Omron JX, JXAB002, JXAB004, JXAB007, JXAB015 System Configuration Manual

...
Page 1
JX
Compact & Complete
• V/f controlled inverter
• Side by side mounting
• Built-in EMC filter
• Built-in RS-485 Modbus
• Overload detection function (150% during 60s)
• Micro-surge voltage suppression
• Automatic energy saving
• Emergency shut-off
• Second motor setting
• Auto carrier-frequency reduction
• PTC thermistor input
• Cooling fan switch control
• PC configuration tool: CX-Drive
• CE, UL, cUL, RoHS
Ratings
• 200 V Class single-phase 0.2 to 2.2 kW
• 200 V Class three-phase 0.2 to 7.5 kW
• 400 V Class three-phase 0.4 to 7.5 kW
System configuration
Power supply
MCCB
AC reactor
Filter
JX
Choke
Motor
Ground
*
RJ45 - USB cable
Remote operator extension cable
DC reactor
Output reactor
CX-Drive CX-One
LCD 5 lines remote operator
* Only needed for 3 phase 200 V or to comply C1 on 3 phase 400 V models
1JX
Page 2
Specifications
JX series
A: Standard specs
JXAB002-EF
Vol tage: B: Single-phase 200 VAC 2: Three-phase 200 VAC 4: Three-phase 400 VAC
Max. applicable motor output 002: 0,2 kW
~
075: 7,5 kW
F: Built-in EMC Filter
E: Europe standard
Type designation
200 V class
Single-phase: JX@ AB002 AB004 AB007 AB015 AB022 - - -
Motor
*1
kW
Rated output current (A) 1.4 2.6 4.0 7.1 10.0 15.9 24.0 32.0
Output
Max. output voltage Proportional to input voltage: 0…240 V Max. output frequency
characteristics
Rated input voltage and frequency
Rated input current (A) Three-phase 200 V 1.8 3.4 5.2 9.3 13.0 20.0 30.0 40.0 Rated input current (A) Single-phase 200 V 3.1 5.8 9.0 16.0 22.5 Allowable voltage
Power
supply
fluctuation Allowable frequency
fluctuation
*1
Three-phase: JX@ A2002 A2004 A2007 A2015 A2022 A2037 A2055 A2075
Applicable motor capacity 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5
Inverter capacity kVA
Built-in filter
Braking torque
Cooling method
Based on a standard 3-Phase standard motor.
200 V
240 V
At short-time deceleration At capacitor feedback
0.4 0.9 1.3 2.4 3.4 5.5 8.3 11.0
0.5 1.0 1.6 2.9 4.1 6.6 9.9 13.3
400 Hz
Single-phase 200…240 V 50/60 Hz
3-phase 200…240 V 50/60 Hz
-15%…+10%
+5%
EMC filter (C1 single phase)
50% for
Approx. 50%
Self cooling Forced-air-cooling
3-phase
20 to 40% for
1-phase
Approx 20% to 40% Approx 20%
400 V class
Motor
*1
kW
Inverter capacity kVA
Rated output current (A) 1.5 2.5 3.8 5.5 8.6 13.0 16.0
Output
Max. output voltage Proportional to input voltage: 0…480 V Max. output frequency
characteristics
Rated input voltage and frequency
Rated input current (A) 2.0 3.3 5.0 7.0 11.0 16.5 20.0 Allowable voltage
fluctuation
Power
supply
Allowable frequency fluctuation
*1
Three-phase: JX@ A4004 A4007 A4015 A4022 A4040 A4055 A4075
Applicable motor capacity 0.4 0.75 1.5 2.2 4.0 5.5 7.5
380 V
480 V
Built-in filter
Braking torque
Cooling method
Based on a standard 3-Phase standard motor.
