Series operationYes (For up to two Power Supplies, external diodes are required.)
Parallel operationYes (Refer to Engineering Data) (For up to two Power Supplies)
Output indicatorYes (LED: Green), lighting from 80% to 90% or more of rated voltage
Withstand voltage
Insulation resistance100 MΩ min. (between all output terminals and all input terminals / PE terminal) at 500 VDC
Ambient operating temperature
Storage temperature–40 to 85°C (with no condensation or icing)
Ambient operating humidity0% to 95% (Storage humidity: 0% to 95%)
Vibration resistance10 to 55 Hz, 0.375-mm half amplitude for 2 h each in X, Y, and Z directions
Shock resistance150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
MTBF135,000 hrs min.
Life expectancy *1010 years min.
Weight700 g max.1,000 g max.
Cooling fanNo
Degree of protectionIP20 by EN / IEC 60529
Harmonic current emissionsConforms to EN 61000-3-2
EMI
EMSConforms to EN 61204-3 high severity levels
Approved Standards *6
Conformed Standards
SEMIConforms to F47-0706 (3-phase, 380 to 480 VAC input)
Note: Refer to page 4 for notes 1 to 13.
3-phase, 400 VAC input *11
3-phase, 400 VAC input *11
3-phase, 400 VAC input28 A typ.29 A typ.
3-phase, 400 VAC input *11
3-phase, 400 VAC input0.05%/°C max.
3-phase, 400 VAC input *11
3-phase, 400 VAC input *11
Conducted Emission
Radiated EmissionConforms to EN 61204-3 Class B EN 55011 Class B
89% typ.89% typ.
3-phase, 380 to 480 VAC (allowable range: 320 to 576 VAC)
2-phase, 380 to 480 VAC (allowable range: 340 to 576 VAC)
450 to 600 VDC (allowable range: 450 to 810 VDC) *8
0.38 A typ.0.69 A typ.
160 mV p-p max. at 20 MHz of bandwidth190 mV p-p max. at 20 MHz of bandwidth
700 ms typ.600 ms typ.
30 ms typ.20 ms typ.
Yes, 130% or higher of rated output voltage, power shut off (shut off the input voltage and turn on
the input again) *5
3.0 kVAC for 1 min. (between all input terminals and output terminals) cutoff current 20 mA
2.5 kVAC for 1 min. (between all input terminals and PE terminal) cutoff current 20 mA
1.0 kVAC for 1 min. (between all output terminals and PE terminal) cutoff current 30 mA
–40 to 70°C (However, only startup is guaranteed for between –40°C to –25°C. (3-phase only))
(Derating is required according to the temperature.) (with no condensation or icing)
Conforms to EN 61204-3 Class B EN 55011 Class B
UL Listed: UL 508 *7
UL Listed: UL 508 *7
EN: EN 50178
Lloyd’s standards *9
ANSI/ISA 12.12.01 *7
SELV (EN 50178), PELV(EN 60204-1, EN 50178)
Safety of Power Transformers (EN 61558-2-16)
EN 50274 for Terminal parts
UL UR: UL 60950-1 (Recognition)
cUR: CSA C22.2 No.60950-1
CSA: CSA C22.2 No.60950-1
EN: EN 50178, EN 60950-1
Lloyd’s standards *9
ANSI/ISA 12.12.01 *7
SELV (EN 60950-1/EN 50178/UL 60950-1)
PELV (EN 60204-1, EN 50178)
Safety of Power Transformers (EN 61558-2-16)
EN 50274 for Terminal parts
2
Page 3
Power rating480 W960 W (768 W *18)
ItemOutput voltage24 V24 V
Efficiency
Input
Output
Additional
functions
Insulation
Environment
Reliability
Construction
Standards
Voltage range *1
Frequency *150/60 Hz (47 to 63 Hz)
Current
Power factor--
Leakage current 3-phase, 400 VAC input3.5 mA max./1.0 mA typ.3.5 mA max./1.2 mA typ.
Inrush current (for a
cold start at 25°C) *2
Rated output current20 A40 A at 3-phase (32 A at 2-phase)
Boost current24 A48 A at 3-phase (Not possible at 2-phase)
Voltage adjustment range *322.5 to 29.5 VDC (with V.ADJ) (guaranteed)22.5 to 29.5 VDC (with V.ADJ) (guaranteed) *14
Ripple & Noise voltage *4
Input variation influence *130.5% max.
Load variation influence *121.5% max.
Temperature
variation influence
Start up time *2
Hold time *2
Overload protectionYes, automatic reset
Overvoltage protection
Series operationYes (For up to two Power Supplies, external diodes are required.)
Parallel operationYes (Refer to Engineering Data) (For up to two Power Supplies)
Output indicatorYes (LED: Green), lighting from 80% to 90% or more of rated voltage
Withstand voltage
Insulation resistance100 MΩ min. (between all output terminals and all input terminals / PE terminal) at 500 VDC
Ambient operating temperature
Storage temperature–40 to 85°C (with no condensation or icing)
Ambient operating humidity0% to 95% (Storage humidity: 0% to 95%)
Vibration resistance10 to 55 Hz, 0.375-mm half amplitude for 2 h each in X, Y, and Z directions
Shock resistance150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
MTBF135,000 hrs min.
