Omron ZN-A2502, ZN Series, ZN-A2502D, ZN-A4105D, ZN-A4105 System Manual

...
Page 1
Clean Sensing System
ZN Series
System Manual
Cat. No. Z267-E1-01
Page 2
Introduction
Thank you for purchasing the ZN. This manual provides only information, such as system components and setup procedures, that is required when using the ZN Series in a system. For details on product functions, performance and handling methods of individual products, refer to the Instruction Sheet packaged with the respective product. When using the ZN, be sure to observe the following:
• The ZN must be operated by personnel knowledgeable in electrical engineering.
• To ensure safe use of the product, please read the Instruction Sheet packaged with each product and this manual to deepen your understanding of the product.
• Please keep this manual and the Instruction Sheet packaged with each product in a safe place so that they can be referred to whenever necessary.
Page 3
Introduction
Section 1
Section 2
Section 3
Section 4
APPLICATION CONSIDERATIONS (Please Read)
FEATURES
UPGRADING THE SYSTEM
BASIC KNOWLEDGE OF CLEAN SENSING SYSTEMS
APPENDICES
Introduction ‚Í‚¶‚ß‚É ‘æ 1 Í‘æ 2 Í‘æ 3 Í‘æ 4 Í
Section 1 Section 2 Section 3 Section 4
System Manual
Clean Sensing System ZN Series
Page 4
Introduction
Introduction
READ AND UNDERSTAND THIS DOCUMENT
Please read and understand this document before using the products. Please consult your OMRON representative if you have any questions or comments.
WARRANTY
OMRON’s exclusive w arranty is that the products are f ree from defects in materials a nd workmanship for a period of one year (or othe r pe ri od if specified) from date of sale by OMRO N .
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGA RDING NON­INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall responsi bility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON’S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
SUITABILITY FOR USE
THE PRODUCTS CONTAINED IN THIS DOCUMENT ARE NOT SAFETY RATED. THEY ARE NOT DESIGNED OR RATED FOR ENSURING SAFETY OF PERSONS, AND SHOULD NOT BE RELIED UPON AS A SAFETY COMPO­NENT OR PROTECTIVE DEVICE FOR SUCH PURPOSES. Please refer to separate catalogs for OMRON’s safety rated products.
OMRON shall not be responsible for conform ity with any standards, codes, or regulations that apply to th e combination of produc ts in the customer’s application or us e of th e pr oduct.
At the customer’s request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the produ cts in comb ination w ith the en d produc t, machi ne, syste m, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the p ro ducts:
• Outdoor use, uses inv olving potential chemical contamination or electrical interference, or conditions or uses not described in this document.
ZN
System Manu al
ii
Page 5
Introduction
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amu sem ent ma chi ne s, v eh ic le s, saf et y eq ui pme nt , an d ins t al la t io ns su bj ec t t o separate industry or government regulations.
• Systems, machin es, and equipment that could present a ris k to lif e or pro per t y.
Please know and obse rv e all p ro hi bi tio ns of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PERFORMANCE DATA
Performance data given in this document is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance i s su bj ect t o th e O M RO N Warranty and Limitations of Liability.
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
Introduction
It is our practice to change model numbers when published ratings or features are changed, or when significant construction chang es are made. However, some specifications o f the product may be changed without any notice. When in do ubt, special m odel numbe rs may be a ssigned to fix or establish key s pecificat ions for your application on your request. Please consu lt with your OMRON repres entative at any time to conf irm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
ERRORS AND OMISSIONS
The information in this do cument has been carefully checked and i s believed to be accurate; however, no responsibility is assum ed for clerical, typographical, or proofreading errors, or omissions.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user’s prog ra m m in g of a pro gr ammable product, or any conse quence thereof.
COPYRIGHT AND COPY PERMISSION
This document shall not be copied for sales or promotions w ithout permission.
This document is protected by copyri ght and is inten ded solely for use in conjunc tion with the pr oduct. P lease notify us before cop ying or reproducing this docum ent in any manner, for any other purpose. I f copying or transmitting this document to another, please copy or transmit it in its entirety.
ZN
System Manu al
iii
Page 6
Introduction Precautions for Safe Use
Introduction
Precautions for Safe Use
The following points are important to ensure safety, so make sure that they are strictly observed.
■ Power Supply and Wiring
• When connecting multiple Air Clean Units to build a system, use a commercially available LAN cable (straight type: Category 5E or higher).
• On models that can be connecte d t o A ir Clea n Units, such as the Air P artic le S ens or (ZN-PDA12) and Interfac e Unit (ZN-SF12), use the cable from the body to directly connect to the unit.
• To extend the cable mentioned above, a commercially available LAN connector female to female, straight type) and a LAN cable (straight type: Category 5E or higher) must be used.
• The cables must be 100 m or shorter in total length.
For details on other precautions for safe use and precautions for correct use, refer to the Instruction Sheet for the respective device, and make sure that they are strictly observed.
iv
ZN
System Manu al
Page 7
Editor's Note
● Title of each section
● Header
● Cross-header
● Index label
● Overview and points of the
function described
● Operation procedure and supplementary explanat ion
Indicates the contents of the page.
Shows the chapter number and contents.
Shows the operation flow and setup method.
Explains the operation procedure and the display status resulting from execution of the operation. Helpful information regarding operation and reference pages is introduced here using symbols.
* This page does not exist.
● Overview of the section
Page Format
Introduction
Editor's Note
Introduction
System Manu al
ZN
v
Page 8
Introduction Editor's Note
Introduction
Notational Conventions
■ Menu
In this manual, menu items displayed on the screen are enclosed with [ ].
■ Operation procedure
Operation steps are numbered to indicate their order .
■ Visual Aids
Indicates points that are important to achieve the full product performance, such as operational precautions and application procedures.
Indicates pages where related information can be found.
Indicates information helpful in operation.
vi
ZN
System Manu al
Page 9
CONTENTS
Introduction
CONTENTS
Introduction
Precautions for Safe Use iv Editor's Note v
Page Format v Notational Conventions vi
CONTENTS vii
Section 1 FEATURES 1
What is the "Clean Sensing System?" 2
System Features 2 Features of the Clean Sensing System 4
System Configuration Examples 7
Direct Clean Sensing System 7 Multi-Clean Sensing System 11
CONTENTS
Section 2 UPGRADING THE SYSTEM 13
Before Upgrading the System 14
Flow of Operations for Upgrading the System 14 Installing the Exclusive Monitoring Software 15
Setup Methods Suited to Specific Applications 18
Automatically Adjusting the Air Volume Level 18 Monitoring/Logging the Amount of Particles 25 Detecting the Cleanliness of Multiple Processes 31
ZN
System Manu al
vii
Page 10
Introduction CONTENTS
Introduction
Section 3 BASIC KNOWLEDGE OF CLEAN SENSING SYSTEMS 35
Feedback Control 36
CONTENTS
What is "Feedback?" 36 How Feedback Control Works 40
Clean Sensing 44
Principle of "Particle Count" 44 What is "Cleanliness?" 45
Section 4 APPENDICES 47
Maintenance 48 Troubleshooting 50
Troubleshooting 50 Error Messages and Countermeasures 51
Specifications and Dimensions 53 List of Products 66 INDEX 69 Revision History 72
viii
ZN
System Manu al
Page 11
Section 1 FEATURES
What is the "Clean Sensing System?" 2
System Features 2 Features of the Clean Sensing System 4
System Configuration Examples 7
Direct Clean Sensing System 7 Multi-Clean Sensi ng Sy st em 11
Section 1 FEATURES
System Manu al
ZN
1
Page 12
Section 1
OPE1
OPE2
OPE3
■ Clean Monitoring System (ZN-SFW Series)
Monitoring the amount of particles at multiple points in manufacturing processes is important in improving product quality. By connecting Interface Units, you can log the measured data of Air Particle Sensors at up to ten locations at once on a personal computer. The Electrostatic Sensor (ZJ-SD) also can be connected, which means that you can al so asce rtain the re latio nship between the amount of s tatic electricity and the amount of particles.
The clean sensing system continuously s enses the amount of particles in a clean boot h or cl ean b ench, and c ontrols the ai r vol ume le ve l of t he Air Clean Unit. This way, it can easily ensure an environment having a fixed cleanliness class at all times. An environment for removing dust and neu tralizing static electri city can be built by incorporating a new-concept Ionizer Unit in this system.
What is the "Clean Sensing System?"
What is the "Clean Sensing System?"
Section 1 FEATURES
System Features
OPE3
OPE2
OPE1
Z N
­S F
12
ZN
System Manu al
2
Page 13
What is the "Clean Sensing System?"
■ Air Clean Unit (ZN-A Series)
Unique twin-blower structure (ZN-A2502) achieves light weight and large air volume. Compact but more powerful. Incorporating a clogged main filter (HEPA) detection function. Visibility is improved by indicators located on two corners of the body.
■ Air Particle Sensor (ZN-PD Series)
High-performance fan used for air suction to ensure measurement at all times. Use of a semiconductor laser and high-sensitivity optical design in the sensor achieves measurement of minute particles of 0.3 µm, 0.5 µm and 1.0 µm in diameter.
Thinnest in industry, large air volume
■ Ionizer Unit (ZN-J Series)
Directly mounted on Air Clean Unit Open structure does not b lock the laminar ai rflow from the Ai r Clean Unit. No more troublesome wiring required. Installation man-hours can be considerably reduced.
An industry first, one-touch dust removal and static neutralization
Smallest in industry, constant measuring
Main Applications
Electronic component production processes
Storage or test
environments
Cell manufacturing
processes
Section 1
Section 1 FEATURES
System Manu al
ZN
3
Page 14
Section 1 What is the "Clean Sensing System?"
Features of the Clean Sensing System
Section 1 FEATURES
■ Feedback-based Automatic Adjustment of Air Volume
The air volume level of the Air Clean Unit can be automati cally controlled based on the amount of particles measured by the Air Par ticle Sensor. The cleanli ness class in clean booths can be maintained at the opt imum air volume level in propor tion to the amount of particles from rapid air feed through to fine air volume operation in the power saving mode.
Setting Method p.18
4
■ Monitoring/Logging the Amount of Particles
The cleanlines s class i nside clean b ooths can be ver ified and ascertained by the amount of particle s per unit volume. The amount of particles can be verified on the Sensor and the Amplifier Unit. Measured values can be easily logged on a personal computer using Interface Units and the exclusive monitoring software (Realtime Clean Air Monitor). Changes in the amount of particles over time observed in this way can be made use of as data for improving product quality.
Setting Method p.25
ZN
System Manu al
OPE3
OPE2
OPE1
Page 15
Section 1
Max. 9 units connected
Max. 10 units connected
What is the "Clean Sensing System?"
■ Improving Product Quality by Multi-point Measurement
Since Air Clean Units and Air Particle Sensors can be conn ected to each other, the amount of air particles in multiple clean booths installed in processes can be comprehensively de tected and controlled. Which process is worseni ng in cleanliness can be linked to quality control for continual management.
