with water cooled exhaust
manifold) Handle, Latch (with Keys) Catch,
Latch
Screw, Tapping - Pan Head
(#14 x 1/2") Nut, Spring Sheet (#14) " Door,
Access - Rear
Screw, Self-locking - Hex
Head (5/16-18 x 1/2")
PART
REF.
NO. NO.
20
21 850-0030 22 405-1780 23 821-0014 .4
24 25
26 27 508-0001 2
28 813-0098 29 850-0030
30' 31 821-0010 32 33
34 821-0010 35
36 821-0010 37 403-0895
38 39
40
PART QTY.
813-0098
405-1812 1 821-0010
234-0369
301-3195 1
821-0014
301-3196
301-3191
800-0048 850-0050 6
403-0894
USED
6 6
1
4
1
. 4
4 .
3 2
1 1 1
8 2
6
1
PART
DESCRIPTION
Screw, Machine - Round
Head (#10-32 x 3/8") Washer, Lock - Spring (#10) Panel,
Access - Rear
Screw,- Self-locking
Head (5/16-18 x 1/2") Panel,
Housing - Rear
Screw,.Self-locking - Hex
Head (1/4-20 x 1/2") Cover, End Bell - Generator Grommet, Rubber
(3/4"
ID x
Screw, Machine - Round
Head (#10-32x3/8") Washer, Lock - Spring (#10) Plate,
Blank - Bottom,
Junction Box Screw, Self-locking - Hex
Head (1/4-20 x 1/2") Screw, Self-locking - Hex
Head (5/16-18 x 1/2")
Bracket, Support - Current
Transformer Assembly Screw, Self-locking - Hex
Head (1/4-20 x 1/2") Box, Junction Screw, Self-locking - Hex
Head (1/4.-20 x 1/2") Plate,
Cover
Screw, Cap - Hex Head
(3/8-16 x 3/4") Washer, Lock - Spring (3/8) Adapter, Chassis - Rear
1-9/32"
=•
Hex
OD)
45
Page 48
MOUNTING
AND HOUSING GROUP (Unhoused Sets)
46
Page 49
MOUNTING
AND HOUSING
GROUP
(Unhoused
Sets)
REF.
NO.
- 6
'9 403-0910 1 Support, Engine • 43 821-0010
10 800-0090 11
12 13 402-0030 1 Mount, Vibration 14 865-0007 15 850-0045 16 526-0115
17 520-0663 18 416-0480 1 Frame, Hold-down - Battery 19 821-0029 6
20 870-0281 6 Nut, Self-locking (3/8-16) 21 416-0666 1 Tray - Battery 22 800-0090 1 Screw, Cap - Hex Head
23 856-0013 1 24 800-0091 1 Screw, Cap - Hex Head 25 26
27 28
29 800-0520 30 800-0071 4 Screw, Cap - Hex Head 31 850-0055 4 Washer, Lock - Spring (7/16)
32 40270030
PART
NO.
1
405-1409
2
821-0014 8 Screw, Self-Locking - Hex 34 850-0055 4
3
870-0113 8 Nut, Clinch (5/16-18)
4
405-1811
5
821-0014 800:0050 *
7 850-0050 •
8 800-0520 . 1
850-0060 862-0016
856-0013 850-0050
862-0016 337-0090
QTY.
USED
1
1 8 2 2
2 2
2
2 2
2 2
1
1
1
1 2
2
PART
DESCRIPTION
Extension,
Spec B Through G Head (5/16-18 x 1/2") (Also used with Housed Sets)
Panel,
with Housed Sets)
Screw, Self-locking - Hex
Head (5/16-18 x 1/2")
Screw, Cap - Hex Head
(3/8-16 x 1") Washer, Lock - Spring (3/8) Screw, Cap - Special Hex
Head,
(3/4-10 x 1") 42 234-0370. 1 Screw, Cap - Hex Head
(1/2-13 x 1") Washer, Lock - Spring (1/2) Nut, Hex (1/2-13)
Nut, Wing (5/16-18) Washer, Lock - Spring (5/16) Washer, Flat (11/32" ID x
11/16" Stud (5/16-18 x
Screw, Self-locking - Hex
Head (3/8-16 x 3/4")
(1/2-13 x 1") 52 Washer, Lock - .External/
Internal Tooth (1/2)
(1/2-13 x Washer, Lock - External/
Internal Tooth (1/2) Washer, Lock - Spring (1/2) Nut, Hex (1/2-13) Lead,
(Flexible) Screw, Cap - Special Hex
Head,
(7/16-14x1") Mount, Vibration 61 301-3154 1
Hood - Radiator
Radiator (Also used
Unplated
OD x 1/16" THK)
3-1/4")
1-1/4")
Electrical - Ground
Unplated (3/4-10 x 1") 59 821-0014 4
REF.
NO.
33
35 232-2106 2
• 36 821-0014 .. 37 870-0020 6
38. 39 403-0914. 1
• 4U 812-0146 4 41 850-0040 4
•/ 44
•/ 44 45 821M?014
46 47
48 49
50 51
-^53 800-0003 4
54 55 850-0040 4
^56
57 301-3155 1 58 SOff-OOOl . 1
60
62 403-1111
PART
NO.
800-0091 4
403-0913 1
234-0361 • 1
815-0350 301-3156
301-3156 815-0350 301-3156 1
815-0350 6 301-3156 1 301-3192
526-0018 8
862-0001
821-0010
QTY.
USED
Screw, Cap - Hex Head
(1/2-13 x Washer, Lock - Spring (1/2) Bracket, Support - Generator
6
N
7
6 1 6
1
4
1
Spec B Through G Screw, Self-locking - Hex
Head (5/16-18 x 1/2") Nut, Plate (5/16-18) Trim,
Chassis - Right Side
Spec B ThroughG Trim,
Chassis - Left Side
Spec B Through G
Screw, Machine - Round Head
(1/4-20 x 3/8")
Washer, Lock - Spring (1/4)
Grille,
Inlet, Air
Screw, Self-locking - Hex
Head (1/4-20 x 1/2")
Wrapper, End Bell - Generator
Screw, Self-locking - Hex
Head (5/16-18 x 1/2") ­Control Box Mounting
Screw, Tapping - Hex Head,
Slotted (#10-32 x 3/8")
Panel,
Blank - Top (Also
used on Housed Sets)
Screw, Tapping - Hex Head,
Slotted (#10-32 x 3/8")
Panel,
Blank - Left Side
Screw, Tapping - Hex Head,
Slotted (#10-32 x 3/8")
Panel,
Blank - Right Side
(Also used on Housed Sets)
Panel,
Circuit Breaker - Right Side - Optional (Used with Line Load Circuit Breaker)
Screw, Cap - Hex Head
(1/4-20 x 1/2)
Washer, Flat (17/64" ID x
5/8" OD x 1/16" THK)
Washer, Lock - Spring (1/4) Nut, Hex (1/4-20) Housing, Grommet, Rubber
(3/4"
Screw, Self-locking - Hex
Head (5/16-18 x 1/2")
Screw, Self-locking - Hex
Head (1/4-20 x 1/2")
Saddle - Control Box Housing Chassis - Engine/Generator
(Also used with Housed Sets)
PART
DESCRIPTION
1-1/4")
Control Box
ID x
1-9/32"
OD)
Page 50
CONTROL GROUP
i«i IM
IM'1» jlK Wl
(AC Output Portion)
2 1
22
m%.
* I
*1 * * A AAA
lM.IM
Wl Ml Wl Wl
23
ie—
Page 51
CONTROL
GROUP
(AC
Output
Portion)
REF.
NO.
