60/90/120/180/240/480-W Models
New Models with Indication
Monitor and Simple Functions
for Easy System
Commissioning
• New 90-W models with indication monitor that
conform to UL Class 2 Output standards.
• New models with screwless terminal blocks
and indication monitor.
• Status displayed on 3-digit, 7-segment display.
• Safety standards:
UL 508/60950-1,
CSA C22.2 No. 107.1/60950-1
EN 50178 (= VDE 0160)
EN 60950-1 (= VDE 0805 Teil 1)
• Input conditions: DC input is also possible from 80 to 370 VDC
(Not compliant with EC Directives and other safety sta nda rd s.)
15/30-W Models
Compact, Thin Power Supplies
That Mount Just About Anywhere
to Contribute to Control Panel
Downsizing
• Compact and thin: 22.5 × 85 × 96.5 mm (W × H × D).
• Three mounting directions
(standard, horizontal, facing horizontal).
• Mounting directly to the panel is possible.
• Safety standards:
UL 508/60950-1,
CSA C22.2 No.107.1/60950-1,
EN 50178 (= VDE 0160),
EN 60950-1 (= VDE 0805 Teil 1)
• Input conditions: DC input is also possible from 80 to 370 VDC
(Not compliant with EC Directives and other safety sta nda rd s.)
Features Common to All Models
• Mount to DIN Rail.
• Complies with SEMI F47-0706 (200-VAC input).
• RoHS-compliant.
Refer to Safety Precautions for All P ow er Supplies and Safety
!
Precautions on page 32.
1
S8VS
Model Number Structure
Model Number Legend
Note: Not all combinations are possible. Refer to List of Models in Ordering Information, below.
S8VS- @@@@@@@@-@
1234 5 6
1. Power Ratings
015: 15 W
030: 30 W
060: 60 W
090: 90 W
120: 120 W
180: 180 W
240: 240 W
480: 480 W
2. Output voltage
05: 5 V
12: 12 V
24: 24 V
3. Indication monitor
None: Without indication monitor (standard model)
A: With indication monitor (maintenance forecast monitor)
B: With indication monitor (total run time monitor)
BE:With indication monitor but without alarm output (total run
time monitor)
Note:
Estimates can be provided for coatings and other specifications that are not given in the datasheet. Ask your OMRON representative for details.
*1. The output capacity of the S8VS-01505 is 10 W.
*2. The output capacity of the S8VS-03005 is 20 W.
*3. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
100 to 240 VAC
(allowable range:
85 to 264 VAC or
80 to 370 VDC
*3)
Models with Indication Monitor (Maintenance Forecast Monitor)
Power ratingsInput voltage
60 W
90 W3.75 A
120 W5 A
180 W7.5 A
240 W10 A
480 W
*1. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
*2. In the Alarm output column, “sinking” indicates an emitter COM and “sourcing” indicates a collector COM.
100 to 240
VAC
(allowable
range: 85 to
264 VAC or 80
to 370 VDC
*1)
Models with Indication Monitor (Total Run Time Monitor)
Power ratingsInput voltage
60 W
90 W3.75 A
100 to 240
VAC
(allowable
120 W5 A
180 W7.5 A
240 W10 A
480 W
*1. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
*2. In the Alarm output column, “sinking” indicates an emitter COM and “sourcing” indicates a collector COM.
Note: Refer to pages 24 to 25 for the options that available.
Voltage *1100 to 240 VAC (allowable range: 85 to 264 VAC, 80 to 370 VDC *5)
Frequency *150/60 Hz (47 to 450 Hz)
Current
Input
Output
Additional
functions
Other
Power factor--Harmonic current regulationConforms to EN61000-3-2
Leakage current
Inrush current *2
Voltage adjustment range *3−10% to 15% (with V.ADJ)
Ripple noise voltage (at rated I/O)60 mV max.70 mV max.60 mV max.60 mV max.90 mV max.150 mV max.
Input variation influence0.5% max. (at 85- to 264-VAC input, 100% load)
Load variation influence
(rated input voltage)
Temperature variation influence0.05%/°C max.