Setting Method p.31
Section 1 FEATURES
System Manu al
ZN
5
Page 16
Section 1
Ion Balance Sensor
What is the "Clean Sensing System?"
■ Simultaneous Dust Removal and Static Neutralization
The Ionizer Unit ZN-J series, the first in industry to be added on later to an Air Clean
Section 1 FEATURES
Unit, provides you with a new clean environment capable of removing dust and neutralizing static electricity.
• Sim ultaneous Removal of Particles and Static Electricity
A variable DC sy stem is used for electrostatic di scharge. This system c an neutralize static electricity in wide spaces. Two ion balance sensors provide c onstant feedback to maintain uniform neutr alizing performance.
• Simultaneous Monitoring of Charged Amount of Workpieces
Electrostatic Sensor ZJ-SD can be connected to the clean sensing system. The problem of adhesion of particles can be solv ed by acc urately asc ertaining the char ged amount of the workpiece, and using the Ionizer Unit to approp riately neutralize static electricity. Also, since ZJ-SD data can also b e cap tured on a person al c omputer via the Inte rfac e Unit, the amount of particles and charged amount can be acquired and collected simultaneously, and made use of as basic data for improving product quality.
ZN
System Manu al
6
Page 17
System Configuration Examples
S
For details on settings, see p.25.
System Configuration Examples
Section 1
Direct Clean Sensing System
■ Data Logging
Clean Monitoring System
ZN-SFW11
Realtime Clean Air Monitor
Interface
Unit
Z
N
­S F
1 1
Amplifier Unit
Section 1 FEATURES
Air Particle Sensor
ensor
ZN-PD03
ZN-PDA11
DC power supply
[Features]
• Monitoring/Logging the Amount of Particles
System Manu al
7
ZN
Page 18
Section 1
S
r
A
For details on settings, see p.18.
To extend the cable mentioned above, a commercially available LAN connector (female to female, straight type) and a LAN cable (straight type: Category 5E or higher) must be used.
System Configuration Examples
■ Feedback
Section 1 FEATURES
C adapter (provided)
Or, DC power supply
Air Clean Unit
ZN-A2502 ZN-A4105
Air Particle Sensor
enso
Amplifier Unit
ZN-PD03
ZN-PDA12
Cable length: standard 2 m
[Features]
• Feedback-based Automatic Adjustment of Air Volume
ZN
System Manu al
8
Page 19
■ Feedback and Data Logging
Z N
­S F
1 1
Air Clean Unit
ZN-A2502 ZN-A4105
[Features]
• Feedback-based Automatic Adjustment of Air Volume
• Monitoring/Logging the Amount of Particles
Air Particle Sensor
Interface
Unit
Realtime Clean Air Monitor
ZN-PD03
Amplifier Unit
ZN-PDA12
Clean Monitoring System
ZN-SFW11
AC adapter (provided)
Or, DC power supply
Cable length: standard 2 m
For details on settings, see p.18, p.25.
To extend the cable mentioned above, a commercially available LAN connector (female to female, straight type) and a LAN cable (straight type: Category 5E or higher) must be used.
Section 1
System Configuration Examples
Section 1 FEATURES
System Manu al
ZN
9
Page 20
Section 1
For details on settings, see p.18, p.25.
To extend the cable mentioned above, a commercially available LAN connector (female to female, straight type) and a LAN cable (straight type: Category 5E or higher) must be used.
System Configuration Examples
■ Dust Removal and Static Neutralization
Connection Example with Different Models (Electrostatic Sensor)
Section 1 FEATURES
Air Clean Unit
AC adapter (provided)
Or, DC power supply
ZN-A2502 ZN-A4105
Connector cable (provided)
Clean Monitoring System
Realtime Clean Air Monitor
Electrostatic
Sensor
ZJ-SD100
ZN-SFW12
Interface
Unit
OPE3
OPE2
OPE1
ZN
­SF
1 2
Amplifier Unit
ZJ-SDA11
Cable length: standard 2 m
Sensor
ZN-J25A ZN-J41A
Ionizer Unit
Air Particle Sensor
Sensor
ZX-CAL2
Amplifier Unit
ZN-PD03
ZN-PDA11
Calculating Unit
OPE3
OPE2
OPE1
ZERO ENABLE
(kV)
Z J
-S D A 1
1
DC power
supply
10
ZN
System Manu al
[Features]
• Simultaneous Monitoring of the Ion Balance
• Feedback-based Automatic Adjustment of Air Volume
• Monitoring/Logging the Amount of Particles
Page 21
ZN-A2502 ZN-A4105
Air Clean Unit
Air Particle Sensor
Calculating Unit
ZX-CAL2
ZN-PD03
Sensor
ace
Unit
e
r
ZN-SFW12
Clean Monitoring System
Commercially available LAN cable
(straight type: Category 5E or higher)
DC power
supply
[Features]
• Feedback-based Automatic Adjustment of Air Volume
• Monitoring/Logging the Amount of Particles
• Detecting the Cleanliness of Multiple Processes
AC adapter
(provided)
Or,
DC power supply
Cable length: standard 2 m
For details on settings, see p.31.
To extend the cable mentioned above, a commercially available LAN connector (female to female, straight type) and a LAN cable (straight type: Category 5E or higher) must be used.
Realtim Clean Air Monito
Multi-Clean Sensing System
Interf
Section 1
System Configuration Examples
Section 1 FEATURES
-
System Manu al
ZN
11
Page 22
Section 1 System Configuration Examples
MEMO
Section 1 FEATURES
12
ZN
System Manu al
Page 23
Section 2 UPGRADING THE SYSTEM
Before Upgrading the System 14
Flow of Operations for Upgrading the System 14 Installing the Exclusive Monitoring Software 15
Setup Methods Suited to Specific Applications 18
Automatically Adjusting the Air Volume Level 18 Monitoring/Logging the Amount of Particles 25 Detecting the Cleanliness of Multiple Processes 31
Section 2 UPGRADING THE SYSTEM
System Manu al
ZN
13
Page 24
Section 2
p.18 p.25 p.31
p.48
Before Upgrading the System
Before Upgrading the System
Flow of Operations for Upgrading the System
Section 2 UPGRADING THE SYSTEM
Preparation
Installation
Connections
Checks
Direct Clean Sensing System
Automatically Adjusting the Air Volume Level
Refer to the Instruction Sheet packaged with each device.
• Setting the ID of the Air Clean Unit
• Connecting the Air Clean Unit and Air Particle Sensor
• Connecting the Air Clean Unit power supply
Checking communications Checking system operation Checking system operation
Monitoring/Logging the Amount of Particles
Installing the exclusive monitoring software
• Connecting the Air Particle Sensor and Interface Unit together
• Connecting the Interface Unit and personal computer
• Connecting the Air Particle Sensor power supply
Multi-Clean Sensing System
Detecting the Cleanliness of Multiple Processes
• Setting the ID of the Air Clean Unit
• Connecting the Air Clean Unit and Interface Unit Connecting Air Clean Units to each other
•
• Connecting the Air Particle Sensor and Interface Unit together
• Connecting the Interface Unit and personal computer
• Connecting the Air Particle Sensor power supply Connecting the Air Clean Unit power supply
•
14
Operations and settings
Resetting during operation
Maintenance
ZN
System Manu al
Setting the feedback conditions
Starting operation
• Resetting the feedback method Resetting the target cleanliness class
•
• Resetting the feedback cycle Resetting the low power air volume level
•
•
Resetting the high power air volume level
• Resetting the high power time
Trend graph display/data logging
Starting monitoring/logging Starting operation
Setting the feedback conditions
• Resetting the feedback method Resetting the target cleanliness class
•
• Resetting the feedback cycle Resetting the low power air volume level
•
• Resetting the calculation type Resetting the high power air volume level
•
• Resetting the high power time
Page 25
Section 2
Clean Monitoring System
(ZN-SFW11/SFW12)
Realtime Clean Air Monitor
Interface Unit
Numerical display of measured amount of particles
Graphic display of changes in measured values over time
Logging of data
Display and setting of Air Particle Sensor and Interface Unit settings
Before Upgrading the System
Installing the Exclusive Monitoring Software
The Exclusive Monitoring Software (Realtime Clean Air Monitor) tool is provided for the ZN Series. This tool allows you to set sensing functions, acquire and collect the amount of measured particles, and display this information as a graph on a personal computer.
ZN-SF12
• Monitoring of measurement results
Section 2 UPGRADING THE SYSTEM
• Function setup support
■ Operating Environment
The following operating environment for Exclusive Monitoring Software is recommended. Check the environment before installing the software.
Item Condition OS Windows 2000/XP CPU PentiumIII 850 MHz or faster (2 GHz or faster recommended) RAM 128 MB or more (256 MB or more recommended) Free space on hard disk At least 50 MB Display screen 1024 x 768 dots
High Color (16-dot) or higher
• Windows is a trademark or registered trademark of Microsoft Corporation.
System Manu al
ZN
15
Page 26
Section 2 UPGRADING THE SYSTEM
Section 2 Before Upgrading the System
■ How to Install/Uninstall the Software
The following describes the preparations for using Exclusive Monitoring Software.
• Installing Exclusive Monitoring Software
Before you install the software, quit all other programs that are running. Also, note that installation may take a long time if antivirus software is installed on the personal computer. Log on as an Admin istrator or a us er, such as a computer adm inistrator, having rights to change system settings.
1. Turn the personal computer's power supply ON to start up Windows.
2. Insert the "Exclusive Mo nitoring Software" CD- ROM into the CD-R OM drive on
the personal computer.
3. The program is launch ed autom aticall y and the in stallatio n screen is display ed.
Follow the on-screen instructions to install the software.
If the installation is not automatically started, execute "setup.exe" in the CD-ROM.
• Uninstalling Exclusive Monitoring Software
Before you uninstall the software, quit al l other programs that are running. A lso, note that uninstallation may take a lon g time if antivirus software is installed on the per so nal computer. Log on as an Admin istrator or a us er, such as a computer adm inistrator, having rights to change system settings.
1. Turn the personal computer's power supply ON to start up Windows.
2. Select [Settings]-[Control Panel] from the [Start] menu of your personal
computer.
3. Double-click [Add/Remove Programs].
4. Select [Realtime Clean Air Monitor] from the list, and click the [Change/Remove]
button.
5. Click [OK].
16
ZN
System Manu al
Page 27
Section 2
Side with no tab
Before Upgrading the System
■ Starting Up the Exclusive Monitoring Software
After installation is completed, start up E xclusive Monitoring S oftware by t he followin g procedure.
1. Check that the current/voltage switc h on the
base of the Interface Unit is set to the side that has no tab (default).
Section 2 UPGRADING THE SYSTEM
2. Set the Air Particle Sensor Amplifier Unit to
the RUN mode.
CNT/CF
3. Connect the Interface Unit to the personal computer.
To connect to a personal computer (PC/AT compatible), use a 9-pin D-sub cross cable (female to female).
p.64
4. Connect the Interface Unit to the Amplifier Unit.
5.
Turn the power supply of each device ON.