At short-time deceleration At capacitor feedback
2 Frequency inverters
0.9 1.6 2.5 3.6 5.6 8.5 10.5
1.2 2.0 3.1 4.5 7.1 10.8 13.3
400 Hz
3-phase 380…480 V 50/60 Hz
-15%…+10%
+5%
EMC filter C2 class
Approx. 50% Approx. 20% to 40% Approx. 20%
Self cooling Forced-air-cooling
Page 3
Specifications
Commom specifications
Model number
Control methods
Output frequency range
Frequency precision
Resolution of frequency set value
Resolution of output frequency
Overload capability
Control functions
Frequency set value
V/f Characteristics
Inputs signals
Output signals
Functionality
Standard functions
Analogue inputs
Accel/Decel times
Display
Motor overload protection
Instantaneous overcurrent
Overload
Overvoltage
Momentary power loss
Cooling fin overheat
Stall prevention level
Protection functions
Ground fault
Power charge indication
Degree of protection
Ambient humidity
Storage temperature
Ambient temperature
Installation
Installation height
Ambient conditions
Vibration
JX@
Specifications
Phase-to-phase sinusoidal modulation PWM (V/f)
0.5..400 Hz
Digital set value: ±0.01% of the max. frequency Analogue set value: ±0.4% of the max. frequency (25 ±10 ºC) Digital set value: 0.1 Hz Analogue set value: 1/1000 of maximum frequency
0.1 Hz
150% rated output current for one minute
0 to 10 VDC (10 kΩ), 4 to 20 mA (250 Ω), frequency setting volume (selectable), RS485 Modbus
Constant/ reduced torque
FW (forward), RV (reverse), CF1 to CF4 (multi-step speed), JG (jogging), DB (external DC injection braking), SET (2nd func­tion), 2CH (2-step acceleration/deceleration), FRS (free run), EXT (external trip), USP (USP function), SFT (soft lock), AT (analog current input function selection), RS (reset), PTC (thermistor input), STA (3-wire startup), STP (3-wire stop), F/R (3- wire forward/reverse), PID (PID selection), PIDC (PID integral reset), UP (UP of UP/DWN function), DWN (DWN of UP/DWN function), UDC (data clear of UP/DWN function), OPE (forced OPE mode), ADD (frequency addition), F-TM (forced terminal block), RDY (operation ready), SP-SET (special setting), EMR (emergency shutoff)
RUN (signal during operation), FA1 (frequency arrival signal 1), FA2 (frequency arrival signal 2), OL (overload warning sig­nal), OD (PID excess deviation signal), AL (alarm signal), DC (analog input disconnection detection signal), FBV (PID FB status output), NDc (network error), LOG (logical operation result), ODc (communication option disconnected), LOC (light load signal)
AVR function, V/f characteristic selection, upper/lower limit, 16-step speeds, starting frequency adjustment, jogging operation, carrier frequency adjustment, PID control, frequency jump, analog gain/bias adjustment, S-shape acceleration/ deceleration, electronic thermal characteristics/level adjustment, retry function, simplified torque boost, trip monitor, soft lock function, frequency conversion display, USP function, 2nd control function, motor rotation speed UP/DOWN, overcurrent suppression function
2 analogue inputs 0 to 10 V (20 kΩ), 4 to 20 mA (250 Ω)
0.01 to 3000 s (line/curve selection), 2nd accel/decel setting available
Status indicator LED’s Run, Program, Power, Alarm, Power, Hz, Amps, Volume Led indicator Digital operator: Available to monitor frequency reference, output current, output frequency Electronic Thermal overload relay and PTC thermistor input
180% of rated current
150% for 1 minute
790 V for 400 V type and 395 for 200 V type
Following items are selectable: Alarm, 0 Hz start, frequency output at interruption, maximum frequency
Temperature monitor and error detection
Selectable level applicable only at constant speed or during acceleration and constant speed
Detected at power-on
On when power is supplied to the control part
IP20
90% RH or less (without condensation)
-20ºC..+65 ºC (short-term temperature during transportation)
10°C to 50°C (Both the carrier frequency and output current need to be reduced at over 40°C.)
Indoor (no corrosive gas, dust, etc.)
Max. 1000 m
5.9 m/s2 (0.6 G), 10 to 55 Hz (Complies with the test method specified in JIS C0040 (1999).)