Startup time
(at rated I/O) *2
Output hold time
(at rated I/O) *2
Overload protection *2The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Overvoltage protection *2Yes *4
Output voltage indication No
Output current indication No
Peak-hold current indication No
Maintenance forecast monitor indicationNo
Maintenance forecast monitor output No
Total run time monitor indicationNo
Total run time monitor outputNo
Undervoltage alarm indication Yes (color: red)
Undervoltage alarm outputNo
Parallel operationNo
Series operation
Operating ambient temperatureRefer to the derating curve in Engineering Data. (with no icing or condensation)
Storage temperature−25 to 65°C
Operating ambient humidity25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
Insulation resistance100 MΩ min. (between all outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Shock resistance150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicatorYes (color: green)
EMI
EMSConforms to EN61204-3 high severity levels
Approved standards
SEMIF47-0706 (With 200-VAC input)
Weight160 g max.180 g max.
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*2. For a cold start at 25°C. Refer to Engineering Data on page 18 for details.
*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range. When adjusting
the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
*4. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
*5. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
With 100-VAC input 74% typical79% typical83% typical74% typical81% typical85% typical
With 200-VAC input 73% typical78% typical80% typical74% typical80% typical86% typical
With 100-VAC input 0.45 A max., 0.34 A typical0.9 A max., 0.66 A typical
With 200-VAC input 0.25 A max., 0.22 A typical0.6 A max., 0.4 A typical
With 100-VAC input 0.5 mA max.
With 200-VAC input 1.0 mA max.
With 100-VAC input 17.5 A max., 14 A typical
With 200-VAC input 35 A max., 28 A typical
With 100-VAC input 580 ms typical530 ms typical600 ms typical500 ms typical560 ms typical560 ms typical
With 200-VAC input 340 ms typical360 ms typical400 ms typical360 ms typical380 ms typical400 ms typical
With 100-VAC input 39 ms typical27 ms typical28 ms typical31 ms typical22 ms typical31 ms typical
With 200-VAC input 187 ms typical134 ms typical134 ms typical174 ms typical123 ms typical140 ms typical
Models with 24-V output: Possible for up to 2 Power Supplies (with external diode)
Models with 5- or 12-V output: Not possible
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detect ion current: 20 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA)
Conducted
Emissions
Radiated Emissions Conforms to EN61204-3 EN55011 Class B
Conforms to EN61204-3 EN55011 Class B and based on FCC Class A
UL Listed: UL508 (Listing, Class2 Output: Per 1310)
UL UR: UL60950-1 (Recognition)
cUL: CSA C22.2 No.107.1 (Class2 Output: Per CSA C22.2 No.223)
cUR: CSA C22.2 No.60950-1
EN/VDE: EN50178 (=VDE0160), EN60950-1 (=VDE0805 Teil1)
4
S8VS
Power ratings60 W90 W
ItemTypeStandard
Efficiency
Voltage *1100 to 240 VAC (allowable range: 85 to 264 VAC or 80 to 370 VDC *11)
Frequency *150/60 Hz (47 to 450 Hz)
Current
Input
Output
Additional
functions
Other
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in
*2. For a cold start at 25°C. Refer to Engineering Data on page 18 for details.
*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range (by more than +10% for 240-W models w ith indi cation m onitor) .
*4. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
*5. Displayed on 7-segment LED. (character height: 8 mm)
*6. Resolution of output voltage indication: 0.1 V, Precision of output voltage indication: ±2% (percentage of output voltage value, ±1 digit)
*7. Resolution of output current indication: 0.1 A; Precision of output current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage)
*8. Resolution of peak-hold current indication: 0.1 A; Precision of peak-hold current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage);
*9. A Type and B Type: Sinking, AP Type and BP Type: Sou r cing, BE Type: No alarm output.
*10. S8VS-06024A, S8VS-09024A/AP, S8VS-12024A/AP, S8VS-18024A/AP, and S8VS-24024A/AP only
*11. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Power factor--Harmonic current regulationConforms to EN61000-3-2
Leakage current
Inrush current *2
Voltage adjustment range *3−10% to 15% (with V. ADJ) (The voltage cannot be adjusted for the S8VS-09024@@@S-@.)
Maintenance forecast monitor outputNo
Total run time monitor indication *5NoYes (selectable)NoYes (selectable)
Total run time monitor output *5No
Undervoltage alarm indication *5NoYes (selectable)NoYes (selectable)
Undervoltage alarm output terminalsNo
Parallel operationNo
Series operationYes for up to 2 Power Supplies (with external diode)
Operating ambient temperatureRefer to the derating curve in . (with no icing or condensation)
Storage temperature−25 to 65°C
Operating ambient humidity25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
Insulation resistance100 MΩ min. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance
Shock resistance150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicatorYes (color: green)
EMI
EMSConforms to EN61204-3 high severity levels
Approved standards *11
SEMI *11F47-0706 (With 200-VAC input)
Weight330 g max.490 g max.
ignition or burning.
