Screwless Clamp Terminal Socket PYF@@S 1
Screwless Clamp Terminal Socket
PYF@@S
• Screwless clamping greatly contributes to reducing wiring time.
• No over or under tightening of cable connection so better contact reliability is achieved.
• Double wiring possible on all the terminals, and easy bridge and
branch connections.
• Use either solid or stranded wires from 0.2 to 1.5 mm
2
(AWG24
to AWG16).
• Safe terminal arrangement: Coil terminals separated from contact terminals.
• Unique ejector enables easy relay replacement.
• Nameplate available
• Finger-protection
Ordering Information
■ List of Models
Specifications
■ Ratings/Characteristics
■ Approved Standards
4-pole for MY4/MY2 2-pole for MY2
Socket PYF14S PYF08S
Clip & Release Lever PYCM-14S PYCM-08S
Nameplate R99-11
Socket Bridge PYDM-14SR, PYDM-14SB PYDM-08SR, PYDM-08SB
Item PYF14S PYF08S Remarks
Relay MY2 Series
MY4 Series
MY2 Series ---
Dimensions 31 × 85 × 36.5 mm max. (W × H × D) 23.2 × 85 × 36.5 mm max. (W × H × D) ---
Rated voltage 250 VAC ---
Rated carry current 10 A at 55°C with MY2 (S)
7 A at 70°C with MY2 (S)
5 A at 70°C with MY4 (S)
10 A at 55°C with MY2 (S)
7 A at 70°C with MY2 (S)
VDE0627
Applicable wires
0.2 to 1.5 mm
2
(AWG24 to AWG16)
Solid wire
Stranded wire
---
Number of wire connections 2 wires per terminal (1 wire per hole) ---
Clamping force
10 N min. (0.2 mm
2
)
40 N min. (1.5 mm
2
)
EN60999
Standard File No.
VDE0627 (IEC664, EN60999) 112467UG
UL508 (UL1059) E87929 Vol. 3
CSA C22.2 No. 14 (CSA C22.2 No. 158) LR31928