Life expectancy *1010 years min.
Weight1,600 g max.2,700 g max.
Cooling fanNo
Degree of protectionIP20 by EN / IEC 60529
Harmonic current emissionsConforms to EN 61000-3-2 *15
EMI
EMSConforms to EN 61204-3 high severity levels
Approved Standards *6
Conformed Standards
SEMIConforms to F47-0706 (3-phase, 380 to 480 VAC input) *17
3-phase, 400 VAC input *11
3-phase, 400 VAC input *11
3-phase, 400 VAC input28 A typ.
3-phase, 400 VAC input *11
3-phase, 400 VAC input
3-phase, 400 VAC input *11
3-phase, 400 VAC input *11
Conducted Emission
Radiated EmissionConforms to EN 61204-3 Class B EN 55011 Class B *16
91% typ.92% typ.
3-phase, 380 to 480 VAC
(allowable range: 320 to 576 VAC)
2-phase, 380 to 480 VAC
(allowable range: 340 to 576 VAC)
450 to 600 VDC
(allowable range: 450 to 810 VDC) *8
1.2 A typ.2.1 A typ.
130 mV p-p max. at 20 MHz of bandwidth90 mV p-p max. at 20 MHz of bandwidth
0.05%/°C max.
500 ms typ.700 ms typ.
20 ms typ.20 ms typ.
Yes, 130% or higher of rated output voltage, power shut off (shut off the input voltage and turn on
the input again) *5
3.0 kVAC for 1 min. (between all input terminals and output terminals) cutoff current 20 mA
2.5 kVAC for 1 min. (between all input terminals and PE terminal) cutoff current 20 mA
1.0 kVAC for 1 min. (between all output terminals and PE terminal) cutoff current 30 mA
–40 to 70°C (However, only startup is guaranteed for between –40°C to –25°C. (3-phase only))
(Derating is required according to the temperature.) (with no condensation or icing)
Conforms to EN 61204-3 Class B EN 55011 Class B *16
UL Listed: UL 508 *7
UL UR: UL 60950-1 (Recognition)
cUR: CSA C22.2 No.60950-1
CSA: CSA C22.2 No.60950-1
EN: EN 50178, EN 60950-1
Lloyd’s standards
ANSI/ISA 12.12.01 *7
SELV (EN 60950-1/EN 50178/UL 60950-1)
PELV (EN 60204-1, EN 50178)
Safety of Power Transformers (EN 61558-2-16)
EN 50274 for Terminal parts
3-phase, 380 to 480 VAC
(allowable range: 320 to 576 VAC)
2-phase, 380 to 480 VAC
(allowable range: 340 to 576 VAC)
Note: Refer to page 4 for notes 1 to 18.
S8VK-T
3
Page 4
S8VK-T
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*2. For a cold start at 25°C. Refer to Engineering Data on page 7 to 8 for details.
*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than 29.5 VDC of the voltage adjustment range.
When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
*4. A characteristic when the ambient operating temperature is between –25 to 70°C.
*5. Refer to Overvoltage Protection on page 8 for the time when input voltage shuts off and input turns on again.
*6. To meet safety standards, the S8VK-T must be protected with an external circuit-breaker or a fuse.
Be sure to use an external circuit-breaker or a fuse. Refer to Precautions for Safe Use on page 13 for details.
*7. The following supplementary Fuse/Circuit Breaker must be installed in accordance with NEC.:
Model FAZ-D5/3-NA, FAZ-D5/3-RT or FAZ-D5/3-DU, EATON INDUSTRIES (AUSTRIA) GMBH (E235139), Model KLKD5, LITTELFUSE INC.
(E10480)
*8. Safety Standards for a DC Input
The following standards apply to a 450 to 600 VDC input: UL 60950-1, EN 50178, EN 60950-1, and Lloyd's standards.
*9. In the case of using side-mounting bracket (S82Y-VK10S, S82YVK20S), Lloyd's Standards are not applicable.
*10. The value is when rated output current is 50% or less, the ambient operating temperature is 40°C or less, standard mounting, and rated input
voltage.
*11. The value is when both rated output voltage and rated output current are satisfied.
*12. 380 to 480 VAC input, in the range of 0 A to the rated output current.
*13. This is the maximum variation in the output voltage when the input voltage is gradually changed within the allowable input voltage range at
the rated output voltage and rated output current.
*14. Use at 26.4 VDC or lower for 2-phase input.
*15. The S8VK-T Power Supply conforms to EN 61000-3-2 under the following conditions for 2-phase input.
480 W: rated output voltage, and 65% or less of rated output current
960 W: rated output voltage, and 45% or less of rated output current
*16. The S8VK-T Power Supply conforms to EMI under the following conditions for 2-phase input.
480 W: Conforms to class B: rated output voltage, and 65% or less of rated output current/
Conforms to class A: rated output voltage, and 65% to 100% of rated output current
960 W: Conforms to class B: rated output voltage, and 45% or less of rated output current/
*17. 480 W: rated output voltage, and 50% or less of rated output current.