When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
Signal width required for peak-hold current: 20 ms
With 100-VAC input 84% typical83% typical8 3% typical83% typical
With 200-VAC input 83% typical85% typical8 4% typical85% typical
With 100-VAC input
With 200-VAC input
With 100-VAC input 0.5 mA max.
With 200-VAC input 1.0 mA max.
With 100-VAC input 17.5 A max., 14 A typical
With 200-VAC input 35 A max., 28 A typical
With 100-VAC input 620 ms typical460 ms typical460 ms typical660 ms typical
With 200-VAC input 400 ms typical290 ms typical300 ms typical420 ms typical
With 100-VAC input 34 ms typical33 ms typical28 ms typical28 ms typical
With 200-VAC input 158 ms typical154 ms typical132 ms typical136 ms typical
Conducted
Emissions
Radiated
Emissions
1.7 A max., 1.3 A typical
1.0 A max., 0.68 A typical
1.5% max. (with rated input, 0 to 100% load)
105% to 160% of rated load current (101% to 110% of rated load current for the S8VS-09024
NoYes (selectable)NoNoYes (selectable)No
3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and PE terminals; detection current for standard models: 30 mA, detection
current for models with indication monitor: 20mA)
500 VAC for 1 min. (between all ou tputs and alarm outputs; detection current: 20 mA)
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z d irections
10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Z directions
Models with indication monitor: Conforms to EN61204-3 EN55011 Class A and based on FCC Class A, Conforms to EN61204-3
EN55011 Class B *11
Standard models: Conforms to EN61204-3 EN55011 Group 1 Class B and based on FCC Class A
Models with indication monitor: Conforms to EN61204-3 EN55011 Class A, Conforms to EN61204-3 EN55011 Class B *11
Standard models: Conforms to EN61204-3 EN55011 Group 1 Class B
UL: UL 508 (Listing; Class 2 Output: Per UL1310), UL UR: UL
60950-1 (Recognition),
cUL: CSA C22.2 No.107.1 (Class 2 Output: Per CSA C22.2 No.
223),
cUR: CSA C22.2 No.60950-1,
EN/VDE: EN 50178 (= VDE 0160), EN 60950-1
(= VDE 0805 Teil 1)
KOSHA S Mark *10
Maintenance
forecast monitor
1.7 A max., 1.3 A typical
1.0 A max., 0.78 A typical
Total run time
monitor
Standard
2.3 A max., 1.9 A typical
1.4 A max., 1.0 A typical
@@@S-@
UL: UL 508 (Listing)
UL Listed (S8VS-09024@@@S-@ only.): UL 508 (Listing, Class 2
Output: Per UL1310),
UL UR: UL 60950-1 (Recognition),
cUL: CSA C22.2 No.107.1,
cUL (S8VS-09024-@@@S-@ only): CSA C22.2 N o.107.1 (Cla ss 2
Output: Per CSA C22.2 No. 223),
cUR: CSA C22.2 No.60950-1,
EN/VDE: EN 50178 (= VDE 0160),
EN 60950-1 (= VDE 0805 Teil 1)
KOSHA S Mark *10
Maintenance
forecast monitor
2.3 A max., 1.9 A typical
1.4 A max., 1.2 A typical
), inverted L voltage drop, intermittent, automatic reset
Yes (transistor output),
30 VDC max., 50 mA max. *9
Yes (transistor output), 30 VDC max., 50 mA max. *9
Total run time
monitor
No
Yes (transistor output),
30 VDC max., 50 mA max. *9
5
S8VS
Power ratings120 W180 W
ItemTypeStandard
Efficiency
Voltage *1100 t o 240 VAC (allowable range: 85 to 264 VAC or 80 to 370 VDC *11)
Frequency *150/60 Hz (47 to 63 Hz)
Current
Input
Output
Additional
functions
Other
Power factor0.9 min.
Harmonic current regulationConforms to EN61000-3-2
Leakage current
Inrush current *2
Voltage adjustment range *3−10% to 15% (with V.ADJ)
Ripple noise voltage (at rated I/O)60 mV max.130 mV max.50 mV max.180 mV max.
Input variation influence0.5% max. (at 85- to 264-VAC input, 100% load)
Load variation influence
(rated input voltage)
Temperature variation influence0.05%/°C max.
