Omron POWLI BX35F, POWLI BX50F, POWLI BX50FW, POWLI BX75SW Instruction Manual

Page 1
• This manual gives you important information to use the this unit safely and therefore be sure to read it before installation and use.
• Keep this manual handy at the place where you install the this unit so that you can read it whenever necessary.
Uninterruptible Power Supply (UPS)
Instruction Manual
BX35F/BX50F/BX50FW/BX75SW
Page 2
Introduction
Notes on the use of the Unit
The unit is designed and manufactured for use for OA equipment such as personal computers. Do not use it when very high reliability and safety are required as listed below.
Medical equipment that may cause death directly
Applications that may cause injury (applications that directly affect the operation and control
of planes, ships, railroads, elevators, and so on)
Applications that are always subjected to vibration such as cars and ships
Applications in which a failure of this product may cause significant damage or effect to
the society and public (essential computer systems, main communication equipment, public transportation systems, and so on)
Equipment with the same level of importance
For equipment that greatly affects the safety of people and maintaining public functions, special considerations must be taken for operation, maintenance, and management, such as duplication of the system and emergency power generation facilities.
Observe the contents of this manual such as the use conditions and environments.
If you want to use the unit for an important system that requires very high reliability, contact
us;______
Do not modify/alter the unit.
This unit is designed for use inside Japan only. Do not use overseas countries (outside
Japan).
If the voltage or frequency of the power supply differs, a failure or fire may occur.
The unit does not comply with overseas safety standards and the EMI standards/regula-
tions.
©OMRON Corporation. 2002 All Rights Reserved.
Introduction
Thank you for purchasing the POWLI BX35F/BX50F/BX50FW/BX75SW Uninterruptible Power Supply (UPS). This unit is a UPS designed specifically for personal computers.
The UPS protects (backs up) personal computers, displays, peripherals, and so on up to a power consumption of 350VA/210W (BX35F), 500VA/300W (BX50F, BX50FW), 750 VA/450W (BX75SW) from failures in the power supply, such as power failures and voltage variations.
It protects connected devices from surge coming from power line.
You can easily replace batteries by yourself.
By using the UPS monitoring software, the system can be shut down automatically when a
power failure occurs.
Read this manual thoroughly to make the most of the unit.
Disclaimers
We are not liable to all damage including malfunction and failure of equipment, connected devices, and software and other secondary damage even if it is caused by the use of our product.
Make sure to read the safety precautions before using the unit.
Note on user registration Please fill out the required items on the included user registration card and send it to our customer support center.
Page 3
1
IMPORTANT SAFETY INSTRUCTION
1.SAVE THESE INSTRUCTIONS.
This manual contains important instruction for Model BX35F, BX50F, BX50FW, BX75SW. That should be followed during instruction of the UPS and batteries.
2.SYMBOL
This symbol indicates earth ground.
This symbol indicates turning on UPS.
This symbol indicates turning off UPS.
3.INTERNAL BATTERY
Internal battery is Lead-acid type. For BX35FW, BX50F, BX50FW model, the internal battery voltage is 6V
7.2AH. Each UPS used 2pcs batteries. And the total battery voltage is 12Vdc. For BX75SW model, the internal battery voltage is 12V 7AH or 7.2AH. The UPS used 2pcs batteries. And the total battery voltage is 24Vdc.
4.TEMPERATURE RATING
Maximun ambit temperature of UPS 40°C.
5.ENVIRONMENT
The unit is intended for installation in a temperature controlled, indoor area free of conductive contaminants. This pluggable type A equipment with battery already installed by the supplier is operator installable and may be operated by laymen. During the installation of this equipment it should be assured that the sum of the leakage currents of the UPS and the connected loads does not exceed 3.5mA. The mains socket outlet that supplies the UPS shall be installed near the UPS and shall be easily accessible. For battery information, see users manual.
Page 4
2
Procedure from installation to operation
Yes
No
Start
Read “Safety precautions”
Pages 4 – 10
Perform installation and
connection Page 15
Check the operation
Page 23
Charge the battery
Page 25
Measure the backup time
Page 25
Operate Page 26
Perform maintenance and
inspection Page 36
Replace the battery
Page 37
Deteriorated battery?
Recharge the battery again
Page 25
* Preparation is complete.
Remove the product from
the package and check
the contents Page 11
Installation/connection
Preparation for operation
Maintenance/inspection
It is possible to omit the backup time measurement step.
Page 5
3
Table of Contents
Table of Contents
Introduction ....................................................................................................................................................... 1
IMPORTANT SAFETY INSTRUCTION ............................................................................................................. 1
Safety precautions ............................................................................................................................................ 4
1. Preparation .................................................................................................................................................11
1-1 Checking the contents ....................................................................................................................... 11
1-2 Part names ....................................................................................................................................... 12
1-3 Explanation of symbol used on unit .................................................................................................. 14
2. Installation and connection ........................................................................................................................ 15
2-1 Precautions and notes on installation and connection ..................................................................... 15
2-2 Installation and connection(BX35F/BX50F/BX50FW) ...................................................................... 18
2-3 Installation and connection (BX75SW) ............................................................................................. 20
2-4 Checking the operation .................................................................................................................... 23
3. Preparation for operation ........................................................................................................................... 25
3-1 Charging the battery ......................................................................................................................... 25
3-2 Measuring the initial value of backup time ....................................................................................... 25
3-3 Recharging the battery ..................................................................................................................... 25
4. Operation ................................................................................................................................................... 26
4-1 Precautions and notes on operation ................................................................................................. 26
4-2 Start and stop procedures and basic operation ................................................................................27
4-3 Interpreting beeps and displays ....................................................................................................... 29
4-4 Suspending a beep .......................................................................................................................... 31
4-5 Description of the self-diagnostic test function ................................................................................. 31
4-6 Description of the auto battery test function ..................................................................................... 31
4-7 Changing the setting of the functions ............................................................................................... 32
5. Maintenance and Inspection ..................................................................................................................... 36
5-1 Checking the battery ........................................................................................................................ 36
5-2 Replacing the battery ....................................................................................................................... 37
5-3 Cleaning ........................................................................................................................................... 42
6. Using the Contact Signal (only for BX50FW, BX75SW) ............................................................................43
7. Measuring the backup time (Checking the discharge time of the battery) ................................................ 46
7-1 Measuring method of the backup time ............................................................................................. 46
7-2 Estimated backup time ..................................................................................................................... 46
8. Troubleshooting ......................................................................................................................................... 48
9. Description of related products .................................................................................................................. 49
9-1 Using the Network Line Surge Protection Function (BX75SW Only) ............................................... 49
9-2 Using the UPS monitoring software ................................................................................................. 50
9-3 Connecting the UPS ......................................................................................................................... 51
9-4 About the included UPS monitoring software ...................................................................................52
References ...................................................................................................................................................... 53
A. Specifications ....................................................................................................................................... 53
B. Related products .................................................................................................................................. 53
C. Dimensional outline drawing (unit: mm) ............................................................................................... 54
D. Circuit block diagram ........................................................................................................................... 56
Page 6
4
Safety precautions
: Indicates prohibition. For example,
indicates that disassembly is prohibited.
: Indicates obligation. For example, indicates that grounding is necessary.
Misuse may cause death or serious injury.
Warning
Caution
Safety precautions
The safety symbols and their meaning used in this manual are as follows:
* Property damage means damage to houses/household effects, livestock, and pets.
Note that events categorized as a caution required matter also may cause more serious results under certain conditions.
Do not use this unit when very high reliability and safety are required as listed below. This unit is designed and manufactured for use with OA equipment such as personal computers.
Medical equipment or system that may cause death directly.
Applications that directly affect the safety of people (For example, the operation and control
of cars and elevators).
Applications in which a failure of the unit may cause significant damage to the society and
public (For example, essential computer systems and main communication equipment.)
Applications with the same level of importance.
Warning
Important information for safe operation is described. Be sure to read it before installation and start of use.
Misuse may cause injury or property damage.
Carry the unit considering its weight and balance, and place it on a stable and robust base.
Dropping or toppling the unit may cause injury.
The weight of this unit is approximately: 5 kg (BX35F/BX50F/BX50FW)/ 9 kg (BX75SW).
If you drop the unit, stop using it and have an inspection and repair be done.
For repair, contact us; ____
Keep plastic package bags out of reach of children.
They may put their heads into it, and may be suffocated.
Make sure to connect the AC input plug of the unit into a wall outlet (commercial power) with rated input voltage.
Connecting to a wall outlet (commercial power) of a different rated input voltage may result in
fire.
The unit may fail.
Caution (for installation and connection)
Page 7
5
Safety precautions
Do not connect devices such as dryers, which have a half-wave rectifier where only half-cycles of the AC power flows.
Overcurrent may damage the UPS.
Connect the unit to a wall outlet (commercial power) with a current capacity of 8A or more (BX35F) or 12A or more (BX50F, BX50FW, and BX75SW).
Otherwise, the power cord may be heated.
When equipment with the maximum output capacity is connected, a maximum current of 8A
or (BX35F) or 12A (BX50F, BX50FW, and BX75SW) flows.
Provide secure grounding.
For a 3P wall outlet, directly connect the AC input plug of the unit to it. Not doing so may cause
an electric shock in the case of unit failure or electric leakage.
When you use a 3P-2P conversion plug for AC input plug, be sure to perform grounding
before connecting the AC input plug into a wall outlet (commercial power). Do not disconnect the grounding before disconnecting the AC input plug from a wall outlet (commercial power).
Grounding is necessary to enable its surge protection function.
Do not disassemble, repair, or modify the unit.
Doing so may cause an electric shock or a fire.
Do not install the unit in other than specified orientations.
Dropping or toppling the unit may cause injury.
If you install the unit in an orientation other than specified, the unit cannot be protected from a
battery fluid leakage.
When installing the unit vertically, do not put any object on it. When installing the unit horizontally, do not put any object heavier than
25kg.
Doing so may cause distortion of/damage to the case, which may cause a fire.
When replacing the battery, remove objects that have been placed on the unit.
Do not use the unit where the maximum temperature exceeds 40°C.
The battery becomes week rapidly, which may cause a fire.
Doing so may cause a failure or malfunction of the unit.
Do not install or store the unit in the places listed below.
The humidity is lower than 25%. The humidity is higher than 85%. A closed place such as in a
cabinet without clearance. There is flammable gas or corrosive gas. A place subject to vibra­tion or shock. Outdoors.
Installation or storing the unit in such a place may cause a fire.
Do not use the unit in a closed place or do not cover the unit.
Doing so may cause abnormal heating or a fire.
Do not connect equipment that exceeds the output capacity of the unit.
The current protection of the unit may operate, which may stop the output.
The wiring of the plug strip heats up, which may cause a fire.
