Uninterruptible Power Supply (UPS)
Instruction Manual
Introduction
Thank you for purchasing Omron's Uninterruptible Power Supply (UPS).
• The UPS protects computers and other devices from surge voltage (a phenomenon in which extraordinary high voltage occurs instantaneously) caused by power failures, voltage variations, instantaneous voltage drops and power failures, and lightning.
• The BN100XR, BN150XR and BN240XR are line interactive UPS with simple output voltage adjustment functions. Under normal service conditions, commercial power input passes through the transformer and is output, and when the input voltage is low, the transformer raises the voltage, and when the input voltage becomes high, the transformer lowers the voltage. In addition, when abnormalities in commercial power are detected, such as in a power failure or when there are large changes in voltage, power supply is shifted to the battery within 10ms, and sine wave output is continued.
• Under normal setting conditions, output capacities are 1000VA/700W for BN100XR, 1500VA/1000W for BN150XR and 2310VA/2000W for BN240XR.
Notes on the use of the UPS
• The UPS is designed and manufactured for OA equipment such as personal computers. Do not use the UPS with the devices that require very high reliability and safety as listed below.
Medical devices that support life directlyParticular applications of devices that may cause injury (applications that directly affect the operation
and control of planes, ships, railroads, elevators, and others)
Applications that are subjected to constant vibration, such as cars and shipsApplications in which a failure of the UPS may cause critical damage or effect on public safety (major
computer systems, main communications equipment, public transportation systems, and others)
Devices with the similar level of importance
• For the devices that adversely affect the safety of people and maintenance of utilities in the event of failure, special considerations related to operation, maintenance, and management of the system must be taken such as a standby system for emergency use and an auxiliary power generator.
• Observe the do's and don'ts of this instruction manual related to the operating and environmental conditions.
• When you want to add the UPS to the critical system that requires very high reliability, contact us; ______.
• Do not modify/alter your UPS.
• The UPS is designated for domestic use only. Do not use the product abroad (outside Japan). Voltages and frequencies may differ abroad and may result in failure and/or fire.
© OMRON Corporation. 2004 All Right Reserved.
1
IMPORTANT SAFETY INSTRUCTIONS
1. SAVE THESE INSTRUCTIONS
This manual contains important instructions for Model BN100XR/BN150XR/ BN240XR/MB240XR that should be followed during installation of the UPS and batteries.
2. SYMBOL
This symbol indicates the ground.
This symbol indicates that the on UPS is ON.
This symbol indicates that the UPS is OFF.
This symbol indicates AC voltage.
This symbol indicates DC voltage.
This symbol indicates phase.
3. INTERNAL BATTERY
Internal battery voltage is 36V DC for BN100XR/BN150XR, 72V DC for BN240XR and MB240XR.
4. TEMPERATURE RATING
The maximum ambient temperature of the UPS is 40°C.
5. ENVIRONMENT
The unit is intended for installation in a temperature controlled, indoor area free of conductive contaminants.