8 9
10
11 12
13
14 15
16 322-0131 17
18
PART
NO.
1
301-3158
2
PANEL ONLY, CONTROL 301-3167 301-3168 301-3341 301-3169 301-3170 301-3342
402-0078 337-0049 320-0431 MARKER STRIP 332-1248 332-1242
TRANSFORMER, VOLTAGE 315-0342 315-0431 303-0032 303-0076 ROTARY SWITCH 308-0012
308-0284 303-0170
350-0556 VOLTMETER
302-0421 302-0718 302-0779 307-1061
322-0130-
301-3244 REGULATOR BOARD, VOLTAGE (See Separate Group
for Breakdown) 332-1268 332-1956
QTY.
USED
1 Box,
1 1 1 1 1
1 1
1
1
1
1
1 1
Sets Without Meter Panel
25.0DEH-53R & 30.0DEH-3R
25.0DEH-515R & 30.0DEH-15R
30.0DEH-9XR Sets Sets With Meter Panel
25.0DEH-53R & 30.0DEH-3R
25.0DEH-515R&30.0DEH-15R
1 30.0DEH-9X.R Sets 4 Mount, Vibration 1 Lead, Electrical - Ground 1 Breaker, Circuit
1 Strip, Marker 1 Strip, Marker - Optional
1
1
(16 Place)
Spec B Through Begin Spec Knob Knob,
' Switch, Rotary
4 Position •
Switch,
4 Position - Optional
Rheostat
tResistor, Composition
(47,000-Ohm,
Voltmeter - Optional
(0-300 Volt)
Voltmeter - Optional
(0-300 Volt,
Voltmeter - Optional
(0-750 Volt)
Relay, Armature
Light, Indicator-Optional
(Lower Scale)
Light, Indicator - Optional
(Upper Scale)
Bracket, Angle - Relay Socket
Spec B Through Begin Spec
DESCRIPTION
Control
Sets
Sets
Sets Sets
H
Pointer
Rotary
H
PART
(12
G
- 2
- 4
1/2
0-600
G
Place)
Pole, Pole,
Watt,
Volt)
5%)
REF.
NO.
19
20 21
22 23
24
25
26
27
28 CURRENTTRANSFORMER
29
30 302-0235 31 302-0236 32 302-0253
33 TERMINAL BOARD
34
35 332-1280 36 315-0384 37 305-0524
38 320-0307
39 307-1157
PART
NO.
HARNESS, WIRING-AC CONTROL (INCLUDES
PARTS MARKED 338-0522 338-0524 338-0570 338-0523
338-0525
338-0571
332-0050
406-0332
406-0333 406-0334
508-0001 TIMETOTALIZING METER 302-0466
302-0469 ELECTRICAL FREQUENCY METER
302-0221
302-0256
AMMETER 302-0412 302-0719
302-0079 302-0209 302-0117 302-0729
332-0607 332-0795
323-0764
QTY.
USED
•)
.
1 1
Meter, Time Totalizing Meter, Time Totalizing
As Req.
As Req. tTerminal,
1 Reactor - Begin Spec 1 Rectifier Assembly - Begin
1 Lock, Handle - Circuit
1 Clip, Retaining - Relay
DESCRIPTION
Sets Without Meter Panel
25.0DEH-53R & 30.0DEH-3R Sets
25.0DEH-515R & 30.0DEH-15R Sets
30.0DEH-9XR Sets Sets With Meter Panel
25.0DEH-53R Sets
25.0DEH-515R & 30.0DEH-15R Sets
30.0DEH-9XR Sets
Clamp, Loop Receptacle, Turnbutton
Fastener
Stud,
Turnbutton Fastener
Washer, Lock - Turnbutton
Stud
Grommet, Rubber (1-1/16"
60 Hertz 50 Hertz
Meter, Electrical Frequency
60 Hertz
Meter, Electrical Frequency-
50 Hertz
Ammeter (0-250) - Optional Ammeter (0-75, 0-150)
25.
ODEH-515R & 30.0DEH-15R Sets
25.0DEH-53R & 30.0DEH-3R Sets
30.0DEH^9XR Siets.
-Bracket, Angle - Current Transformer Mounting
Clamp, Retaining, Transformer,
Upper
Clamp, Retaining, Transformer
Lower
Shim - Transformer Mounting
tBoard,
Terminal
-(•Board, tSocket, Relay
Terminal
Optional
Lug
Spec
G
Breaker - Optional (Penn State Sets)
PART
8i
30.0DEH-3R
(12
Place)
(16
Place)
OD)
-
-
-
'.
-.
-
-
G
t - Included in Wiring Harness
* - See Separate Group
for
Components
Page 52
CONTROL
GROUP
(Engine Section)
16-
36-
36-
36-
37-
37-
37-
FAUIT
OVERCRANK
LO Oil PRES
4 1- HI OIL TEMP
38-
39-
40-
SO
Hl ENG TEMP
10 ENG TEMP
OVERSPEED
Page 53
CONTROL
REF.
PART
NO. NO.
PANEL ONLY, ENGINE CONTROL *
301-3165 301-3267
2
301-3253
308-0138 308-0002 GAUGE, OILPRESSURE
193-0107. 1 Spec B Through G 193-0243 1 Begin Spec H GAUGE, WATER TEMPERATURE 193-0106 1 Spec B Through G 193-0245 1 Begin Spec H
7
302-0061 1 Ammeter (30-0-30)
8
332-1239 1 Strip, Marker
9
332-1241 i Strip, Marker
10
308-0003 1 Plate, Switch (On-Off)
11
332-1276 4 Plug, Key
12
307-1058 2 Relay, Armature
13
307-1031 1 Relay. Armature
14
322-0149 1 Light, Panel
15
322-0004 i Lamp, Incandescent (12 Volt)
16
322-0128 1 Light. Indicator (Fault)
17
300-0733 1 'Control, Cycle Cranker
18
300-0679 1 'Control, Engine Monitor
19
HARNESS ASSEMBLY, WIRING - CONTROL (INCLUDES PARTS MARKED tj
338-0528 338-0534
20
332-0537
21
332-0795
22
332-0765
QTY.
USED
1
PART
DESCRIPTION
Sets With One Fault Light Sets With Five Fault Lights -
Optional
Bracket, Angle - Control
Mounting
Switch,
Toggle (SPDT)
Switch,
Toggle (SPST)
Sets With One Fault Light -
Standard
Sets'With Five Fault Lights -
Optional
tBoard,
Terminal (4 Place)
tBoard,
Terminal (16 Place)
tSocket.Relay
GROUP
(Engine Section)
REF.
NO. NO.
23 24 332-0051 1 25 GAUGE, OILTEMPERATURE-OPTIONAL
26 302-0749 1 Tachometer, Electrical ­27 323-0764 1 tSocket, Relay
28 332-1269 As Req. tContact, Electrical ­29
30 31 307-1061 1 Relay, Armature 32 33 332-1240 1 34 307-1157 3
.35
36 37
38 322-0109 1 Light, Indicator (Hi Engine 39 322-0110 1 Light, Indicator (Low Engine 40 322-0111 1 Light, Indicator (Overspeed)
41 322-0112 1 42 300-0714 1
43 300-0730 1 44 300-0681 1
PART
332-1271
193-0187 193-0248
332-1280 As Req. tTerminal, Lug 332-1043
332-0699 1
308-0327 1 322-0107
322-0108
See Separate Group for Components. Included in Wiring Harness.
t -
QTY.