On the ZN-SF11, the ERR indicators for the sensor communications indicator and external terminal communications indicator go out. On the ZN-SF12, the model indication when it is started up goes out, and the indication changes to the normal display (measured value display, etc.). The Interface Unit is now ready for communications.
Power indicator
Sensor communication
indicator (BUSY/ERR)
External terminal communication indicator (BUSY/ERR)
6.
Start up the exclusive monitoring software.
Communications is automatically started.
■ Exiting the Exclusive Monitoring Software
Exit Exclusive Monitoring Software by the following procedure.
1. Select [File]-[Close] from the Exclusive Monitoring Software menu bar.
System Manu al
ZN
17
Page 28
Section 2 UPGRADING THE SYSTEM
1. Setting the ID of the Air Clean Unit
2. Connecting peripheral devices
3. Checking communications
4. Setting the feedback conditions
p.18
p.19
p.19
p.20
4-1. Rapid feedback 4-2.
Constant feedback
p.23
Section 2 Setup Methods Suited to Specific Applications
Setup Methods Suited to Specific Applications
Automatically Adjusting the Air Volume Level
Feedback control is perfor med between the Air Particle Sensor an d Air Clean Unit to feed in highly clean air (i.e. air containing little dust). The following describes an exam ple where the air vo lume le vel of the Air Cle an Unit is automatically adjusted.
To use multiple Air Particle Sensors or multiple Air Clean Units to apply feedback on the control loop, configure a multi-clean sensing system using the Interface Unit (ZN-SF12).
1. Setting the ID of the Air Clean Unit
ZN
System Manu al
18
1. Set DIP switch SW1 on the rear of the Air Clean Unit to ON (external
communications control enabled).
2. Set the ID rotary switch on the rear of the Air Clean Unit to 0 (0ch).
p.11
The ID rotary switch must always be set to "0" (0ch) when using the Air Particle Sensor (ZN-PDA12). Feedback communications cannot be performed when the ID is set to other than "0" (0ch).
Page 29
Section 2
Setup Methods Suited to Specific Applications
2. Connecting peripheral devices
Connect the Air Clean Unit to the Air Particle Sensor to supply power to the Air Clean Unit.
System Configuration Examples p.8
3. Checking communications
Check that communications between the units is being performed correctly by manually switching the air volume level of the Air Clean Unit on the Air Particle Sensor.
1. Set the mode switch of the Ai r Parti cl e
Sensor Amplifier Unit to the FUN mode.
2. Display [SPCL] on the main display.
Section 2 UPGRADING THE SYSTEM
3. Display [ACU] on the sub-display.
4. Press the ENT key.
5. Display [CNTRL] on the main display.
6. Select [MNUAL].
(default value: MANUAL)
7. Press the ENT key.
This sets the selected mode.
System Manu al
ZN
19
Page 30
Section 2 UPGRADING THE SYSTEM
Section 2 Setup Methods Suited to Specific Applications
8. Display [LWIND] on the main display.
9. Set the air volume level of the Air
Clean Unit.
Set the desired air volume level, and check that the air volume level is changed. (range: 1 to 5, default value: 1)
10. Press the ENT key.
Check the air volume level of the Air Clean Unit. If the air volume changes, this indicates that communications is being performed normally.
If the air volume does not change: Check the Air Clean Unit settings, Air Particle Sensor operation, and the wiring of connected cables. When the Air Clean Unit settings have been changed, turn the power supply OFF and then back ON to enable the settings.
4. Setting the feedback conditions
Set the feedback conditions for the Air Clean Unit. There are two feedback methods, and each of their setup methods is different.
Rapid feedback p.20
Constant feedback p.23
For details on feedback operation and setup parameters, see "Feedback Methods."
p.38
4-1. Rapid feedback
Set this method to quickly improve the environment when a drop in cleanliness is detected.
Selecting the air volume level control method
1. Display [CNTRL] on the main display.
Set the method for controlling the air volume level control of the Air Clean Unit.
2. Select [AUTO].
Set air volume level control of the Air Clean Unit to automatic.
3. Press the ENT key.
This sets the selected mode.
20
ZN
System Manu al
Page 31
Setup Methods Suited to Specific Applications
Selecting the feedback method
4. Display [FBTYP] on the main display.
Set the feedback method.
Section 2
5. Display [RAPID] on the sub-display.
6. Press the ENT key.
This sets the rapid feedback method.
Setting the target cleanliness
7. Display [CLASS] on the main display.
8. Select the target cleanliness class.
9. Press the ENT key.
This sets the specified target value.
Section 2 UPGRADING THE SYSTEM
Setting the low power air volume level
10. Display [LWIND] on the main display.
11. Set the low power air volume level of
the Air Clean Unit.
Set the air volume level for when the target cleanliness is satisfied.
12. Press the ENT key.
This sets the specified air volume level.
System Manu al
ZN
21
Page 32
Section 2 Setup Methods Suited to Specific Applications
Setting the high power air volume level
13. Display [HWIND] on the main display.
Section 2 UPGRADING THE SYSTEM
14. Set the high power air volum e level of
the Air Clean Unit.
Set the air volume level within 1 to 5 (default value: 5). Set the air volume level for when the target cleanliness is not satisfied.
For the high power air volume level, always set an air volume greater than the low power air volume level. Feedback will not function properly if a smaller value is set.
15. Press the ENT key.
This sets the specified air volume level.
Setting the high power time
16. Display [HTIME] on the main display.
Set the high power time.
17.
Set the high po wer time of th e A ir C lea n U nit.
Set the time (s) within 0 to 999 (default value: 60). Set the time that the high power air volume level is to be held for.
22
18. Press the ENT key.
This sets the specified time.
The time that the high power air volume level is actually held is an integer multiple of the feedback cycle (i.e. measurement cycle). Example: Measurement cycle: 60 s When the high power time is set to "100 s", the actual high power time is 120 s.
19. Set the mode switch to RUN.
This starts feedback control operation.
When the setting is next used, feedback is automatically started simply by turning the Air Clean Unit power supply ON.
ZN
System Manu al
Page 33
Setup Methods Suited to Specific Applications
4-2. Constant feedback
Set this method to stabilize cleanliness in the booth (area) at all times.
Selecting the air volume level control method
1. Display [CNTRL] on the main display.
2. Select [AUTO].
Set air volume level control of the Air Clean Unit to automatic.
3. Press the ENT key.
This sets the selected mode.
Selecting the feedback method
Section 2
Section 2 UPGRADING THE SYSTEM
4. Display [FBTYP] on the main display.
Set the feedback method.
5. Display [CONST] on the sub-display.
6. Press the ENT key.
This sets the constant feedback method.
Setting the target cleanliness
7. Display [CLASS] on the main display.
8. Select the target cleanliness class.
System Manu al
ZN
23
Page 34
Section 2 Setup Methods Suited to Specific Applications
9. Press the ENT key.
This sets the specified target value.
Setting the low power air volume level
Section 2 UPGRADING THE SYSTEM
10. Display [LWIND] on the main display.
11. Set the low power air volume level of
the Air Clean Unit.
Set the air volume level within 1 to 5 (default value: 1). Set a limit value for the air volume beyond which air is not to be fed.
12. Press the ENT key.
This sets the specified air volume level.
13. Set the mode switch to RUN.
This starts feedback control operation.
When the setting is next used, feedback is automatically started simply by turning the Air Clean Unit power supply ON.
24
ZN
System Manu al
Page 35
Section 2
3. Checking system operation
p.26
p.26
4-1. Displaying trend graphs
1. Installing the Exclusive Monitoring Software
p.27
5-1. Starting monitoring
p.28
p.25
2. Connecting peripheral devices
4-2. Data logging
p.29
5-2. Starting logging
p.30
Setup Methods Suited to Specific Applications
Monitoring/Logging the Amount of Particles
Measured particle values can be easily c aptured on a personal computer by using a n Interface Unit (sold separately) and the Exclusive Monitoring Software. The following describe s an example where the amount of particles is displ ayed as a trend graph and is saved as data.
OPE3
OPE2
OPE1
Section 2 UPGRADING THE SYSTEM
1. Installing the Exclusive Monitoring Software
Install the software (exclusive monitoring software) on the personal computer beforehand.
Installing the Exclusive Monitoring Software p.15
System Manu al
ZN
25
Page 36
Section 2 UPGRADING THE SYSTEM
Section 2 Setup Methods Suited to Specific Applications
2. Connecting peripheral devices
Connect the Air Clean Unit, Air Particle Sensor, Interface Unit, and the personal computer, and turn the power supply of all of these devices ON. Before connecting these devices, turn their power supplies OFF.
System Configuration Examples p.7, p.9
3. Checking system operation
Make sure that the Air Particle Sensor and Interface Unit have started up normally.
• W hen the Air Particle Sensor has not started up normally: Check the Sensor connection. Also, refer to the Instruction Sheet for the Air Particle Sensor in the case of other errors.
• W hen the Interface Unit has not started up normally: Make sure that the Air Particle Sensor Amplifier Unit is in the RUN mode. Also, check the connections of the peripheral devices.
26
ZN
System Manu al
Page 37
4-1.Displaying trend graphs
Select the number of planes to draw graphs in. Single:All channels to be drawn as a waveform are
drawn in a single graph plane.
Multi: One waveform is drawn in one graph plane.
Select the type of the graph. Line Chart: Displays the minimum and maximum
values within a specific time period.
Color Chart: The current value is displayed color-coded. Select the channel No. to be drawn as a waveform.
Single CH:Select this item to draw only a specific
channel No.
Multi CH: Select this item to draw multiple channel Nos.
simultaneously.
CH No.: Select the channel No. to be drawn.
Up to five waveforms can be drawn simultaneously.
Select the particle size to be drawn as a waveform.
Display the amount of particles as a trend graph.
1. Start up Exclusive Monitoring Software.
Starting Up the Exclusive Monitoring Software p.17
2. Click the [Graph] button and then [Edit graph ] button to display the Edit Graph
screen.
Section 2
Setup Methods Suited to Specific Applications
Section 2 UPGRADING THE SYSTEM
3. In the Edit Graph screen, set the graph drawing conditions.
System Manu al
ZN
27
Page 38
Section 2 UPGRADING THE SYSTEM
Sets the scale of the vertical axis. Sets the value at the center of the vertical scale.
Sets the vertical axis to a scale that allows all waveforms to be displayed.
Sets the scale of the horizontal axis.
Section 2 Setup Methods Suited to Specific Applications
4. Click the [Set] button.
5. Align the scales of the horizontal and vertical axes.
5-1.Starting monitoring
Click the [START] button to start drawing the graph. To stop drawing the graph, click the [STOP] button.
ZN
System Manu al
28
To save waveform data, click the [Save Waveform] button. (Data is saved in CSV format.) The data for up to five planes including past data can be saved.
Page 39
4-2.Data logging
Select the time data display method that is saved at the same time as the data when performing logging. Elapsed Time:The elapsed time is saved as the data
starting from the logging start time.
Real Time: The actual time is saved as data.
Select the particle size to be saved. (Multiple selections are allowed.)
Select the channel and particle size to be drawn during logging. Also, set the horizontal and vertical scales, center of the vertical axis, and the display unit.
