Refer to Safety Precautions for All Power Supplies and Safety
Precautions on page 17.
Related Products
Noise Filter
S8V-NF
DC Electronic Circuit Protector
S8V-CP
Note: Refer to the S8V-NF Datasheet
(Cat. No. T212) for details.
Note: Refer to the S8V-CP Datasheet (Cat. No. T226-E1)
for details.
(15/30/60/120/240/480-W Models)
S8VK-G
Reliable and Easy Operation-Worldwide Power Supply
Resistant in tough environments
Easy and fast installation
The most compact class on the market
• Universal input for worldwide applications:
100 to 240 VAC (85 to 264 VAC)
• DC input can be available: 90 to 350 VDC
• Possible for 2-phase input usage.
• Wide operation temperature range: –40 to 70 °C
• Power Boost function at 120%
• Safety standards:
UL508/62368-1, CSA C22.2 No. 107.1/62368-1
EN50178, EN62368-1.
Lloyd’s standards, EN60204-1 PELV
Safety of Power Transformers: EN61558-2-16
• 15-W,30-W, and 60-W models conform to
UL Class 2 output Standards
• EMS: EN 61204-3
EMI: EN 61204-3 Class B
• Three years Warranty *1
*1.Refer to Period and Terms of Warranty on page 23.
1
S8VK-G
12 34
S8VK- @@@@@@-@
1. Input voltage type
G: Single phase
2. Power Ratings
015: 15 W
030: 30 W
060: 60 W
120: 120 W
240: 240 W
480: 480 W
3. Output voltage (VDC)
05: 5 V
12: 12 V
24: 24 V
48: 48 V
4. Option
None: Standard model
400: Coationg
Model Number Structure
Model Number Legend
Note: Not all combinations are possible. Refer to List of Models in Ordering Information, below.
Ordering Information
Note: For details on normal stock models, contact your nearest OMRON representative.
Power ratingsInput voltageOutput Voltage (VDC)Output currentBoost CurrentModel number
5 V3 A3.6 AS8VK-G01505
15 W
30 W
60 W
120 W
240 W
480 W
Single phase
100 to 240 VAC
90 to 350 VDC
12 V1.2 A1.44 AS8VK-G01512
24 V0.65 A0.78 AS8VK-G01524
5 V5 A6 AS8VK-G03005
12 V2.5 A3 AS8VK-G03012
24 V1.3 A1.56 AS8VK-G03024
12 V4.5 A5.4 AS8VK-G06012
24 V2.5 A3 AS8VK-G06024
24 V5 A6 AS8VK-G12024
24 V10 A12 AS8VK-G24024
48 V5 A6 AS8VK-G24048
24 V20 A24 AS8VK-G48024
48 V10 A12 AS8VK-G48048
2
S8VK-G
Specifications
Ratings, Characteristics, and Functions
ItemOutput voltage (VDC)5 V12 V24 V5 V12 V24 V
Efficiency230 VAC input *677% typ.77% typ.80% typ.79% typ.82% typ.86% typ.
Input
Output
Additional
functions
Insulation
Environment
Reliability
Construction
Standards
*1.
Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply
may result in ignition or burning.
*2. For a cold start at 25°C. Refer to Engineering Data on page 9 to 11 for details.
*3.
If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range. When adjusting the output voltage, confirm
the actual output voltage from the Power Supply and be sure that the load is not damaged.
*4. A characteristic when the ambient operating temperature is between –25 to 70°C.
*5. Refer to Overvoltage Protection on page 10 for the time when input voltage shuts off and input turns on again.
*6. The value is when both rated output voltage and rated output current are satisfied.
*7. 100 to 240 VAC input, in the range of 0 A to the rated output current
*8.
This is the maximum variation in the output voltage when the input voltage is gradually changed within the allowable input voltage range at the rated output voltage and rated output current.
*9. Refer to Recommended Replacement Periods and Periodic Replacement for Preventive Maintenance on page 23 for details.
*10. Safety Standards for a DC Input
The following safety standards apply to a DC input: UL 62368-1, cUR (CSA C22.2 No. 62368-1), EN 50178, EN 62368-1, and Lloyd’s.