USED
tHousing,
2
Clamp, Loop Spec B Through G
1 1
Begin Spec H
Optional
PC Board Connector
tJumper
1
tBoard,
Strip, Clip,
Retaining - Relay
Switch,
1 Light, Indicator (Overcrank) 1 Light, Indicator (Low Oil
(SPDT) Penn State
Pressure) Temp) Temp)
Light, Indicator (Hi Oil Temp)
Light, Indicator (Hi Oil Temp)
'Control,
'Control,
Optional
Optional
'Control,
Optional
'Control,
Ootional
PART
DESCRIPTION
Connector (PC Boar<
Terminal (6 Place)
Marker
Toggle - Optional
Cycle Cranker -
Cycle Cranker ­ Engine Monitor -
Engine Monitor - i
51
Page 54
cna
VOLTAGE REGULATOR
ffl
cms
SPEC
1 1
R12
1 1.
B THROUGH G
C5
C5
C5
a
GROUP
a
-CE3-
c^r
f
332-1268
PART QTY.
REF.
NO.
NO.
Cl
C2 C3 C4 C5
C6
C7
C8
C9 CIO Cll C12 C13
'CR4 357-0014
CRS CR6 CR7 CRS CR9 CR10 357-0014 CR11 CRI2 359-0016 CRI3 359-0025 CRI4 359-0026 CRI5 359-0015 El-5 332-0833 HI 812-0081
H2 853-0005
H3
Kl 307-1063
MPI
Ql
Q2
Q3
USED
355-0018 355-0005 355-0017 355-0006 355-0016 355-0015
355-0005
355-0016 355-0017
355-0014 355-0020 355-0006
356-0039
357-0014 357-0014 357-0014 357-0014 357-0014
357-0014
860-0008 517-0127
362-0017 362-0017
361-0004
(LATEST PRODUCTION)
PART
Capacitor, Plastic Die (.47 MFD, 100 VDC, 2%)
1
Capacitor, Plastic Die (.22 MFD, 200 VDC,10%)
1
Capacitor, Plastic Die (.47 MFD, 400 VDC,10%)
1
Capacitor, Plastic Die (.47 MFD, 200 VDC,10%)
1
Capacitor, Plastic Die(1 MFD, 100 VDC, 10%)
1 1
Capacitor, Plastic'Die(.1 MFD, 200 VDC, 1.0%) Capacitor, Plastic Die ( 22 MFD, 200 VDC,10%)
1
Capacitor, Plastic Die(1 MFD, 100 VDC, 10%)
1 1 1
1
1
1
1 1 1 1 1 1 1 1 1
' Diode, Zener
i
i i
5
'Terminal,
2
•Screw, Round Head (#8-32 x 5/8") 'Washer, Lock - External Tooth (#8)
2
2
*Nut, Hex (#8-32)
1
1
1 1
DESCRIPTION
Capacitor, Plastic Die(.47 MFD,400 VDC.IO %) Capacitor, Plastic Die(.047 MFD.200 VDG10%! Capacitor, Plastic Die(.1 MFD,400VDC.10%) Capacitor, Plastic Die (.47 MFD,200VDC, 10%) Capacitor, Electrolytic (100 MFD, 10 Volts)
Diode, Rectifier Diode, Rectifier Diode, Rectifier . Diode, Rectifier . Diode, Rectifier
Diode, Rectifier Diode, Rectifier Diode, Rectifier
Diode, Zener Diode, Zener Diode, Zener
Stud
Relay, Armature Cover, Potentiometer Transistor
Transistor Transistor
332-12e*
REF.
PART QTY.
NO.
NO USED
350-0355
Rl
350-0351
R2
350-0351
R3
350-1075
R4
353-0040
R5
353-0039
R6
350-0398
R7
R8 350-0447
350-0423
R9
350-0423
R10 Rll 352-0151 R12
350-1014
R13
350-1007 350-0443
R14
350-0435
R15
350-0447
R16
351-0521
R17
303-0168 1
R18 R19 R20
351-0520 351-0522
R21
351-0520
R22
350-0355 1
R23
351-0523
R24
350-1011
R25
303-0164
R26
350-0447
R2 7
350-0459 1
R28
332-1252 1
TBI
332-1258
TB2
(EARLY
1
1
1
1
1 1 1 1
1
1 1 1
1 1 1
1
1
1 1 1
1 1
1
1
1
PRODUCTION)
DESCRIPTION Resistor, Composition (47-Ohm, 1/2 Watt, 5%) Resistor, Composition (33-Ohm, 1/2 Watt, 5%) Resistor, Composition (33-Ohm, 1/2 Watt, 5%) Resistor, Composition (4.7 Megohm, 2 Watt, 5%) Resistor, Wire Wound (270-6hm, 10 Watt. 5%) Resistor, Wire Wound (5000-Ohm, 15 Watt, 5%) Resistor, Composition (3000-Ohm, 1/2 Watt, 5%) Resistor, Composition (330,000-Ohm," 1/2 Watt, 5%) Resistor, Composition (33,000-Ohm, 1/2 Watt, 5%) Resistor, Composition (33,000-Ohm, 1/2 Watt, 5%) Resistor, Wire Wound (15,000-Ohm. 5 Watt, 5%) Resistor. Composition (13,000-Ohm, 2 Watt, 5%) Resistor, Composition (6800-Ohm, 2 Watt, 5%) Resistor, Composition (220,000-Ohm, 1/2 Watt. 5%i Resistor, Composition (100,000-Ohm, 1/2 Watt, 5%)
Resistor, Composition (330,000-Ohm, 1/2 Watt, 5%) Resistor, Film (12,100-Ohm, 1/4 Potentiometer (5000-Ohm, 3 Watt,
Not used
Resistor, Film (28,000-Ohm, 1/4 Watt, 1%)
Resistor, Film (5110-Ohm,.1/4 Watt, 1%)
Resistor, Film (28,000-Ohm, 1/4 Watt, 1%)
Resistor, Composition (47-Ohm. 1/2 Watt, 5%)
Resistor, Film (8870-Ohm, 1/4 Watt, 1%)
Resistor, Composition (10,000-Ohm, 2 Watt, 5%)
Potentiometer (8000-Ohm, 3Watt, 20%) Resistor, Composition(100,00b-Ohm, 1/2 Watt, 5%) Resistor, Compositionji Megohm, 1/2 Watt, 5%) Terminal Board Printed Wiring Board
- Used only on Early Production Units.
PART
[_^_J [
Watt,
5%)
c
1
1%)
52
Page 55
VOLTAGE
C*9
CBIO *«
X
REGULATOR
BEGIN
SPEC
GROUP
H
C5 CRQ
• — vnn
1
cs I
JU rU
V T
mt
• ••
CI2
Rie T
0
0
JL
T
©
0
1
2 3 4 5 6 7 8 9 10 II 12
REF.
NO.
C1,14 . 355-0042 2 Capacitor - 47 Mfd, 250 Volt C2,
C7 ' 355-0043 2 Capacitor - 22 Mfd, 250 Volt C3 355-0047 1 Capacitor - 47 Mfd, 400 Volt C4,
C12 355-0044 2 Capacitor - 47 Mfd, 250 Volt C5,
C8 355-0046 2 Capacitor - 1 Mfd, 100 Volt C6 355-0056 1 Capacitor - .33 Mfd, 250 Volt Cll 355-0048 1 C13 356-0039 1 Capacitor - Electrolytic
CR3
CR3
Thru 11 357-0014 9 Rectifier - Silicon
CR12 CR13 359-0025 1 CR14 359-0026 1 Fl,
F2, F3 321-0204 3 Fuse 1/4 Amp
ICI 367-0005 1 Integrated Circuit Q2 362-0017 1 Transistor - Silicon NPN Q3 361-0004 1 Transistor - Unijunction Rl 350-0355 1 Resistor - 1/2 Watt, 47-Ohm R2,
R3 350-0351 2 R4 350-1075 1 R5 353-0040 1
R6 353-0039 1 R7
R8,
R16 R10
PART QTY.