[Center Point] can be set directly by clicking the [Input] button and entering a value. The unit selected at [Unit] is also reflected in the unit in the graph plane.
Select the sampling interval at which data is to be logged.
Click the [Output Data Selection] button to select the channel to output data from in the output channel selection screen.
Select the logging end conditions. Time Designation: None:
Logging is continued until it is ended manually.
Log Time: Set the time up to when logging
ends after the [Input] button is clicked. When the time set here has elapsed, logging automatically ends. (A time up to 24 hours can be set.)
When this item is selected, a logging file is automatically created and saved at each new day.
Data logging saves the trends for the amount of particles in a clean booth as data.
1. Start up the Exclusive Monitoring Software.
2. Click the [Logging] button to display the Logging screen.
Section 2
Setup Methods Suited to Specific Applications
Section 2 UPGRADING THE SYSTEM
Starting Up the Exclusive Monitoring Software p.17
3. In the Logging screen, set the logging conditions.
System Manu al
ZN
29
Page 40
Section 2 UPGRADING THE SYSTEM
Section 2 Setup Methods Suited to Specific Applications
5-2.Starting logging
Click the [Exe.] button to start Logging.
30
ZN
System Manu al
Page 41
Section 2
4. Checking system operation
p.32
p.32
5. Setting the feedback conditions
1. Installing the Exclusive Monitoring Software
p.32
p.31
3. Connecting peripheral devices
p.32
2. Setting the ID of the Air Clean Unit
n units connected
m units connected
n: max. 9 units m: max. 10 units
1ch2chnch 3ch
1ch2ch3chmch
Setup Methods Suited to Specific Applications
Detecting the Cleanliness of Multiple Processes
The cleanliness of multiple processes can be verified a t each individual process by multiple Air Particle Sensors and multiple Air Clean Units. The air volume level also can be controlled on individual equipment or booth (area). The following describes an example where the cleanliness of multiple processes is controlled.
Section 2 UPGRADING THE SYSTEM
1. Installing the Exclusive Monitoring Software
Install the software (exclusive monitoring software) on the personal computer beforehand.
Installing the Exclusive Monitoring Software p.15
System Manu al
ZN
31
Page 42
Section 2 UPGRADING THE SYSTEM
Section 2 Setup Methods Suited to Specific Applications
2. Setting the ID of the Air Clean Unit
1. Set DIP switch SW1 on the rear of the Air Clean Unit to ON (external
communications control enabled).
2. Set each of the channels (1 to n) by the ID rotary switch on the rear of the Air
Clean Unit.
Be sure to set unique ID numbers to each Unit. The Units will not function properly when the same ID is set to multiple units. When using the ZN-SF12 to perform feedback control, do not set the ID number to "0" (0ch). A ZN-SF12 set to 0ch cannot be controlled.
3. Connecting peripheral devices
Connect the Air Clean Unit, Air Particle Sensor, Interface Unit, and the personal computer, and turn the power supply of all of these devices ON. Before connecting these devices, turn their power supplies OFF.
System Configuration Examples p.11
4. Checking system operation
Check operation of the Air Clean Unit, Air Particle Sensor and Interface Unit.
• When the Air Particle Sensor has not started up normally: Check the Sensor connection. Also, refer to the Instruction Sheet for the Air Particle Sensor in the case of other errors.
• W hen the Interface Unit has not started up normally: Make sure that the Air Particle Sensor Amplifier Unit is in the RUN mode. Also, check the connections of the peripheral devices.
• Check that the Air Clean Unit is in the standby mode.
5. Setting the feedback conditions
Operate the Exclusive Monitoring Software to set multiple feedback conditions.
1. Start up Exclusive Monitoring Software.
32
Starting Up the Exclusive Monitoring Software p.17
ZN
System Manu al
Page 43
Section 2
Feedback destination Air Clean Unit: Select the Air Clean Unit to be controlled.
Area selection: Select the target area to be set.
Air Volume Level Control: Select the method for controlling the air volume level.
Feedback source Sensor channel: Select the Air Particle Sensors located in the target areas.
Set the details.
Setup Methods Suited to Specific Applications
2. Click the [IFU Settings] button to display the Settings for Interface Unit screen.
3. In the Settings for Interface Unit screen, set the control conditions.
Set the information of the Air Clean Units and Air Particle Sensors located in the areas, and the method for controlling the air volume level of the target areas.
Section 2 UPGRADING THE SYSTEM
The detailed settings are as follows:
Item Description
Calculation Type Selects the method for calculating the measured value.
Max: Select this parameter to set the maximum value of the
measurement result measured by the selected Air Particle Sensor as the cleanliness of the target area.
Min: Select this parameter to set the minimum value of the
measurement result measured by the selected Air Particle Sensor as the cleanliness of the target area.
Ave: Select this parameter to set the average value of the
measurement result measured by the selected Air Particle
Sensor as the cleanliness of the target area. Feedback Type Selects the feedback method. Feedback Cycle Selects the feedback cycle. Target class(0.5µm) Selects the cleanliness class to be controlled. Low Power(Wind) When "Constant" is selected at "Feedback Type", select the limit
value for the air volume beyond which air is not to be fed, and when "Rapid" is selected, select the air volume level for when the cleanliness has reached the target value.
High Power(Wind) Select the air volume level for when the cleanliness has not reached
High Power(Time) Select the time that the high power air volume level is to be held for.
the target value. This item can be selected only when "Rapid" is selected at "Feedback Type".
System Manu al
ZN
33
Page 44
Section 2 UPGRADING THE SYSTEM
Section 2 Setup Methods Suited to Specific Applications
• For the high power air volume level, always set an air volume greater than the low power air volume level. Feedback will not function properly if a smaller value is set.
• The time that the high power air volume level is actually held is an integer multiple of the feedback cycle. Example: When Feedback Cycle is set to "60 s" and High Power(Time) is set to "100 s", the actual high power time is 120 s.
• We recommend setting the f eedback cycle to t he measurement cy cle of the Air Particle Sensor or higher. Otherwise, feedback control will be endlessly executed based on the same measurement result, and correct feedback control will not be possible.
How Feedback Control Works p.40
4. Click the [OK] button to start feedback controlled operation.
• When the setting is next used, feedback is automatically started simply by turning the Air Clean Unit and Air Particle Sensor (and Interface Unit) power supplies ON.
• Feedback sometimes is not performed smoothly (i.e. a control lag occurs during execution of feedback operation) when the power supply of the Air Clean Unit set as t he control target in feedback control is not turned ON. To solve this, either set feedback c ontrol so that it is performed only on po wered ON Air Clean Units, or turn the power supply of all currently set Air Clean Units ON.
34
ZN
System Manu al
Page 45
Section 3 BASIC KNOWLEDGE OF CLEAN SENSING SYSTEMS
Feedback Control 36
What is "Feedback?" 36 How Feedback Control Works 40
Clean Sensing 44
Principle o f "Particle Count" 44 What is "Cleanliness?" 45
Section 3 BASIC KNOWLEDGE OF CLEAN SENSING SYSTEMS
System Manu al
ZN
35
Page 46
Section 3
OPE1
OPE2
OPE3
Air Clean Unit
Air Particle Sensor
(3) Air volume level increases
to improve cleanliness inside the area.
(1) Cleanliness inside the area
falls and is about to exceed the target cleanliness.
(2) The command for increasing
the air volume level is sent.
OPE1
OPE2
OPE3
Air Clean Unit
Air Particle Sensor
Feedback Control
Feedback Control
What is "Feedback?"
"Feedback" is th e control o f the air vol ume level o f the Air Clea n Unit in pr oportion to the amount of particles to maintain the cleanliness of target spaces. The ZN series incorporates the "F O feedback" (Fle xible & Optimu m Feedback) funct ion. This control program performs fl exible and optimum fe edback suited to the user's environment s o
Section 3 BASIC KNOWLEDGE OF CLEAN SENSING SYSTEMS
that a clean environment can be maintained and managed.
■ System Configuration
There are two system configurations that use the feedback function, a "direct clean sensing system" and "multi-clean sensing system."
• Direct Clean Sensing System
In this system, the cleanliness of one area is managed by an Air Particle Sensor and an Air Clean Unit. Feedback processing is perfo rmed by the Air Parti cle Sen so r. On the direct clean sensing system, you can select between "rapid feedback" and "constant feedback" as the feedback method.
Feedback Methods p.38
Various feedback parameters (described later) can also be set.
ZN
System Manu al
36
Page 47
Section 3
Air Clean Unit
Air Particl e Sensor
Interface Unit
Feedback Control
• Multi-Clean Sensing System
In this system, the cleanliness of multiple areas is managed by multiple Air Particle Sensors and multiple Air Clean Units. The Interface Units acquire the da ta from the Air Particle Sensors th at are connected together to perform feedback processing on the entire system. Besides feedback processing on individual Air Particle Sensors, correspondence between Air Particle Se nso r and A ir Cle an Un it c han nel s a nd c alc ul ati on o f Ai r Par tic l e Sensor data also are possible.
Section 3 BASIC KNOWLEDGE OF CLEAN SENSING SYSTEMS
When using multiple Air Particle Sensors or multiple Air Clean Units, configure a multi-clean sensing system using the ZN-SF12.
System Manu al
ZN
37
Page 48
Section 3
(2) When the high power
time elapses, the air volume level returns to low power.
(1) The air volume level is
changed to high power when the cleanliness exceeds the target cleanliness.
(3) The air volume level is
changed to high power when the cleanliness exceeds the target cleanliness again.
Amount of particles
Target cleanliness
High power air volume level
Low power air volume level
Feedback cycle
High power time
Time
Time
[Feedback Cycle]
• In a multi-clean sensing system: The feedback cycle can be set on the Interface Unit.
• In a direct clean sensing system: The feedback cycles equals the measurement time of the Air Particle Sensor.
Feedback Control
■ Feedback Methods
There are two feedback methods, "rapid feedback" and "constant feedback."
• Rapid feedback
When cleanliness has deteriorated, rapid feedback quickly increases the air volume level to recover the cleanliness. This feedback method is effective in environments with relatively lots of change.
Section 3 BASIC KNOWLEDGE OF CLEAN SENSING SYSTEMS
<Feedback Operation>
• When the high power time is set to a value other than "0": The high power air volum e level is switch ed to regardle ss of changes in the amount of particles when the hig h p owe r air vo lum e level c ont inu es un til th e high power time elapses.
• When the high power time is set to "0": The high power air volume level continues until the amount of particles falls to a fixed level or lower, and the low power air volume level is switched to.
ZN
System Manu al
38
• For the high power air volume level, set an air volume greater than the lower power air volume level. Otherwise, feedback will not function properly.
• If the cleanliness is not restored after the high power time has elapsed, operation will continue at the low power air volume level (i.e. the high power air volume level will not be switched to). When this happens, either set a longer high power time or set the high power time to 0.
Page 49
Section 3
(1) The air volume level is
increased a level when the target cleanliness is about to be exceeded.
(2) The air volume level is
lowered a level when the amount of particles is at a fixed level or below.