*18. When using 2-phase input. Refer to 2-Phase Input Operation For 960 W Model in Precautions for Safe Use on page 16 for details.
Conforms to class A: rated output voltage, and 45% to 100% of rated output current
960 W: rated output voltage, and 92.5% or less of rated output current.
4
Page 5
Connections
S8VK-T12024 (120 W)
S8VK-T24024 (240 W)
S8VK-T48024 (480 W)
S8VK-T96024 (960 W)
Block Diagrams
S8VK-T
INPUT
INPUT
L1
L2
L3
L1
L2
L3
Rectifier
Rectifier
Noise filter
Noise filter
Overcurrent
detection circuit
Overcurrent
detection circuit
lnrush
current
protection
Drive
control
circuit
lnrush
current
protection
Drive
control
circuit
Smoothing
circuit
Photocoupler
Smoothing
circuit
Photocoupler
Rectifier/
smoothing
circuit
Voltage
detection circuit
Overvoltage
detection circuit
Rectifier/
smoothing
circuit
Voltage
detection circuit
Overvoltage
detection circuit
+V
DC OUTPUT
−V
+V
DC OUTPUT
−V
5
Page 6
S8VK-T
12
3
5
4
12
3
5
4
6
Note:
A: The output current can use 100% of the rated output current.
B: Overcurrent protection limits the output current to 80% of the rated
output current.
Construction and Nomenclature
Nomenclature
120 W Model240 W Model480 W Model
S8VK-T12024S8VK-T24024S8VK-T48024
3
960 W Model
S8VK-T96024
4
5
12
12
4
5
3
No.NameFunction
1Input terminals (L1), (L2), (L3)Connect the input lines to these terminals. *1
2Protective Earth terminal (PE) / Ground Connect the ground line to this terminal. *2
3DC Output terminals (−V), (+V)Connect the load lines to these terminals.
4Output indicator (DC ON: Green)Lights while a direct current (DC) output is ON.
5Output voltage adjuster (V.ADJ)Use to adjust the voltage.
6Operation Switch *3 *4To operate in parallel or 2-phase input, set the switch to the "B" side. (960 W model only).
*1. For wiring, refer to Wiring in Precautions for Safe Use on page 13.
*2. This is the protective earth terminal specified in the safety standards. Always ground this terminal.
*3. For parallel operation, refer to Parallel Operation in Precautions for Safe Use on page 15.
*4. For 2-phase input, refer to 2-Phase Input Operation For 960 W Model in Precautions for Safe Use on page 16.
6
Page 7
Engineering Data
−40 −25 −10 0 10 20 30 40 50 60 70 80
120
100
80
60
40
20
0
A
B
C
Load ratio (%)
Ambient temperature (°C)
−40 −25 −10 0 10 20 30 40 50 60 70 80
120
100
80
60
40
20
0
A
B
C
Load ratio (%)
Ambient temperature (°C)
−40 −25 −10 0 10 20 30 40 50 60 70 80
120
100
80
60
40
20
0
A
B
C
Load ratio (%)
Ambient temperature (°C)
Derating Curve
120 W (S8VK-T12024)
Note: This is the guaranteed value for startup. (3-phase only)
A. Standard mounting
B. Face-up mounting at 480 VAC or lower or 678 VDC or lower
C. Face-up mounting at 576 VAC or lower or 810 VDC or lower
240 W (S8VK-T24024)
S8VK-T
960 W (S8VK-T96024): Standard mounting
120
100
80
Load ratio (%)
60
40
20
0
−40 −25 −10 0 10 20 30 40 50 60 70 80
Ambient temperature (°C)
Note: This is the guaranteed value for startup. (3-phase only)
A. 3-Phase (340 VAC or over to 576 VAC or lower)
For less than 340 VAC, it is possible to use with output voltage at
28.5 VDC or lower and load rate 60% or lower.
B. 2-Phase (380 VAC or over to 576 VAC or lower, and output voltage
26.4 VDC or lower)
C. 2-Phase (360 VAC or over to 380 VAC or lower, and output voltage
26.4 VDC or lower)
For 340 VAC or over to less than 360 VAC, it is possible to use with
output voltage at 26.4 VDC or lower, and whichever is the smaller of
the load rate 60% or lower or the value of C.
960 W (S8VK-T96024): Face-up mounting
120
100
80
Load ratio (%)
B
C
A
D
E
F
Note: This is the guaranteed value for startup. (3-phase only)
A. Standard mounting
B. Face-up mounting at 480 VAC or lower or 678 VDC or lower
C. Face-up mounting at 576 VAC or lower or 810 VDC or lower
480 W (S8VK-T48024)
Note: This is the guaranteed value for startup. (3-phase only)
A. Standard mounting
Over 528 VAC: the derating is 0.21%/VAC
Over 746 VAC: the derating is 0.16%/VDC
B. Face-up mounting at 480 VAC or lower or 678 VDC or lower
C. Face-up mounting at 576 VAC or lower or 810 VDC or lower
60
40
20
0
−40 −25 −10 0 10 20 30 40 50 60 70 80
Ambient temperature (°C)
Note: This is the guaranteed value for startup. (3-phase only)
D. 3-Phase (340 VAC or over to 576 VAC or lower)
For less than 340 VAC, it is possible to use with output voltage at
28.5 VDC or lower and load rate 60% or lower.
E. 2-Phase ( 380 VAC or over to 480 VAC or lower, and output voltage
26.4 VDC or lower)
F. 2-Phase (Over 480 VAC to 576 VAC or lower)
For 340 VAC or over to less than 380 VAC, it is possible to use with
output voltage at 26.4 VDC or lower, and whichever is the smaller of
the load rate 60% or lower or the value of F.