Caution (for installation and connection)
Page 8
6
Safety precautions
Do not wet or pour water onto the unit.
Doing so may cause an electric shock or a fire.
If you wet the unit, stop using it and the unit must be inspected and/or repaired.
For repair, contact us; ____
When the battery is dead, replace it immediately or stop using the unit.
Continuing the use of it may cause a fire.
Wipe the 100-VAC input plug clean of dirt with a dry cloth occasionally.
Settled dust may cause a fire.
Caution (for use)
* The values in the table are the expected life under standard
use conditions and are not guaranteed.
Ambient temperature
20°C
30°C
Expected life
4 to 5 years
2 to 2.5 years
Caution (for installation and connection)
Do not pinch or tie the cable of the unit.
Doing so may cause the cable to be damaged or heated, which may cause an electric shock or a fire.
If the cable is damaged, stop using the unit and the cable must be repaired. For repair, contact us; ____
Do not connect devices that use power supply with an improved power factor.
Overcurrent may damage the UPS.
All of the included accessories are designed to be used exclusively with the unit. Do not use the accessories with other devices.
Doing so may compromise the safety of devices.
This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit The
unit contains no user serviceable parts.Only factory service personnel may perform repairs.
Connection to any other type of receptacle other than a two-pole,three-wire grounded recep­tacle may result in shock hazard as well as violate local electical codes.
Do not allow liquids or any foreign object to enter the UPS.DO not place beverages or any other liquid-containing vessels on or near the unit.
This unit intended for installation in a controlled environment (temperature controlled, indoor area free of conductive contaminants).Avoid installing the UPS in locations where there is standing or running water,or excessive humidity.
Do not attach a power strip or surge suppressor to the UPS.
Do not attach non-computer-related items,such as medical equipment,life-support
equipment,microwave ovens,or vacuum cleaners to UPS.
With the installation of the equipment it should be prevented, that the sum of the leakage current of the UPS and the connected consumer does not exceed 3.5mA.
Page 9
7
Safety precautions
Caution (for battery replacement)
If you notice abnormal sound or smell, smoke, or leakage from the inside, immediately turn off the power switch and disconnect the AC input plug from a wall outlet (commercial power).
Using the unit under such conditions may cause a fire.
If you notice such a condition, stop using the unit and contact us at _____ for inspection and repairs.
Use the unit under the conditions in which you can immediately disconnect the AC input plug from a wall outlet (commercial power) in the case of an abnormal event.
If fluid leaks from the unit, do not touch the fluid.
Doing so may cause blindness or burns.
If the fluid contacts your eyes or skin, wash it out with lots of clean water and consult your doctor.
Caution (for maintenance)
Perform replacement on a stable and flat place.
Handle the battery carefully not to drop it.
Not doing so could cause injury or burns due to liquid (acid) leakage.
Use a specified battery for replacement.
Not doing so may cause a fire.
Product model: BXB50F (battery pack for BX35F/BX50F/BX50FW)
BXB75S (battery pack for BX75SW)
Do not replace the battery in a place where there is flammable gas.
Spark may occur when connecting the battery, which may cause an explosion or fire.
If fluid (dilute sulfuric acid) leaks from the battery, do not touch the fluid.
Doing so may cause blindness or burns.
If it contacts your eyes or skin, wash it out with lots of clean water and consult your doctor.
Do not disassemble or modify the battery.
Doing so could cause dilute sulfuric acid leak, which could cause blindness and burns.
Do not drop the battery or do not give strong impact on it.
Dilute sulfuric acid may leak.
When maintaining the connected equipment, turn OFF the power switch and disconnect the AC input plug.
Even if you disconnect the AC input plug while the UPS is operating, the power output of this unit does not stop and power is supplied from the outlet during a power failure.
Do not disassemble, repair, or modify the unit.
Doing so may cause an electric shock or a fire.
If fluid leaks from the unit, do not touch the fluid.
Doing so may cause blindness or burns.
If the fluid contacts your eyes or skin, wash it out with lots of clean water and consult your doctor.
Do not throw the unit into fire.
The lead battery in the unit may explode, or leak dilute sulfuric acid.
Caution (for use)
Page 10
8
Safety precautions
Do not short the battery with metal objects.
Doing so could cause an electric shock, fire or burn.
Some electrical energy still remains inside the spent battery.
Do not put the battery into fire or do not break it.
The battery may explode or leak dilute sulfuric acid.
A battery can present a risk of electrical shock and high short circuit current.The following
precautions should be observed when working on batteries:
1) Remove watches, rings, or other metal objects from the hands.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries.
5) Disconnect charging source prior to connecting or disconnecting batteries terminals.
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
Notes
When moving the unit from a cold place to a warm place, leave it for several hours before using it.
If the unit is moved to a warmer place and the power is turned on soon, the unit failure may occur due to condensation to the unit.
Charge the battery for at least 12 hours soon after purchasing the unit.
If you do not use the unit for a long time after the purchase, the property of the battery may deteriorate and the battery may become unusable.
To charge a battery, connect the AC input plug of the unit to a wall outlet (commercial power).
When storing the unit, charge the battery for at least 12 hours and turn off the power switch.
Even if the unit is not used, the battery gradually discharges, and if it is left for a long time, it goes into an over discharge state. The backup time may become shorter or the battery may become unusable.
The storable period of the built-in battery of the unit is 6 months after complete charging.
If you want to store the battery longer than 6 months, connect the AC input plug of the unit to a commercial
power wall outlet for at least 12 hours within 6 months.
Turn off the power switch of the unit during storage.
Do not short the output lines of the unit each other and the output lines to the ground.
The unit may fail.
Do not connect the AC input plug of the unit to its Power Supply Output Receptacle during the Battery Mode.
The unit may fail.
Do not install or store the unit in a place exposed to direct sunlight.
The rise of temperature may cause the built-in battery to deteriorate rapidly and become unusable.
Do not perform a withstand voltage test.
The input circuit has a built-in surge absorption device. A withstand voltage test may break it.
When performing an insulation resistance test, use the 250VDC range.
Caution (for battery replacement)
Page 11
9
Safety precautions
Notes
Before stopping the commercial power to the unit, turn OFF the power switch of the unit.
The unit enters Battery Mode when commercial power is stopped. If you frequently use the unit in Battery Mode, the battery life may be significantly shortened.
Do not connect a page printer (laser printer, etc.) to the unit.
The Commercial Power Mode and Battery Mode are repeated frequently, which may shorten the life of the battery.
As the peak current of a page printer is large, an excess of the connection capacity or a power failure due to instantaneous voltage drop may be detected.
Do not use the unit for devices that malfunction due to an instantaneous power failure of 10msec (0.01 second) or less.
The connected device may stop due to switching time of 10msec or less.
Do not use the unit for inductive devices such as fluorescent lamps.
Connected devices may stop due to a rectangular wave output.
Inductive devices include devices incorporating transformers, coils, motors, and so on for their input.
Do not fail to confirm the system operation beforehand if the unit is used combined with devices which power supply frequency fluctuate widely, such as private electric generator.
This unit automatically recognizes the input power frequency when input power is supplied. If the unit is connected when the input power frequency is not stable at the rated level, the unit may misidentify the power supply frequency and may fail to operate normally. (If the unit is in operation, changing from commercial power supply to another power supply source, such as generating equipment, will cause no problem.)
Do not fail to confirm the system operation beforehand if the unit is used other than “Output 100V mode”. (for BX50FW/BX75SW only)
At the time of battery operation, the maximum voltage (peak voltage) of output (rectangular wave) may be lower than the maximum voltage at the time of usual operation (commercial power supply). For this reason, some connected devices may fail to operate normally.
Battery recycling
This unit uses lead acid batteries. The lead acid batteries are precious recyclable resources. Please cooperate recycling. For information on recycling, please contact our Electronic Systems & Equipments repair center.
Pb
Page 12
10
Safety precautions
Explanation
Usual operation
You may either leave the power switch of the unit on (operation status) or turn it off each time when stopping the connected system. You can choose either of the operation methods for your convenience. We recom­mend turning off the power switch when you do not use connected devices for a long time.
The battery is charged when the AC input plug of the unit is connected to a wall outlet (commercial power).
End of Battery Mode
If a power failure lasts long, the battery discharges and power output from the unit stops. Shut down your computer after performing appropriate procedure (for example, saving data) while the unit supplies power.
Reboot
If the battery discharges completely during a power failure, the unit stops. After the recovery from the power failure, the unit automatically restarts and supplies power. If you do not want to restart connected devices, turn off the power switch of either the unit or the connected devices.
Page 13
11
1. Preparation
BX35F BX50F BX50FW BX75SW
User’s manual 1 1 1 1
Warranty 1 1 1 1
User registration card 1 1 1 1
3P-2P conversion adaptor 1 1 1 1
Label (How to determine operating status) 1 1 1 1
Rubber feet None None None 4
Vertical stand 1 set (2 pieces) 1 set (2 pieces) 1 set (2 pieces) None
1. Preparation
1-1 Checking the contents
Check whether all the package contents are included and there is no damage found on their appearance. If you should notice defects or anything wrong, contact us; ____
(1) Accessories related to the main unit
(2) UPS monitoring software
BX35F BX50F BX50FW BX75SW
User’s manual 1 1 1 1
CD-ROM 1 1 1 1
Communication cable 1 (USB) 1 (USB) 1 (RS-232C) 1 (RS-232C)
Page 14
12
1. Preparation
1-2 Part names
BX35F/BX50F
BX50FW
Front view
Rear view
Digital Status Indicator
Beep Stop/Test Switch
Battery Replacement Indication Lamp
Power Switch
Battery Replacement Cover
Grounding Terminal
AC Input Cord/Plug
Power Supply Output Receptacle
AC Input Overcurrent Protection
USB Communication Connector
DIP Switch
Digital Status Indicator
Beep Stop/Test Switch
Battery Replacement Indication Lamp
Power Switch
Battery Replacement Cover
AC Input Cord/Plug
Power Supply Output Receptacle
Communication Method Selection Switch
Serial/Contact Communication Connector
AC Input Overcurrent Protection
DIP Switch
Front view
Rear view
Page 15
13
1. Preparation
BX75SW
Front view
Rear view
Digital Status Indicator
Beep Stop/Test Switch
Battery Replacement Indication Lamp
Power Switch
Battery Replacement Cover
Grounding Terminal
Network Surge Protection (Optional)
AC Input Cord/Plug
Power Supply Output Receptacle
AC Input Overcurrent Protection
DIP Switch
Communication Method Selection Switch
Serial/Contact Communication Connector
Page 16
14
1. Preparation
1-3 Explanation of symbol used on unit
Symbol Description
Start the UPS.
Stop the UPS.
Suspend a beep.
UPS output power enable, supplied by operating on line mode, battery mode.