Amount of particles
Target cleanliness
Low power air vo lu me leve l
Feedback cycle
Time
Time
[Feedback Cycle]
• In a multi-clean sensing system: The feedback cycle can be set on the Interface Unit.
• In a direct clean sensing system: The feedback cycle equals the "measurement time x 16" of the Air Particle Sensor.
(3) The air volume level is
increased a level again when the target cleanliness is about to be exceeded.
Feedback Control
• Constant feedback
The air volume level is altered so that the cleanliness stabilizes at the target value. This feedback method is effective in environments with relatively little change since the cleanliness is maintained at the bare minimum air volume level.
Section 3 BASIC KNOWLEDGE OF CLEAN SENSING SYSTEMS
<Feedback Operation>
The air volume level is switched in stages according to the chang e in the amount of particles.
The controlled air volume level never falls below the lower power air volume level. Set the bare minimum air volume level as the lower power air volume level.
ZN
System Manu al
39
Page 50
Section 3
(1)
(
Air Clean Unit
Air Particle Sensor
Control signal
Area 1
Feedback Control
How Feedback Control Works
The following describ es the "flow of d ata for feedback" and "measurement p rocessing flow" during feedback con tr ol for each sy s tem con fig ur ati on.
■ Direct Clean Sensing System
• Flow of data for feedback
Section 3 BASIC KNOWLEDGE OF CLEAN SENSING SYSTEMS
(3)
(2)
In a system configured as shown above: (1) The a mou nt o f part ic les i n ar ea 1 i s detected by the Sensor, and the measuremen t
result is calculated by the Amplifier Unit.
(2) The control air volume level value of area 1 is calculated based on the
measurement results, pr eset target values and var ious feedback paramete rs, and is sent to the Air Clean Unit.
(3) The air volume level is altered according to the controlled air volume level value
that arrives from the Air Particle Sensor.
40
ZN
System Manu al
Page 51
• Flow of processing on the Air Particle Sensor
Start of
measurement
Measurement result calculated for each measurement time
Air Particle Sensor
1ch
Measurement result table (example)
Measured air volume level calculated based on feedback parameters
Setting values to be used
Feedback Control
Measurement result
2000
Target level
1000
Feedback type
Constant
Low power air volume level
2
Section 3
Section 3 BASIC KNOWLEDGE OF CLEAN SENSING SYSTEMS
Control air volume level value is sent by communications.
Calculation of control air volume level value (example)
Control air volume level value
2
System Manu al
ZN
41
Page 52
Section 3
Air Clean Unit
Air Particle Sensor
Control signal
Area 1
Interface Unit
Area 2
Feedback Control
■ Multi-Clean Sensing System
• Flow of data for feedback
3CH
4CH
2CH
(3)
1CH2CH
1CH
Section 3 BASIC KNOWLEDGE OF CLEAN SENSING SYSTEMS
ZN-SF21
(1)
(2)
In a system configured as shown above: (1) The a mount of par ticles in area 1 is detec ted by t he sens ors on ch annels 1 ch and
2ch, and the amount of particles in area 2 is detected by the sensors on ch annels 3ch and 4ch, the measureme nt result is calculated by the Am plifier Unit, and the result is transferred to the Interface Unit.
(2) The controlled air volume level value of ea ch area is calculated based on preset
target values and various feedback parameters, the measurement results sent from the Air Particle Sensor s on channels 1c h to 4ch, and is sen t to the Air Clean Units on channels 1ch and 2ch.
(3) The air volume level is altered according to the controlled air volume level value
that arrives from the Interface Units.
42
ZN
System Manu al
Page 53
Section 3
Measurement result calculated for each measurement time
Measured air volume level calculated based on feedback parameters
Measurement result
Air Particle Sensor
1 3500
Measurement result table (example)
Calculation method
Target level
Feedback type
MAX
1000
Constant
Control air volume level value is sent by communications.
Start of
measurement
Area 1
Low power air volume level
3
2 2000
3 2500
4 3100
Calculation of control air volume level value for each area
Enabled/ disabled
1ON
2ON
3 OFF
4 OFF
Air Particle Sensor Channel
Enabled/ disabled
1ON
2 OFF
Air Clean Unit ID
Calculation method
Target level
Feedback type
AVE
1000
Constant
Area 2
Low power air volume level
2
Enabled/ disabled
1 OFF
2 OFF
3ON
4ON
Air Particle Sensor Channel
Enabled/ disabled
1 OFF
2ON
Air Clean Unit ID
Calculation of control air volume level value and measurement result for control (example)
1 3500
2 2800
Measurement result for control
Area
Control air volume level value
5
3
Setting values to be used
Feedback Control
• Flow of processing on In terface Unit
The following shows an examp le of pr ocess ing flow du ring measure ment an d the da ta to be used when feedback processing is performed under the following conditions:
• The Air Clean Unit (ID:1) is controlled based on the l arger value of the Air Particle Sensors on channels 1ch and 2ch.
• The Air Clean Unit (ID:2) is controlled based on the average value of Air Particle Sensors on channels 3ch and 4ch.
Section 3 BASIC KNOWLEDGE OF CLEAN SENSING SYSTEMS
System Manu al
ZN
43
Page 54
Section 3
Particles
Suction inlet
Receiving lens
Light-receiving lens
Fan
Amplifier Comparator
Light source
Emission lens
Signal processing circuit
Received light signal
Threshold
Time
Comparator output
Incident value
Received light signal and comparator output
Clean Sensing
Clean Sensing
Principle of "Particle Count"
The ZN-PD series judges the cleanliness of target spaces by measuring the amount of particles (dust or dirt) floating in the air. The amount of particles is measured using the "fan method" and "scattered light method" m ounted on the Air Particle Sensor (Senso r + Amplifier Unit).
Section 3 BASIC KNOWLEDGE OF CLEAN SENSING SYSTEMS
The ZN-PD series adopts the "fan method" for sucking in air. Compared with the "pump method" used on handy-type particle sensors, for example, this method has a service life that is about 10 times longer. This enables the amount of particles to be measured stably over a long period of time.
(1)
(2)
(3)
(1) Air inside the clean booth is sucked in from the suction inlet by the fan. (2) The sucked in air is illuminated by a laser beam.
If the air contains particles, the light is scattered.
(3) Particles a re detected by scattered lig ht entering the light receivi ng lens, and the
amount of particles is measured. The scattered light ent ering the l ig ht rec ei ving lens is converted to electric si gnal by the amplifier and comparator, and is sent to the signal processing circuit. The amount of particles is measur ed ba se d on th e ele ctri ca l signals that are sent to this circuit.
44
■ Measurement of the Amount of Particles
ZN
System Manu al
The amount of particles is measured bas ed on the incident value. However, this incident value increases the larger the particles become. Thresholds are set for each of the target particle diameters of 0.3 µm/0.5 µm/1.0 µm, and the particle dia meter is judged according to the size of the incident value.
Page 55
Section 3
1 max. → Class 1
100 max. → Class 100
10,000 max. → Class 10,000
1f (approx. 30 cm)
1f (approx. 30 cm)
1f (approx. 30 cm)
Clean Sensing
What is "Cleanliness?"
Cleanliness is expressed by the size, number and weight of polluting substances (dust, dirt, etc.) contained in a fixed area or volume. The degree of cleanliness that is indicated by the amount of dust or dirt contained in specific air is called the "cleanliness level." This is further broken down into classes called "cleanliness class."
■ Cleanliness Standards
Standards that relate to the clea nliness of c lean room s, for exampl e, include Fed-Std­209D in the United States and JIS B 9921 in Japan. The unit volume and particle diameter of polluting su bstances that the criteria for these standards are based on are different. The ZN series adopts cleanliness annotation that complies with Fed-Std­209D, the most widely used standard at production sites.
■ Definition of Cleanliness According to Fed-Std-209D
Cleanliness is defined by the number of particles of 0.5 µm or more in diameter that are contained in 1 cubic foot (28.3 liters or approximately a 30 cm cube) of air, and is broken into classes de fine d by mul tip le s of ten. Thi s class i fic ati on is i ntu iti ve and e as y­to-understand, and has been used the longest at production sites.
Section 3 BASIC KNOWLEDGE OF CLEAN SENSING SYSTEMS
Number of particles of
0.5 µm or more/cf
Class
1
1 10 100 1,000 10,000 100,000
Class
10
Class
100
Class
1,000
Class
10,000
Class
100,000
ZN
System Manu al
45
Page 56
Section 3 Clean Sensing
MEMO
Section 3 BASIC KNOWLEDGE OF CLEAN SENSING SYSTEMS
46
ZN
System Manu al
Page 57
Section 4 APPENDICES
Maintenance 48 Troubleshooting 50
Troubleshooting 50 Error Messages and Countermeasures 51
Specifications and Dimensions 53 List of Products 66 INDEX 69
Section 4 APPENDICES
System Manu al
ZN
47
Page 58
Section 4 Maintenance
Maintenance
For details on inspection and maintenance, refer to the Instruction Sheet for the respective product.
■ Air Clean Unit
ZN-A series filters are in a double-filter s tructure comprising a HEPA filter and a pre­filter, and filter air that is sucked in.
• Periodic inspection
When the filter becomes dirty, highly clean air can no longer be suppl ied stably for a long time. So, dust must be periodically removed from the pre-filter.
Section 4 APPENDICES
• Replacement
When the filter become s clogged, the two indicators (green/red) on the corner of the body light simultaneously to notify that the filter must be replaced with a new one. For details on how to repl ace the filter, refer to the Ins truction Sheet f or the Air Clean Unit.
Indicator
■ Air Particle Sensor
The ZN-PDA series uses a high-performance fan on the suction module to enable continuous operation.
• Periodic inspection
Dirt and dust car ried i n b y the fa n o n thi s sy st em caus es th e fil ter to become dirty over extended use. When th e filter bec omes dir ty, the amount of particles can no longe r be monitored accurately. So, dust must be periodically removed from the pre-filter. If dirt on the pre-filter is stubbor n and cannot be removed, replace the pre-filter wit h Filter Set ZN9-PF1 (sold separately).
• Cleaning
When the system has carried in air containing lots of particulates, install Cleaning Filter ZN9-PC1 (sold separately) to maintain the inside of the Sensor in a clean state.
48
ZN
System Manu al
Page 59
Section 4
Cleaning notice/ warning indicator
Maintenance
■ Ionizer Unit
The ZN-J series generates ions by applying a high voltage on the discharge needles to cause corona discharge.
• Periodic inspection
If the discharge needles become dirty or worn, the amount of generated ions decreases and causes the neutralizing performance to drop. So, the discharge needles must be cleaned periodically.
• Replacement
The cleaning noti ce indicator flashes orange to notify you that the discharg e needles are dirty and the product's neutralizing capabilities are about to drop. The cleaning notice indicator wil l stop flashing and stay lit (cleaning warn ing) when the discharge needles become even dir tier and the product's neutral izing capabilities can no longer be sustained. Replace the discharge needle s if the cleaning warning indicator stays lit after they are cleaned. If the cleaning warning indicator lights even after replacing the discharge needles, contact your OMRON representative. For details on how to replace the di scharge needles, r efer to the Instructi on Sheet for the Ionizer Unit.