7
Page 8
S8VK-T
(B) Face-up mounting
(A) Standard (Vertical) mounting
The values shown in the above diagrams are for reference only.
050100
Output current (%)
Output voltage (V)
Intermittent operation
29.5 V
22.5 V
0 V
+30%
(approx.)
Overvoltage protection
operating
Variable range
Rated output
voltage
Output voltage (V)
The values shown in the above diagram is for reference only.
90%
96.5%
Startup time
AC input
voltage
AC input
current
Output
voltage
Inrush current on input application
Input OFF
Input ON
Hold time
Mounting
Overload Protection
The load and the power supply are automatically protected from
overcurrent damage by this function.
Overload protection is activated if the output current rises above
121% of the rated current.
When the output current returns within the rated range, overload
protection is automatically cleared.
Overvoltage Protection
Consider the possibility of an overvoltage and design the system so
that the load will not be subjected to an excessive voltage even if the
feedback circuit in the Power Supply fails. If an excessive voltage that
is approximately 130% of the rated voltage or more is output, the
output voltage is shut OFF. Reset the input power by turning it OFF
for at least five minutes and then turning it back ON again.
Note: Do not turn ON the power again until the cause of the
overvoltage has been removed.
Inrush Current, Startup Time, Output Hold Time
Note: 1. Internal parts may occasionally deteriorate or be damaged
if a short-circuited or overcurrent state continues during
operation.
2. Internal parts may possibly deteriorate or be damaged if the
Power Supply is used for applications with frequent inrush
current or overloading at the load end. Do not use the Power
Supply for such applications.
Note: Twice the input current or above will flow during the parallel
operation or redundant system.
Therefore, check the fusing characteristics of fuses and
operating characteristics of breakers making sure that the
external fuses will not burn out and the circuit breakers will not
be activated by the inrush current.
Reference Value
Value
Reliability
(MTBF)
Definition
Life expectancy10 years. Min.
Definition
120 W: 390,000 h
240 W: 350,000 h
480 W: 280,000 h
960 W: 260,000 h
MTBF stands for Mean Time Between
Failures, which is calculated according to the
probability of accidental device failures, and
indicates reliability of devices.
Therefore, it does not necessarily represent a
life of the product.
The life expectancy indicates average
operating hours under the ambient
temperature of 40°C and a load rate of 50%.
Normally this is determined by the life
expectancy of the built-in aluminum electrolytic
capacitor.
8
Page 9
S8VK-T
S8VK-T12024 (120 W)
S8VK-T24024 (240 W)
6.356.35
3025
19.8
(26.8)
Rail Stopper
4.7
(Sliding: 7.5 max.)
(10)
125±1
145.6
(4)140
(1)
150
±1
52.3
95
±1
S8VK-T48024 (480 W)
S8VK-T96024 (960 W)
Dimensions(Unit: mm)
±1
40
6.35
104.6125±1
6.35
19.8
104.6
4.7
(Sliding: 7.5 max.)Rail Stopper
60
±1
6.35
6.35
(1)
125±1
122.2±1
117.8
112.2
(4)
(10)
150
(1)
±1
145.6
(4)140
4.7
(Sliding: 7.5 max.)
135
±1
(1)
125±1
10.16
10.16
19.8
Rail Stopper
47.9
(10)
180
175.6
170
±1
(4)
19.8
(36.7)
41.7832.95
Rail Stopper
4.7
(Sliding: 7.5 max.)
(10)
9
Page 10
S8VK-T
4.5
15 2525
1010
1,000 (500) *
252515(5) *
35
±
0.3
7.3
±
0.15
27
±
0.15
1
* Values in parentheses are for the PFP-50N.
4.5
15 2525
1010
1,000
2525 15
11.5
29.2242735
±
0.3
16
1.3
4.8
35.5
35.5
1.8
1.8
10
6.2
1
50
11.5
10
M4 spring washer
M4×8 pan-
head screw
DIN Rail (Order Separately)
Note: All units are in millimeters unless otherwise indicated.
Mounting Rail (Material: Aluminum)
PFP-100N
PFP-50N
Mounting Rail (Material: Aluminum)
PFP-100N2
End Plate
PFP-M
Note: If there is a possibility that the Unit will be subject to vibration or shock, use a steel DIN Rail. Otherwise, metallic filings may result from
aluminum abrasion.
