Thank you for purchasing the ZFX-C.
This manual provides information regarding functions, performance and operating methods that
are required for using the ZFX-C.
When using the ZFX-C, be sure to observe the following:
• The ZFX-C must be operated by personnel knowledgeable in electrical engineering.
• To ensure correct use, please read this manual thoroughly to deepen your understanding of the
product.
• Please keep this manual in a safe place so that it can be referred to whenever necessary.
Manuals Provided with this Product
Smart Sensor
Vision Sensor with built-in LCD monitor
ZFX-C10
User's Manual
Smart Sensor
Vision Sensor with built-in LCD monitor
ZFX-C10
Serial Communication
Command Reference
Cat. No. Z251-E1-01
Cat. No. Z252-E1-01
User's Manual
This manual describes basic operations, such as
installation and connections, and information on settings
and specifications to ensure safe and correct use of this
product.
Serial Communication Command
Reference (this document)
This manual provides reference information for when this
product performs communications with an external
device, such as a PC or a programmable controller, via
the serial interface.
You can use the USB port or RS-232C/422 connector of the Controller to perform serial communication with
external devices such as a personal computer or programmable controller.
Serial communication functions in the RUN mode. Communication cannot be performed in the ADJ or MENU
modes.
<USB>
This interface allows Full speed (12 Mbps) communications compliant with USB2.0 with a PC equipped with
the same USB interface.
Synchronization method Start-stop
Transmission codeASCII (Binary format can be selected only when outputting measurement values set at
[Setup] - [Support] - [Calculation] - [Data].)
Communication speedUSB2.0-compliant
Data length-
Parity-
Stop bit-
DelimiterCR, LF, CR+LF
Transmission protocolNormal (Note, however, that XMODEM protocol is used when sending image data, system
data and other data.)
<RS-232C/422>
This interface allows data communications compliant with the EIA RS-232C/422 standards up to a maximum
speed of 115200 bps.
Synchronization method Start-stop
Transmission codeASCII (Binary format can be selected only when outputting measurement values set at
[Setup] - [Support] - [Calculation] - [Data].)
Communication speed9600, 19200, 38400, 57600, 115200
Data length7 bits, 8 bits
ParityNone, even, odd
Stop bit1 bit, 2 bits
DelimiterCR, LF, CR+LF
Transmission protocolNormal (Note, however, that XMODEM protocol is used when sending image data, system
data and other data.)
For details on how to set the communication specifications, refer to the User's Manual.
<Ethernet>
Communication protocol TCP/IP
Transmission modePeer to Peer
2
Communication Interface Specifications
ZFX-C Serial Communication Command Reference
Connection
Ferrite cores
Connecting a PC
<USB>
Use a USB cable (ZFX-XUSB) to connect the Controller to the
PC.
Important
• When connecting the PC, refer to the Instruction Manual for the PC.
• Attach the ferrite cores supplied to both ends of the USB cable.
Note
Installation of the USB driver is necessary only when connecting an external device to the USB interface for the first
time.
For the USB driver, please contact your OMRON representative.
<Ethernet>
Use a commercially available LAN cable to connect the Controller
to the PC.
There are two ways of making the LAN connection to the PC,
directly to the PC or via a hub.
Important
The following communications are not possible:
• Communications with the Controller from outside the LAN
• Communications between the Controller and two or more PCs
• Communications between Controllers
• Communications between the Controller and the PLC
ZFX-C Serial Communication Command Reference
Connection
3
• 1:1 Connection
If communications software for a TELNET
connection is activated on the PC to access the
Controller, the Controller will automatically switch to
the Ethernet connection.
The parallel interface's ENABLE signal will be OFF during measurement.
To end the Ethernet connection, input the
EXIT command.
Input command.
Execute
measurement.
Output the
processing result.
Receive the
measurement result.
MEASURE
IP address
192.168.250.010
Start the TELNET communications software on the PC, and
specify individual IP addresses to access each Controller.