Startup time
(at rated I/O) *2
Output hold time
(at rated I/O) *2
Overload protection *2105% to 160% of rated load current, inverted L voltage drop, automatic reset
Overvoltage protection *2, *4Yes
Output voltage indication *5NoYes (selectable) *6NoYes (selectable) *6
Output current indication *5NoYes (selectable) *7NoYes (selectable) *7
Peak-hold current indication *5NoYes (selectable) *8NoYes (selectable) *8
Maintenance forecast monitor indication *5 NoYes (selectable)NoNoYes (selectable)No
Maintenance forecast monitor output No
Total run time monitor indication *5NoYes (selectable)NoYes (selectable)
Series operationYes for up to 2 Power Supplies (with external diode)
Operating ambient temperatureRefer to the derating curve in . (with no icing or condensation)
Storage temperature−25 to 65°C
Operating ambient humidity25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
Insulation resistance100 MΩ min. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance
Shock resistance150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicatorYes (color: green)
EMI
EMSConforms to EN61204-3 high severity levels
Approved standards *11
SEMI *11F47-0706 (200-VAC input)
Weight550 g max.850 g max.
Note: Refer to page 5 for notes 1 to 11.
With 100-VAC input 84% typical8 3% typi cal85% typical85% typical
With 200-VAC input 87% typical8 5% typi cal88% typical87% typical
With 100-VAC input 1.9 A max., 1.5 A typical2.9 A max., 2.2 A typical
With 200-VAC input
With 100-VAC input 0.5 mA max.
With 200-VAC input 1.0 mA max.
With 100-VAC input 17.5 A max., 14 A typical
With 200-VAC input 35 A max., 28 A typical
With 100-VAC input 550 ms typical650 ms typical570 ms typical580 ms typical
With 200-VAC input 400 ms typical520 ms typical470 ms typical490 ms typical
With 100-VAC input 52 ms typical56 ms typical58 ms typical70 ms typical
With 200-VAC input 54 ms typical56 ms typical62 ms typical70 ms typical
Conducted
Emissions
Radiated Emissions
1.1 A max.,
0.71 A typical
1.5% max. (with rated input, 0 to 100% load )
3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ al arm outputs and PE terminals; de tection current f or standard model s: 30mA, detection
current for models with indication monitor: 20 mA
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA)
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Z directions
Models with indication monitor: Confo rms to EN61 204-3 E N550 11 Cla ss A and b ased on FC C Class A , Con forms to E N612 04-3
EN55011 Class B *11
Standard models: Conforms to EN61204-3 EN55011 Group 1 Clas s B and based on FCC Class A
Models with indication monito r: Conforms to EN61204-3 EN55011 Class A, Conforms to EN61204- 3 EN55011 Class B *11
Standard models: Conforms to EN61204-3 EN55011 Group 1 Class B
UL Listed: UL 508 (Listing),
UL UR: UL 60950-1 (Recognition),
cUL: CSA C22.2 No. 107.1,
cUR: CSA C22.2 No. 60950-1,
EN/VDE: EN 50178 (= VDE 0160), EN 60950-1 (= VDE 0805 Teil 1)
KOSHA S Mark *10
Maintenance
forecast monitor
1.1 A max., 0.72 A typical1.6 A max., 1.1 A typical
Yes (transistor
output), 30 VDC
max., 50 mA max.
*9
Yes (transistor output), 30 VDC max.,
50 mA max. *9
Total run time
monitor
NoNo
Yes (transistor
output), 30 VDC
max., 50 mA max.
*9
Standard
No
No
Maintenance
forecast monitor
Yes (transistor
output), 30 VDC
max., 50 mA max.
*9
Yes (transistor output), 30 VDC max.,
50 mA max. *9
Total run time
monitor
No
Yes (transistor
output), 30 VDC
max., 50 mA max.
*9
6
Power ratings240 W480 W
ItemTypeStandard
Efficiency
Input
Output
Additional
functions
Other
Voltage *1
Frequency *150/60 Hz (47 to 63 Hz)
Current
Power factor0.9 min.0.95 min.
Harmonic current regulationConforms to EN61000-3-2
Leakage current
Inrush current *2
Voltage adjustment range *3−10% to 15% (with V.ADJ)−10% to 15% (with V.ADJ)
Ripple noise voltage (at rated I/O)140 mV max.160 mV max.310 mV max.