Section 4 APPENDICES
System Manu al
ZN
49
Page 60
Section 4 Troubleshooting
Troubleshooting
Troubleshooting
This section describes countermeasures for temporary device problems. Check the malfunction in this section before sending the hardware for repair.
For details on how to connect devices, refer to the Instruction Sheet for the respective product.
Problem Probable cause and possible countermeasure Pages
The sensor communications LED or
Section 4 APPENDICES
the external terminal communications LED ERR indicator does not light even after 5 seconds has elapsed.
The Air Clean Unit power supply is not ON.
The Air Particle Sensor power supply is not ON.
No communications with personal computer
(i) The communications ports do not match.
(ii) The BUSY indicator does not light up.
(iii) There is no response from the Interface Unit.
(iv) An error message appears and the Sensor cannot start up.
The respective product is not connected correctly.
• Is the mode switch on the Air Particle Sensor Amplifier Unit set to RUN?
• Are the Amplifier Units connected correctly to each other, or is the Interface Unit connected correctly to the Amplifier Unit?
• Has the Amplifier Unit started up properly?
• Check the power supply voltage if the DC power supply wire is used.
• Is the AC adapter (provided) used?
• Check the power supply voltage if the DC power supply is used.
• Are all cables connected correctly?
Turn the power supplies of the Interface Unit and Air Particle Sensor Amplifier Units OFF then back ON again. If communications still does not start, check the following points (i) to (iv), and then restart the Sensor.
• Set the same communications port No. as that on the personal computer (the other communications conditions are set automatically).
• Quit the application program that is using the communications port.
No signal is being sent to the Interface Unit.
• Is the Sensor connected with the correct cable? (Check if it is connected with a straight cable by mistake.)
• Is the sensor connected correctly?
• Is the correct communications port set?
• Is the switch on the rear of the Interface Unit set to the default side?
• Is the mode switch on the Air Particle Sensor's Amplifier Unit set to RUN?
Is the Interface Unit in use the correct one? (The dedicated Interface Unit (ZN-SF11/SF12) is required to communicate with the ZN-PDA series.)
-
-
-
-
-
-
p.17
-
50
ZN
System Manu al
Page 61
Section 4
Troubleshooting
Error Messages and Countermeasures
This section outlin es the error m essages that a re displa yed and the c ountermeasur es for those messages. Check the malfunction in this section before sending the hardware for repair.
■ Air Clean Unit (ZN-A Series)
[Indicator]
Indication Error Countermeasure
Green, red lit simultaneously
Red lit The fan is rotating irregularly. Turn the fan power supply OFF then back ON again.
Green, blue flashing
The air outlet or air inlet is blocked.
The filter is blocked. Replace the filter.
The fan has reached the end of its service life.
A voltage outside the rated voltage is applied to the fan.
The I/O terminal power supply and AC adapter are connected at the same time .
The top case is open. Clos e the top case, turn the power supply OFF then
Remove the object blocking the air outlet or air inlet.
If turning the power supply OFF then back ON again does not remedy the problem, contact your OMRON representative.
Turn the fan power supply OFF then back ON again. If turning the power supply OFF then back ON again does not remedy the problem, a probable cause is that the fan has reached the end of its service life. Contact your OMRON representative.
Check the power supply voltage.
Check the power supply.
back ON again, and press the ON/OFF switch.
Section 4 APPENDICES
■ Ionizer Unit (ZN-J Series)
[Cleaning notice indicator/cleaning warning indicator]
Indication Error Countermeasure
Orange flashing
Orange lit The discharge needles are dirty.
The discharge needles are dirty. Continued use in this state will cause neutralizing performance to drop.
The neutralizing performance has already dropped.
[Error output indicator]
Indication Error Countermeasure
Red lit Abnormal discharge Turn the power supply OFF then back ON again.
Clean the discharge needles.
Clean the discharge needles. If this does not solve the error, the discharge needles are worn. Replace the discharge needles.
If turning the power supply OFF then back ON again does not remedy the problem, contact your OMRON representative.
System Manu al
ZN
51
Page 62
Section 4 Troubleshooting
■ Air Particle Sensor (ZN-PDA Series)
[Main display]
Display Error Countermeasure
E-SEn (flashing)
E-hEd (flashing)
E-EEP (flashing)
E-Sht (flashing)
----- This error is indicated until the
Section 4 APPENDICES
[Sub-display (during communication status display)]
Display Error Countermeasure
Err-_ Communications timeout and
The Sensor fan or laser is in error or has deteriorated.
The Sensor is not connected or is in error.
The EEPROM is damaged or data is in error.
One or all of the judgment outputs is short-circuited.
initial data is obtained after the power supply is turned ON or the FUN mode is switched to the RUN mode.
other communications errors
Check the connection with the Sensor and Amplifier Unit, and turn the power supply OFF then back ON again. If this does not solve the problem, the Sensor is malfunctioning. Replace the Sensor.
Hold down the ENT key for at least 3 seconds. If this does not solve the error, the Amplifier Unit is malfunctioning. Replace the Amplifier Unit.
Correct short-circuiting of short-circuited loads. (The sensor is automatically restored after the short­circuited load is canceled.)
The time it takes to obtain the initial data depends on the settings for the number of samples to average and the measurement time.
• Check the cable connection with the Air Clean Unit.
• Make sure that the channel No. of the Air Clean Unit is "0".
• Switch DIP switch 1 on the Air Clean Unit to ON (external communications control enabled).
■ Interface Unit for Clean Monitoring System (ZN-SF Series)
[Main display]
Display Error Countermeasure
E-AmP (flashing)
E-EEP (flashing)
Err__ (during communications status di spl a y)
The Amplifier Unit is not connected or the adjacent Amplifier Unit cannot be recognized correctly.
The EEPROM is damaged or data is in error.
Communications timeout and other communications errors on the channel indicated by __.
• Set all mode switches on the Amplifier Unit to the RUN mode.
• Make sure that the Amplifier Unit and Calculating Unit are connected correctly, and turn the power supply back ON again. If this does not solve the problem, the Amplifier Unit or Calculating Unit is malfunctioning. Replace the Amplifier Unit or Calculating Unit.
Hold down the ENT key for at least 3 seconds. If this does not solve the error, the Amplifier Unit is malfunctioning. Replace the Amplifier Unit.
• Check the cable connection with the Air Clean Unit.
• Check the channel No. of the Air Clean Unit and the feedback function settings.
52
ZN
System Manu al
Page 63
Specifications and Dimensions
276
250
250
97.5
45 160
28
220
226.6
205.6
4-M4, depth 17
Operation indicator
Operation indicator
Air volume level switch
Air volume level indicator
ON/OFF switch
(Unit: mm)
417
129.5
15
15 380
360
4-M5, depth 20
380 360
410
436
410
Operation indicatorOperation indicator
Air volume level switch
Air volume level indicator
ON/OFF switch
(Unit: mm)
Specifications and Dimensions
Air Clean Unit ZN-A2502/A2502D
Section 4
Section 4 APPENDICES
ZN-A4105/A4105D
System Manu al
ZN
53
Page 64
Section 4 Specifications and Dimensions
Item ZN-A2502/A2502D ZN-A4105/A4105D Air outlet dimension 225 x 205 mm 360 x 360 mm Particle outlet efficiency More than 99.99% for 0.3 µm particles Air volume (m Sound noise level (dB) Air volume level 3: 53 dB (typical)
Fan motor DC brushless compact centrifugal
Main filter HEPA filter Main filter model ZN9-AHP25 ZN9-AHP41 Pre-filter model ZN9-APF25 ZN9-APF41 Power supply voltage 24 VDC ±10% Ripple (p-p) 10% max. Current consumption
Section 4 APPENDICES
Indicator Operation: Green/Red
Output Alarm output 1: Alarm output 1 turns OFF when one of the following happens.
Functions Air volume selectable (Level 1 to 5), automatic control by ZN-PDA,
Ambient temperature Operating and storage: 0 to 40°C (with no icing or condensation) Ambient humidity Operating and storage: 35 to 85% (with no condensation) Material Upper case: ABS, Bottom frame: Steel Dimensions (mm) 250 (W) x 250 (D) x 97.5 (H) 410 (W) x 410 (D) x 129.5 (H) Weight (packed state) Approx. 2 kg (approx. 3.3 kg) Approx. 5.2 kg (approx. 8.6 kg) Accessories Instruction Sheet, Sealing parts, Mounting screws, I/O connector (XW4B-06B1-H1),
(*1) AC adapter:
3
/min) 0.3 to 1.8 m3/min (typical) 1.0 to 5.0 m3/min (typical)
Air volume level 3: 53 dB (typical)
Air volume level 1: 41 dB (typical)
blower: 2
Air volume level 5:2.1 A max. (RMS value) Air volume level 1:0.4 A max. (RMS value)
Air volume: Blue
(Normally, Alarm output 1 is ON.) Check the indicator to find out which one is happening.
• Filter clogged
• Fan error
• Cleaning alarm for discharge needle (when ZN-J is used with)
• Discharge error (when ZN-J is used with)
Alarm output 2: Only for ZN-J used with
Alarm output 2 turns OFF with the cleaning notice for the discharge needles. (Normally, Alarm output 2 is ON.)
30 VDC, 50 mA max. Residual voltage: 1 V max. with load current 10 mA, 2 V max. with load current 50 mA
filter clogging alarm, available with ZN-J (Ionizer Unit), multi connection up to 9 units
AC adapter (*1) Not for ZN-A2502D, ZN-A4105D
made by Sanken Electric Co., Ltd. Model SEB100P2-24.0 (for ZN-A2502), Supply voltage 100 VAC to 240 VAC. made by Sanken Electric Co., Ltd. Model SEC165P2-24.0 (for ZN-A4105), Supply voltage 100 VAC to 240 VAC.
Air volume level 1: 40 dB (typical) DC brushless turbo fan: 1
Air volume level 5:3.5 A max. (RMS value),
(Peak: 5.5 A)
Air volume level 1:0.32 A max. (RMS value)
54
ZN
System Manu al
Page 65
Ionizer Unit
Mount hole dimensions/panel cutout dimensions
252
6 3.3
33
45
310
AC adapter terminal
Power input /signal output connector
GND terminal
/cleaning warning indicator (orange lit)
Cleaning notice indicator (orange flashing)
Ion balance adjustment buttons
Power switch
Error output indicator (red flashing)
Power indicator (green lit)
Discharge needles (4)
210
248
mm dia.