2
Table of Contents
Table of Contents
Introduction
IMPORTANT SAFETY INSTRUCTIONS ........................................................................................................... 1
Directions for safe use ....................................................................................................................................... 3
1. Preparation .................................................................................................................................................. 11
1-1 Unpacking the UPS ........................................................................................................................... 11
1-2 Checking the accessories ................................................................................................................. 11
1-3 Part names ........................................................................................................................................12
1-4 Explanetion of symbols used on unit ................................................................................................. 16
2. Installation and connection ..........................................................................................................................17
2-1 Precautions and notes on installation and connection ...................................................................... 17
2-2 Installation ......................................................................................................................................... 20
2-3 Adding a battery unit (MB240XR) ...................................................................................................... 23
2-4 Connection of AC input cable ............................................................................................................ 24
2-5 Connecting the devices .....................................................................................................................25
2-6 Checking the operation ..................................................................................................................... 28
2-7 Charging the battery .......................................................................................................................... 29
2-8 Measuring the backup time ............................................................................................................... 29
3. Operating the UPS ..................................................................................................................................... 30
3-1 Precautions and notes on operation .................................................................................................. 30
3-2 Operating and stopping procedures ..................................................................................................31
3-3 Beeps and displays ........................................................................................................................... 33
4. Measuring the backup time ........................................................................................................................ 36
4-1 Measuring method of the backup time .............................................................................................. 36
4-2 Estimated backup time ......................................................................................................................36
5. Maintenance and inspection ........................................................................................................................ 37
5-1 Checking the battery ......................................................................................................................... 37
5-2 Replacing the battery ........................................................................................................................ 37
5-3 Maintenance of the main unit ............................................................................................................ 43
5-4 Caution when maintaining connected devices .................................................................................. 43
6. Using the UPS monitoring software ...........................................................................................................44
6-1 Performing auto shutdown ................................................................................................................ 44
6-2 Connection methods ......................................................................................................................... 45
6-3 About the included UPS monitoring software .................................................................................... 46
7. Using the contact signal I/O card ...............................................................................................................48
7-1 Adding a signal I/O card ....................................................................................................................48
7-2 Details on contact signal I/O (SC05 card) ......................................................................................... 48
7-3 Notes and explanations for the use of contact signal I/O ..................................................................49
8. Using SNMP/WEB card .............................................................................................................................. 50
8-1 Addition of SNMP/Web card .............................................................................................................. 50
8-2 SNMP/Web card outline ....................................................................................................................50
9. Additional functions and function setting changes for the UPS .................................................................. 51
9-1 Auto battery test ................................................................................................................................ 51
9-2 Estimated backup time and backup time test in battery mode ..........................................................52
9-3 UPS functions whose settings can be changed from the UPS monitoring software ......................... 52
10. Troubleshooting ......................................................................................................................................... 54
Reference ................................................................................................................................................... 56
A. Specifications ......................................................................................................................................... 56
B. Dimensional outline drawings ................................................................................................................ 58
C. Circuit block diagram ............................................................................................................................. 59
D. Optional products ................................................................................................................................... 59
3
Directions for safe use
Misuse may cause death or serious injury.
Warning
Caution
Directions for safe use
The safety symbols used in this manual and their meanings are as follows.
* Property damage means damage to houses/household effects, livestock, and pets.
Notice that do's and don'ts of "Caution" may bring about a serious accident according to the circumstances. These do's and don'ts are critical and must be observed strictly.
Warnings
Read this instruction manual before installation and use to ensure that you fully understand the critical do's and don'ts of your UPS.
Misuse may cause injury or property damage.
Do not disassemble, repair, and/or modify your UPS.
Doing so may cause an electric shock or fire.
If battery liquid leaks from the UPS, do not touch it.
Doing so can lead to blindness and/or or burns.
If the liquid gets in eyes or spills on your skin, wash with clean water and consult a doctor.
When replacing the battery, do not insert anything metal into the battery.
An electric shock or short may occur.
Unpacking and carrying the UPS requires the following number of people:
BN100XR/BN150XR: 2 or more people BN240XR/MB240XR: 3 or more people
The UPS is heavy, so be careful when unpacking and carrying it.
Keep the weight in mind when unpacking and carrying the UPS. Place and run the UPS on a structurally sound and level base.
If the UPS falls over, or if you drop it, it may cause injury.
The weight of the UPS
BN100XR: 20kg BN150XR: 20kg BN240XR: 38kg MB240XR: 29kg (add-on battery unit)
If the UPS falls, immediately stop using it, inspect it, and repair it if necessary.
Do not add the UPS where very high reliability and safety are required as listed below. (The UPS is designed and manufactured for uses with OA equipment, such as personal computers.)
Medical devices and/or systems that support life directly
Applications that may adversely affect the safety of people (for example, the operation and control of auto-
mobiles and elevators)
Applications that adversely affect the maintenance of utilities in the event of failure (for example, critical
computer systems and trunk lines)
Applications with the similar level of importance
Warnings (uses of the UPS)
: Indicates prohibited action (don'ts). For example, indicates that disassembly is prohibited.