NO.
332-1956 1
359-0036 1
350-0398 350-0447 2 351-0885 1
USED
PART
DESCRIPTION
Board Assembly, Printed -
Complete
Capacitor - 1 Mfd, 400 Volt
lOOMfd,
Diode - Zener 5.6 Volt Diode - Zener 20 Volt Diode - Zener 18 Volt
Resistor - 1/2 Watt, 33-Ohm Resistor - 2 Watt, 4.7 Meg-Ohm Resistor-Fixed 10 Watt,
270-Ohm
Resistor - Fixed 15 Watt,
5,000-Ohm
1
Resistor - 1/2 Watt, Resistor - 1/2 Watt, 330,000-Ohm Resistor - 1/2 Watt, 51,100-Ohm
10 Volt
3,000-Ohm
R8
e. '<]
i
RiS RlS
T
T
CRH r1! X
4.
.ce_x I_I i i I R2i
,, . , , , ^ l!*°a
REF.
NO.
...Rll
Ri2
R13 R14 R15, R17
R18 R20,
29 & 30
R21
R24 R25,
R26
R28 TBI CR15
CR15
Kl R9 R19
R27
22 '
R31
352-0151
352-0151 351-0909
350-0411 350-0443 350-0435 351-0521
351-0521
303-0210
303-0210 351-0520
351-0522
351-0522 351-0523
351-0523 350-1011
303-0211
303-0211
350-0568 332-1252
359-0015
359-0015
359-0015
359-0015 321-0163
321-0163
321-0163
321-0163 307-1063
307-1063
307-1063
307-1063 350-1014
350-1014
350-1014
350-1014 350-1007
350-1007
• I OS
CR5 ««
H
PART
NO.
QTY. PART
USED DESCRIPTION
1 Resistor - Fixed 5 Watt,
15,000-Ohm Resistor - 1/2 Watt, 90,900-Ohm Resistor - 1/2 Watt, 10,000-Ohm
Resistor- 1/2 Watt, 220,000-Ohm Resistor­Resistor, Metal Film -
Potentiometer-5,000-Ohm, 1/2 Watt Resistor '- 1/4 Watt, 28,000-Ohm
Resistor - Metal Film ­Resistor - Metal Film ­Resistor - 2 Watt, 10,000-Ohm
Potentiometer - 1/2 Watt,
Resistor - 1/2 Watt .47 Meg-Ohm
Terminal Block Diode - Zener - 24 Volt Clip - Fuse Relay, Magnetic Reed Resistor - 2 Watt, 13.000-Ohm Resistor - 2 Watt,
1/2Watt,
1/4 Watt, 12,100-Ohm
1/4 Watt,
1/4 Watt,
100,000-Ohm
100,000-Ohm
5,110-Ohm
8,870-Ohm
6,800-Ohm
53
Page 56
CRANKER
CONTROL
STANDARD
GROUP
- 12
VOLT
-onr>
CR2
HZIO-
-tZiO
300-071
300-0733
o
REF.
PART QTY. • PART
NO.
NO. USED DESCRIPTION
CRI 357-0004 - 1
•TBI 332-1285 1 . Printed Wiring Board
CRANKER OPTIONAL
Hl-3
CR3
-nr-v
Iv—
4 O
TBI
300-0733 Control, Cranker•-. 12 Volt
CYCLE
CONTROL
Di
Rectifier
0de
(400.MA, 400 Volt)
GROUP
REF.
NO.
300-0714
Cl C2 CRI
CR2 CR3 CR4
HI
H2 H3 Ql Q2 Q3 Q4 Q5 Rl R2
R3
R4 R5
R6 R7 R8 R9 R10 Rll TBI
356-0039 355-0010 359-0027
357-0014 357-OU04 357-0004 812-0061
853-0003 860-0006 362-0008 362-0008
362-0017 362-0026 362-0019 303-0171
350-0560 350-0548 303-0171
350-0558
350-0420
350-0546
350-0520
350-0548
350-0500 352-01.52
332-1275
PART
NO.
O
- 12
VOLT
QTY. PART
USED DESCRIPTION
Control, 1 Capacitor, Electrolytic 1 Capacitor, Plastic Dielectric 1 Diode, Zener .
1 Diode, Rectifier '400 MA, 400 Volt) 1
D.oae, 1 Diode, Rectifier (400 MA, 400 Volt) 2 Screw, Machine, Round
2 Washer, Lock - External Tooth (#6) 2 Nut, Hex (#6-32)
Transistor Transistor Transistor Transistor Transistor
Potentiometer (100,000-Ohm, 1/4 Watt) Resistor, Composition
Resistor, Composition Potentiometer (100,000-Ohm, 1/4 Watt)
Resistor, Composition Resistor, Composition Resistor, Composition Resistor, Composition Resistor, Composition Resistor, Composition,
Resistor, Wirewound Printed Wiring. Board
Cranker Cycle -
12 Volt (100 Mfd, 10 Volt) (.0022
Mfd, 100 VDC, 10%)
Rectifier (400 MA, <!00 uolt)
Head (#6-32 x 3/8")
(0.1 Megohm, 1/2 Watt, 10%) (10,000-Ohm, 1/2 Watt, 10%)
(68,000-Ohm, 1/2 Watt, 10%) (24,000-Ohm, 1/2 Watt, 5%) (6800-Ohm, 1/2 Watt, 10%) (47-Ohm, (10,000-Ohm, 1/2 Watt, 10%) (1-Ohm, (25-Ohm,
1/2 Watt, 5%)
1/2 Watt, 10%)
5 Watt, 5%)
54
Page 57
ENGINE
CONTROL
-QO- -CUD-
CRI
f
MONITOR
GROUP
- 12
o
VOLT
fll
•E3
Tl
RIO
300-0679
REF.
NO. NO.
Cl C2
C3' C4 356-0030 1 Capacitor, Electrolytic C5 355-0005 CRI . 359-0027 CR2 357-0004 CRS 357-0004 1 Diode, Rectifier
CR4 357-0004 1 Diode, Rectifier CRS 357-0004 1 Diode, Rectifier CR6 364-0017 1 Diode, Rectifier
CR7
CR7 Kl 307-1039
Ql 361-0003 Q2 QS Q4 361-0003 Q5 Q6 362-0025 Q7 Q8
PART
300-0679
355-0005 356-0040
357-0004 1 Diode, Rectifier
362-0025 362-0025
362-0025 362-0008
362-0008
QTY. PART
USED DESCRIPTION
Monitor, Engine Control -
12 Volt
Not used
1 Capacitor, Plastic Dielectric
(.22 Mfd, 200 VDC, 10%) .
1 Capacitor, Electrolytic
(10 Mfd, 20 Volt) (1 Mfd. 35 Volt)
1 Capacitor, Plastic Dielectric
(.22 Mfd, 200 VDC, 10%)
1 Diode, Zener
(1 Watt, 7.5 Volt, 5%)
1 Diode, Rectifier
(400 MA, 400 Volt) (400 MA, 400 Volt)
(400 MA, 400 Volt) (400 MA, 400 Volt) (8 Amp, 30 Volt)
. (400 MA, 400 Volt)
.1 Relay, Armature (12 Volt)
1 Transistor 1 Transistor 1 Transistor 1 Transistor 1 Transistor 1 Transistor 1 Transistor 1 Transistor 1 Transistor
-rm-
(qa) CR2
a.
-mo-
-CHE}-
CB3
ffl
Kl
CR4
ffi
, -QID-
-CUD-
-CUD-
REF.