For a DC input, safety is ensured by an external fuse.
Select an external fuse that meets the following conditions.
S8VK-G015@@: 350 VDC min, 3 A
S8VK-G030@@: 350 VDC min, 4 A
*11.
Clamp filter “ZCAT2035-0930” manufactured by TDK Corporation. or equivalent should be installed in the cable connected to the input - output terminals of S8VK-G series.
Noise filter “FN2080-10-06” manufactured by SCHAFFNER Corporation. or equivalent should be connected to the Input terminals of S8VK-G series.
*12.At −40 to −25°C, time will be required before the rated output voltage is output after the input voltage is input.
Also, the ripple noise value may exceed the value shown in the above table.
Voltage range *1Single-phase, 85 to 264 VAC, 90 to 350 VDC *10
Frequency *150/60 Hz (47 to 450 Hz)
Current
Power factor
Leakage current
Inrush current *2 (for
a cold start at 25
Rated output current3 A1.2 A0.65 A5 A2.5 A1.3 A
Boost current3.6 A1.44 A0.78 A6 A3 A1.56 A
Voltage adjustment range *3–10% to 15% (with V.ADJ) (guaranteed)
Ripple & Noise
voltage *4
Input variation influence *80.4% max.0.4% max.
Load variation influence *70.8% max.0.8% max.
Temperature variation
influence
Start up time *2
Hold time *2
Overload protectionYes, automatic resetYes, automatic reset
Overvoltage protection *5
Series operationYes (For up to two Power Supplies, external diodes are required.)
Parallel operationYes (Refer to Safety Precautions) (For up to two Power Supplies)
Output indicatorYes (LED: Green), lighting from 80% to 90% or more of rated voltage
Withstand voltage
Insulation resistance100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC
Ambient operating temperature *12
Storage temperature–40 to 85°C (with no condensation or icing)
Ambient operating humidity0% to 95% (Storage humidity: 0% to 95%)
Vibration resistance10 to 55 Hz, 0.375 mm half amplitude for 2 h each in X, Y, and Z directions
Shock resistance150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
MTBF 135,000 hrs min.
Life expectancy *910 years min.
Weight150 g max.195 g max.
Cooling fanNo
Degree of protectionIP20 by EN/IEC 60529
Harmonic current emissionsConforms to EN 61000-3-2
EMI
EMSConforms to EN 61204-3 high severity levels
Approved Standards
Conformed Standards
Marine StandardsLloyd’s register *10 *11
SEMIConforms to F47-0706 ( 200 to 240 VAC input)
115 VAC input *60.32 A typ.0.3 A typ.0.31 A typ.0.5 A typ.0.57 A typ.0.58 A typ.
230 VAC input *60.2 A typ.0.21 A typ.0.2 A typ.0.32 A typ.0.37 A typ.0.36 A typ.
230 VAC input, 100% load
115 VAC input0.14 mA typ.0.13 mA typ.
230 VAC input0.25 mA typ.0.24 mA typ.
115 VAC input16 A typ16 A typ
°
C)
230 VAC input32 A typ.32 A typ.
100 to 240 VAC input,
100% load *6
115 to 230 VAC input0.05%/°C max.0.05%/°C max.
115 VAC input *6530 ms typ.520 ms typ.580 ms typ.550 ms typ.550 ms typ.600 ms typ.
230 VAC input *6330 ms typ.400 ms typ.400 ms typ.430 ms typ.490 ms typ.480 ms typ.
115 VAC input *628 ms typ.29 ms typ.32 ms typ.33 ms typ.36 ms typ.23 ms typ.
230 VAC input *6134 ms typ.138 ms typ.134 ms typ.177 ms typ.170 ms typ.154 ms typ.
Conducted Emissions Conforms to EN 61204-3 Class B, EN 55011 Class B
Radiated EmissionsConforms to EN 61204-3 Class B, EN 55011 Class B
Power rating15 W30 W
0.42 min.0.43 min.