UPS has Error.
Page 17
15
2. Installation and connection
Carry the unit considering its weight and balance, and place it on a stable and robust base.
Dropping or toppling the unit may cause injury.
The weight of this unit is approximately: 5 kg (BX35F/BX50F/BX50FW)/ 9 kg (BX75SW).
If you drop the unit, stop using it and have an inspection and repair be done.
For repair, contact us; ____
Keep plastic package bags out of reach of children.
They may put their heads into it, and may be suffocated.
Make sure to connect the AC input plug of the unit into a wall outlet (commercial power) with rated input voltage.
Connecting to a wall outlet (commercial power) of a different rated input voltage may result in fire.
The unit may fail.
Do not connect devices such as dryers, which have a half-wave rectifier where only half-cycles of the AC power flows.
Overcurrent may damage the UPS.
Connect the unit to a wall outlet (commercial power) with a current capacity of 8A or more (BX35F) or 12A or more (BX50F, BX50FW, and BX75SW).
Otherwise, the power cord may be heated.
When equipment with the maximum output capacity is connected, a maximum current of 8A
or (BX35F) or 12A (BX50F, BX50FW, and BX75SW) flows.
Provide secure grounding.
For a 3P wall outlet, directly connect the AC input plug of the unit to it. Not doing so may cause an electric shock in the case of unit failure or electric leakage.
When you use a 3P-2P conversion plug for AC input plug, be sure to perform grounding before connecting the AC input plug into a wall outlet (commercial power). Do not disconnect the grounding before disconnecting the AC input plug from a wall outlet (commercial power).
Grounding is necessary to enable its surge protection function.
Do not disassemble, repair, or modify the unit.
Doing so may cause an electric shock or a fire.
Do not install the unit in other than specified orientations.
Dropping or toppling the unit may cause injury.
If you install the unit in an orientation other than specified, the unit cannot be protected from a
battery fluid leakage.
When installing the unit vertically, do not put any object on it. When installing the unit horizontally, do not put any object heavier than 25kg.
Doing so may cause distortion of/damage to the case, which may cause a fire.
When replacing the battery, remove objects that have been placed on the unit.
Caution
(for installation and connection)
2. Installation and connection
2-1
Precautions and notes on installation and connection
Page 18
16
2. Installation and connection
Notes
When moving the unit from a cold place to a warm place, leave it for several hours before using it.
If the unit is moved to a warmer place and the power is turned on soon, the unit failure may occur due to condensation to the unit.
Charge the battery for at least 12 hours soon after purchasing the unit.
If you do not use the unit for a long time after the purchase, the property of the battery may deteriorate and the battery may become unusable.
To charge a battery, connect the 100 VAC input plug of the unit to a wall outlet (commercial power).
When storing the unit, charge the battery for at least 12 hours and turn off the power switch.
Even if the unit is not used, the battery gradually discharges, and the battery is left for a log time, it goes into an over discharge state. The backup time may become shorter or the battery may become unusable.
The storable period of the built-in battery of the unit is 6 months after complete charging.
If you want to store the battery longer than 6 months, connect the AC input plug of the unit to a commercial
power wall outlet for at least 12 hours within 6 months.
Turn off the power switch of the unit during storage.
Caution
(for installation and connection)
Do not use the unit where the maximum temperature exceeds 40°C.
The battery becomes week rapidly, which may cause a fire.
Doing so may cause a failure or malfunction of the unit. Do not install or store the product in
the places listed below.
Do not install or store the unit in the places listed below.
The humidity is lower than 25%. The humidity is higher than 85%. A closed place such as in a cabinet without clearance. There is flammable gas or corrosive gas. A place subject to vibra­tion or shock. Outdoors.
Installation or storing the unit in such a place may cause a fire.
Do not use the unit in a closed place or do not cover the unit.
Doing so may cause abnormal heating or a fire.
Do not connect equipment that exceeds the output capacity of the unit.
The current protection of the unit may operate, which may stop the output.
The wiring of the plug strip heats up, which may cause a fire.
Do not pinch or tie the cable of the unit.
Doing so may cause the cable to be damaged or heated, which may cause an electric shock or a fire.
If the cable is damaged, stop using the unit and the cable must be repaired. For repair, contact us; ____
Do not connect devices that use power supply with an improved power factor.
Overcurrent may damage the UPS.
All of the included accessories are designed to be used exclusively with the unit. Do not use the accessories with other devices.
Doing so may compromise the safety of devices.
Page 19
17
2. Installation and connection
Notes
Do not short the output lines of the unit each other and the output lines to the ground.
The unit may fail.
Do not connect the AC input plug of the unit to its Power Supply Output Receptacle during the Battery Mode.
The unit may fail.
Do not connect a page printer (laser printer etc.) to the unit.
The Commercial Power Mode and Battery Mode are repeated frequently, which may shorten the life of the battery.
As the peak current of a page printer is large, an excess of the connection capacity or a power failure due to instantaneous voltage drop may be detected.
Do not use the unit for devices that malfunction due to an instantaneous power failure of 10msec (0.01 second) or less.
The connected device may stop due to the switching time of 10msec or less.
Do not use the unit for inductive devices such as fluorescent lamps.
Connected devices may stop due to a rectangular wave output.
Inductive devices include devices incorporating transformers, coils, motors, and so on for their input.
Do not fail to confirm the system operation beforehand if the unit is used combined with devices which power supply frequency fluctuate widely, such as private electric generator.
This unit automatically recognizes the input power frequency when input power is supplied. If the unit is connected when the input power frequency is not stable at the rated level, the unit may misidentify the power supply frequency and may fail to operate normally. (If the unit is in operation, changing from commercial power supply to another power supply source, such as generating equipment, will cause no problem.)
Do not install or store the unit in a place exposed to direct sunlight.
The rise of temperature may cause the built-in battery to deteriorate rapidly and become unusable.
Do not perform a withstand voltage test.
The input circuit has a built-in surge absorption device. A withstand voltage test may break it.
When performing an insulation resistance test, use the 250 VDC range.
Before stopping the commercial power to the unit, turn OFF the power switch of the unit.
The unit enters Battery Mode when commercial power is stopped. If you frequently use the unit in Battery Mode, the battery life may be significantly shortened.
Do not fail to confirm the system operation beforehand if the unit is used other than "Output 100V mode". (for BX50FW/BX75SW only)
At the time of battery operation, the maximum voltage (peak voltage) of output (rectangular wave) may be lower than the maximum voltage at the time of usual operation (commercial power supply). For this reason, some connected devices may fail to operate normally.
Page 20
18
2. Installation and connection
(2) Install the unit.
Do not install the unit in any position other than those indicated below.
2-2 Installation and connection(
BX35F/BX50F/BX50FW
)
Connection to back up your computer and peripherals
Write the usage start date on the label on the top side. Also, by using the included UPS monitoring software, possible to keep a record of usage start date by the software.
(1) Disconnect all AC input plugs of your computer and peripherals from a wall outlet (commercial power).
Note
Before installing this device, make a record of the serial number of this device. The serial number is required when contacting us about the device. The serial number is written in the label on the unit.
Do not position the unit in the ways shown below.
Front panel
Horizontal BX35F/BX50F/BX50FW
Vertical BX35F/BX50F/BX50FW
(Attach the included stand so that the left side is the bottom.)
• Detach the rubber feet from the bottom surface when positioning vertically.
• Once the rubber feet are removed, protrusions on the bottom surface will become visible. Align the stand with these protrusions to attach it.
Front panel facing upward
Front panel facing downward
Ver tical (Right side at bottom)
Upside down
Front panel
Computer
Modem or other
peripheral
Wall outlet
(commercial power)
Page 21
19
2. Installation and connection
(3) Connect devices that require backup to the unit’s power supply output receptacle.
When the unit’s 3 output receptacles (the BX35F/50F has 3, the BX50FW has 2) are insufficient, increase the number of output receptacles by attaching a separately purchased power strip.
<Connection example 1>
• Even when the connected device has a 2P AC input plug, it can be connected to the power supply output receptacle.
However, when a 2P AC input plug has a ground wire, attach the ground wire to the grounding terminal ( ) on the back of the unit.
<When connected device has 3P plug> <When connected device has 2P plug> <When connected device has 2P plug + ground>
<Connection example 2>
PC
PC
Separately purchased power strip
External HD
Modem or other peripheral
Plug of connected device
Connect directly Connect directly Connect the plug directly
Plug of connected device
Plug of connected device
The unit’s power supply output receptacle
Connect the ground wire to the
grounding terminal ( ) on the unit
Page 22
20
2. Installation and connection
2-3 Installation and connection (BX75SW)
Connection to back up your computer and peripherals
(1) Disconnect all computer and peripheral AC input plugs from the wall outlet (commercial power).
AC input plug
of the unit
Plug of connected device
Connect it directly.
Use the attached 3P-2P Conversion Plug.
Attached 3P-2P Conversion Plug
Wall outlet
(commercial power)
Connect the grounding wire to the grounding terminal equipped to the building. (If no grounding terminal is available, a means of grounding must be constructed.)
Wall outlet
(commercial power)
(4) When the installation and connection are complete, connect the AC input plug of this unit to a wall outlet
(commercial power).
When you connect the AC input plug of this unit to a wall outlet (commercial power), battery charging automatically starts regardless of the on/off state of the Power Switch and charging completes within 12 hours.
< 3P wall outlet > < 2P wall outlet >
• This unit was charged before shipment, but if it is being used for the first time, the backup time may be reduced due to natural discharge. We recommend charging the unit before use.
Computer
Modem or other
peripheral
Wall outlet
(commercial power)
Page 23
21
2. Installation and connection
(2) Install the unit.
Do not use this unit in any position other than the “proper positions” indicated in the illustration below.
Write the usage start date on the label on the side. Also, by using the included UPS monitoring software, possible to keep a record of usage start date by the software.
Vertical Proper positions
* Attach the rubber feet to each of the four corners on the bottom surface of the unit.
Horizontal
Improper positions
The left surface in on the bottom.
✕✕
The front surface in on the bottom.
The back surface in on the bottom.
Page 24
22
2. Installation and connection
(3) Connect devices that require backup to the unit’s power supply output receptacle.
A total of up to 750VA (7.5A) or 450W can be connected.
(4) When installation and connection are complete, connect the unit’s AC input plug to a wall outlet (commer-
cial power).
When the AC input plug is connected to a wall outlet (commercial power), the battery automatically starts charging, taking up to 12 hours to complete.
< 3P wall outlet > < 2P wall outlet >
• Even when the connected device has a 2P AC input plug, it can be connected to the power supply output receptacle.
However, when a 2P AC input plug has a ground wire, attach the ground wire to the grounding terminal ( ) on the back of the unit.
AC input plug
of the unit
Plug of connected device
Connect it directly.