: Indicates necessary action (do's). For example,
indicates that grounding is necessary.
Cautions (installation)
4
Directions for safe use
Keep packing materials, including plastic bags and film, out of the reach of children
Should children swallow or put their head into the packing materials, there is danger of suffocation.
Provide secure grounding
Earth the ground terminals of the UPS and devices connected to the UPS. (See "2. Installation
and connection" on page 17) You may receive an electric shock in the event of trouble or power failure. When both the UPS and devices are not grounded and you touch both, you may receive an electric shock.
For BN100XR/BN150XR, when you use a 3-pin to 2-pin plug for the AC Input Plug, be sure to
perform grounding before putting the AC Input Plug in a wall outlet (commercial power). On the other hand, be sure to disconnect the grounding terminal after removing the AC Input Plug from a wall outlet (commercial power).
Connect the UPS grounding terminal to a grounded-type wall outlet (commercial power) to ensure
that the Power Line Surge Protection works as intended.
Do not use the UPS where the maximum temperature exceeds 40°C.
Battery deterioration will occur rapidly.
Doing so may result in a failure or malfunction of the UPS.
Do not exceed the specified ranges in the operating and storage environments. Do not install or store the UPS in the following types of places.
Places with high temperatures, low temperatures, or high humidity
Places that receive direct sunlight
Places that are directly heated by a stove or other heat source
Places where the UPS may experience vibration or physical shock
Places where there is dust, corrosive gas, salt, or flammable gas
Outdoors
Placing the UPS in these types of areas may result in malfunction, deterioration, and/or fire.
Do not obstruct the air inlets and outlets on the sides and rear of the UPS. Do not place the UPS in an enclosed space or cover the UPS.
Doing so may lead to abnormal overheating or fire.
Temperature will increase inside the UPS and may cause a failure of the UPS and battery
deterioration.
Install the UPS 5cm or further away from the wall.
Do not install the UPS in other orientations. Do not install the UPS on a structurally unsound base.
See "2-2 Installation" on page 20.
If the UPS falls over, or if you drop it, injury may result.
Do not clip the cables, and do not use when the cables are bundled.
If the cables become damaged or overheated, there is a danger of electric shock or fire.
If the cables become damaged, immediately stop using the UPS, and make the necessary
repairs.
Do not connect a device such as a voltage transformer or isolated transformer to the output side.
Overcurrent may damage the UPS.
Even when connected to the input side, the UPS may fail or malfunction. Make sure to check the
operation before use.
Cautions (installation)
5
Directions for safe use
Cautions (installation)
When performing rack installation, ensure that the UPS is supported and stabilized by using both the support angles and the table clamps that were included. When connecting a battery unit and/or adding another battery unit, be sure to place the battery unit in a position lower than the main unit.
When installing on a rack, make sure that the UPS is supported by the each unit individually.
When installing on a rack, make sure to use the support angles and table clamps included with the
product. Without the support angles, the front clamp alone cannot support the weight of the UPS.
The mass of the UPS: BN100XR: 20 kg BN150XR: 20 kg
BN240XR: 38 kg MB240XR: 29 kg (add-on battery unit)
In a case where the UPS is to be mounted on a rack, place it on the lowest part of the rack.
Dropping it may result in injury.
Be sure to use the supplied mounting screws.
Screws other than those supplied may not be strong enough to support the UPS, causing it to fall.
Do not place things on the units.
Doing so may make battery change difficult due to the load.
Connect the UPS to a wall outlet (commercial power) with a current capacity greater than the maximum input current of the UPS.
Electrical wiring may become hot.
When connected to a rated capacity device, the maximum current that can flow is as follows:
BN100XR: 13.5A, BN150XR: 18A, and BN240XR: 27A.
Be sure to put the input plug of the UPS in a 100V AC (50/60 Hz) wall outlet (commercial power).