60 mVp-p max. at 20
MHz of bandwidth
Yes, 130% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again)
3.0 kVAC for 1 min. (between all input terminals and output terminals), current cutoff 20 mA
2.0 kVAC for 1 min. (between all input terminals and PE terminals), current cutoff 20 mA
1.0 kVAC for 1 min. (between all output terminals and PE terminals), current cutoff 20 mA
–40 to 70°C (Derating is required according to the temperature. Refer to Engineering Data) (with no condensation or icing)
UL Listed: UL 508 (Listing, Class2 Output: Per UL 1310)
UL UR: UL 62368-1 (Recognition)
cUL: CSA C22.2 No.107.1 (Class2 Output: Per CSA C22.2 No.223)
cUR:CSA C22.2 No.62368-1
EN/VDE: EN 50178, EN 62368-1
PELV (EN 60204-1, EN 50178)
EN 61558-2-16
50 mVp-p max.at 20
MHz of bandwidth
30 mVp-p max. at 20
MHz of bandwidth
30 mVp-p max. at 20
MHz of bandwidth
0.42 min.0.43 min.
30 mVp-p max. at 20
MHz of bandwidth
30 mVp-p max. at 20
MHz of bandwidth
3
S8VK-G
ItemOutput voltage (VDC)12 V24 V24 V
Efficiency230 VAC input *6
Input
Output
Additional
functions
Voltage range *1
Frequency *1
Current
Power factor
Leakage current
Inrush current *2 (for
a cold start at 25
Rated output current
Boost current
Voltage adjustment range *3
Ripple & Noise
voltage *4
Input variation influence *8
Load variation influence *7
Temperature variation
85% typ.88% typ.89% typ.
Single-phase, 85 to 264 VAC, 90 to 350 VDC *10
50/60 Hz (47 to 450 Hz)50/60 Hz (47 to 63 Hz)
1.0 A typ. 1.1 A typ. 1.3 A typ.
0.6 A typ. 0.7 A typ. 0.7 A typ.
0.46 min.0.45 min.
0.94 min.
0.16 mA typ.0.24 mA typ.
0.30 mA typ.0.38 mA typ.
16 A typ. 16 A typ.
32 A typ. 32 A typ.
4.5 A 2.5 A 5 A
5.4 A 3 A 6 A
−10% to 15% (with V. ADJ) (guaranteed)
150 mVp-p max.
at 20 MHz of bandwidth
50 mVp-p max.
at 20 MHz of bandwidth
150 mVp-p max.
at 20 MHz of bandwidth
0.4% max.0.4% max.
0.8% max.0.8% max.
0.05%/°C max.0.05%/°C max.
570 ms typ. 650 ms typ. 790 ms typ.
430 ms typ. 500 ms typ. 750 ms typ.
26 ms typ. 25 ms typ. 42 ms typ.
139 ms typ. 129 ms typ.42 ms typ.
Yes, automatic resetYes, automatic reset
Yes, 130% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again)
Yes (For up to two Power Supplies, external diodes are required.)
Yes (Refer to Safety Precautions) (For up to two Power Supplies)
Yes (LED: Green), lighting from 80% to 90% or more of rated voltage
3.0 kVAC for 1 min. (between all input terminals and output terminals), current cutoff 20 mA
Insulation
Environment
Reliability
Construction
Standards
*1.
Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply
may result in ignition or burning.
*2. For a cold start at 25°C. Refer to Engineering Data on page 9 to 11 for details.
*3.
If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range. When adjusting the output voltage, confirm
the actual output voltage from the Power Supply and be sure that the load is not damaged.
*4. A characteristic when the ambient operating temperature is between –25 to 70°C.
*5. Refer to Overvoltage Protection on page 10 for the time when input voltage shuts off and input turns on again.
*6. The value is when both rated output voltage and rated output current are satisfied.
*7. 100 to 240 VAC input, in the range of 0 A to the rated output current
*8.
This is the maximum variation in the output voltage when the input voltage is gradually changed within the allowable input voltage range at the rated output voltage and rated output current.