Use the attached 3P-2P Conversion Plug.
Attached 3P-2P Conversion Plug
Wall outlet
(commercial power)
Connect the grounding wire to the grounding terminal equipped to the building. (If no grounding terminal is available, a means of grounding must be constructed.)
Wall outlet
(commercial power)
• This unit was charged before shipment, but if it is being used for the first time, the backup time may be reduced due to natural discharge. We recommend charging the unit before use.
<Connection example 1> <Connection example 2>
PC
PC
External HD
Modem or other peripheral
Separately purchased power strip
Page 25
23
2. Installation and connection
2-4 Checking the operation
When you are complete with connecting devices to the unit, the backup function must be confirmed.
Check that the Battery Mode is performed normally according to the following procedure.
This operation check simulates a power failure by disconnecting the AC input plug from a wall outlet.)
(1) Turn on the Power Switch of this unit.
The beeper sounds and the current settings are displayed on the LED.
After 5 secounds, the self-diagnostic test is performed in Battery Mode for approximately 10 seconds.
When the self-diagnostic test finishes successfully, switching to AC output from commercial power is per­formed and the following display is obtained.
(If the battery voltage is low, the self-diagnostic test is not performed and the operation starts immediately, using output from commercial power.)
(2) Bring all the connected devices into operation.
(Including devices connected to the AC outlet of your PC.)
Operate the devices in a way in which abrupt power stop does not damage the connected devices, data, etc.
(3) Under this condition, check the LED display and a beep of this unit.
Are they in the same status as shown below?
Are the same as shown above. The operation is normal. Proceed to (4). Are not the same as shown above. The operation is abnormal. One of the description in "4. Display
and beeps when there is an equipment failure" of "4-3 Interpreting a beep and display" on page 29 must apply. Take necessary measures and then proceed to (4).
(4) Disconnect the AC input plug of this unit from a wall outlet (commercial power).
The UPS enters Battery Mode.
Status indicator Description
Power switch “ON”
Operating normally
Status indicator
Beep
Power supply output receptacles
None
Outputs power (connected devices are powered)
Page 26
24
2. Installation and connection
(5) In Battery Mode, check the LED display and a beep of the unit.
Are the LED display in the same status as A or B below?
Are not the same as shown above. Operation is abnormal. Check the status of lamps and beep and
turn off the Power Switch.
• If the display is one of those shown in “4. Displays and beeps when there is an equipment failure” in “4-3 Interpreting beeps and displays” on page 29, take the necessary measures and then go back to (1) on page 23.
• If no Battery Mode is performed and the UPS and the connected devices stop, insufficient charging of the battery is suspected.
Connect the AC input plug of the UPS to a wall outlet (commer­cial power), charge the battery for approximately 6 hours, and then go back to (4) on page 23.
• If the problem persists after checking the 2 points above, con­tact us; ____
(6) Connect the AC input plug to a wall outlet (commercial power) again.
The Status indicator stops blinking and turns on without intervals, and the beeper stops. (The status is as shown below.)
Checking the operation is now complete.
Installation and connection is now complete.
( indicates blinking)
Status indicator Description
Backup is operating due to power failure or AC input error.
The battery will be depleted if backup operation continues.
(Same as above.)
Battery level is low, so output will stop soon.
Battery is dead, so output stopped. (This is displayed only
for a few seconds.)
Status indicator Description
Power switch “ON”
Operating normally
Beep
Intermittent
4-second
intervals
Intermittent
1-second
intervals
None
Output
ON
ON
OFF
Charging
OFF
Discharging
OFF
Discharging
OFF
Discharging
Page 27
25
3. Preparation for operation
3. Preparation for operation
3-1 Charging the battery
When you connect the AC input plug of this unit to a wall outlet (commercial power), the battery charg­ing automatically starts regardless of the on/off state of the Power Switch, and it is fully charged within 12 hours.
This unit has been charged prior to shipment. However, the backup time becomes shorter when using it for the first time due to spontaneous discharge. We recommend charging this unit before using it.
If you do not perform the initial backup time measurement described below in “3-2 Measuring the initial value of backup time”, proceed to “4. Operation”. Page 26
3-2 Measuring the initial value of backup time
When you measure the backup time initial value of the unit in your environment, this value can be used as a guide when checking the battery and deciding the UPS monitoring software setting values.
See also
"7. Measuring the backup time" Page 46
3-3 Recharging the battery
The battery is discharged completely when the backup time is measured, so you need to recharge it before using the UPS.
You can use connected devices while recharging the battery, but the backup time when a power failure occurs is shorter until the battery is fully charged. (If a power failure occurs immediately after the start of charging, backup stops immediately.)
See also
Charge the battery as described in "3-1 Charging the battery."
Preparation for starting operation is now complete.
Page 28
26
4. Operation
4. Operation
4-1 Precautions and notes on operation
Do not wet or pour water onto the unit.
Doing so may cause an electric shock or a fire.
If you wet the unit, stop using it and the unit must be inspected and/or repaired.
For repair, contact us; ____
When the battery is dead, replace it immediately or stop using the unit.
Continuing the use of it may cause a fire.
For more on how to check the battery, see “5. Maintenance and inspection” on page 36.
For more on how to replace the battery, see“5-2 Replacing the battery” on page 37.
Wipe the AC input plug clean of dirt with a dry cloth occasionally.
Settled dust may cause a fire.
If you notice abnormal sound or smell, smoke, or leakage from the inside, immediately turn off the power switch and disconnect the AC input plug from a wall outlet (commercial power).
Using the unit under such conditions may cause a fire.
If you notice such a condition, stop using the unit and contact us at _____ for inspection and repairs.
Use the unit under the conditions in which you can immediately disconnect the AC input plug from a wall outlet (commercial power) in the case of an abnormal event.
If fluid leaks from the unit, do not touch the fluid.
Doing so may cause blindness or burns.
If the fluid contacts your eyes or skin, wash it out with lots of clean water and consult your doctor.
Caution (for use)
* The values in the table are the expected life under standard
use conditions and are not guaranteed.
Ambient temperature
20°C
30°C
Expected life
4 to 5 years
2 to 2.5 years
Notes
Before stopping the commercial power to the unit, turn OFF the power switch of the unit.
The unit enters Battery Mode when commercial power is stopped. If you frequently use the unit in Battery Mode, the battery life may be significantly shortened.
Page 29
27
4. Operation
4-2 Start and stop procedures and basic operation
When the AC input plug is connected to a wall outlet and the power switch is in the OFF position:
• The status indicator displays " ".
• Power output is stopped.
• The battery is charged automatically.
Start procedure
Operation
Turn on the power switch of the UPS.
• The details of the most recent error are displayed. (item 4 on page 29)
• The beeper sounds and the current setting is displayed on the status indicator. Cold start ON/OFF setting Output voltage setting.
• The status indicator displays “ ”, and the self-diagnostic test is performed in Battery Mode for about 10 seconds. (If the battery voltage is low, the self-diagnostic test is not performed. It is automatically executed after the battery is charged.)
• When the self-diagnostic test finishes successfully, switching to AC output from commercial power is performed and normal operation starts.
• If the self-diagnostic test is not executed, the UPS immediately starts outputting AC from commercial power.
Explanation
Usual operation
You may either leave the power switch of the unit on (operation status) or turn it off each time when stopping the connected system. You can choose either of the operation methods for your convenience. We recom­mend turning off the power switch when you do not use connected devices for a long time.
The battery is charged when the AC input plug of the unit is connected to a wall outlet (commercial power).
End of Battery Mode
If a power failure lasts long, the battery discharges and power output from the unit stops. Shut down your computer after performing appropriate procedure (for example, saving data) while the unit supplies power.
Reboot
If the battery discharges completely during a power failure, the unit stops. After the recovery from the power failure, the unit automatically restarts and supplies power. If you do not want to restart connected devices, turn off the power switch of either the unit or the connected devices.
• During operation, the battery is charged automatically.
Status indicator
Beep
Power supply output receptacles
None
Outputs power (connected devices are powered)
Page 30
28
4. Operation
Operation during a power failure
• If a power failure or abnormal input power supply occurs, the UPS automatically switches to Battery Mode, continuing power output from the Power Supply Output Receptacles supplied from the battery.
• The status is displayed and the beeper sounds intermittently to alert the user.
See also
Setting switch 1 can be used to turn the beeper ON/OFF. Page 32
Operation during recovery from a power failure
• If a power failure or abnormal power input is resolved while the UPS supplies power, it returns to the commercial power output status automatically. Charging the consumed battery starts.
• If a power failure or abnormal power input is resolved after the battery is discharged completely and power output is stopped, the UPS restarts automatically and resumes power output. Charging the con­sumed battery starts.
Stop procedure
Operation
Turn on the power switch of the UPS.
• The power output from the UPS stops.
• Even if you turn off the power switch, if 1AC is supplied from commercial power, the battery is automati­cally charged.
Status
indicator
Battery
replacement
Beep Output Charging Description Solution
Intermittent
4-second
intervals
Intermittent
1-second
intervals
None
OFF
Discharging
ON
OFF
Discharging
ON
OFF
Discharging
OFF
Backup is operating due to power failure or AC input error. The battery will be depleted if backup operation continues.
Perform shutdown operations for the connected devices and stop them.
(Same as above.) Battery level is low, so output will stop soon.
(Same as above.)
Battery is dead, so output stopped. (This is displayed only for a few seconds.)
Charge the battery.
Status
indicator
Battery
replacement
Beep Output Charging Description
None ONOFF
There is AC input Power switch “OFF”
( indicates blinking)
Page 31
29
4. Operation
4-3 Interpreting beeps and displays
Status
indicator
No.
1
2
3
Battery
replacement
Beep Output Charging Description Solution
None
None
None
OFF
ON
ON
OFF
OFF
ON
No AC input Operation stopped
There is AC input Power switch “OFF”
Power switch “ON” Operating normally
1. Displays and beeps during normal operation
indicates blinking
4
5
None
None
OFF
Discharging
OFF
Discharging
ON
ON
Self-diagnostic test in progress
Auto battery test in progress
2. Displays and beeps while testing
6
7
8
None
Intermittent
4-second
intervals
Intermittent
1-second
intervals
OFF
Discharging
OFF
Discharging
OFF
Discharging
ON
ON
OFF
Backup is operating due to power failure or AC input error. The battery will be depleted if backup operation continues.
Perform shutdown operations for the connected devices and stop them.
(Same as above.)
Charge the battery.
(Same as above.) Battery level is low, so output will stop soon.
Battery is dead, so output stopped. (This is displayed only for a few seconds.)
9
10
None
None
(ON)
(ON)
OFF
OFF
AC input voltage or frequency is too high (over) Power switch “OFF”
Use within the input voltage/frequency range described in the specifications.
(Same as above.)