Connecting the input plug to a wall outlet (commercial power) of a different voltage may cause a
fire.
The UPS may fail.
When using the 15A plug (NEMA 5-15P) with the BN150XR The maximum capacity that can be connected to the output is about 1100VA1000W.
Power consumption over 1100VA/1000W results in an input current of more than 15A, which can
lead to overheating or fire.
When the "Input over 15A" display appears, replace it with a 20A plug.
When replacing the input plug for the BN150XR, make sure to follow the connection directions correctly, and make sure not to mistake the colors of the plug receptacle and wire.
See "2-4. Connection of AC input cable" on page 24.
Doing so may cause a leakage or an electric shock.
Do not connect devices that exceed the output capacity of the UPS. You can add extra devices with a plug strip. Note that the plug strip does not permit the connection of devices that exceed the current capacity of the plug strip.
The UPS may detect overload and stop the output.
The plug strip cord may heat up and could lead to a fire.
Do not connect to a device (such as a dryer) that uses half-wave rectification in which AC power supply current flows in half-cycles only.
The UPS may fail.
Cautions (connection)
6
Directions for safe use
In a case where the Battery Replacement Lamp comes on or the backup time becomes shorter than the required backup time, replace the battery pack with a new one while the UPS is running, or stop the UPS and discard the old battery pack.
The continuous operation of the UPS may result in fire.
For further information on how to inspect the battery, see "5. Maintenance and inspection" on
page 37.
When you notice abnormal sound or smell, smoke, or liquid coming from the inside of the UPS, immediately turn OFF the power switch (
) and
remove the AC Input Plug from the wall outlet (commercial power).
Continuous operation under the abnormal conditions may cause a leakage of current or fire.
If you notice the abnormal conditions, never operate the UPS, and contact us or the distribu-
tor from which you purchased your UPS for inspection and repair.
Your UPS must permit instant removal of the AC Input Plug from a wall outlet (commercial
power) at the onset of a failure.
Do not place objects on the UPS and do not drop metal objects into the UPS.
Doing so may cause distortion and/or damage to the top case of the UPS or an internal circuit
failure, which may lead to a fire.
Do not place the UPS in an enclosed space or put a cover over the UPS.
Doing so may lead to abnormal overheating and/or fire.
Do not spill water on the UPS or get it wet.
Doing so may cause an electric shock or fire.
If the UPS gets wet, immediately stop using it, inspect it, and make repairs if necessary.
Do not insert metal objects into the output receptacles of the UPS.
Doing so may cause an electric shock.
Do not insert metal objects into the battery connector or add-on battery connector. Do not short-circuit the connector terminals.
Doing so may cause an electric shock.
There is a risk of combustion, battery explosion, and burn injury.
Cautions (use)
* The table on the left shows the estimated life expect-
ancy of a battery pack in normal usage conditions. This is not the warranty period.
Ambient temperature
20°C
30°C
Estimated life expectancy
2 to 3 years
1 to 1.5 years
7
Directions for safe use
Before maintaining devices connected to the UPS, turn off the UPS and remove the AC Input Plug from the wall outlet (commercial power).
Even if you remove the AC Input Plug during the operation of the UPS, the backup function of
the UPS keeps feeding power through the power supply output receptacle of the UPS.
In a case where the scheduled operation is ON and the AC Input Plug of the UPS is put in a
wall outlet (commercial power), the UPS starts feeding power at the starting time of the scheduled operation.
Cautions (maintenance)
Do not short-circuit the battery with a metal object.
Doing so may result in burn injury or fire.
Even in a dead battery, there is some current remaining.
Do not toss a battery into a fire. Do not try to break a battery.
The battery may explode or dilute sulfuric acid may leak.
Do not use any batteries other than those specified.
Doing so may lead to a fire.
Battery pack product models: BP150XR (for BN100XR, BN150XR), BP240XR (for BN240XR,
MB240XR)
Do not use a new battery and an old battery at the same time (when adding BN240XR battery).