The method for inputting commands is the same as for a 1:1
connection.
HUB
IP address
192.168.250.100
IP address
192.168.250.101
IP address
192.168.250.102
When connecting the Controller directory to the PC, use a 10BASE-T or 100BASE-TX cross cable (Category 5
or higher). Limit the cable length to 30 m.
Example: A measurement command is input and the result is acquired.
• 1:N Connection
When connecting two or more Controllers to one PC via a hub, use a 10BASE-T or 100BASE-TX straight cable
(Category 5 or higher). Also, limit the cable lengths between the PC and the hub, and the Controllers and the
hub to 30 m, respectively. Be sure to set unique IP addresses to each Controller. Do not set duplicate IP
addresses to Controllers.
Example:
4
Connection
ZFX-C Serial Communication Command Reference
Connecting a PLC
Use the exclusive RS-232C cable (ZFX-XPT2A) / RS-422 cable
(ZFX-XPT2B) to connect the Controller to a PLC.
Important
When connecting to a PLC, refer to the Instruction Manual for the
PLC.
ZFX-C Serial Communication Command Reference
Connection
5
About Communication Commands
Command dataDelimiter
Response data
Record
separator
Record
separator
Record
separator
KO
RE
When processing ends successfully
When processing fails
Command/Response Format
< Command >
< Response >
Command dataSpecifies the command and parameters in ASCII code.
Response dataStores the acquired data.
DelimiterThis control code indicates the end of the data.
Record separatorThis delimiter is appended to one session's worth of output data. (default delimiter: CR)
6
About Communication Commands
ZFX-C Serial Communication Command Reference
Configuration of Measurement Value Data
Field separator
Number of digits past the decimal point: max. 3
Decimal separator: 1 digit
Sign + number of digits of integer section: max. 8 digits
(Insert "0" for spaces.)
Record
separator
Measurement value of data 0Measurement value of data 1Measurement value of data 31
23456 . 789
C
R
01
04567 . 800
C
R
00
04567 . 800
C
R
-0
123456.789
4567.8
-4567.8
< Measurement value > < Data structure >
Example: Number of digits of integer section: 7, number of digits past the decimal point: 3,
decimal separator: period
The following explains the output format of measurement values.
To output measurement values by serial communication, the following items must be set.
Note
Output content
Set the output content as an expression.
Set the output content at [Setup] - [Support] - [Calculation] - [Data].
Output destination
Specify [RS-232C/422] or [USB] at [System] - [Output] - [Data output].
Output format
Set the output format at [System] - [Output] - [Serial output].
For detailed settings, refer to the User's Manual.
ASCII Format
Up to 32 results are output as a data structure of fixed length of up to 12 characters including the sign.
SignThe sign of the measurement value is stored. Plus: 0/Minus: -
Number of digits of integer section"0" is inserted in spaces in the integer section and digits past the decimal
Number of digits past the decimal point
Decimal separator
Field separator
Record separator
ZFX-C Serial Communication Command Reference
point.
When a value is greater than the preset number of digits, all digits other
than the sign digit become "9".
Output range: -9999999.999 to 09999999.999
About Communication Commands
7
Binary Format
4 bytes
Measurement value
of data 0 x 1000
Measurement value
of data 1 x 1000
Measurement value
of data 31 x 1000
4 bytes4 bytes
Example: Data 0 "256.324" and data 1 "-1.000"
Data 0: 256324
(256.324 x 1000)
Data 1: -1000
(-1.000 x 1000)
The value obtained by multiplying the measurement value by 1000 is output continuously as four bytes per
single data item. Minus values are output as 2's complement. Up to 32 results can be output.
The binary format differs from the ASCII format in that data separators, such as field separator or record
separator, do not exist.
Output range: -2147483.648 to 2147483.647
$00$44$03$FF$E9$FF $FC $18
Note
• A value obtained by multiplying by 1000 also is output as the judgment result (JG).