AC input voltage or frequency is too low (under) Power switch “OFF”
3. Displays and beeps during power failure or AC input error
11
Intermittent
0.5-second intervals
ON, or
Discharging
ON
Reduce the number of connected devices until the display appears as in status No. 3.
There are too many connected devices and the rated capacity is exceeded. If this status continues for 5 minutes or more, the status No. 12 occurs and output stops.
12
Continuous
ON, or
Discharging
OFF
Turn OFF this unit and all connected devices. Reduce the number of connected devices, and then turn ON this unit and the connected devices.
Stopped due to excess connection capacity. When the connection capacity is 120% or more, the unit immediately enters this status without first entering status No. 11.
4. Displays and beeps when there is an equipment failure
Page 32
30
4. Operation
Status
indicator
No.
13
14
16
17
18
15
Battery
replacement
Beep Output Charging Description Solution
Continuous
Continuous
Continuous
ON, or
Discharging
OFF
OFF
OFF
Stopped because of output short-circuit.
Stopped because of failure.
Stopped because of output voltage error (over).
Continuous
OFF
Stopped because of output voltage error (under).
Continuous
OFF
Stopped because of battery charge voltage error (over).
Continuous
OFF
Stopped because of battery charge voltage error (under).
4. Displays and beeps when there is an equipment failure
(continued)
indicates blinking
20
Intermittent
2-second
intervals
ONON The battery test detected a weak battery.
Charge the battery. You can replace the weak battery with a separately purchased replacement battery as needed.
Check that the AC input of connected devices is not short-circuited.
Details of error are displayed only when the “Beeper stop” switch is pressed while in status No. 14.
(Same as above.)
(Same as above.)
(Same as above.)
19
Continuous
OFF
Stopped because of abnormal internal temperature.
(Same as above.)
Turn OFF this unit and all connected devices. Then, turn the power switch back ON for this unit only. If the display does not change, there is a problem with the UPS. Contact the shop of purchase or our Electronic Systems & Equipments customer support center at: _____.
5. Display and beep for battery replacement
21
Cold start ON setting UPS can start up even when there is no AC input
22
Cold start OFF setting UPS can start up only when there is AC input
23
Output 100V mode Output voltage is 100V (effective value)
24
Output 110V mode Output voltage is 110V (effective value)
25
Output 115V mode Output voltage is 115V (effective value)
26
Output 120V mode Output voltage is 120V (effective value)
6. UPS operation mode setting display
Page 33
31
4. Operation
4-4 Suspending a beep
You can suspend a beep by pressing and holding the Beep Stop/Test Switch while a beep is sounding for 0.5 second or longer.
4-5 Description of the self-diagnostic test function
You can use the following procedure to check whether a failure occurs inside the unit and whether replacing the battery is required.
If the battery is not fully charged, the self-diagnostic test is not executed immediately. After charging is complete, it is automatically executed.
(1) Connect your computer and other devices to the UPS and then turn on the power switch of the UPS.
(2) Press and hold the Beep Stop/Test Switch of the UPS for 0.5 second or longer.
Release the Beep Stop/Test Switch when a beep sounds. The Battery Mode starts for testing purpose. (No beep sounds.) When the test is complete, the normal operation automatically starts.
(3) If the status indicator/battery replacement lamp blinks and the beeper sounds:
See also
"4-3 Interpreting a beep and display" Page 29
Follow the directions for the solutions described in “4. Displays and beeps when there is an equipment failure” and “5. Display and beep for battery replacement”.
4-6 Description of the auto battery test function
This UPS provides functions to automatically check whether replacing the battery is required and whether the internal circuit is at fault. (You do not have to perform any operation.)
The test is performed at intervals of 4 weeks after the AC Input Plug is connected to a wall outlet (commercial power).
The test is not performed if the power switch is OFF or if the battery is not fully charged.
(1) When the auto battery test starts, the Battery Mode automatically starts. (No beep sounds.) After the auto
battery test is complete, the normal operation automatically starts.
(2) If the status indicator/battery replacement lamp blinks and the beeper sounds:
See also
"4-3 Interpreting a beep and display" Page 29
Follow the directions for the solutions described in “4. Displays and beeps when there is an equipment failure” and “5. Display and beep for battery replacement”.
The setting switch on the rear of the UPS allows you to select the "disable the auto battery test" setting.
See also
"4-7 Changing the setting of the functions" Page 32 See "Auto battery test ON/OFF setting."
Page 34
32
4. Operation
4-7 Changing the setting of the functions
1. Selecting functions with the setting switches
Operation
After changing the setting switches, turn ON the power switch again while the AC input plug is
connected to a wall outlet (commercial power).
• Otherwise, the change will not take effect.
Power output stop delay time setting (setting switch 1 ) … Factory-shipped setting: OFF
OFF: The beeper sounds when an alarm is necessary.
ON: The beeper does not sound for backup operation or battery replacement. The beeper sounds for
other errors (connection capacity exceeded, operation error, etc.).
Auto restart setting (setting switch 2 ) … Factory-shipped setting: OFF
ON
1 2
56783 4
OFF: Automatically restarts when power is restored.
After a power failure occurs and the unit shuts down using the shutdown software or contact signal, the unit automatically starts and begins to output when the commercial power is restored.
ON: Does not automatically restart when power is restored.
After the unit shuts down using the shutdown software or contact signal, it does not start up when commercial power is restored. Startup is performed manually by turning the power switch OFF once, and then back ON again.
Auto battery test ON/OFF setting (setting switch 3 ) … Factory-shipped setting: OFF
ON
1 2
53 4 86 7
OFF: The battery test is automatically executed at intervals of 4 weeks.
ON: The auto battery test is disabled.
Use this setting to disable Battery Mode in for the regularly performed auto battery test.
ON
1 2
53 4 86 7
Page 35
33
4. Operation
Power output stop delay time setting (setting switches 5 and 6 ) … Factory- shipped setting: OFF and OFF (Only for BX50FW and BX75SW)
The UPS delays the shutdown timing.
If the user sets “switch 5: ON, switch 6: ON”, the UPS does not stop the output, even if the backup stop (BS) is valid.
ON
1 2 3 4
5678
ON
OFF
ON
OFF
ON
AC input
BS signal
UPS output
OFF
Shutdown delay timing This delay corresponds to the settings for switch 5 and switch 6 .
This timing is 10 ms or 10 sec. Timing corresponds to the settings for switch 7 .
0 second
60 seconds
120 seconds
Setting switch 5 Setting switch 6
OFF OFF
ON OFF
OFF ON
ON ON
Does not stop power output
Power output stop
delay time
<Note>
The remote ON/OFF signal is not related to this setting.
When the remote ON/OFF signal is “High”, the UPS stops the output immediately.
Page 36
34
4. Operation
UPS stop signal setting (setting switch 7 ) … Factory-shipped setting: OFF (Only for BX50FW, BX75SW)
OFF: The unit’s power output can be stopped by inputting a “High” backup power supply stop signal (BS)
that continues for 10 seconds or more. The power supply output is stopped with a voltage signal input, even in commercial operation.
After stopping power output, a “Low” backup power supply stop signal (BS) restarts the unit once the commercial power supply is normal. However, it does not restart if the automatic restart setting (setting switch 2 ) is ON.
ON: The unit’s power output can be stopped by inputting a “High” backup power supply stop signal (BS)
that continues for 0.01 (10 ms) seconds or more. Power supply output can be stopped when the stop signal is received, only during backup operation (Battery Mode).
After stopping power output, a “Low” backup power supply stop signal (BS) restarts the unit once the error that caused the power failure is eliminated.
Use this setting in commercial operation when you do not want to stop operations when a backup power supply stop signal (BS) is received.
Communication connector 9th-pin output signal switching setting (setting switch 8 ) …Factory-shipped setting: OFF (Only for BX50FW, BX75SW)
* Valid only when using contact signal interface.
ON
1 2
53 4 86 7
OFF: Outputs a signal when a deteriorated battery needs to be replaced (WB signal)
ON: Outputs the BU inversion signal
2. Switching switch (Only for BX50FW, BX75SW)
ON
1 2
53 4 86 7
Caution
• Before operating the switching switch, turn OFF the power switch of the main unit and unplug the AC input plug (turn OFF the AC input).
• If the switching switch is changed during operation, communication with peripherals (PC, etc.) will cease to perform normally.
• If the AC input plug is not disconnected, the switching switch setting changes will not become valid.
Use when switching the communication interface (serial communication, contact com­munication).
Contact
Serial
Page 37
35
4. Operation
3-1. The UPS operation mode can be set if the power switch is turned ON while the beeper stop switch is
pressed.
Note: While in setting mode, output from the output receptacles are OFF, even if the power switch is ON.
How to make settings:
There are 2 items to select.
1) Cold start ON/OFF setting
2) Output voltage setting (only for BX50FW, BX75SW)
(1) When the beeper stop switch is pressed (for less than 3 seconds), the next item is displayed.
(2) Setting mode starts if the beeper stop switch is held (for more than 3 seconds).
(3) When the power switch is turned OFF, setting mode quits and it returns to normal status (Status
No.2).
Note: The output voltage setting is disabled for the BX35F and BX50F.
(Example: When making output power supply settings, selection between 110V/115V/120V modes is not possible. Only 100V mode is possible.)
Cold start ON/OFF setting Output voltage setting
(A) Turn ON the power switch while the beeper stop switch is pressed. (B) Turn OFF the power switch. (C) Press and hold the beeper stop switch (for more than 3 seconds). (D) Press the beeper stop switch (for less than 3 seconds).
3. UPS operation mode settings
The settings available for this operation are shown below.
• Cold start ON/OFF setting When ON, it is possible to start up the unit even when there is no AC input plug.
(It is not possible, however, to start up the unit by the remote signals.)
• Output voltage setting (100V/110V/115V/120V) Four types of output voltage can be set. (Applicable only for BX50FW and BX75SW)
Cold start ON: The unit can start up even when there is no AC input
Output 100V mode
Output 110V mode
Output 115V mode
Output 120V mode
Cold start OFF: The unit can start up only when there is AC input
Setting mode
Normal status “ ” There is AC input
Power switch “OFF” (Status No. 2)
(A) (B)
(D)
(C)
(C)
(C)
(C)
(D)
(D)
(D)
(D)
(D)
(D)
(D)
ON
OFF
100V
110V
115V
120V
Cold start
ON/OFF setting
Output voltage setting
Only for BX50FW, BX75SW
Page 38
36
5. Maintenance and inspection
When maintaining the connected equipment, turn OFF the power switch and disconnect the AC input plug.
Even if you disconnect the AC input plug while the UPS is operating, the power output of this unit does not stop and power is supplied from the outlet during a power failure.
Do not disassemble, repair, or modify the unit.