Rapid deterioration of battery may occur, and dilute sulfuric acid may leak.
Do not drop the battery, and make sure that it does not receive any strong impact.
Dilute sulfuric acid may leak.
Do not replace the battery in a place near flammable gas.
A spark may occur when connecting the battery, and lead to a fire.
Replace a battery on a structurally sound base.
Hold the battery securely with both hands to avoid dropping.
Failure to do so may result in injury due to the battery falling, burns, or injury.
If there is liquid coming from the replaced battery pack, do not touch it.
If touched, the liquid (dilute sulfuric acid) may cause burn injury or blindness.
Do not disassemble or modify the battery.
Doing so may cause a leakage of dilute sulfuric acid, which may cause blindness and burns.
Cautions (battery replacement)
8
Directions for safe use
Pb
Notes
After purchasing the UPS, charge the battery until the battery charge indication shows that the battery is fully charged.
If you do not use your UPS for a long time after purchase, the battery may deteriorate and become unusable.
After inserting the AC Input Plug of the UPS into a wall outlet (commercial power), the battery automatically
begins to charge.
Before storing the UPS, charge the battery until the battery charge indication shows that the battery is fully charged.
In a case where you do not use the battery, it discharges naturally and goes into over discharge status
after it is left for a long time. The backup time may become shorter or the battery may become unusable.
The maximum possible storage period for the battery installed in the UPS is 6 months (after being fully
charged).
If the storage period is to exceed 6 months, recharge the battery before 6 months have passed by con-
necting the AC Input Plug to a wall outlet (commercial power).
When storing the UPS, make sure that power switch ( ) is turned OFF.
Do not create a short between the output lines of the UPS, or a ground fault between the output lines and the ground.
The UPS may fail.
When the UPS is in operation, do not insert the AC Input Plug into the Power Supply Output Receptacle of the same UPS.
The UPS may fail.
Shut down the UPS before cutting commercial power supply. If the power switch cannot be turned OFF, perform an auto shutdown of the UPS using the UPS monitoring software with the minimum required backup time.
The UPS goes into Battery mode whenever commercial power is cut. By continuing to run the devices on the
battery and recharging the battery, the life expectancy of the battery is significantly shortened. The less you repeat charges and discharges, the longer the life expectancy of the battery will become.
Do not connect a page printer to the UPS.
The peak current of the page printer is large, so it may be detected as an overcurrent, or the resulting
instantaneous voltage drop may be detected as a power failure.
Operation may switch between Line mode and Battery mode, reducing battery life.
If the unit is used with an inductive device such as a coil or motor, check the operation beforehand.
With some types of devices, the effect of inrush current may cause this unit to stop operating properly.
Do not perform a withstand voltage test.
The power input circuit has a built-in surge absorber element. A withstand voltage test may break it.
When performing an insulation resistance test, conduct it in the 250V DC range.
Recycling and discarding the battery
The UPS has a lead acid battery. The battery is a recyclable and valuable resource. We need
your cooperation in recycling old batteries, batteries that you replace with a new batteries, and the batteries you used to discard.
Installation and storage places
Do not install or store the UPS in a place exposed to direct sunlight.
High temperatures may cause the battery to deteriorate and become unusable.
9
Directions for safe use
Explanations
Usual operating method
You may keep the UPS running without shutting down, or you may turn off the UPS each time the devices
connected the UPS are turned off. You can choose either way, depending on which is convenient.
When connected to commercial power, the battery starts charging.
Terminating backup operation
In the case of an extended power failure, the battery keeps discharging until power supply from the UPS
stops. Before that happens, turn off your computer in the usual manner (including data backup).
Rebooting
If the battery discharges completely during a power failure, the UPS stops. After the recovery from a failure
of the power supply (for example, a power failure), the UPS automatically restarts and starts to feed power. If you do not want to run the devices connected to the UPS, keep the devices turned off.
Using UPS monitoring software, automatic restart can be disabled.
The USB and RS-232C ports cannot be used simultaneously.