*9. Refer to Recommended Replacement Periods and Periodic Replacement for Preventive Maintenance on page 23 for details.
*10. Safety Standards for a DC Input
The following safety standards apply to a DC input: UL 62368-1, cUR (CSA C22.2 No. 62368-1), EN 50178, EN 62368-1, and Lloyd’s.
For a DC input, safety is ensured by an external fuse.
Select an external fuse that meets the following conditions.
S8VK-G060@@: 350 VDC min, 6 A
S8VK-G12024: 350 VDC min, 5 A
*11.
Clamp filter “ZCAT2035-0930” manufactured by TDK Corporation. or equivalent should be installed in the cable connected to the input - output terminals of S8VK-G series.
Noise filter “FN2080-10-06” manufactured by SCHAFFNER Corporation. or equivalent should be connected to the Input terminals of S8VK-G series.
*12.At −40 to −25°C, time will be required before the rated output voltage is output after the input voltage is input.
Also, the ripple noise value may exceed the value shown in the above table.
Withstand voltage
Insulation resistance
Ambient operating temperature *12
Storage temperature
Ambient operating humidity0% to 95% (Storage humidity: 0% to 95%)
Vibration resistance10 to 55 Hz, 0.375 mm half amplitude for 2 h each in X, Y, and Z directions
Shock resistance150 m/s2, 3 times each in ±X, ±Y, ±Z directions
MTBF 135,000 hrs min.
Life expectancy *910 years min.
Weight260 g max.620 g max.
Cooling fanNo
Degree of protectionIP20 by EN/IEC 60529
Harmonic current emissionsConforms to EN 61000-3-2
EMI
EMSConforms to EN 61204-3 high severity levels
Approved Standards
Conformed Standards
Marine StandardsLloyd’s register *10 *11
SEMIConforms to F47-0706 (200 to 240 VAC input)
Conducted Emissions Conforms to EN 61204-3 Class B, EN 55011 Class B
Radiated EmissionsConforms to EN 61204-3 Class B, EN 55011 Class B
2.0 kVAC for 1 min. (between all input terminals and PE terminals), current cutoff 20 mA
1.0 kVAC for 1 min. (between all output terminals and PE terminals), current cutoff 20 mA
100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC
−
40 to 70°C (Derating is required according to the temperature. Refer to
Engineering Data
) (with no condensation or icing)
−40 to 85°C (with no condensation or icing)
UL Listed: UL 508 (Listing, For 60 W only Class2 Output: Per UL 1310 )
UL UR: UL 62368-1 (Recognition)
cUL: CSA C22.2 No.107.1 (For 60 W only Class2 Output: Per CSA C22.2 No.223)
cUR: CSA C22.2 No.62368-1
EN/VDE: EN 50178, EN 62368-1
PELV (EN 60204-1, EN 50178)
EN 61558-2-16
4
S8VK-G
ItemOutput voltage (VDC)24 V48 V24 V48 V
Efficiency230 VAC input *6
92% typ.93% typ.
Single-phase, 85 to 264 VAC, 90 to 350 VDC *10
50/60 Hz (47 to 63 Hz)
2.4 A typ. 4.7 A typ.
1.3 A typ. 2.3 A typ.
0.9 min.0.97 min.
0.23 mA typ.0.3 mA typ.
0.33 mA typ.0.49 mA typ.
16 A typ. 16 A typ.
32 A typ. 32 A typ.
10 A 5 A 20 A 10 A
12 A 6 A 24 A 12 A
−10% to 15% (with V.ADJ) (guaranteed)
180 mVp-p max.
at 20 MHz of bandwidth
350 mVp-p max.
at 20 MHz of bandwidth
230 mVp-p max.
at 20 MHz of bandwidth
0.4% max.0.4% max.
0.8% max.0.8% max.
0.05%/°C max.0.05%/°C max.
250 ms typ. 290 ms typ. 380 ms typ.
250 ms typ. 290 ms typ. 260 ms typ.
44 ms typ. 43 ms typ. 40 ms typ.
44 ms typ. 50 ms typ.