Doing so may cause an electric shock or a fire.
If fluid leaks from the unit, do not touch the fluid.
Doing so may cause blindness or burns.
If the fluid contacts your eyes or skin, wash it out with lots of clean water and consult your doctor.
Do not throw the unit into fire.
The lead battery in the unit may explode, or leak dilute sulfuric acid.
5- 1 Checking the battery
The sealed lead battery used in the unit has a limited life. (The life varies depending on your storage/use environment and backup frequency.) The nearer the end of the life is, the more rapidly deterioration proceeds.
1. Life of battery (estimated replacement timing)
2. Method to check the battery
There are 3 methods for checking the battery.
• Perform a self-diagnostic test. (See page 31.)
• Use the auto battery test function. (See page 31.)
• Measure the backup time. (See page 46.)
By measuring the backup time, the battery life can be determined more accurately.
See also
Measure the backup time according to "7-1 Measuring method of the backup time." Page 46
If the measured value is equal to the "initial value of the backup time" or less than half the value obtained from the graph of "Estimated backup time" on page 46, replace the battery.
• When you compare the "initial value of the backup time" you measured and the current backup time, make the capacity of devices connected to the UPS same as when you measured the initial value to make judgment accurately.
3. Guideline on the frequency of checking the battery (measuring the backup time)
* The battery deteriorates even if it is stored. The higher the temperature is, the shorter the life
becomes.
5. Maintenance and Inspection
Caution (maintenance)
Ambient temperature
20°C
30°C
Life of battery
4 to 5 years
2 to 2.5 years
Replacement estimation
4 to 5 years after staring use
2 years after staring use
Ambient temperature
20°C
30°C
Check at intervals of 6 months
Until 3 years from purchase
Until 1.5 years from purchase
Check at intervals of 1 month
From after 3 years
From after 1.5 years
Page 39
37
5. Maintenance and inspection
5-2 Replacing the battery
The battery can be replaced either while the unit is stopped (power supply output stopped) or while it is in operation (outputting power supply).
* When replacing the battery, stop the connected devices, turn OFF the power switch of the UPS, and
disconnect the AC input plug from the wall.
* If an input power supply error such as a power failure occurs when replacing the battery while in opera-
tion, backup cannot be performed and output stops.
*Do not replace the battery during backup operation. Output will stop.
Perform replacement on a stable and flat place.
Handle the battery carefully not to drop it.
Not doing so could cause injury or burns due to liquid (acid) leakage.
Use a specified battery for replacement.
Not doing so may cause a fire.
Product model: BXB50F (battery pack for BX35F/BX50F/BX50FW)
BXB75S (battery pack for BX75SW)
Do not replace the battery in a place where there is flammable gas.
Spark may occur when connecting the battery, which may cause an explosion or fire.
If fluid (dilute sulfuric acid) leaks from the battery, do not touch the fluid.
Doing so may cause blindness or burns.
If it contacts your eyes or skin, wash it out with lots of clean water and consult your doctor.
Do not disassemble or modify the battery.
Doing so could cause dilute sulfuric acid leak, which could cause blindness and burns.
Do not drop the battery or do not give strong impact on it.
Dilute sulfuric acid may leak.
Do not short the battery with metal objects.
Doing so could cause an electric shock, fire or burn.
Some electrical energy still remains inside the spent battery.
Do not put the battery into fire or do not break it.
The battery may explode or leak dilute sulfuric acid.
Caution (for battery replacement)
Caution
When the unit is used in compliance with UL standards, do not replace the battery while in operation (while power is being output). Replacing the battery while in operation does not comply with UL stan­dards. Make sure to stop the operation of the unit before replacing the battery.
Page 40
38
5. Maintenance and inspection
Notes
Battery recycling
This unit uses lead acid batteries. The lead acid batteries are precious recyclable resources. Please cooperate recycling. For information on recycling, please contact our
ElectronicSystems&Equipments repair
center.
Pb
A battery can present a risk of electrical shock and high short circuit current.The following precautions should be observed when working on batteries:
1) Remove watches, rings, or other metal objects from the hands.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries.
5) Disconnect charging source prior to connecting or disconnecting batteries terminals.
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
Caution (for battery replacement)
5-2-1 Battery replacement procedure (BX35F/BX50F/BX50FW)
Preparation
(1) Purchase a BXB50F spare battery pack (sold separately).
(2) If you place the UPS horizontally and put a heavy object such as CRT on it, put it down until you finish
replacement.
Replacing the battery (BX35F/BX50F/BX50FW)
(1) Open the front panel.
(Disconnect the red and black connectors. Hold one connector in each hand and pull them apart.)
(1) Slide the front metal cover to the right, and
(2) Pull it toward you to remove it.
Use a screwdriver to remove the screw (1). Detach the front panel.
(2) Disconnect the battery connector and remove the metal cover.
Page 41
39
5. Maintenance and inspection
Pull on the white label attached to the battery, and then hold the battery with your hands to remove it.
Be careful not to drop the battery.
Insert the new battery.
(4) Reattach the metal cover and connect the connectors.
•You may hear a “pop” sound when you connect the battery if it is replaced after the unit’s operation is stopped, but this is not abnormal.
Fit the metal cover into the grooves and slide it to the left to secure it.
(The battery is secured inside the case.)
Connect the red and black connectors.
(Make sure that the connectors are securely connected.)
(5) Reattach the front panel.
Fit the left side of the panel on the case, and then attach it.
Tighten the screw with a screwdriver to secure the front panel.
If liquid (dilute sulfuric acid) leaks from the battery do not touch the fluid. Do not make the batter pack upside down.
• Doing so could cause burns and, if it is put into your eye, blindness.
• If the liquid touches your eyes or skin, wash it out with lots of clean water and consult your doctor.
• Just put the spare batter pack into the packaging plastic bag and seal it with tape.
Do not drop the battery pack.
• Hold the battery securely not to drop it.
Do not remove the battery by holding the cables.
Caution
(3) Remove the old battery, and insert the new battery.
Page 42
40
5. Maintenance and inspection
<After replacing the battery during operation...>
Press the beeper stop/test button for 0.5 sec. to perform a self-diagnostic test. Normal operation resumes after the 10-second test. If the beeper is sounding, it will stop the first time the switch is pressed. Press the switch again to start the test. If the battery replacement display and beeper were activated before replacing the battery, the display and beeper stop after the test is complete, and normal operation resumes.
<After replacing the battery when operation was stopped...>
Connect the AC input plug to a wall outlet (commercial power) and turn ON the power switch of the UPS. When operation starts, the self-diagnostic test is automatically performed. Normal operation resumes after the 10-second test.
5-2-2 Replacing the battery (BX75SW)
Preparation
(1) Purchase a BXB75S spare battery pack (sold separately).
(2) If you normally position the UPS horizontally and place a heavy object such as a CRT on top of it, remove
the object until you finish replacing the battery.
Replacing the battery (BX75SW)
(1) Open the front panel.
Loosen and remove the 2 screws. Detach the front panel.
(Hold one connector in each hand and pull them apart.)
(1) Slide the front metal cover upward, and
(2) Pull it toward you to remove it.
(2) Disconnect the battery connector and remove the metal cover.
Battery replacement is complete.
Write the usage start date on the label on the top side. Also, by using the included UPS monitoring software, possible to keep a record of usage start date by the software.
Page 43
41
5. Maintenance and inspection
(3) Hold the label stuck to the battery pack and remove it.
Insert the new battery pack.
If liquid (dilute sulfuric acid) leaks from the battery do not touch the fluid. Do not make the batter pack upside down.
• Doing so could cause burns and, if it is put into your eye, blindness.
• If the liquid touches your eyes or skin, wash it out with lots of clean water and consult your doctor.
• Just put the spare batter pack into the packaging plastic bag and seal it with tape.
Do not drop the battery pack.
• If you see red tape stuck on the top of the battery pack, you can remove the battery completely by pulling it 10 cm further. Hold the battery securely not to drop it.
Do not remove the battery by holding the cables.
Caution
(4) Reattach the metal cover and connect the connectors.
You may hear a “pop” sound when you connect the battery if it is replaced after the unit’s operation is stopped, but this is not abnormal.
Pull on the white label attached to the battery, and then hold the battery with your hands to remove it.
Be careful not to drop the battery.
Insert the new battery pack.
Fit the metal cover into the grooves and slide it downward to secure it.
(The battery is secured inside the case.)
Connect the red and black connectors.
(Make sure that the connectors are se­curely connected.)
Page 44
42
5. Maintenance and inspection
(5) Fit the front panel.
Turn the 2 screws to secure the font panel clockwise with a screwdriver.
Fit the front panel. Tighten the 2 screws.
<After replacing the battery during operation...>
Press the beeper stop/test button for 0.5 sec. to perform a self-diagnostic test. Normal operation resumes after the 10-second test. If the beeper is sounding, it will stop the first time the switch is pressed. Press the switch again to start the test. If the battery replacement display and beeper were activated before replacing the battery, the display and beeper stop after the test is complete, and normal operation resumes.
<After replacing the battery when operation was stopped...>
Connect the AC input plug to a wall outlet (commercial power) and turn ON the power switch of the UPS. When operation starts, the self-diagnostic test is automatically performed. Normal operation resumes after the 10-second test.
5-3 Cleaning
Cleaning the UPS
Wipe the UPS lightly by tight squeezed soft cloth soaked with water or detergent
Do not use chemicals such as thinner and benzene. (They cause deformation or discoloration.)
Removing dust from the Power Plug
•Turn off connected devices and the Power Switch of the UPS.
• Disconnect the AC Input Plug from a wall outlet (commercial power) and remove dust around the plug with a dry cloth.
• Disconnect the AC Input plugs of the connected devices from the UPS and clean them also.
• Connect the AC Input plugs of the connected devices to the UPS again, and connect the AC Input Plug of the UPS to a wall outlet (commercial power).
(For information on the connection procedure:)
See also
"2-2 Installation and connection" Page 18
Write the usage start date on the label on the side. Also, by using the included UPS monitor­ing software, possible to keep a record of usage start date by the software.
Battery replacement is now completed.
Page 45
43
6. Using the Contact Signal
6. Using the Contact Signal
(only for BX50FW, BX75SW)
You can develop your unique system based on the following specifications to automate the process at the power failure.
Your can perform power-failure or closing procedure of the system by detecting the Backup Signal and the Battery Low Signal, or receive failure notification by detecting the Trouble Signal.
You can stop the UPS by inputting the UPS Stop Signal from the system, and remote control start and stop of the UPS by using the Remote ON/OFF Signal.
Also, this function is valid only when “connection communication” is selected for the “switching switch”. (See item 2 on page 34.)
1. Signal output
The UPS has 5 kinds of output signals. The output circuit consists of an open collector circuit using a photo coupler (a kind of electronic switch).