10
Page 11
Mounting Brackets
140
±0.1
50
±0.1
15.5
±0.1
150125
73
4-4.5 dia.
±0.1
4940
t = 2.0
NameModelQty used
Front-mounting bracket (for 120, 240 and 480 W models)S82Y-VK10F1
Front-mounting bracket (for 960 W model)S82Y-VK10F2
Side-mounting bracket (for 120 W model)S82Y-VK10S1
Side-mounting bracket (for 240 W model)S82Y-VK20S1
Note: Be sure to use the accessory screws.
Mounting screw tightening torque (recommended): 4.43 to 5.31 lb-in (0.5 to 0.6 N·m)
TypeModelDimensionsAppearance
S8VK-T
Front-mounting
bracket
(for 120, 240,
480 W and 960 W
models)
S82Y-VK10F
5.4
4-4.5 dia.
t = 2.0
120 W model
±0.1
±0.1
140
For 960W type
150
240 W model
960 W model
±0.1
25
38
±0.1
64
Left-side mountingRight-side mounting
Side-mounting
bracket
(For 120 W model)
Side-mounting
bracket
(For 240 W model)
S82Y-VK10S
S82Y-VK20S
Left-side mounting
(DIN Rail) *
Right-side mounting
(DIN Rail) *
Left-side mountingRight-side mounting
73
±0.1
40
59
t = 2.0
50
4-4.5 dia.
±0.1
15.5
±0.1
±0.1
140
Left-side mounting
150125
(DIN Rail) *
Right-side mounting
(DIN Rail) *
* You can mount the side of the Power Supply to a DIN Rail by removing the DIN Rail Back-mounting Bracket and then attaching a Side-mounting
Bracket to the Power Supply.
11
Page 12
S8VK-T
Safety Precautions
Warning Indications
Indicates a potentially hazardous
CAUTION
Precautions for
Safe Use
Precautions for
Correct Use
Meaning of Product Safety Symbols
Used to warn of the risk of electric shock under
specific conditions.
Used to warn of the risk of minor injury caused by
high temperatures.
situation which, if not avoided, may
result in minor or moderate injury or in
property damage.
Supplementary comments on what to
do or avoid doing, to use the product
safely.
Supplementary comments on what to
do or avoid doing, to prevent failure to
operate, malfunction or undesirable
effect on product performance.
Used for general mandatory action precautions
for which there is no specified symbol.
Used to indicate prohibition when there is a risk of
minor injury from electrical shock or other source
if the product is disassembled.
!CAUTION
Minor electric shock, fire, or Product failure may
occasionally occur. Do not disassemble, modify, or
repair the Product or touch the interior of the
Product.
Minor burns may occasionally occur. Do not touch
the Product while power is being supplied or
immediately after power is turned OFF.
Fire may occasionally occur. Tighten terminal screws
to the specified torque.
S8VK-T12024, S8VK-T24024, S8VK-T48024:
4.43 to 5.31 lb-in (0.5 to 0.6 N•m)
S8VK-T96024:
10.62 to 13.28 lb-in (1.2 to 1.5 N•m)
Minor injury due to electric shock may occasionally
occur. Do not touch the terminals while power is
being supplied.
Minor electric shock, fire, or Product failure may
occasionally occur. Do not allow any pieces of metal
or conductors or any clippings or cuttings resulting
from installation work to enter the Product.
If the external breaker or fuse is tripped, the
equipment may have been seriously damaged.
Do not turn ON the input again.
12
Page 13
Precautions for Safe Use
L1
TT
L2
L3
N
L1
IT
L2
L3
+
DC
-
PE
FUSE
Wiring
• Connect the ground completely. A protective earthing terminal
stipulated in safety standards is used. Electric shock or malfunction
may occur if the ground is not connected completely.
• Minor fire may possibly occur. Ensure that input and output
terminals are wired correctly.
• Do not apply more than 75-N force to the terminal block when
tightening it.
• Be sure to remove the sheet covering the Product for machining
before power-ON so that it does not interfere with heat dissipation.
• To comply with safety standards and to ensure equipment safety,
connect the input to the S8VK-T through one of the following
Breakers or Fuses.
S8VK-T
• Use the following material for the wires to be connected to the
S8VK-T to prevent smoking or ignition caused by abnormal loads
or phase failure.
• Wire the input as shown in the following figures depends on your
power distribution system. Do not connect the neutral line in a
3-phase, 4-wire system.
TN-S
TN-C
2-phase
Power circuit-breakers
ModelInputPower circuit-breakers
Circuit breaker Conforming UL/CE
S8VK-T12024
S8VK-T24024
3-phase
2-phase/DC
480 V, 5 A, characteristic D, 3-pole, or
equivalent breaker
Fuse Conforming
Fast Acting or identical function fuse
Circuit breaker Conforming UL/CE
S8VK-T48024
S8VK-T96024
3-phase
2-phase/DC
480 V, 5 A, characteristic D, 3-pole, or
equivalent breaker
Fuse Conforming
UL/CE 600 V, 10 A
Fast Acting or identical function fuse
Note: Do not use the S8VK-T96024 with a DC input.