NO.
Rl R2
R2 R3
R3 R4
R4
R5
R5 R6
R6 R7
R7 R8
' R9
R10
R10 Rll
R12
R12 R13
R13 R14
R14 R15
R15 R16
R16
R17
R17 TBI 332-1246
PART
NO.
350-0536 350-0526
350-0548 303-0169
303-0169 350-0572
350-0572 350-0552
350-0552
350-0536 350-0505 350-0517
303-0169
303-0169 350-0584
350-0529
350-0529 350-0529
350-0529
350-0529 350-0540
350-0540 350-1128
QTY. PART
USED DESCRIPTION
Resistor,.Composition
(1000-Ohm, 1/2 Watt, 10%)
Resistor, Composition •
(100-Ohm,
Resistor, Composition
(10,000-Ohm, 1/2 Watt, 10%)
13
Potentiometer
(3.5 Meg Ohm, 1/4 Watt, 30%)
Resistor, Composition
(1-Meg Ohm, i/2 Watt, 10%)
Resistor, Composition
(22,000-Ohm, 1/2 Watt, 10%)
Resistor, Composition
(1000-Ohm, 1/2 Watt, 10%)
Resistor, Composition
(2.7-Ohm,
Resistor, Composition
(27-Ohm,
Potentiometer
(3.5-Meg Ohm, 1/4 Watt, 30%)
Resistor, Composition
(10-Meg Ohm, 1/2 Watt, 10%)
Resistor, Composition
(270-Ohm,
Resistor, Composition
• (270-Ohm, 1/2 Watt, 10%)
Resistor, Composition
(270-Ohm,
Resistor, Composition
(2200-Ohm, 1/2 Watt, 10%).
Resistor, Composition
(2200-Ohm, 1/2 Watt, 10%)
Resistor, Composition
(220-Ohm,
Printed Wiring Board
1/2 Watt, 10%)
1/2 Watt, 10%)
1/2 Watt, 10%)
1/2 Watt, 10%)
1/2 Watt, 10%)
2 Watt, 10%)
55
Page 58
WATTMETER
GROUP
- OPTIONAL
REF.
NO.
3 853-0008 2 Washer, Lock - External 4 301-3476 1 Cover, Box - Transducer 6 7 526-0003 8 Washer, Flat (11/64" ID x 8 402-0354. 4 Mount, Vibration
9 10 11 821-0014 4
12 402-0070 4 Mount, Vibration 13 14 812-0063 4
15 853-0003 4 Washer, Lock - External' 16 860-0006 4 Nut, Hex (#6-32)
17 332-0609: 1 18
PART
NO. USED DESCRIPTION
1
302-0766
2 815-0026 2
5
860-0008 8 853-0005
302-0902 508-0001 2
301-3477
332-0610
QTY. PART
1
Wattmeter (0-35KW)' Screw, Machine - Truss Head
(#10-32 x 3/8")
Tooth'(#10)
Nut, Hex (#8-32)
8
Washer, Lock - External
Tooth (#8)
3/8" OD x 1/32" THK)
1
Transducer, Watt Grommet, Rubber (1-1/6" OD) Screw, Self-locking - Hex
Head (5/16-18 x 1/2")
1 Box, Transducer
Screw, Machine - Round Head
(#6-32 x 1/2")
Tooth (#6)
Board,
1 .
Terminal (2 Place)
Strip,
Marker
CIRCUIT
REF.
NO.
, 5
6 526-0022 10 7 850-0045 5
8 862-0015 5 9 226-0891 3
10 812-0094 4 11 850-0025 4
12 320-0412 1 13 800-0003 2 - Screw, Cap - Hex Head 14 850-0040 2 Washer, Lock - Spring (1/4)
15 301-3197 1 Bracket, Angle - Circuit 16 301-3192
PART
NO.
800-0028 5
.
QTY.
USED
1.
DESCRIPTION
Screw, Cap - Hex Head
(5/16-18 x 1")
Washer, Flat (21/64" ID x
9/16" OD x 1/16" THK) Washer, Lock - Spring (5/16) Nut, Hex (5/16-18) Lead,
Electrical
Screw, Machine - Round
Head (#8-32 x Washer, Lock - Spring (#8) Circuit Breaker (3 Pole,
100 Amp, 240 VAC)
(1/4-20 x 1/2")
Breaker Mounting Panel,
Circuit Breaker
(Illustrated in Housing
Group, Item 54)
BREAKER
PART
3-5/8")
GROUP
- OPTIONAL
56
Page 59
179-0441
INSTALLATION DAY
FUEL
3
TANK - OPTIONAL EQUIPMENT
REF.
NO.
10
PART
NO.
179-0441
1 501-0008 2
2
501-0015 1
3
502-0041 3
4
502-0051 1
5
821-0018 2
6
870-0212 2
7
149-0554
8
821-0014
9 402-0070
813-0098 •
QTY.
USED
1 8 4
1
PART
DESCRIPTION
Installation of Day Fuel Tank
Line,
Fuel - Flexible
Line,
Fuel - Flexible
Elbow, Pipe - Street, Brass
(1/4"
x 1/4")
Coupling, Screw, Self-locking - Hex Nut, Hex - Self-locking
Pump, Fuel - Electric (See Screw, Self-locking - Hex Mount, Vibration
Screw, Machine - Round Head
Pipe - Brass
(1/4"
x 1/4")
Head (1/4-20 x 5/8")
Separate Group for Components) Head (5/16-18 x 1/2")
(#10-32x3/8")
REF.
NO.
11 12 13
14 15
16 870-1183 17 323-0897
18 821-0013 19
20 21 22
23 24
PART
NO.
850-0030 415-0326 307-1157 307-1058 812-0001
415-0323 415-0324 505-0110
505-0054 415-0321 415-0325
QTY.
USED
1
Washer, Lock - Spring (#10) , Cover, Relay
1
Spring,
1
1
2
Retaining - Relay Relay, Armature - 12 VDC Screw, Machine - Round Head
(#6-32 x 3/8")
Nut, Hex - With External
Tooth Lockwasher (#6-32) Socket, Relay (Includes leads) Screw, Self-locking - Hex
Head (1/4-20 x 1")
Strap.
Retaining Bracket, Angle - Tank Support Plug,
Pipe - Square Head (3/8")
Plug,
Pipe - Square Head (1/4")
Switch,
Float - Liquid Level
Tank, Fuel
PART
DESCRIPTION
57
Page 60
(179-0368)
INSTALLATION
Optional Equipment -
REF."
NO.
2 3 4 5
6 850-0045 7
PART
NO.
179-0368 Installation of Exhaust Muffler 505-0454
1
505-0172 1 155-1082 505-0203 800-0028
862-0015
QTY.
USED
1
Union, Nipple, Pipe (Close x 2") Pipe,
• 1
1
4 „
4 Washer, Lock - Spring (5/16") 4 Nut, Hex (5/16-18)
Exhaust - Flexible Coupling, Screw, Cap - Hex Head
(5/16-18 x 1")
PART
DESCRIPTION
Pipe (2")
Pipe (2")
Spec
EXHAUST
B Through
1'
«
. 14
MUFFLER
Serial
REF,
NO. NO.
9 155-1268 1 Muffler, Exhaust 10 11 526-0172 4 Washer, Flat (1/2" ID x
12 800-0026 6 . Screw, Cap - Hex Head
13 850-0045 6 Washer, Lock - Spring .(5/16") 15
#K760188585
PART
.140-0649
155-0978 1 Heat Shield
862-0015
155-0789 2 Support - Muffler
(HOUSED
During
QTY.