Backup Signal output: BU
Backup Signal reverse output: NBU
BU stays ON (NBU OFF) during a power failure.
NBU is output only when the”gcommunication con­nector 9th-pin output signal switching setting” (set­ting switch 8 ) is set to ON.
Battery Low Signal output: BL
Goes ON when the battery becomes weak during the Battery Mode.
Trouble Signal output: TR
Goes ON when an internal failure of the UPS occurs.
Battery Replacement Signal output (WB)
Goes ON when the battery needs to be replaced due to deterioration.
WB is output only when the “communication connec­tor 9th-pin output signal switching setting” (setting switch 8 ) is set to OFF.
2. Input of the UPS Stop Signal (BS)
Stops the output of the UPS after the time period speci­fied by the “power output stop delay time setting” (set­ting switches 5 and 6 ) has elapsed.
(1)
When the "UPS Stop Signal setting" (setting switch 7 ) is set to OFF:
You can stop the output of the UPS by inputting the voltage signal (HIGH) that lasts at least 10 seconds from the outside.
(2) When the "UPS Stop Signal setting" (setting switch 7 ) is set to ON:
You can stop power output by inputting the voltage signal (HIGH) that lasts at least 0.01 second (10 ms) from the outside that is accepted only during backup.
See also
"4-7 Changing the setting of the functions" Pages 32
BU-COM ON when a power failure occurs
NBU-COM
OFF when a power failure occurs
BL-COM ON when the battery is low
TR-COM ON when a power failure occurs
BS-COM UPS stops
WB-COM
ON when battery deterioration is detected
Page 46
44
6. Using the Contact Signal
External contact Operate
Open Start
Close Stop
3. Remote ON/OFF Signal
You can start and stop the UPS by the remote ON/OFF signals, by the contact connected to the outside, or the ON/OFF status of the open collector circuit. To use this function, turn on the Power Switch of the UPS. (Note: When there is no AC power supply, it is not possible to start up UPS by the remote ON/OFF signals even though cold start is set ON.)
4. Connection to the system
Please make a cable to connect to the system by yourself.
See also
"8. Example of the use of the Contact Signal circuit" Page 45
5. Contact Signal Connector (female DSUB9P)
6. Contact Signal ratings
Signal output (BL, TR, BU, WB/NBU) UPS Stop Signal input (BS)
Photo coupler ratings Input voltage HIGH 5 to 15 VDC
Appliable voltage: 35 VDC or less LOW 0.7 VDC or less
Maximum current: 10 mA
Remote ON/OFF
Voltage between terminals: 10 VDC
Current when closed: max.10 mA
7. Contact Signal circuit inside the UPS
Front view Screw size: inch screw
#4-40 UNC
Pin assignment Pin number Signal name
1BL 2TR 3
BS
4— 5COM 6 Remote ON/OFF (–) 7 Remote ON/OFF (+) 8BU 9 WB/NBU
Remote ON (+)
Remote OFF (-)
10V
BL
TR
BU
BS
COM
2k
WB/NBU
Page 47
8. Example of the use of the Contact Signal circuit
Example of the use of the BU signal
6. Using the Contact Signal


 
 
! 
"#
1KΩ

 

   
Example of the use of the BS signal
UPS side
BS
COM
Connecting cable (twisted or shielded)
12V
.2 Ω
C2458
System side
1K Ω
TLP521
From port on PC
GND
9. Precautions and notes on the use of the Contact Signal
Notes
When connecting a device that generates counter electromotive force to the signal output circuit such as a relay, connect diodes to prevent counter electromotive force at the both end of the relay.
Explanation
When power is restored after the unit stopped automatically during a power failure, the unit automatically restarts and supplies power. If you do not want to start the connected devices, turn OFF their switches or set the auto restart setting (setting switch 2) to ON. (See page 32.)
45
Page 48
46
7. Measuring the backup time (checking the discharge time of the battery)
7. Measuring the backup time
(Checking the discharge time of the battery)
7-1 Measuring method of the backup time
(1) Connect the AC Input Plug of the UPS to a wall outlet (commercial power) and charge it for approximately
12 hours. If you operate the UPS for 12 hours or more, it is charged. If a power failure occurred during this period, charge it again.
(2) Turn ON all devices connected to the power output to be “backed up during a power failure”.
(Including devices connected to the AC outlet of your computer.) Operate them in a way in which it is allowable that power supply to the connected devices stops.
For Windows Server 2003/XP/Me/2000/Windows NT/Linux:
To be performed in case of hard drive stops.
For Windows 98/95:
Choose Shut Down of Windows and follow the procedure below to shut down your OS.
Choose "Restart in MS-DOS mode" to exit from OS and display the MS-DOS mode screen.
(3) Disconnect the AC Input Plug of the UPS and measure the backup time.
Measure the time until the unit automatically stops and all displays disappear with the plug disconnected.
* The backup time you measure for the first time after purchase is the "initial value of the backup time."
7-2 Estimated backup time
The backup time varies depending on the capacity of connected devices. After calculating the total capacity of connected devices, refer to the graph of the backup time to obtain an estimation of the initial value of the backup time. (This is also applied to checking the battery.) (1) Unify the total capacity (power consumption) of connected devices to W (Watt).
For the indication of connected devices, check your computer and the rear of the display. There are 3 types of indication: VA (Volt·Ampare) indication, A (Ampare) indication, and W indication.
Example 1) 100 VAC, 50/60Hz,
145 W
Example 2) 100 VAC, 50/60Hz,
1.8 A
Example 3) 100 VAC, 50/60Hz, 150 VA
For devices that use the VA or A indication, convert the capacity into W. Multiply the value indicated on devices by the value in the right table for conversion.
(When the power factor is unknown, enter “1”. The power factor usually ranges between 0.6 and 1.)
(2) Add the values converted into W to obtain the total capacity of the connected devices.
Indication Value
VA × power factor = W
A × power factor × 100 = W
Page 49
47
7. Measuring the backup time (checking the discharge time of the battery)
(3) Calculate the initial value of the backup time for the total capacity of the connected devices from the graph
below.
Graph of backup time (initial value for product that has not been used)
The smaller the capacity of connected devices becomes, the longer the backup time becomes.
Connection capacity (total capacity)
0
42 60 90
84 120 180
126 180 270
168 240 360
210 300 450
: BX35F : BX50F/BX50FW : BX75SW
3.5
5
10
20
30
40
50
60
<Reference diagram>
BX35F BX50F/BX50FW BX75SW
Backup time
Page 50
48
8. Troubleshooting
UPS does not operate. The LED display does not light up, even though the AC input plug is connected to a wall outlet (commercial power) and the power switch is ON.
Backup is not possible. The computer stops when a power failure occurs.
Backup is performed too frequently. Frequent switching is performed although a power failure does not occur. You hear the sound of switching.
The display is abnormal.
The display is unstable.
White lines occur.
Noise increases.
The battery replacement lamp blinks and the beeper sounds at 2-second intervals.
The status indicator shows “
”, and the beeper sounds
at 0.5-second intervals.
The status indicator blinks “ ”, and the beeper sounds continuously.
The output voltage is only approximately 80 V when measuring it with a tester.
8. Troubleshooting
Perform the checks shown below if the unit is operating abnormally. If the unit continues to operate abnormally, please contact our Electronic Systems & Equipments customer support center at _____.
Problem
1. Check that the AC Input Plug is connected to the commercial power securely.
2. The AC Input Overcurrent Protection worked and opened. (If the black button is popped up, it is suspected that there are too many connected devices or there is a short in connected devices.) Disconnect all of the connected devices, push in the AC Input Overcurrent Protection Black Button, and turn on the Power Switch of the UPS again. If the status indicator does not display normally, there is a problem with the UPS. (See "Interpreting a beep and display" on page 29.)
3. Isn't the voltage of the wall outlet (commercial power) too low? Stop devices that consume a lot of power such as an air conditioner. Check the UPS, for example, by connect it to a wall outlet (commercial power) in another room or house. (It does not operate when the voltage is less than 90V.)
Isn't charging insufficient? Perform the test after charging the battery for at least 12 hours. You can charge the battery by connecting the AC input plug of the UPS to a wall outlet (commercial power).)
1. The input power supply may be at fault. Connect the UPS to a wall outlet (commercial power) in another room or, if possible, another house and check it. Or, stop large devices such as a cooler.
2. Isn't a page printer connected? Because large current flows instantaneously in printers, normal backup is not possible.
1. The UPS generates some noise when performing backup. For displays susceptible to noise, distortion or white lines may occur, but the UPS is not at fault.
2. Grounding the UPS, computer, and display may improve this problem.
3. Noise during backup may become larger depending on connected devices, you can continue to use the UPS because this occurs due to rectangular wave output.
The battery is judged to be dead in the auto battery test or the self-diagnostic test. Battery Mode cannot be performed and therefore replace the battery pack.
There are too many connected devices. There are too many connected devices. Reduce the number of connected devices until “
” is displayed on the status indicator.
The UPS stopped because too many devices were connected for 3 minutes or more, or because 120% was exceeded. Turn OFF all power to the unit and connected devices, and reduce the number of connected devices. Then, turn the power to the unit and connected devices back ON and check whether "
" is displayed on the status indicator.
The UPS outputs a special rectangular wave during the Batter Mode. Due to its characteristics, simple testers indicates approximately 80 V. The UPS is not at fault. To make correct measurement, you need a voltmeter that can measure "true rms value."
Check and remedy
Page 51
49
9. Description of related products
9. Description of related products
9-1
Using the Network Line Surge Protection Function (BX75SW Only)
Using the optional BT75XSX, you can protect your modem, TA, and network card from damage due to surge by absorbing surge voltage (abnormally high voltage) that may occur on the telephone line, ISDN line or network cable due to thunder.
* If you do not use the Network Line Surge Protection Function, this section is not required.
The following 2 types of connectors are available for the Network Line Surge Protection Function.
- RJ45 (8 Pins) - RJ11 (2 Pins, 4 Pins, or 6 Pins)
1. When connecting to the telephone line
Connect the telephone line from the wall to the Line/Hub Side jack of the Network Line Surge Protection. Use the telephone cable (modular cable) included with the BT75XSX to connect between the unit’s Modem/ TA/PC Side jack of the Network Line Surge Protection and your modem, FAX, etc.
2. When connecting to the ISDN line
Connect the ISDN line that comes out of the wall to the Line/Hub Side of the Network Line Surge Protection of the UPS. Use the telephone cable (modular cable) attached to the BT75XSX to connect between the Modem/TA/PC Side Jack of the Network Line Surge Protection of the UPS and your DSU (or terminal adaptor with built-in DSU).