UL/CE 600 V, 5 A
L1
L2
L3
N
PE
Recommended Wire Type/Cross-sectional Area and Stripping Length
INPUTOUTPUTPE / Ground
Model
S8VK-T12024AWG22 to 10
S8VK-T48024AWG20 to 10
S8VK-T96024AWG16 to 6
American
Wire Gauge
Solid Wire
/Stranded Wire
0.35 to 6 mm
2
/0.35 to 4 mm
0.35 to 6 mm
2
/0.35 to 4 mm
0.5 to 6 mm
/0.5 to 4 mm
1.5 to 16 mm
2
2
2
/1.5 to 16 mm
American
Wire Gauge
AWG18 to 10
2
AWG14 to 10
2
AWG12 to 10
AWG8 to 6
2
Solid Wire
/Stranded Wire
0.75 to 6 mm
/0.75 to 4 mm
2.5 to 6 mm
/2.5 to 4 mm
4 to 6 mm
2
/4 mm
10 to 16 mm
/10 to 16 mm
2
2
2
2
2
2
American
Wire Gauge
2
AWG14 to 10
AWG14 to 6
PEN
FUSE
mm
mm
mm
mm
2
2
2
2
L1
L2
(L3)
PE
Wire tripping
Length
8 to 10 mmS8VK-T24024AWG22 to 10
13 to 16 mm
L1
L2
L3
Solid Wire
/Stranded Wire
2.5 to 6
/2.5 to 4
2.5 to 16
/2.5 to 16
• The wire insertion hole, and applicable screwdriver of the terminal block are as follows.
Model
S8VK-T12024
Wire Insertion Hole
(Refer to the diagram on the right)
WLNo.
Applicable Screwdriver
Driver
Diameter
Length
L
2.92.9#24.9 mm max.10 mm min.S8VK-T24024
S8VK-T48024
S8VK-T960245.45#25.1 mm max.12 mm min.
Installation Environment
• Do not use the Power Supply in locations subject to shocks or
vibrations. In particular, install the Power Supply as far away as
possible from contactors or other devices that are a vibration
source. For usage onboard a ship, always attach an End Plate
(PFP-M) to both sides of the Power Supply to hold the Power
Supply in place.
• Install the Power Supply well away from any sources of strong,
high-frequency noise and surge.
Operating Life
• The life of a Power Supply is determined by the life of the
electrolytic capacitors used inside. Here, Arrhenius Law applies,
doubled for each drop of 10°C. The life of the Power Supply can
thus be increased by reducing its internal temperature.
Ambient Operating and Storage Environments
• Store the Power Supply at a temperature of −40 to 85°C and a
humidity of 0% to 95%.
• Do not use the Power Supply in areas outside the derating curve
otherwise, internal parts may occasionally deteriorate or be
damaged.
• Use the Power Supply at a humidity of 0% to 95%.
• Do not use the Power Supply in locations subject to direct sunlight.
• Do not use the Power Supply in locations where liquids, foreign
matter, or corrosive gases may enter the interior of Products.
W
i.e., the life will be cut in half for each rise of 10°C or the life will be
13
Page 14
S8VK-T
*1. Convection of air
*2. 20 mm min.
*1
*1
*2
(C)
30 mm min.
Rail stopper
[A]
Ip: Boost current
Rated current
lave: Average current
t2
t1
output current
Mounting
• Take adequate measures to ensure proper heat dissipation to
increase the long-term reliability of the Product. Be sure to allow
convection in the atmosphere around devices when mounting. Do
not use in locations where the ambient temperature exceeds the
range of the derating curve.
• When cutting out holes for mounting, make sure that cuttings do
not enter the interior of the Products.
• Improper mounting will interfere with heat dissipation and may
occasionally result in deterioration or damage of internal parts. Use
the Product within the derating curve for the mounting direction that
is used.
Overload Protection
• Internal parts may possibly deteriorate or be damaged if a
short-circuited or overcurrent state continues during operation.
• Internal parts may possibly deteriorate or be damaged if the Power
Supply is used for applications with frequent inrush current or
overloading at the load end. Do not use the Power Supply for such
applications.
• The DC ON indicator (green) flashes if the overload protection
function operates.
Charging a Battery
If you connect a battery as the load, install overcurrent control and
overvoltage protection circuits.
Power Boost Function
For All Models
Power Boost is a function that can output the temporary repeated
boost current larger than the rated current.
However, it should meet the following four Boost current conditions.
1. Time that the boost current flows: t1
2. The maximum value of the boost current: lp
3. The average output current: lave
4. The time ratio of the boost current flow: Duty
Note: Boost current conditions
• t1
≤ 10 s
• Ip
≤ Rated boost current
• lave
≤ Rated current
t1
t1 + t2
× 100 [%] ≤ 30%
Duty=
• Do not allow the boost current to continue for more than 10
seconds.
Also, do not let the duty cycle exceed the boost current conditions.
These conditions may damage the Power supply.
• Ensure that the average current of one cycle of the boost current
does not exceed the rated output current.
This may damage the Power Supply.
• Lessen the load of the boost load current by adjusting the ambient
temperature and the mounting direction.