PART
USED
DESCRIPTION
2.
Strap,
2-1/4" OD x 1/4" THK)
(5/16-18x3/4")
6 Nut, Hex (5/16-18)
SETS)
Spec
Retaining
G
REF.
NO.
2 3 4 5
6 7
PART
NO.
179-0264
1
130-0674 502-0074 502-0073 503-0183 2 503-0386
505-0135 505-0120
179-0264
INSTALLATION
OPTIONAL
QTY.
USED
Installation of Water Cooled
1 1 . 1
As Req
2 1
Exhaust Manifold Line Assembly,. Water Elbow, Pipe - 90° (3/8 NPT) Elbow, Pipe-90° (1/2 NPT) Clamp, Hose Hose,
30" Nipple, Pipe - Half
(3/8" Elbow, Pipe - 90°, Street
(3/8"
EQUIPMENT
.2 N
1
4
PART
DESCRIPTION
Rubber (5/8" ID) -
Required
NPT x
1-1/2")
NPT)
WATER
COOLED
REF.
PART
NO. NO.
8 505-0019 1 Reducer, Pipe 9 505-0040 1 Elbow, Pipe - 90" (1/2" NPT)
10 505-0100 1 Nipple, Pipe - Close 11 505-0175 1 Elbow, Pipe - 90° (2" NPT)
12 505-0172 1 Nipple, Pipe (2" NPT x 2" LG) 13 154-0888 1 Manifold, Exhaust - Water
EXHAUST
6
QTY.
USED
MANIFOLD -
9-10
PART DESCRIPTION
(1/2"
NPT x 3/8" NPT)
(1/2"
NPT)
Cooled
58
Page 61
(179-0368)
Optional
INSTALLATION
EXHAUST
Equipment - Begin
Serial
MUFFLER
#K760188586
(HOUSED
During
Spec
SETS)
G
4£,
REF.
r
NO.
10 813-0105 11 870-0188
12 155-0978 1 13 895-0157
14 505-0454 1 15 155-1484 1 16 17 505-0645 1
PART
NO.
1
140-0649
2
155-0988 1
3
155-1430 4
4 155-0978 1 5
800-0037
6 870-0048 4 Nut, Lock (5/16-18) 7 800-0026 6
8 870-0048 6 Nut, Lock (5/16-18) 9 155-0789
505-0056 1
QTY.
USED
2
4
2 2
2 1
PART
DESCRIPTION
Band,
Muffler
Muffler, Exhaust Spacer, Muffler Shield.
Heat
Screw, Cap - Hex Head
(5/16-18 x 3" lg)
Screw, Cap - Hex Head
(5/16-18 x 3/4" lg)
Bracket, Muffler Support Screw, Machine - Round Head
(#10-32 x 1" lg) Nut, Lock (#10-32) Shield,
Rain
Asbestos
Union,
Pipe (2")
Tube.
Exhaust (9" lg)
Plug,
Pipe (1/2")
Nipple, Pipe
59
Page 62
179-0388
HEAT
OPTIONAL
EXCHANGER
EQUIPMENT
COOLING
WITH
30-31-32
30-31-32
30-31-32
REGULATOR
REF.
NO.
10. 11 505-0043 1 Elbow, Pipe - 90° (1-1/2" NPT)
12 503-0311 2 . Clamp, Hose 13 505-0628 1 Nipple, Pipe - Half
14 503-0356 As Req. 15 505-0444 1 Nipple, Pipe - Half 16 505-0462 1 Elbow, Pipe - Street, 90°
'l7
18 307-0833 19
PART QTY.
NO.
179-0388 Installation of Heat 1 800-0004 1 Screw, Cap - Hex Head 21 309-0241 . 1 2
850-0040 3 862-0001 1 Nut, Hex (1/4-20) 4 503-0311 4 Clamp, Hose 5 503-0441 2
6 505-0628 , 1 Nipple, Pipe - Half 7 504-0003 " 1 Cock,.Drain (1/4" NPT)
8 505-0426 , > 1 Reducer, Pipe • •< 9 505-0317 1
505-0424 1 Nipple, Pipe
505-0129
505-0100
USED
Exchanger with Regulator (1/4-20 x 5/8") 22
Washer, Lock - Spring (1/4")
1 .
Hose,
Rubber (Premolded) -
1-3/4" (1-1/2"
i
1 1
1 Nipple, Pipe (1/2" NPT x
(1-1/2"-NPT x 1/4" NPT)
Tee,
Pipe (1-1/2" NPT)
(1-1/2"
(1-1/2"
Hose,
Rubber (1-3/4" ID) -
8" Required
(1-1/2" (1-1/2"
Reducer, Pipe
(1"
NPT x 3/4" NPT) 40 130-0785 .1
Valve,
Solenoid
PART
DESCRIPTION
ID
NPT x 3") -
NPT x 16-1/2")
NPT x 3")
NPT x 2-1/4") NPT)
1-1/8")
REF.
. -NO.
20
23 24 25
26 27 28 504-0005 29 30
31 32
. 33 130-0819
34 800-0012 35 " 850-0040
36 862-0001 1
•37 38 39 130-0805
PART
NO.
505-0021
505-0102
505-0691 •
800-0004
850-0040 862-0001' 130-0802
130-0796 800-0026
850-0045 862-0015
331-0101 212-1197
QTY.
USED
Reducer, Pipe
1
1 Nipple, Pipe - Close
1. 4 Screw, Cap^- Hex Head 4 Washer, Lock - Spring (1/4")
4 Nut, Hex (1/4-20) . . 2
. 1
1 Tank, Heat Exchanger 3
3 3 1
• 1
1 1
1 1
(3/4"
Valve,
Regulator
(3/4"
' Elbow, Pipe - Street, 45°
(3/4" (1/4-20 x 5/8")
Strap,
Retaining
Cock, Drain (1/8" NPT)
Screw, Cap - Hex Head
(5/16-18x3/4")
Washer, Lock - Spring (5/16")
Nut, Hex (5/1^-18) Bracket, Mounting - Heat
Exchanger
Screw, Cap - Hex Head
(1/4-20 x 2-1/4")
Washer, Lock - Spring (1/4")
Nut, Hex (1/4-20)
. Hanger, Pipe
Spacer, Sleeve (1-11/16" LG)
Bracket, Support - Heat
Exchanger
Guard,
PART
DESCRIPTION -
NPT x 1/2" NPT)
NPT) NPT)
Belt
60
Page 63
179-0371
INSTALLATION
40
HEAT
EXCHANGER
COOLING
- OPTIONAL EQUIPMENT
REF.
NO. NO.
10 505-0424 1 Nipple, Pipe 11 505-0043 1
12 503-0311 2 13 505-0628 1 •
14 503-0356 15 505-0444 1 16 505-0462 1 17 505-0140 1
18 504-0019 1
PART
179-0371
1 800-0004 1 . Screw, Cap - Hex Head 21 2 850-0040 1
3 862-0001 1 Nut, Hex (1/4-20) 4 503-0311 4 Clamp, Hose 5 503-0441 2
6 505-0628 . 1
7 504-0003 1
8 • 505-0426 1 9 505-0317 . 1
QTY.
USED DESCRIPTION
Installation of Heat
Exchanger (1/4-20 x 5/8") 22
Washer, Lock - Spring (1/4")
Hose,
Rubber (Premolded) -
1-3/4"
Nipple, Pipe - Half 25
(1-1/2" Cock, Drain (1/4" NPT) 27 Reducer, Pipe
(1-1/2" Tee,
Pipe (1-1/2" NPT) 30
(1-1/2" Elbow, Pipe - 90° (1-1/2" NPT) Clamp, Hose Nipple, Pipe - Half
As Req.