The UPS monitoring software and can be used with either the USB or RS-232C ports of the UPS, but they
both cannot be used at the same time.
Scheduled operation using UPS monitoring software
When scheduled operation is being used, if commercial power is stopped during the scheduled shutdown
period, set the period of time until the start of next operation at about one month. The timer is activated by the built-in battery for the period of time that the commercial power supply input is stopped. If the timer stops, operation start cannot be performed according to schedule.
Using UPS service of Windows NT
If you are using Windows NT Server, make the settings using the server menu as shown below. An incorrect
setting of the remote UPS shutdown the UPS will be unable to perform backup in the event of a power failure. For more detailed information, refer to the Windows NT 4.0 manual or the Windows NT 4.0 help file.
The signal settings are as follows:
Power supply shutdown signal: Negative (for initial value, Windows NT server is set as negative, and
OS2Lan server is set as positive)
Battery weak/dead signal: Negative (for initial value, Windows NT server is set as negative, and
OS2Lan server is set as negative)
Remote UPS shutdown: Positive (for initial value, Windows NT server is set as negative, and
OS2Lan server is set as negative)
For Netware users, call up the command input screen, and enter the following to load a UPS module into the
file server.
LOAD UPS TYPE=6 PORT=__ REV=2
After this is input, press the Enter key. In the command line, after "PORT=", enter the number of the serial port that is connected to the UPS. (1 or 2)
10
Directions for safe use
Explanations
Auto restart after shutdown processing by UPS monitoring software
In the event of a power failure, some PC models (see *1 below) automatically restart immediately after the
completion of the OS shutdown processing by the UPS monitoring software. In this case, the UPS stops during restart or after startup, possibly damaging files and/or the hard disk. This problem can be avoided by disabling POWER MANAGEMENT in the BIOS settings.
*1) PC models: This problem has been reported with MICRON's Millennia Mme.
When the PC does not start up automatically, select the "System startup at power restoration" setting (example:
"Restore On AC/Power Loss") in the BIOS settings of your PC, and change to a "System startup after power restoration" setting (example: "Power On"). Individual BIOS setting methods and/or displays may differ depending on the PC. For more information, consult your PC instruction manual or contact the technical support center for your PC.
When considering a system with automatic startup at power restoration, choose a PC that satisfies the
condition below. For more information on PC operation when input power is supplied, consult your PC instruction manual or contact the PC technical support center.
<Condition>
Without having the power switch pressed, the PC starts up when input power is supplied.
After shutdown processing, the UPS restarts automatically and supplies power once power is restored. If
you do not want the devices connected to the UPS to start up, turn off their switches in advance.
The automatic restart setting can be disabled in the included UPS monitoring software.
11
1. Preparation
Keep the weight in mind when unpacking and carrying the UPS. Place and run the UPS on a structurally sound and level base.
If the UPS falls over, or if you drop it, it may cause injury.
The weight of the UPS
BN100XR/BN150XR: 20kg BN240XR: 38kg MB240XR: 29kg (add-on battery unit)
If the UPS falls, immediately stop using it, inspect it, and repair it if necessary.
1-2 Checking the accessories
If you should notice defects or anything wrong, please contact your distributor at once.
Cautions
1. Preparation
1-1 Unpacking the UPS
20A AC plug
USB cable for UPS
monitoring software
EIA 19-inch rackmount
fittings and supports
Upright stand
Battery unit
connection cable
Signal cable
(modular cable for battery unit)
Connect to the battery unit connecting cable
Upright coupling plate
Accessories Quantity BN100XR BN150XR BN240XR MB240XR
1. Main unit 1 ○○○○
2. UPS monitoring software
1 set ○○○ --
(CD-ROM, RS232C cable, etc.)
3.