• Power Boost Function is not possible for the S8VK-T 960 W at
2-phase input or in parallel operation.
14
Output Voltage Adjuster (V.ADJ)
• The output voltage adjuster (V.ADJ) may possibly be damaged if it
is turned with unnecessary force. Do not turn the adjuster with
excessive force.
• After completing output voltage adjustment, be sure that the output
capacity or output current does not exceed the rated output
capacity or rated output current.
DIN Rail Mounting
To mount the Block on a DIN Rail, hook portion (A) of the Block onto
the rail and press the Block in direction (B).
(A)
(B)
To dismount the Block, pull down portion (C) with a flat-blade
screwdriver and pull out the Block.
Series Operation
Two power supplies can be connected in series.
+V
L1
L2
−V
L3
+V
L1
L2
L3
−V
Note: 1. The diode is connected as shown in the figure. If the load is
short-circuited, a reverse voltage will be generated inside
the Power Supply. If this occurs the Power Supply may
possibly deteriorate or be damaged. Always connect a
diode as shown in the figure.
Select a diode having the following ratings.
TypeSchottky Barrier diode
Dielectric strength (V
Forward current (I
RRM) Twice the rated output voltage or above
F)Twice the rated output current or above
2. Although Products having different specifications can be
connected in series, the current flowing through the load
must not exceed the smaller rated output current.
Load
Page 15
S8VK-T
+V
−V
+V
−V
+V
0 V
−V
L1
L2
L3
L2
L1
L3
LoadLoad
+V
−V
+V
−V
L1
L2
L3
L2
L1
L3
LoadLoad
Load
D2
D1
Making Positive/Negative Outputs
• The outputs are floating outputs (i.e., the primary circuits and
secondary circuits are separated). You can therefore make
positive and negative outputs by using two Power Supplies.
You can make positive and negative outputs with any of the
models.
If positive and negative outputs are used, connect Power Supplies
of the same model as in the following figure. (Combinations with
different output capacities or output voltages can be made.
However, use the lower of the two maximum rated output currents
as the current to the loads.)
• Depending on the model, internal circuits may be damaged due to
startup failure when the power is turned ON if loads such as a
servomotor or operational amplifier may operate in series.
Therefore, connect bypass diodes (D
following figure.
If the list of models that support series connection of outputs says
that an external diode is not required, an external diode is also not
required for positive/negative outputs.
1, D2) as shown in the
Parallel Operation
Parallel operation is used when the output current from one Power
Supply is insufficient for the load. Power Supplies are connected in
parallel to increase the output current.
Two Power Supplies can be connected in parallel.
1. Parallel operation is possible only if the standard mounting and
3-phase input is used.
Maintain an ambient temperature of between -25 and 40°C.
2. For parallel operation, always use two Power Supplies with the
same capacity.
3. Use the output voltage adjusters (V. ADJ) to adjust the difference
in the output voltages between the two Power Supplies to 50 mV
or less.
4. If the output current from the two Power Supplies is not balanced,
the Power Supply with the higher output voltage will operate in an
overcurrent protection state, which will extremely reduce its
service life. After you adjust the difference in the output voltages
between the two Power Supplies, make sure that the currents are
well balanced.
5. The length and thickness of each wire connected to the load and
each unit must be the same so that there is no difference in the
voltage drop value between the load and the output terminals of
each Power Supply.
6. For Parallel Operation with units 120 W, 240 W S8VK-T Power
Supplies, connect diodes or S8VK-R to the outputs of each unit if
sudden load variation influence occurs in the ambient operation
environment.
Refer to the S8VK-R datasheet (Catalog No.: T059) for S8VK-R
specifications and the model number for each capacity.
S8VK-T
L1
L2
L3
S8VK-T
L1
L2
L3
+V
−V
+V
−V
S8VK-R
IN 1
IN 2
+V
Load
−V
• Use the following information as a guide to the diode type,
dielectric strength, and current.
TypeSchottky Barrier diode
Dielectric strength (V
Forward current (I
RRM) Twice the rated output voltage or above
F)Twice the rated output current or above
7. The internal parts may occasionally be deteriorated or broken. Be
sure to set the OPERATION SWITCH to B when using S8VK-T
480 W, 960 W for Parallel Operation.
For Parallel Operation with units 960 W S8VK-T Power Supplies,
connect diodes to the outputs of each unit if sudden load variation
influence occurs in the ambient operation environment.
+V
L1
L2
−V
L3
+V
L1
L2
L3
−V
Load
• Use the following information as a guide to the diode type,
dielectric strength, and current.
TypeSchottky Barrier diode
Dielectric strength (V
Forward current (I
RRM) Twice the rated output voltage or above
F)Twice the rated output current or above
15
Page 16
S8VK-T
+V
−V
+V
−V
+V
−V
L1
L2
L3
L2
L1
L3
Load
S8VK-R
IN 1
IN 2
S8VK-T
S8VK-T
+V
−V
+V
−V
L1
L2
L3
L2
L1
L3
A
B
D
1
D2
Load
Note:
A: The output current can use 100%
of the rated output current.