8- 5 Mount hole (thru hole)
210
25.50
220
70
210
160 ± 0.2
220 ± 0.2
220 ± 0.2
160 ± 0.2
210
8-5 mm dia. hole
(Unit: mm)
360
240 ± 0.2
380 ± 0.2
360
240 ± 0.2
380 ± 0.2
412
470
(3.3)
Power switch
Power indicator (green lit)
Error output indicator (red lit)
Ion balance Adjustment buttons
Cleaning notice indicator (orange flashing) /cleaning warning indicator (orange lit)
Power input/signal output connector
GND terminal
AC adapter terminal
45
33
6
Mount hole dimensions/panel cutout dimensions
12-6
mm dia. hol
e
Discharge needles (4)
240
380
360
240
360
380
408
70
65.5
12-6 mm dia. mount hole (thru hole)
(Unit: mm)
ZN-J25/J25A
Section 4
Specifications and Dimensions
Section 4 APPENDICES
ZN-J41/J41A
System Manu al
ZN
55
Page 66
Section 4 Specifications and Dimensions
Item ZN-J25A ZN-J25 ZN-J41A ZN-J41
Available Air Clean Unit ZN-A2502 - ZN-A4105 ­Power supply voltage 24 VDC±10% Ripple (p-p) 10% max. Current consumption 300 mA max Output voltage ±7 kV max. Discharge method Variable DC Neutralizing time (typical) *1 5 sec max. Ion balance (typical) *2 ± 30 V max. Indicator Power (green), Cleaning notice (orange blinking), Cleaning warning (orange)
Error (red)
Output Error output,
cleaning notice/alarm output: photo MOS relay (30 VDC 300 mA max.)
Functions Manual ion balance adjustment, cleaning alarm, error alarm
Section 4 APPENDICES
Ambient temperature Operating and storage: 0 to 40°C (with no icing or condensation) Ambient humidity Operating and storage: 35 to 65% (with no condensation) Materials Case: ABS, Discharge needles: Tungsten Dimensions (mm) 248 (W) x 310 (D) x 45 (H) mm 408 (W) x 470 (D) x 45 (H) mm Weight (packed state) Approx. 0.6 kg (approx. 1.4 kg) Approx. 1.5 kg (approx. 2.7 kg) Accessories Instruction sheet,
Sealing parts, Mounting screws, Connector cable for Air Clean Unit, Ferrite core, English warning label
(*1) Measurement conditions: Distance 300 mm, Air Clean Unit: ZN-A series
with air level 5, At center of air outlet, Neutralization: From ±1000 V down to ±100 V with Charge Plate monitor (150 x 150 mm, 20 pF) Temperature: 18 to 28°C, Humidity: 35 to 55% The performance might not be able to be satisfied when there is gas such as solvent gas in the measurement area.
(*2) Measurement conditions: Distance 300 mm, Air Clean Unit: ZN-A series
with air level 5, At center of air outlet, Measurement time: 10 seconds at Charge Plate monitor (150 x 150 mm, 20 pF) Temperature: 18 to 28°C, Humidity: 35 to 55% The performance might not be able to be satisfied when there is gas such as solvent gas in the measurement area.
(*3) AC adapter: made by Sanken Electric Co., Ltd. Model SEA40N2-24.0, Supply voltage 100 VAC to 240 VAC.
Instruction sheet, Sealing parts, Mounting screws, I/ O cable (2 m), AC adapter (*3), Ferrite core, English warning label
Instruction sheet, Sealing parts, Mounting screws, Connector cable for Air Clean Unit, Ferrite core, English warning label
Instruction sheet, Sealing parts, Mounting screws, I/ O cable (2 m), AC adapter (*3), Ferrite core, English warning label
56
ZN
System Manu al
Page 67
Air Particle Sensor
1
a.
(Unit: mm)
Round vinyl insulated cable
5.2 mm dia., 10-wire Standard length: 0.5 m
Suction inlet
Exhaust outlet
Mount hole dimensions
Mounting screw holes 2-M4, depth 6
(Unit: mm)
Mount hole d ime n s i on s
Mounting bracket
Oblong mount hole
6-3.2 x 6.2
Mounting screws 2-M4x6
• Sensor ZN-PD03
76
Section 4
Specifications and Dimensions
21.5
39.4
120
14.3
46
44
22
70
14.4
22.4
15.85
36.8
25 70
35
When sensor mounting bracket (ZN9-PB1, sold separately) is used
70
0.
4545
6-M3
2
4.2 mm di
Section 4 APPENDICES
82 ± 0.1
42
2.6
82 44
(90)
(100)
455545
ZN
System Manu al
57
Page 68
Section 4 Specifications and Dimensions
Item ZN-PD03
Available Amplifier Unit ZN-PDA 11/ZN-PDA12 Measurement method 90° sideway light-scattering method Light source Semiconductor laser Available particle size 0.3 µm/0.5 µm/1.0 µm Available cleanliness class Class100 to 100,000 corresponding (FED-STD-209D) Indicator Level indicator for Class100 to 100,000 (FED-STD-209D) Suction tube Inside diameter: 4 mm, Length: 1 m max. Ambient temperature Operating: 0 to 40°C, Storage: -15 to +50°C (with no icing or condensation) Ambient humidity Operating and storage: 35 to 85% (with no condensation) Dielectric strength 1,000 VAC, 50/60 Hz for 1 min Vibration resistance 10 to 55 Hz, 0.7-mm double amplitude 80 min each in X, Y and Z directions
Section 4 APPENDICES
Shock resistance 150 m/s Connection method Connector cable (standard cable length: 0.5 m) Materials ABS Weight (packed state) Approx. 300 g (approx. 450 g) Accessories Instruction sheet, Suction tube
2
3 times each in six directions (up/down, left/right, forward/backward)
58
ZN
System Manu al
Page 69
• Amplifier Unit
(Unit: mm)
(Unit: mm)
ZN-PDA11
Section 4
Specifications and Dimensions
Wide range indicatorPower indicator
Unit indicator
ZN-PDA12
OUT1 indicator
OUT2 indicator
30
(133)
44
15.5 mm dia.
13.2
Round vinyl insulated cable
5.1 mm dia. standard 100 mm
3
36.813
Main display indicator
Sub-display indicator
4.264.34.2
Round vinyl insulated cable
5.2 mm dia. standard 2 m
15.8
31.5
16.86
Section 4 APPENDICES
Power indicator
OUT1 indicator
OUT2 indicator
11.7
2.2
29
Wide range indicator Unit indicator
Judgment output OUT2/reset input switch
11.7
(Default setting is judgment output.)
Judgment outputs
Modular jack
Main display indicator
Sub-display indicator
30
15.5 mm dia.
13.2
Round vinyl insulated cable
5.1 mm dia. standard 100 mm
21.46
6.6
31.5
16.86
Round vinyl insulated cable 5.1 mm dia., 10-wire (conductor cross-sectional area: 0.08 mm insulator diameter: 0.7 mm) standard 2 m
15.8
2
/
11.7
3
36.813
29
(133)
44
2.2
4.264.34.2
11.7
ZN
System Manu al
59
Page 70
Section 4 Specifications and Dimensions
Item ZN-PDA11 ZN-PDA12 Sampling time 1 to 599 s (selectable) Average count setting 1/2/4/8/16/32/64 Indicator Operation indicators: OUT1 (orange),
OUT2 (yellow), 7-segment main display (red), 7-segment sub-display (yellow) Power (green), wide range display (green), unit selection display (green)
Judgment outputs OUT1/ OUT2(*1)
Reset input *1 ON: Short-circuited with 0 V terminal or
Functions Measured value display, setting value
Section 4 APPENDICES
Communication with Air Clean Unit
Power supply voltage 24 VDC±10% Ripple (p-p) 10% max. 24 VDC±10% Ripple (p-p) 10% max.
Current consumption 300 mA max. Ambient temperature Operating: 0 to 40°C, Storage: -15 to +50°C (with no icing or condensation) Ambient humidity Operating and storage: 35 to 85% (with no condensation) Insulation resistance 20 MΩ at 500 VDC Dielectric strength 1,000 VAC, 50/60 Hz for 1 min Vibration resistance 10 to 150 Hz, 0.7-mm double amplitude 80 min each in X, Y and Z directions Shock resistance 300 m/s Connection method Cable
Materials Case: PBT (polybutylene terephthalate), Cover: polycarbonate Weight (packed state) Approx. 180 g (approx. 350 g) Accessories Instruction sheet
((*1) Judgment output OUT2 and reset input are switched by the DIP switch on the rear of the Amplifier Unit.
NPN open-collector outputs, 30 VDC 30mA max., Residual voltage: 1.2 V max.
1.5 V or less
OFF:Open
display, unit selection, scaling, peak hold, hysteresis setting, threshold level selection, wide range display, key lock, ECO mode, display reverse, display digit change, initial reset
- Unique communication specification
2
3 times each in six directions (up/down, left/right, forward/backward)
(standard cable length: 2 m)
7-segment main display (red), 7-segment sub-display (yellow), Power (green), wide range display (green), unit selection display (green)
-
-
Measured value display, communication status display, unit selection, scaling, Air Clean Unit automatic control, Air Clean Unit air level change, wide range display, key lock, ECO mode, display reverse, display digit change, initial reset
(RJ-45 connector and straight wiring LAN cable)
(supplied by Air Clean Unit)
Connector cable (standard cable length: 2 m)
60
ZN
System Manu al
Page 71
■ I/O Circuit Diagram
C
{
n
ue
y
W
e
(1) 24 VDC (2) GND (0V)
(3) Warning judgment output
(4) Caution judgment output (5) Reset input
NPN type (ZN-PDA11)
Brown
Section 4
Specifications and Dimensions
24 VDC
I/O switch
Caution judgment output
White
Reset input
Warning judgment output
Gray
Load
Load
24 VD
Internal circuit
GND (0V)
Blue
■ External I/O
Brow
Bl
Gra
hit
• Wire the cable correctly. Otherwise, the Amplifier Unit might be damaged.
• The function of the white lead can be selected by the switch on the rear of the Amplifier Unit.
(1)This is the power terminal. Connect the 24 VDC power supply to this terminal. (2)This is the 0 V power s upply term inal. On an NP N type Am plifier Uni t, this termi nal
becomes the common terminal for inputs/outputs other than the linear output.
(3)This output turns ON when "measured value ≥ warning threshold".
Operation is the same as lighting of the OUT1 indicator.
(4)This output turns ON when "measured value ≥ caution threshold".
Operation is the same as lighting of the OUT2 indicator.
(5) This input is for resetting each of the outputs. When this input is ON, internal
calculations are stopped, and judgment outputs are fo rcibly tur ned OFF. This input can also be used to clear the peak hold value.
Section 4 APPENDICES
System Manu al
ZN
61
Page 72
Section 4
6
57
54.9
5
36.7
9
(Unit: mm)
Specifications and Dimensions
• Calculating Unit ZX-CAL2
24.