Yes, automatic resetYes, automatic reset
Yes, 130% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again)
Yes (For up to two Power Supplies, external diodes are required.)
Yes (Refer to Safety Precautions) (For up to two Power Supplies)
Yes (LED: Green), lighting from 80% to 90% or more of rated voltage
470 mVp-p max.
at 20 MHz of bandwidth
3.0 kVAC for 1 min. (between all input terminals and output terminals), current cutoff 20 mA
Insulation
Environment
Reliability
Construction
Standards
*1.
Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning.
*2. For a cold start at 25°C. Refer to Engineering Data on page 9 to 11 for details.
*3.
If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range. When adjusting the output voltage, confirm
the actual output voltage from the Power Supply and be sure that the load is not damaged.
*4. A characteristic when the ambient operating temperature is between –25 to 70°C.
*5. Refer to Overvoltage Protection on page 10 for the time when input voltage shuts off and input turns on again.
*6. The value is when both rated output voltage and rated output current are satisfied.
*7. 100 to 240 VAC input, in the range of 0 A to the rated output current
*8.
This is the maximum variation in the output voltage when the input voltage is gradually changed within the allowable input voltage range at the rated output voltage and rated output current.
*9. Refer to Recommended Replacement Periods and Periodic Replacement for Preventive Maintenance on page 23 for details.
*10. Safety Standards for a DC Input
The following safety standards apply to a DC input: UL 62368-1, cUR (CSA C22.2 No. 62368-1), EN 50178, EN 62368-1, and Lloyd’s.
For a DC input, safety is ensured by an external fuse.
Select an external fuse that meets the following conditions.
S8VK-G240@@: 350 VDC min, 8 A
S8VK-G480@@: 350 VDC min, 12 A
*11.
Clamp filter “ZCAT2035-0930” manufactured by TDK Corporation. or equivalent should be installed in the cable connected to the input - output terminals of S8VK-G series.
Noise filter “FN2080-10-06” manufactured by SCHAFFNER Corporation. or equivalent should be connected to the Input terminals of S8VK-G series.
*12.At −40 to −25°C, time will be required before the rated output voltage is output after the input voltage is input.
Also, the ripple noise value may exceed the value shown in the above table.
Withstand voltage
Insulation resistance
Ambient operating temperature *12
Storage temperature
Ambient operating humidity
Vibration resistance
Shock resistance
MTBF
Life expectancy *9
Weight
Cooling fan
Degree of protection
Harmonic current emissions
EMI
EMS
Approved Standards
Conformed Standards
Marine Standards
SEMI
Conducted Emissions
Radiated Emissions
2.0 kVAC for 1 min. (between all input terminals and PE terminals), current cutoff 20 mA
1.0 kVAC for 1 min. (between all output terminals and PE terminals), current cutoff 20 mA
100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC
−
40 to 70 °C (Derating is required according to the temperature. Refer to Engineering Data) (with no condensation or icing)
−40 to 85°C (with no condensation or icing)
0% to 95% (Storage humidity: 0% to 95%)
10 to 55 Hz, 0.375 mm half amplitude for 2 h each in X, Y, and Z directions
150 m/s2, 3 times each in ±X, ±Y, ±Z directions
135,000 hrs min.
10 years min.
900 g max.1,500 g max.