3. When connecting to LAN 10Base-T/100 Base-Tx
To protect your 10Base-T/100 Base-Tx (twisted pair cable without shielding) network interface, you need to separately purchase a cable equivalent to your cable in use. Connect the 10Base-T/100Base-Tx cable from the HUB to the unit’s Line/Hub Side jack of the Network Line Surge Protection. Connect between the Mo­dem/TA/PC Side jack of the Network Line Surge Protection and the network interface of your computer with a separately purchased cable.
Notes
Do not reverse the connection of Line/Hub Side and Modem/TA/PC Side of the Network Line Surge Protection.
If a failure of the protection circuit occurs, the ISDN line and so on may be damaged.
Page 52
50
9. Description of related products
Modem, FAX, or LAN card
Connect to the
Line/HUB Side
Connect to the
Modem/TA/Network Card Side
Telephone line, ISDN line, or 10Base-T
* If you do not use the UPS monitoring software, you can disregard this section.
Note 1: Files cannot be automatically saved. Note 2: To automatically stop the UPS, it may be necessary to change the PC’s BIOS settings.
Change the PC’S BIOS settings so that the PC’s power supply is not automatically cut after OS shutdown is performed. Note 3: Even if the UPS does not stop when the OS is shut down, it stops automatically when the battery is depleted. Note 4: If the connected PC is an NEC PC-9800 series or PC9821-series computer, use BUC19. Note 5: For the latest information, check our website at http://www.omron.co.jp/ese/
Model
BX35F BX50F
BX50FW BX75SW
OS
Communication
method
UPS monitoring
software
Required options
(sold separately)
Serial (USB 1.1)
Serial (USB 1.1)
Windows Server2003
Windows XP/2000
Windows ME/98
PowerAct Pro (included software)
UPS service (OS standard) + UPS service driver (included software)
PowerAct Pro (included software)
Serial (USB 1.1) (Note 1)
Mac OS X (10.3 or later) Mac OS X Server (10.3 or later)
UPS Power Manager (included software)
Serial (RS-232C) PowerAct Pro
(included software)
UPS service (OS standard) + UPS service driver (included software)
Contact signal (Note 1) (Note 3)
UPS service
(OS standard) Contact signal (Note 1) (Note 2)
UPS service
(OS standard)
BUC16, BUC24 optional cable BUC16 (Note 4), BUC24 optional cable
Serial (RS-232C)
PowerAct Pro
(included software) Serial (RS-232C) PowerAct Pro
(included software)
Windows Server2003 Windows XP/2000
Windows NT4.0
Windows ME/98
Linux(Note 5)
4. Connection example
1. Using the included monitoring software
To use the software, use the “PowerAct Pro” (Windows/Linux), “UPS Power Manager” (Mac) and connect the PC to the unit using one of the following methods.
BX35F/BX50F (USB connection) ....................... Use the included USB cable to connect
BX50FW/BX75SW (RS-232C connection) ......... Use the included RS-232C cable to connect
9-2 Using the UPS monitoring software
UPS monitoring software selection table
Page 53
51
9. Description of related products
2. Using the UPS service in Windows Server2003/XP/2000
Install the “UPS service driver” that is on the included CD-ROM, and connect to the unit using the method shown below.
BX35F/BX50F (USB connection) ....................... Use the included USB cable to connect
BX50FW/BX75SW (RS-232C connection) ......... Use the included RS-232C cable to connect
When there is a problem with the power supply, files can be saved, applications can be quit, Windows can be shut down, and the UPS can be stopped (shut down).
3. When using the UPS service in Windows NT 4.0
The OS standard UPS service can be used with a separately purchased cable.
DOS/V machine (use a BUC16 or BUC24 optional cable to connect)
NEC PC9801, 9821 machine (use a BUC19 or BUC24 optional cable to connect)
9-3 Connecting the UPS
1. USB connection 2. RS-232C connection
USB port
Connector
Connect to USB terminal
Connect to USB port on PC
Included USB cable
Connector
Connect to USB port on UPS
BX35F/BX50F
BX50FW
Connector
Connect to RS-232C port on PC
Included RS-232C cable
Connector
Connect to RS-232C terminal
Connect to RS-232C port on UPS
BX75SW
Connector
Connect to RS-232C port on PC
Connector
Connect to RS-232C terminal
Connect to RS-232C port on UPS
Included RS-232C cable
Page 54
52
9. Description of related products
9-4
About the included UPS monitoring software
Using the included UPS monitoring software allows you to automatically save data files and shut down your computer when a power failure occurs. However, make settings so that the time from the occurrence of the power failure until computer shutdown is less than the maximum backup time. For more details, refer to the instruction manual and online help for the UPS monitoring software.
Using the included UPS monitoring software also enables you to change the unit’s operation mode settings, use additional functions, perform scheduling operations, etc.
Explanation
Starting operation during a scheduled stop with UPS monitoring software
If the unit starts operation during a scheduled stop period, turn the power switch OFF once, and then turn it back ON.
You can start the unit manually. In this case, the next scheduled ON operation is cancelled.
Auto restart after OS shutdown by UPS monitoring software
In the event of a power failure, some PC models (see *1 below) automatically restart immediately after the completion of the OS shutdown processing by the UPS monitoring software. In this case, the unit stops during restart or after startup, possibly damaging files and/or the hard disk. This problem can be avoided by disabling POWER MANAGEMENT in the BIOS settings. *1) PC models: This problem has been reported with MICRON Millenia Mme.
When the PC does not start up automatically, select the “System startup at power restoration” setting (example: “Restore On AC/Power Loss) in the BIOS settings of your PC, and change to a “System startup after power restoration” setting (example: “Power On). Individual BIOS setting methods and/or displays may differ depending on the PC. For more information, refer to your PC instruction manual or the technical support center for your PC.
When considering a system with automatic startup at power restoration, choose a PC that satisfies the condition shown below. For more information on PC operation when input power is supplied, consult your PC instruction manual or contact the PC technical support center. <Condition> Without pressing the power switch, the PC starts up when input power is supplied.
After shutdown processing in the event of a power failure, the unit restarts automatically and supplies power once power is restored.
If you do not want the devices connected to the UPS to start up, turn OFF their switches.
The automatic restart setting can be disabled in the included UPS monitoring software.
Page 55
53
Reference
References
A. Specifications
90 to 110 VAC
(during backup
operation)
90 to 110 VAC
(during backup
operation)
100V mode 90 to 110 VAC 110V mode 100 to 120 VAC 115V mode 105 to 120 VAC 120V mode 105 to 120 VAC (During backup operation)
100V mode 90 to 110 VAC 110V mode 100 to 120 VAC 115V mode 105 to 120 VAC 120V mode 105 to 120 VAC (During backup operation)
86 + 4 to 114 + 4 VAC
BX35F BX50F BX50FW BX75SW
Method
Operation method
Connectable devices
Input voltage range
Frequency
Maximum current 8A 12A 12A 12A
350VA/210W 500VA/300W 500VA/300W 750VA/450W
approx. 5kg approx. 5kg approx. 5kg approx. 9kg
287 x 287 x 45 287 x 287 x 45 287 x 287 x 45 90 x 287 x 278
10W 10W 10W 10W
5 minutes or more
3.5 minutes or more 3.5 minutes or more
5 minutes or more
Battery fully charged and with no condensation / 12 hours
Waveform
(In Commercial Powe
r Mode/
Batttery Mode)
Output capacity (shared maximum)*1
Voltage *2
Switching time
Backup time*3
Type
Charging time
Operating ambient temperature
Operating ambient humidity
Full-time commercial power supply method
PC, display, and peripherals
50/60Hz±4Hz
Sine wave / Rectangular wave
10 msec. or less
Compact sealed lead battery
0 to 40°C (during operation)/ -15 to 40°C (during storage)
25 to 85%RH (during operation)/10 to 90%RH (during storage)
Input
Output
Battery
Environment
External dimensions (W x D x H mm)
Weight of UPS
Internal power consumption (Normal, Max.)
*1: Do not use the UPS exceeding allowable connection capacity either in VA or W values specified in the specifications. *2: Do not fail to confirm the system operation beforehand if the unit is used other than "Output 100V mode".
At the time of battery operation, the maximum voltage may be lower than the voltage at the time of usual operation (commercial power supply). Rectangular waveforms during backup operation take the following values.
*3: At the rated load connection, 20°C, initial characteristics
BX35F/BX50F/BX50FW BX75SW
100V mode 90V 103V 90V 115V 110V mode 100V* 103V* 100V 115V 115V mode 105V* 103V* 105V 115V 120V mode 105V* 103V* 105V 115V
*: The figures at 110V/115V/120V modes are effective only to BX50FW.
The minimum voltage of the effective value
The minimum voltage of the peak voltage
The minimum voltage of the effective value
The minimum voltage of the peak voltage
Peak voltage
100V mode
86 + 4 to 114 + 4 VAC
110V mode
96 + 4 to 124 + 4 VAC
115V mode
101 + 4 to 129 + 4 VAC
120V mode
106 + 4 to 134 + 4 VAC
100V mode
86 + 4 to 114 + 4 VAC
110V mode
96 + 4 to 124 + 4 VAC
115V mode
101 + 4 to 129 + 4 VAC
120V mode
106 + 4 to 134 + 4 VAC
Page 56
54
Reference
C. Dimensional outline drawing
BX35F/BX50F
287
45
2.5
287
11
Power cable (approx. 1.8m)
Communication cable USB (approx. 2m)
BX35F BX50F BX50FW BX75SW
Spare battery pack BXB50F BXB50F BXB50F BXB75S
Attachment fittings BXP50F BXP50F BXP50F
Network line surge protection kit BT75XSX
Rack mounting bracket BYP50R BYP50R BYP50R
B. Related products
(unit : mm / Tolerance : +1mm)
Page 57
55
Reference
BX75SW
278
287
90
Communication cable RS232C (approx. 2.2m)
Power cable (approx. 1.8m)
BX50FW
287
11
45
2.5
287
Communication cable RS232C (approx. 2.2m)
Power cable (approx. 1.8m)
(unit : mm / Tolerance : +1mm)
(unit : mm / Tolerance : +1mm)
Page 58
56
Reference
Charging
circuit
Input Overcurrent
Protection
AC input plug
Power Supply Output
Receptacle
Power Switch
Commercial Power Mode
Battery Mode
DC-DC
converter
Battery
Inverter
circuit
ON
D. Circuit block diagram
This UPS outputs power input from commercial power as it is and charges the battery at the same time. If a power failure or voltage variation occurs, the UPS automatically switches to operation using the battery and continues power output. At this time, the beeper sounds intermittently. When the power is recovered, normal operation using commercial power is automatically recovered. (The beeper stops.) You do not have to perform any operation.
Page 59
No part or whole of this manual may be reproduced without permission. The contents of this manual are subject to change without notice.
OMRON Corporation
K1L-D-04141F