15.1
12
8
2
.4
Section 4 APPENDICES
Item ZX-CAL2 Available Amplifier Unit ZN-PD series, ZX series, ZJ-SD series Current consumption 12 mA or less (supplied from the Amplifier Unit) Ambient temperature Operating: 0 to 50°C, Storage: -15 to +60°C (with no icing or condensation) Ambient humidity Operating and storage: 35 to 85% (with no condensation) Connection method Connector Dielectric strength 1,000 VAC, 50/60 Hz for 1 min Insulation resistance 100 MΩ at 500 VDC Vibration resistance 10 to 150 Hz, 0.7-mm double amplitude 80 min each in X, Y and Z directions Shock resistance 300 m/s Materials Display: Acrylic, Case: ABS resin Weight (packed state) Approx. 50 g
2
3 times each in six directions (up/down, left/right, forward/backward)
ZN
System Manu al
62
Page 73
Interface Unit for Clean Monitoring System
(Unit: mm)
(Unit: mm)
ZN-SF11
Section 4
Specifications and Dimensions
ZN-SF12
Sensor communications indicator (busy)
Sensor communications indicator (communications error)
Power indicator
30
15
Round vinyl insulated cable
13.2
5.2 mm dia. standard 300 mm
(33.1)
Connector
(46)
(336)
Power indicator
4.2 3
11. 7
Connector
External terminal communications indicator (busy)
External terminal communications indicator (communications error)
64.3
36.813
29
2.2
Status indicator
4.2
31.5
4.3
3
11. 7
5
6.55
Modular jack
Section 4 APPENDICES
Operation indicator
30
(336)
(46)
15
13.2
Round vinyl insulated cable
5.2 mm dia. standard 300 mm
(33.1)
Connector
3
29
11.7
Main display indicator
Sub-display indicator
36.813
2.2
4.3
4.264.34.2
21.46
6.6
31.5
15.8
Round vinyl insulated cable 5.1 mm dia., 10-wire (conductor cross-sectional area: 0.08 mm insulator diameter: 0.7 mm) standard 2 m
11.7
3
5
6.55
2
/
ZN
System Manu al
63
Page 74
Section 4
Connect the ZN-SF11/SF12 and the personal computer using a 9-pin D-sub cross cable (female-female).
Personal computer side (PC/AT compatible)ZN-SF11/SF12 side
* Pin Nos. may vary with the type and
model of the external device to be connected. For details, refer to the instruction manual of your programmable controller or personal computer.
Specifications and Dimensions
■ Connector Pin Arrangement and Connection Example with Personal Computer
12 3 45
67 89
Pin No.Name
1 N.C.
Section 4 APPENDICES
2RD
3SD
4 N.C.
5SG
6 N.C.
7 N.C.
8 N.C.
9 N.C.
12 3 45
67 89
Pin No.Name
1CD
2RD
3SD
4ER
5SG
6DR
7RS
8CS
9CI
Connector hood
FG
64
ZN
System Manu al
Page 75
Section 4
Specifications and Dimensions
Clean Monitoring System
Item ZN-SFW11 ZN-SFW12 Power supply voltage Supplied from ZN-PDA Current consumption 45 mA with 24 VDC without Amplifier Unit Available Sensor Amplifier ZX series, ZJ-SD series, ZN-PD series Available Sensor Amplifier
software version
Available number of connected Sensor Amplifiers
Indicator Power : green
Functions - Air Clean Unit automatic control
Communication
Ambient temperature Operating: 0 to 40°C, Storage: -15 to +50°C (with no icing or condensation) Ambient humidity Operating and storage: 35 to 85% (with no condensation) Insulation resistance 20 MΩ at 500 VDC Dielectric strength 1,000 VAC, 50/60 Hz for 1 min Vibration resistance 10 to 150 Hz, 0.7-mm double amplitude 80 min each in X, Y and Z directions Shock resistance 300 m/s Connection method - Connector cable
Materials Case: PBT (polybutylene terephthalate), Cover: polycarbonate Weight (packed state) Approx. 100 g (approx. 480 g) Approx. 200 g (approx. 550 g) Accessories CD-ROM (Realtime Clean Air Monitor), Instruction sheet, two clamps
Port RS-232C (9-pin D-sub connector) Protocol CompoWay/F Baud rate 38400 bps Data configuration Data bits: 8, Parity: none, Start bits: 1, Stop bits: 1, Flow control: none For external
device 2
ZX-LDA__-N V1,000 or higher ZX-EDA__ V1,300 or higher ZX-TDA__ V1,100 or higher ZX-SDA__ V1,000 or higher ZX-PDA__ V1,000 or higher
10 max. (for ZN-PDA)
Power (POWER: green) Sensor communications busy: green Sensor communications error: red Serial communications: green Serial communications error: red
- Unique communication specification
2
3 times each in six directions (up/down, left/right, forward/backward)
Serial communications (STA1: green)
Not Clean (OPE1: orange)
Clean (OPE2: green)
(multiple unit system control)
Air Clean Unit air level change
(RJ-45 connector and straight wiring
LAN cable)
(standard cable length: 2 m)
Section 4 APPENDICES
System Manu al
ZN
65
Page 76
Section 4 List of Products
List of Products
■ Air Clean Unit
• Main unit
Type Model Remarks 250 mm Square ZN-A2502 250 mm Square ZN-A2502D Without AC adaptor 410 mm Square ZN-A4105 410 mm Square ZN-A4105D Without AC adaptor
When connecting multiple Air Clean Units to build a system, use a commercially available LAN cable (straight type: Category 5E or higher).
Section 4 APPENDICES
• Accessories
Type Model Remarks Replacement filter ZN9-AHP25 1 (for 250 mm Square filter)
ZN9-AHP41 1 (for 410 mm Square filter)
Replacement pre-filter ZN9-APF25 2 (for 250 mm Square filter)
ZN9-APF41 1 (for 410 mm Square filter)
■ Ionizer Unit
• Main Unit
Type Model Remarks 250 mm Square ZN-J25A When used together with the Air Clean Unit (ZN-A2502) as
a set
410 mm Square ZN-J41A When used together with the Air Clean Unit (ZN-A4105) as
a set 250 mm Square ZN-J25 410 mm Square ZN-J41
• Accessories
Type Model Remarks Replacement needles ZN9-JH04 4 (with needle holder) Single-ended connector
cable 5 m Single-ended connector
cable 10 m
ZN-JC05 1 (for DC power supply, I/O cable connection)
ZN-JC10 1 (for DC power supply, I/O cable connection)
66
ZN
System Manu al
Page 77
■ Air Particle Sensor
• Main Unit
Type Model Remarks Sensor ZN-PD03 Amplifier Units ZN-PDA11 Cable type 2 m
ZN-PDA12 Connector type 2 m
• Accessories
Type Model Remarks Calculating Unit ZX-CAL2 Double-ended connector
cable 1 m Double-ended connector
cable 4 m Double-ended connector
cable 8 m (Sensor)
Replacement filter set Cleaning filter ZN9-PC1 1 Sensor mounting bracket ZN9-PB1 1
ZX-XC1A 1 (for extension between Sensor and Amplifier Unit)
ZX-XC4A 1 (for extension between Sensor and Amplifier Unit)
ZX-XC8A 1 (for extension between Sensor and Amplifier Unit)
ZN9-PF1 1
Section 4
List of Products
Section 4 APPENDICES
■ Clean Monitoring System
Type Model Remarks Interface Unit (ZN-SF11)/
Realtime Clean Air Monitor set
Interface Unit (ZN-SF12)/ Realtime Clean Air Monitor set
ZN-SFW11 Personal computer to RS-232C connection only
ZN-SFW12 Personal computer to RS-232C connection, for Air Clean
Unit feedback connection
System Manu al
ZN
67
Page 78
Section 4 List of Products
MEMO
Section 4 APPENDICES
68
ZN
System Manu al
Page 79
INDEX
Section 4
INDEX
A
Accessories
List of Products 66
Air Clean Unit 3
Dimensions 53 Error Messages 51 Indicator 48 List of Products 66 Maintenance 48 Specifications 54
Air Particle Sensor 3
Dimensions 57, 59 Error Messages 52 Flow of processing 41 List of Products 67 Maintenance 48
Specifications 58, 60 Automatic adjustment of air volume level 4 Automatically Adjusting the Air Volume Level 18
C
Calculating Unit
Dimensions 62
Specifications 62 Clean Monitoring System 2, 15
List of Products 67
Specifications 65 Cleaning notice indicator 49 Cleaning warning indicator 49 Cleanliness 45 Cleanliness Class of Multip le Processes 5 Cleanliness of Multiple Processes
Constant feedback 23, 39
D
Dimensions
Air Clean Unit 53
Air Particle Sensor 57, 59
Calculating Unit 62
Interface Unit 63
Ionizer Unit 55 Direct Clean Sensing System
System Configuration 7, 36 Dust Removal and Static
31
Neutralization 6, 10
E
Electrostatic Sensor 10 Error Messages 51 Exclusive Monitoring Software
Exiting 17 Installing 16 Operating Environment 15 Starting Up 17 Uninstalling 16
F
Feedback 4, 8 , 9, 36 Flow of data
Direct Clean Sensing System 40
Multi-clean Sensing Sys tem 4 2 Flow of Operations for Upgrading the System 14
I
Interface Unit
Connector Pin Arrangement 64
Dimensions 63
Error Messages 52
Example with Personal Computer
Exclusive Monitoring Software 17
Flow of processing 43 Ion Balance Sensor 6 Ionizer Unit 3
Dimensions 55
Error Messages 51
List of Products 66
Maintenance 49
Specifications 56
L
Logging 4, 7, 9, 25
M
Main Applications 3 Monitoring
Amount of Particles 4, 25
Charged Amount 6 Multi-Clean Sensing System
How Feedback Control Works 42
System Configuration 11, 37
Section 4 APPENDICES
64
System Manu al
ZN
69
Page 80
Section 4 INDEX
P
Principle of "Particle Count" 44
R
Rapid feedback 20, 38
S
Scattered light method 44 Setting the feedback conditions
20, 32
Specifications 53
Air Clean Unit 54 Air Particle Sensor 58, 60 Calculating Unit 62 Clean Monitoring System 65
Section 4 APPENDICES
Ionizer Unit 56
Static Electricity Sensor 6
T
Troubleshooting 50
70
ZN
System Manu al
Page 81
MEMO
Section 4
INDEX
Section 4 APPENDICES
System Manu al
ZN
71
Page 82
Section 4
Revision History
Revision History
A manual revision cod e appears as a s uffix to the catalog number at the bottom of the fron t and back covers of this manual.
Cat. No.
Revision code Date Revised contents
01 June 2007 Original production
Z267-E1-01
Revision code
Section 4 APPENDICES
72
ZN
System Manu al
Page 83
OMRON Corporation Industrial Automation Company
Sensing Devices Division H.Q. Application Sensors Division
Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 Japan Tel: (81) 75-344-7068/Fax: (81) 75-344-7107
Regional Headquarters
OMRON EUROPE B.V.
Sensor Business Unit Carl-Benz-Str. 4, D-71154 Nufringen, Germany Tel: (49) 7032-811-0/Fax: (49) 7032-811-199
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg, IL 60173-5302 U.S.A. Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2), Alexandra Technopark, Singapore 119967 Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower, 200 Yin Cheng Zhong Road, Pu Dong New Area, Shanghai, 200120, China Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
Cat. No. Z267-E1-01
©OMRON Corporation 2007 All Rights Reserved.
Note: Specifications subject to change without notice.
Printed in Japan.
0707- 0.5C (0707) (M)
Loading...