USB cable for UPS monitoring 1
○○○ --
software
4. 3P-2P adapter plug 1 ○○ -- --
5. 20A AC plug 1 -- -- --
6. Upright stand 1
-- --
--
7
. Battery unit connection cable set 1 -- -- --
8. Signal cable
1
-- -- --
(modular cable for battery unit)
9. Upright coupling plate 1
-
-- -- --
10. EIA19-inch rackmount fittings
1 set ○○○
and supports
11. Instruction manual (Japanese) 1 ○○○○
12. Instruction manual (English) 1 ○○○○
13. Warranty 1 ○○○○
14.
User registration card 1 ○○○ --
15. Label (Identification of
operating
1 ○○○ --
condition)
12
1. Preparation
1-3 Part names
1. Front panel
BN100XR
Note: There is a fixing screw for the battery panel beneath the logo plate.
BN150XR
Note: There is a fixing screw for the battery panel beneath the logo plate.
BN240XR
MB240XR (Add-on battery)
Note: There is a fixing screw for the battery panel beneath the logo plate.
BN150XR
BACK UP POWER SUPPLY
BN240XR
AC115V OUTPUT
B
25% 50% 75% 100%
C
AC115V OUTPUT
B
25% 50% 75% 100%
C
BN100XR
BACK UP POWER SUPPLY
AC115V OUTPUT
B
25% 50% 75% 100%
C
BATTERY UNIT
MB240XR
BACK UP POWER SUPPLY
Logo plate
Battery panel
Control panel
Logo plate Battery panel
Control panel
Logo plate
Outer panel
Logo plate
Battery panel
Control panel
13
1. Preparation
AC115V
OUTPUT
B
25% 50% 75% 100%
C
ACDEH1 H2 H3
H4
I 1 I 2 I 3
I 4
FG B
Power switch
To turn ON To turn OFF
ON OFF
Press
Press
Switch FUNCTION
A Power switch
Indication
Lit
lamp
Continuous illumination Blinking display
A (green)
Power supply output/receptacle A output indication Charging (blinks once every 10 seconds) B (yellow) Battery mode indication Testing the battery (blinks once per second) C (red) Warning indication (failure)
Battery deterioration indication (blinks once every
two seconds) D (yellow) Input over 15A indication (BN150XR only) Overload indication (once every 0.5 second) E (green) Output indication for output receptacle B F (green) Output indication for output receptacle C G (yellow) 115V AC output mode indication H1 to H4 (green)
Connection capacity indication H1 0 to 25% H2 25 to 50% H3 50 to 75% H4 75 to 100% I1 to I4 (green) Battery charge/remaining capacity indicator
(approximate value)
I10 to 25% I2 25 to 50% I3 50 to 75% I4 75 to 100%
Control panel (BN150XR/BN240XR)
14
1. Preparation
2. Rear panel
BN100XR/BN150XR
BN240XR
A AC input cable
BN100XR: NEMA 5-15 (15A) plug BN150XR: NEMA 5-15 (15A) plug BN240XR: NEMA L5-30 (30A) plug
B Input overcurrent protection
BN100XR: 15A BN150XR: 20A BN240XR has built-in fuse (30A) CGrounding screw terminal (FG) D1 Output receptacle A
BN100XR (10A max.) BN150XR (15A max.) BN240XR (20A max.) D2 Output receptacle B (Delayed output at startup/ON-OFF control possible)
BN100XR (10A max.) BN150XR (15A max.) BN240XR (20A max.) D3 Output receptacle C (Delayed output at startup/ON-OFF control possible)
BN100XR (10A max.) BN150XR (15A max.) BN240XR (20A max.) E USB interface F RS232C interface G Option card slot H1 Output receptacle A overcurrent breaker (20A) H2 Output receptacle B overcurrent breaker (20A) H3 Output receptacle C overcurrent breaker (15A) I Add-on battery (MB240XR) connector J Add-on battery (MB240XR) signal connector K Air vent
INPUT AC100V 50/60Hz 15A MAX.
INPUT AC100V 50/60Hz 15A MAX.
INPUT PROTECTION
15A
RS232C
USB
SER. :
1
OUTPUT AC100-115V 50/60Hz 15A/1000W MAX.