(1-1/2" Hose,
Rubber (1-3/4" ID) -
8" Required 35 Nipple,. Pipe - Half 36
(1-1/2" Elbow, Pipe - Street, 90°
(1-1/2" Plug,
Pipe (1" NPT)
Valve,
Globe
PART
ID
NPT x 3") 26
NPT x 1/4" NPT) .
NPT x 16-1/2") / 31
NPT x 3") 34
NPT x 2-1/4") • NPT)
REF.
NO.
19 505-0100
20
23 24
28 29
32 33
37 38 39
40
PART
NO.
307-0833 1 505-0100 1 505-0021
505-0691 1 800-0004 4 850-0040
862-0001
130-0802 .2 504-0005 1
130-0796 800-0026 3
850-0045 862-0015 130-0819
800-0012
850-0040 1 862-0001 331-0101 212-1197
130-0805 130-0785
1-2-3
'•30-31-32
30-31-32
30-31-32
QTY.
USED
1
1
4 4
1
3 3
1 1
1
1 1 1
1
PART
DESCRIPTION
Nipple, Pipe (1/2" NPT x
Valve,
Solenoid Nipple, Pipe (1/2" NPT x Reducer, Pipe
(3/4"
NPT x 1/2" NPT)
Elbow, Pipe - Street, 45°
(3/4"
NPT)
Screw, Cap - Hex Head
(1/4-20 x 5/8")
Washer, Lock - Spring (1/4")
Nut, Hex (1/4-20)
Strap,
Retaining Cock, Drain (1/8" NPT) Tank, Heat Exchanger Screw, Cap - Hex Head
(5/16-18 x 3/4") Washer, Lock - Spring (5/16") Nut, Hex (5/16-18) Bracket, Mounting - Heat
Exchanger
Screw, Cap - Hex Head
(1/4-20 x 2-1/4") Washer, Lock - Spring (1/4")
• Nut, Hex (1/4-20) Hanger, Pipe
Spacer, Sleeve (1-11/16" LG) Bracket, Support - Heat
Exchanger
Guard,
Belt
1-1/8") 1-1/8")
61
Page 64
179-0180
INSTALLATION
WATER
JACKET
HEATER
- 120
VOLT
OPTIONAL
EQUIPMENT
REF.
NO.
1 812^0076 2 Screw, Machine - Round Head 2
3 4 332-0149 1 5
. 6 520-0446 2 Stud (#10-32 x 3/4")
7 850-0030 2 Washer, Lock - Spring (#10) 8 870-0053 . 2 Nut, Hex (#10-32) 9 508-0008 1 Grommet, Rubber
10 -333-0012 1 Box, Thermostat 11 503-0197 2 Clamp, Hose 12 503-0386 As Req.
13 505-0135 1 Nipple, Pipe -
PART
179-0180
850-0025 2 Washer, Lock - Spring (#8) 333-0013 1 Cover, Box - Thermostat --
309-0106. 1 Thermostat
; QTY.
NO. ' ~
.-
USED
Installation of Water
- Jacket Heater - 120 Volt (#8-32x5/16")
Terminal,
Hose,
Rubber (5/8" ID) -
12;'
Required
(3/8"
PART
DESCRIPTION
Lug
Half.
NPT x
1-1/2")
• * - •
REF.
NO.
14 15 16
17 505-0112 1
• 18
\ 19 800-0030 1
20 ­21
22 856-0008. 23 862-0015
24 25 333-0052
PART
NO.
503-0197 503-0183 503-0386
505-0071 1 Nipple, Pipe (1/4" NPT x 2")
850-0045 526-0030
130-0755
62
QTY.
USED
Clamp, Hose
1 1 Clamp, Hose
As Req.
As Req.
Hose,
Rubber (5/8" ID) - - •
24"
Required
Elbow, Pipe - 45° (1/4" NPT) Screw, Cap - Hex Head
1
2 Washer, Flat (13/32" ID x 2 Washer, Lock - External/
1 Nut, Hex (5/16-18) 1
1
(5/16-18 x
Washer, Lock - Spring (5/16")
7/8" OD x 1/8" THK) Internal Tooth (5/16")
Bracket, Support - Water
Heater
Heater, Water - Engine
Heater, Water - Engine
PART
DESCRIPTION
1-1/4")
Page 65
179-0256 EXHAUST
INSTALLATION
MANIFOLD
- OPTIONAL EQUIPMENT
CITY
WATER
COOLING
WITH
WATER
COOLED
1716 48
22
23 26 25
REF.
NO. NO.
10 . 503-0311 2 Clamp, Hose
11 503-0356 As Req. 12 505-0302 1 Nipple, Pipe - Half 39 13 505-0018 1
14 503-0189 2 Clamp, Hose 41 15 503-0386 As Req.
16
17 505-0108 18 505-0100 1 Nipple, Pipe - Close (1/2" NPT) 19 505-0040 20 505-0100 21
22 505-0040 23 505-0100 1 Nipple, Pipe - Close (1/2" NPT) 24 504-0028 1 Cock, Drain (3/8" NPT)
PART
179-0256 Installation of City Water -
1
503-0183
2
503-0110 As Req.
3
505-0302 1 Nipple, Pipe - Half
4 505-0038 1 5
505-0099 1 Nipple, Pipe - Close (1/4" NPT)
6 505-0020 1 Reducer, Pipe 7 505-0166 1
8 505-0102 1 Nipple, Pipe - Close (3/4" NPT) 9 110-1543 1 Adapter, Hose to Pipe
110-0576 1
505-0185 1 Nipple, Pipe - Half
QTY.
USED
Cooling with Water Cooled
2 .
1 1 Elbow, Pipe - 90° (1/2" NPT)
1
1
Exhaust Manifold 26 Clamp, Hose 27 Hose,
Rubber (1/2" ID) -
12"
Required
(1/4" Elbow, Pipe - 90° (1/4" NPT)
(3/4"
Tee,
Pipe (3/4" NPT)
Hose,
Rubber (1-3/4" ID) -
3" Required
(1/4" Reducer, Pipe (1/2" NPT x 1/4" NPT)
Hose,
Rubber (5/8" ID) -14" Required Adapter (1-3/4 x 1/2") Tee,
Pipe (1/2" NPT)
Nipple, Pipe - Close (1/2" NPT)
(1/2"
Elbow, Pipfe - 90° (1/2" NPT)
PART
DESCRIPTION
NPT x
1-1/2")
NPT x 1/4" NPT)
NPTx
1-1/2")
NPT x
1-1/2")
.Q42liJ_
LR
REF
NO. NO.
25
28 29 30
31 32
33
34 35 36 37 38
40
42 43
43 44 505-0100 1
45 505-0175 " 1 46 505-0172 1 47 504-0005 48 154-0888 i
PART
505-0019 505-0108
505-0100 1
110-0576 503-0311 503-0356
504-0019 1 821-0014
800-0007
850-0040 862-0001
130-0499 110-0526
307-0833 503-0189 505-0185
503-0386 505-0185 505-0040
505-0040
QTY.
USED
As Req.
As Req.
As Req.
As Req.