No
IP20 by EN/IEC 60529
Conforms to EN 61000-3-2
Conforms to EN 61204-3 Class B, EN 55011 Class B
Conforms to EN 61204-3 Class B, EN 55011 Class B
Conforms to EN 61204-3 high severity levels
UL Listed: UL 508 (Listing)
UL UR: UL 62368-1 (Recognition)
cUL: CSA C22.2 No.107.1
cUR: CSA C22.2 No.62368-1
EN/VDE: EN 50178, EN 62368-1
PELV (EN 60204-1, EN 50178)
EN 61558-2-16
Lloyd’s register *10 *11
Conforms to F47-0706 (200 to 240 VAC input)
5
S8VK-G
S8VK-G015@@ (15 W)
Voltage
detection circuit
Overcurrent
circuit
Current
detection circuit
Photocoupler
Rectifier/
smoothing
circuit
AC (L)
INPUT
AC (N)
Drive
control
circuit
Fuse:
250 VAC 4.0 A HBC
Overvoltage
detection circuit
Noise filter
Inrush
current
protection
Rectifier
Smoothing
circuit
Overcurrent
detection circuit
+V
+V
−V
−V
−V
DC OUTPUT
S8VK-G030@@ (30 W)
Voltage
detection circuit
Photocoupler
Rectifier/
smoothing
circuit
AC (L)
INPUT
AC (N)
Drive
control
circuit
Fuse:
250 VAC 6.3 A HBC
Overvoltage
detection circuit
Noise filter
Inrush
current
protection
Rectifier
Smoothing
circuit
Overcurrent
detection circuit
+V
+V
−V
−V
−V
DC OUTPUT
Overcurrent
circuit
Current
detection circuit
S8VK-G060@@ (60 W)
Connections
Block Diagrams
INPUT
Fuse:
250 VAC 3.15 A HBC
AC (L)
AC (N)
Noise filter
Rectifier
Overcurrent
detection circuit
Inrush
current
protection
Drive
control
circuit
Smoothing
circuit
Photocoupler
Rectifier/
smoothing
circuit
detection circuit
Overvoltage
detection circuit
Voltage
+V
+V
DC OUTPUT
−V
−V
6
S8VK-G
Photocoupler
Noise filter
AC (L)
INPUT
AC (N)
Fuse:
250 VAC 5.0 A HBC
Rectifier
Inrush current
protection
circuit
Smoothing
circuit
Harmonic current
suppression circuit
(Power factor improvement)
Drive control
circuit
Rectifier/smoothing circuit
Voltage
detection circuit
Overvoltage
detection circuit
+V
+V
−V
−V
−V
DC OUTPUT
Overcurrent
detection circuit
S8VK-G12024 (120 W)
Photocoupler
Noise filter
AC (L)
INPUT
AC (N)
Fuse:
250 VAC 8.0 A HBC
Rectifier
Inrush current
protection
Smoothing
circuit
Harmonic current
suppression circuit
(Power factor improvement)
Drive control
circuit
Rectifier/smoothing circuit
Voltage
detection circuit
Overvoltage
detection circuit
+V
+V
−V
−V
−V
DC OUTPUT
Overcurrent
circuit
Current
detection circuit
Overcurrent
detection circuit
S8VK-G240@@ (240 W)
Photocoupler
Noise filter
AC (L)
INPUT
AC (N)
Fuse:
250 VAC 12.0 A HBC
Rectifier
Inrush current
protection
circuit
Smoothing
circuit
Harmonic current
suppression circuit
(Power factor improvement)
Drive control
circuit
Rectifier/smoothing circuit
Voltage
detection circuit
Overvoltage
detection circuit
+V
+V
−V
−V
−V
DC OUTPUT
Overcurrent
circuit
Current
detection circuit
Overcurrent
detection circuit
S8VK-G480@@ (480 W)
7
S8VK-G
3
12
4
5
3
12
5
4
3
12
5
4
12
5
4
3
Construction and Nomenclature
Nomenclature
15-W Models30-W Models60-W Models
S8VK-G015@@S8VK-G030@@S8VK-G060@@
120-W Models240-W Models480-W Models
S8VK-G12024S8VK-G240@@S8VK-G480@@
3
4
5
12
No.NameFunction
1Input terminals (L), (N)Connect the input lines to these terminals. *1
2Protective Earth terminal (PE) Connect the ground line to this terminal. *2
3DC Output terminals (−V), (+V)Connect the load lines to these terminals.
4Output indicator (DC ON: Green)Lights while a direct current (DC) output is ON.
5Output voltage adjuster (V.ADJ)Use to adjust the voltage.
*1. The fuse is located on the (L) side. It is not user-replaceable. For
a DC input, connect the positive voltage to the L terminal.
*2. This is the protective earth terminal specified in the safety
standards. Always ground this terminal.
12
4
5
3
8