B: Overcurrent protection limits the
output current to 80% of the rated
output current.
Backup Operation
Backup operation is possible if you use two Power Supplies of the
same model.
Even if one Power Supplies fails, operation can be continued with the
other Power Supply.
Make sure that the maximum load does not exceed the capacity of
one Power Supply.
For backup operation, connect the S8VK-R for 120 W, 240 W, and
480 W.
Refer to the S8VK-R datasheet (Catalog No.: T059) for S8VK-R
specifications and the model number for each capacity.
For 960 W, always connect diodes to the output sides of the two
Power Supplies as shown in the following diagram.
In Case There Is No Output Voltage
The possible cause for no output voltage may be that the overcurrent
or overvoltage protection has operated. The internal protection may
operate if a large amount of surge voltage such as a lightening surge
occurs while turning ON the power supply.
In case there is no output voltage, please check the following points
before contacting us:
• Checking overload protected status:
Check whether the load is in overload status or is short-circuited.
Remove wires to load when checking.
• Checking overvoltage or internal protection:
Turn the power supply OFF once, and leave it OFF for at least
5 minutes. Then turn it ON again to see if this clears the condition.
2-Phase Input Operation For 960 W Model
The internal parts may occasionally be deteriorated or broken. Be sure
to set the OPERATION SWITCH to B when using S8VK-T 960 W at
2-phase input.
• Use the following information as a guide to the diode type,
dielectric strength, and current.
TypeSchottky Barrier diode
Dielectric strength (V
Forward current (I
RRM) Twice the rated output voltage or above
F)Twice the rated output current or above
• Increase the output voltage setting of Power Supply A and Power
Supply B by the drop in the forward voltage (V
2.
D
F) of diodes D1 and
Also, the diodes will cause a power loss equivalent to the Power
Supply output current (I
OUT) times the diode forward voltage (VF).
Therefore, cooling measures must be implemented so that the
temperature of the diodes decreases to the catalog value or lower.
• Because of the load power and power loss due to the diodes, do
not exceed the rated power of one Power Supply (rated output
voltage × rated output current).
16
Page 17
S8VK-T
(1) Failures that result from handling or operation of the product under conditions or in environments that are not given in this document and
not given in any other specifications exchanged between OMRON and the customer
(2) Failures that originate in causes other than the delivered product itself
(3) Failures caused by disassembly, modification, or repair of the product by anyone other than OMRON
(4) Failures caused by applications or uses for which the product was not originally intended
(5) Failures caused by factors that could not be anticipated with the scientific or technical knowledge available when the product was shipped
(6) Failures caused by other causes for which OMRON is not responsible, such as natural disasters and other acts of God
This warranty is limited to the individual product that was delivered and does not cover any secondary, subsequent, or related damages.
Period and Terms of Warranty
Warranty Period
The product warranty is valid for a period of three years from the date of shipment from the factory.
Terms of Warranty
The warranty is valid only for the following operating conditions.
1. Average ambient operating temperature of the product: 40°C max.
2. Average load rate: 80% max.
3. Mounting method: Standard mounting
* The maximum ratings must be within the derating curve.
If the product fails for reasons attributable to OMRON within the above warranty period, OMRON will repair or replace the faulty part of the product
at the place of purchase or the place where the product delivered without charge.
This warranty does not cover the following types of failures.
Recommended Replacement Periods and Periodic Replacement for
Preventive Maintenance
The recommended replacement period for preventive maintenance is greatly influenced by the application environment of the product. As a
guideline, the recommended replacement period is 7 to 10 years.*
To prevent failures or accidents that can be caused by using a product beyond its service live, we recommend that you replace the product as early
as possible within the recommended replacement period.
However, bear in mind that the recommended replacement period is for reference only and does not guarantee the life of the product.
Many electronic components are used in the product and the product depends on the correct operation of these components to achieve the original
product functions and performance.
However, the influence of the ambient temperature on aluminum electrolytic capacitors is large, and the service life is reduced by half for each
10°C rise in temperature (Arrhenius law).
When the capacity reduction life of the electrolytic capacitor is reached, the product failures or accidents may occur.
We therefore recommend that you replace the product periodically to minimize product failures or accidents in advance.
* The recommended replacement period applies under the following conditions: rated input voltage, load rate of 50% max., ambient temperature
of 40°C max., and the standard mounting method. (The fan is excluded for models with fans.)
This product model is designed with a service life of 10 years minimum under the above conditions.
17
Page 18
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing
by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE
PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL
SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products
or otherwise of any intellectual property right. (c) Buy
er Remedy. Omron’s sole obligation hereunder shall be
, at Omron’s election,
to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price
of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other
claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored,
installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with an
y electrical or electronic components, circ
uits, system
assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in
writing, are not to be construed as an amendment or addition to the above warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is
not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system,
or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with
respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING
THAT THE SYSTEM AS A W
HOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it
to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice
to change part numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be
assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to
confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
Page 19
OMRON Corporation Industrial Automation Company
Kyoto, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69, 2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200
Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China CSM_8_1_1116
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200