Input variation influence0.5% max. (at 85- to 264-VAC input, 100% load)
Load variation influence
(rated input voltage)
Temperature variation influence0.05%/°C max.
Startup time
(at rated I/O) *2
Output hold time
(at rated I/O) *2
Overload protection *2105% to 160% of rated load current, inverted L voltage drop, automatic reset
Overvoltage protection *2, *4Yes
Output voltage indication *5NoYes (selectable) *6NoYes (selectable) *6
Output current indication *5NoYes (selectable) *7NoYes (selectable) *7
Peak-hold current indication *5NoYes (selectable) *8NoYes (selectable) *8
Maintenance forecast monitor indication *5 NoYes (selectable)NoYes (selectable)No
Maintenance forecast monitor output No
Total run time monitor indication *5NoYes (selectable)NoYes (selectable)
Series operationYes for up to 2 Power Supplies (with external diode)
Operating ambient temperatureRefer to the derating curve in . (with no icing or condensation)
Storage temperature−25 to 65°C
Operating ambient humidity25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
Insulation resistance100 MΩ min. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance
Shock resistance150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicatorYes (color: green)
EMI
EMSConforms to EN61204-3 high severity levels
Approved standards *11
SEMI *11F47-0706 (200-VAC input)
Weight1,150 g max.1,700 g max.
With 100-VAC input 85% typical85% typical
With 200-VAC input 88% typical89% typical
100 to 240 VAC (allowable range: 85 to 264 VAC or 80 to 370 VDC *11)
With 100-VAC input 3.8 A max., 2.9 A typical7.4 A max., 5.8 A typical
With 200-VAC input 2.0 A max., 1.5 A typical3.9 A max., 2.8 A typical
With 100-VAC input 0.5 mA max.
With 200-VAC input 1.0 mA max.
With 100-VAC input 17.5 A max., 14 A typical
With 200-VAC input 35 A max., 28 A typical
1.5% max. (with rated input, 0 to 100% load )
With 100-VAC input 540 ms typical510 ms typical460 ms typical
With 200-VAC input 230 ms typical510 ms typical340 ms typical
With 100-VAC input 64 ms typical46 ms typical37 ms typical
With 200-VAC input 64 ms typical46 ms typical41 ms typical
3.0 kVAC for 1 min. (between all inputs and outputs/alarm outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and PE terminals; detection current for standard 240-W and 480-W
models: 30 mA, detection current for 240-W models with indication monitor: 20 mA)
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA)
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Z directions: 240 W
10 to 150 Hz, 0.35-mm single amplitude (3 G max.) for 80 min each in X, Y, and Z directions: 480 W
Models with indication monito r: Conforms to EN61204-3
Conducted
Emissions
Radiated Emissions
EN55011 Class A and based on FCC Class A, Conforms to
EN61204-3 EN55011 Class B *11
Standard models: Conforms to EN61204-3 EN55011 Group 1
Class B and based on FCC Class A
Models with indication monito r: Conforms to EN61204-3
EN55011 Class A, Conforms to EN61204-3 EN55011 Class B
*11
Standard models: Conforms to EN61204-3 EN55011 Group 1
Class B
UL Listed: UL 508 (Listing),
UL UR: UL 60950-1 (Recognition),
cUL: CSA C22.2 No.107.1,
cUR: CSA C22.2 No. 60950-1,
EN/VDE: EN 50178 (=VDE 0160), EN 60950-1 (=VDE 0805 Teil 1)
KOSHA S Mark *10
Note: Refer to page 5 for notes 1 to 11.
Maintenance
forecast monitor
Yes (transistor output),
30 VDC max., 50 mA
max. *9
Yes (transistor output), 30 VDC max.,
50 mA max. *9
Total run time
monitor
No
Yes (transistor output),
30 VDC max., 50 mA
max. *9
S8VS
Standard
100 to 240 VAC (allowable range: 85 to 264 VAC)
No
No
Conforms to EN61204-3 EN55011 Class A and based on FCC
Class A
Conforms to EN61204-3 EN55011 Class B *11
Conforms to EN61204-3 EN55011 Class A
Conforms to EN61204-3 EN55011 Class B *11
Maintenance
forecast monitor
Yes (transistor
output), 30 VDC
max., 50 mA max.
Yes (transistor output), 30 VDC max.,
50 mA max. *9
Total run time
monitor
No
Yes (transistor output),
30 VDC max., 50 mA
max. *9