A
34Z5 U.P.S.
MODEL : BN150XR
B C
B
KC
GAFE D
1
D2D
3
INPUT AC100V 50/60Hz 30A MAX.
34Z5 U.P.S.
無停電電源装置
SER.
MODEL : BN240XR
BATTERY CONNECTOR Volt : 72Vdc XX A
20A MAX.
A
C
20A MAX.
B
15A MAX.
C
BA
USB
RS232C
TO BATTERY CABINET
OUTPUT AC100-115V 50/60Hz 24A/2000W MAX.
EH
1H2
C
AD
3
D
2
D
1
H
3
KGJ
F
I
15
1. Preparation
MB240XR
A Add-on battery connector (to BN240XR/previously connected MB240XR) B Add-on battery (MB240XR) connector (to additionally connected MB240XR) C1, C2 Add-on battery signal connector D Battery overcurrent breaker (63A)
(Switch “ON” the breaker when operating.)
34Z5 U.P.S.
BATTERY SUPPLY
MODEL : MB240XR
SER.
EXTENDED BATTERY FOR OMRON UPS BN240XR
Volt : 72Vdc Ah : 9Ah
FOR DETECTION OF No. OF BATTERY CABINET ONLY
DC BRAKER XXA XXXVdc
OFF
ON
BATTERY CONNECTOR Volt : 72Vdc XXA TO UPS or TO OTHER BATTERY MODULES
BATTERY CONNECTOR Volt : 72Vdc XXA TO UPS or TO OTHER BATTERY MODULES
A C2
C1
B D
Battery unit
16
1. Preparation
Symbol Description
UPS is ON.
UPS is OFF.
Add-on battery unit is connected to the UPS.
An error occurred with the UPS.
Connection overload. Output capacity exceeded by connected devices.
Batteries at end of useful life. Necessary to replace the batteries.
Output receptacle B is ON.
Output receptacle C is ON.
AC input / output power supplied.
DC power supplied.
Phase of AC power, 1
φ
: Single phase.
Indicates earth ground.
C
1-4 Explanation of symbols used on unit
B
17
2. Installation and connection
Cautions (Compulsory (do's))
2. Installation and connection
2-1
Precautions and notes on installation and connection
Precautions and notes on installation and connection are given below. Be sure to read them for correct use.
Keep the weight in mind when unpacking and carrying the UPS. Place and run the UPS on a structurally sound and level base.
If the UPS falls over, or if you drop it, it may cause injury.
The weight of the UPS
BN100XR: 20kg BN150XR: 20kg BN240XR: 38kg MB240XR: 29kg (add-on battery unit)
If the UPS falls, immediately stop using it, inspect it, and repair it if necessary.
Keep packing materials, including plastic bags and film, out of the reach of children
Should children swallow or put their head into the packing materials, there is danger of suffocation.
Provide secure grounding
Earth the ground terminals of the UPS and devices connected to the UPS. You may receive an electric shock in the event of trouble or power failure. When both the UPS and devices are not grounded and you touch both, you may receive an electric shock.
For BN100XR/BN150XR, when you use a 3-pin to 2-pin plug for the AC Input Plug, be sure to perform grounding before putting the AC Input Plug in a wall outlet (commercial power). On the other hand, be sure to disconnect grounding terminal after removing the AC Input Plug from a wall outlet (commercial power).
Connect the UPS grounding terminal to a grounded-type wall outlet (commercial power) to ensure that the Power Line Surge Protection works as intended.
Connect the UPS to a wall outlet (commercial power) with a current capacity greater than the maximum input current of the UPS.
Electrical wiring may become hot.
When connected to a rated capacity device, the maximum current that can flow is as follows:
BN100XR: 13.5A, BN150XR: 18A, and BN240XR: 27A.
Be sure to put the input plug of the UPS in a 100V AC (50/60 Hz) wall outlet (commercial power).
Connecting the input plug to a wall outlet (commercial power) of a different voltage may cause a fire.
The UPS may fail.