OK: 0
NG: -1000 (-1 x 1000)
• When the measurement value is less than -2147483.648, "-2147483.648" is output.
When the measurement value is greater than 2147483.647, "2147483.647" is output.
8
About Communication Commands
ZFX-C Serial Communication Command Reference
Available Commands
Bank Control Commands
Command nameDescriptionPage
BANK (or BK)This command acquires the current bank No.p.11
This command switches the bank to be used.p.11
BANKGROUP (or BG)This command acquires the current bank group No.p.12
This command switches the bank group to be used.p.12
Measurement Control/Measurement Value Acquisition Commands
Command nameDescriptionPage
MEASDATA (or MD)This command acquires the measurement result of the measurement item. p.13
MEASURE (or M)This command executes a single measurement.p.14
This command starts continuous measurement.p.15
This command ends continuous measurement.p.15
Setting Acquisition/Change Commands
Command nameDescriptionPage
DATE (or DT)This command acquires the date and time of the calendar timer incorporated
into the Controller.
This command changes the date and time of the calendar timer incorporated
into the Controller.
MODELSET (or MS)This command re-registers the model of the specified item. It does not reset
filters, etc.
PASSWORD (or PW)This command acquires the currently set password.p.17
It sets and changes the password character string.p.18
VERGET (or VR)This command acquires the version information of the Controller.p.18
p.16
p.16
p.17
Backup/Restore Commands
Command nameDescriptionPage
BGRLOAD (or GL)This command uploads bank group data to the Controller from an external
device.
This command uploads bank group data to the Controller from an SD card. p.19
BGRSAVE (or GS)This command backs up bank group data to an external device from the
Controller.
This command backs up bank group data to an SD card from the Controller. p.20
BNKLOAD (or BL)This command uploads bank data to the Controller from an external device. p.21
This command uploads bank data to the Controller from an SD card. p.21
BNKSAVE (or BS)This command backs up bank data to an external device from the Controller. p.22
This command backs up bank data to an SD card from the Controller. p.22
DATASAVE (or SV)This command saves the current settings to the Controller. p.23
IMGLOAD (or IL)This command uploads image data to the Controller from an external device. p.23
This command uploads image data to the Controller from an SD card. p.24
ZFX-C Serial Communication Command Reference
About Communication Commands
p.19
p.20
9
Command nameDescriptionPage
IMGSAVE (or IS)This command backs up image data to an external device from the Controller. p.25
This command backs up image data to an SD card from the Controller. p.26
SYSLOAD (or SL)This command uploads system data to the Controller from an external device. p.27
This command uploads system data to the Controller from an SD card. p.27
SYSSAVE (or SS)This command backs up system data to an external device from the Controller. p.28
This command backs up system data to an SD card from the Controller. p.28
Utility Commands
Command nameDescriptionPage
RESET (or RS)This command restarts the Controller. p.29
EXITThis command ends the TELNET connection for Ethernet communications and
disconnects the line.
p.29
10
About Communication Commands
ZFX-C Serial Communication Command Reference
Bank Control Commands
BANK
C
R
BK
C
R
or
C
R
ER
C
R
OK
C
R
When processing ends successfully
When processing fails
Bank No. (max. 2 digits)
BANK
C
R
BK
C
R
Bank No.
(max. 2 digits)
or
Bank No.
(max. 2 digits)
O K
C
R
E R
C
R
When processing ends successfully
When processing fails
Acquiring/Switching the Bank No. < BANK command >
Acquiring a bank No.
This command acquires the current bank No.
< Command format >
< Response format >
< Explanation of parameters >
Bank No.The acquired bank No. is returned. (0 to 31)
Switching to another bank
This command switches the bank to be used.
< Command format >
< Response format >
< Explanation of parameters >
Bank No.Specifies the bank No. after the bank is switched. (0 to 31)
ZFX-C Serial Communication Command Reference
About Communication Commands
11
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.