45
47 4(
PART
DESCRIPTION
1
Reducer, Pipe
(1/2"
1
1 2
6 2 2
2
1 . 1
1 2 1
1
1
i
NPT x 3/8" NPT)
Tee,
Pipe (1/2" NPT) Nipple, Pipe - Close (1/2" NPT) Adapter, Hose to Pipe Clamp, Hose
Hose,
Rubber (1-3/4" ID) -
3" Required
Valve,
Globe
Screw, Self-locking - Hex
Washer Head (5/16-18 x 1/2")
Screw, Cap - Hex Head
(1/4-20 x 1")
Washer, Lock - Spring (1/4")
Nut, Hex (1/4-20)
Bracket, Angle
Bracket & Nipple Assembly
Valve,
Globe Clamp, Hose Nipple, Pipe - Half
(1/2"
NPTx
Hose,
Rubber (5/8" ID) -
36"
Required
Nipple, Pipe - Half
(1/2" Elbow, Pipe - 90° (1/2" NPT) Nipple, Pipe - Close (1/2" NPT) Elbow, Pipe - 90° (2" NPT) • Nipple, Pipe - Close (2" NPT)
Cock, Drain
Manifold,
Cooled
1-1/2")
NPT x
1-1/2")
Exhaust - Water
63
Page 66
179-0319
INSTALLATION
CITY
WATER
COOLING
- OPTIONAL EQUIPMENT
32-33-34
REF.
NO.
2 3 503-0032 2 Clamp, Hose 4
5 505-0010 1 Nipple, Pipe - HALF 6 505-0038 1 Elbow, Pipe - 90° (1/4" NPT)
7 505-0099 1 Nipple, Pipe - Close 8 9 503-0365 2 Clamp, Hose
10 11 110-1543 1 Adapter, Hose to Pipe
12 505-0102 2 Nipple, Pipe - Close 13 505-0166 1
14 •505-0132 1 Elbow, Pipe - 90° (3/4" NPT) 15 505-0324 1 Nipple, Pipe - HALF
16 505-0010 1 Nipple, Pipe - Half 17 505-0017 1 Reducer, Pipe
PART
NO.
179-0319
1 130-0785 1
148-0284 1 Bracket, Hose Support
503-0110
505-0020
503-0356 As Req.
QTY. PART
USED
Installation of City Water Guard,
As Req.
Hose,
1 Reducer, Pipe
Hose,
Tee,
DESCRIPTION
Cooling
Belt
Rubber (1/2" ID) -
30"
Required
(1/4"
NPT x 1")
(1/4"
NPTx 7/8")
(3/4"
NPT x 1/4" NPT)
Rubber (1-3/4" ID)-
3" Required
(3/4"
NPT x
Pipe (3/4" NPT)
(3/4" (1/4" (3/8"
1-3/8")
NPT x 2") NPT x 1") NPT x 1/4" NPT)
REF PART
NO. NO.
18
505-0119 1
19
503-0365
20 503-0356 ' As Req. 21 110-0576
22
505-0100
23 504-0003 24 505-0018
25
505-0108 26 503-0189 27
503-0191 As Req. 28 505-0185 29 505-0040
30
505-0100 31
504-0019 32 800-0007 2
33 850-0040 34
862-0001'
130-0499
35
110-0526 1
36
QTY.
USED
2
' As Req.
1
1
1 1
1 1
As Req.
2
1 1-
1
2 2 1
PART
DESCRIPTION
Elbow, Pipe - 45° Street
(3/8"
NPT) Clamp, Hose Hose,
Rubber (1-3/4" ID) -
3" Required
Adapter, Hose to Pipe
Nipple, Pipe - Close
(1/2"
NPT x
NPT x
NPT x
1-1/8")
1-1/2")
1-1/8").
Cock, Drain (1/4" NPT) Reducer, Pipe (1/2" NPT x
1/4" NPT)
Tee,
Pipe (1/2" NPT) Clamp, Hose Hose,
Rubber (3/4" ID) -
11"
Required
Nipple, Pipe - Half
(1/2" Elbow, Pipe - 90°. (1/2" NPT) Nipple, Pipe - Close
(1/2"
Valve,
Globe
Screw, Cap - Hex Head
(1/4-20 x 1")
Washer, Lock - Spring (1/4")
Nut, Hex. (1/4-20) Bracket, Angle Bracket & Nipple Assembly
64
Page 67
179-0376
INSTALLATION
WATER
JACKET
HEATER
- 240
VOLT
OPTIONAL
EQUIPMENT
REF.
NO.
10 333-0012 11 12
13
PART
NO.
179-0376
1
812-0076
2
850-0025
3
333-0056
4 332-0149 5
309-0256 1
6
520-0446 2
7
850-0030
8
870-0053
9
508-0008 1
503-0197 503-0386
505-0135
QTY.
USED
As.
PART
DESCRIPTION
Installation of Water 2 2
1 1
2 2
1
2
Req
1
Jacket Heater - 240 Volt
Screw, Machine - Round Head
(#8-32x5/16") Washer, Lock - Spring (#8) Cover, Box - Thermostat Terminal, Thermostat Stud (#10-32 x 3/4") Washer, Lock - Spring (#10) Nut, Hex (#10-32) Grommet, Rubber Box, Thermostat Clamp, Hose Hose,
Nipple, Pipe - Half
Lug
Rubber (5/8" ID) -
12"
Required
(3/8"
NPT x
1-1/2")
65
REF.
NO. NO.
' 14
15 16
17 505-0112 1 Elbow, Pipe - 45° (1/4" NPT) 18 505-0071 1 19 800-0030
20 21 526-0030
22 23 862-0015
24 25
PART
503-0197 503-0183 503-0386
850-0045
856-0008
130-0755
333-0073 1 Heater, Water - Engine
QTY.
USED
1
Clamp, Hose
1. Clamp, Hose Hose,
As Req.
1 Screw, Cap - Hex Head 1 Washer, Lock - Spring (5/16")
2 2
1 1 Bracket, Support - Water
Rubber (5/8" ID) -
24"
Required
Nipple, Pipe (1/4" NPT x 2")
(5/16-18 x
Washer, Flat (13/32" ID x
7/8" OD x 1/8" THK)
Washer, Lock - External/
Internal Tooth (5/16"}
Nut, Hex (5/16-18)
Heater
PART
DESCRIPTION
1-1/4")
Page 68
HARDWARE
Illustrated hardware items are only for identification purposes. All hardware items listed throughout this parts
catalog are steel SAE grade five (5) or lower (zinc plated with clear chromate dip) unless parts description
indicates differently. All dimensions are in inches.
IDENTIFICATION
WASHER
EXTERNAL TOOTH INTERNAL TOOTH EXTERNAL-INTERNAL COUNTERSUNK SPRING
LOCK (ET) LOCK (IT) TOOTH LOCK (EIT) EXTERNAL TOOTH LOCK
Flat washer dimensions given are: Inside Diameter (ID), Outside Diameter (OD) and Thickness (Thk).
BOLT
CARRIAGE BOLT TRUSS HEAD BINDER HEAD
ROUND HEAD HEXAGON WASHER OVAL HEAD
HEAD
AND
SQUARE HEAD SOCKET HEAD
SCREW TYPES
TYPES
LOCK
PAN HEAD HEXAGON HEAD FILLISTER HEAD FLAT HEAD
TWELVE POINT
CAP
®
SLOTTED
SET
•FLAT
SOCKET
SET
L - Measure length between these points.
INTERNAL DRIVE TYPES
e
CROSS RECESSED
(PHILLIPS)
STD.
SLOTTED
FULL HEXAGON JAM HEXAGON HEXAGON WASHER SQUARE
#35
SIX POINT
SOCKET
TWELVE POINT
NUT
SOCKET
TYPES
Nominal size (fractional diameter or screw number)
Number ot threads per inch — Length in inches
1/4-20
x 3/4"
WING
ACORN
Page 69
,* 1 «.
-
-«•-*
ONAN
1400 73RD
AVENUE
N.E. • MINNEAPOLIS, MINNESOTA 55432
A DIVISION OF ONAN CORPORATION
Loading...