JX 3
Page 4
Dimensions
Figure 1
Figure 2
6
5
5
W
H1
W1
H
t1
D1
1.9
D
H1
5
H
W1
W
5
6
t1
D1
D
1.9
Rasmi model
Dimensions
Weight
kg
W H L X Y M
1x200 V
AX-FIJ1006-RE 81 40 193 183 57 M4 0.5
AX-FIJ1010-RE 112 47 226 216 88 M4 0.6
AX-FIJ1026-RE 112 47 226 216 88 M4 0.8
3x200 V
AX-FIJ2006-RE 81 50 193 183 57 M4 1.0
AX-FIJ2020-RE 112 50 226 216 88 M4 1.3
AX-FIJ2040-RE 182 55 289 279 150 M5 2.3
3x400 V
AX-FIJ3005-RE 112 45 226 216 88 M4 0.9
AX-FIJ3011-RE 112 45 226 216 88 M4 1.1
AX-FIJ3020-RE 182 45 289 279 150 M4 1.7
IP 20 type 0.2 to 7.5 kW
Voltage class
Single-phase
200 V
Max. applicable
motor output kW
Inverter model JX@ Figure
0.2 AB002 1
0.4 AB004
0.75 AB007
1.5 AB015 2
W1 H1 W H D t1 D1 Weight
1
67 143 80 155
2
98 176 110 189
2.2 AB022 2 2.4
0.2 A2002 1
0.4 A2004 1 109.5 27 0.9
67 143 80 155
0.75 A2007 1 132.5 50 1.1
Three-phase
200 V
1.5 A2015 2
2.2 A2022 2
98 176 110 189 157.5 6 55
3.7 A20372
5.5 A2055 2
7.5 A2075 2
164 235 180 250 167.5 1.6 77.5 4.2
0.4 A4004 2
0.75 A4007 2
Three-phase
400 V
1.5 A4015 2
4.0 A4040 2
5.5 A4055 2
7.5 A4075 2
98 176 110 189
164 235 180 250 167.5 1.6 77.5 4.2
Rasmi footprint Filters
Filter only needed by the 1-phase 200 V or 3-phase 400 V to comply with C1 EMC class.
Dimensions in mm
95.5
109.5 27 0.9
130.5 28 1.5
157.5 6 55
95.5
130.5 2.6 28 1.5
157.5 6 55
2.6
13 0.8
2.3
13 0.8
2.6
2.2
2.4
2.3
2.42.2 A4022 2
4 Frequency inverters
Page 5
Input AC Reactor
Voltage Reference
Dimensions Weight
kg
A
B2 C2 D E F
200 V
AX-RAI02800080-DE 120 70 120 80 52 5.5 1.78 AX-RAI00880175-DE 120 80 120 80 62 5.5 2.35 AX-RAI00350335-DE 180 85 190 140 55 6 5.5
400 V
AX-RAI07700042-DE 120 70 120 80 52 5.5 1.78 AX-RAI03500090-DE 120 80 120 80 62 5.5 2.35 AX-RAI01300170-DE 120 80 120 80 62 5.5 2.50
Voltage Reference
Dimensions Weight
kg
A
B C D E F G H
200 V
AX-RC21400016-DE
84 11396101 66 5 7.5 2
1.22
AX-RC10700032-DE AX-RC06750061-DE
105 1.60
AX-RC03510093-DE AX-RC02510138-DE
116 1.95
AX-RC01600223-DE
108 135 124 120 82 6.5
9.5
9.5 3.20
AX-RC01110309-DE
120 152
136
13594 7 -
5.20
AX-RC00840437-DE
146 6.00
400 V
AX-RC43000020-DE
84 11396101 66 5 7.5 2
1.22
AX-RC27000030-DE
105 1.60
AX-RC14000047-DE AX-RC10100069-DE
116 1.95
AX-RC06400116-DE
108 135133 120 82 6.5
9.5
9.5 3.70
AX-RC04410167-DE
120 152
136
13594 7 -
5.20
AX-RC03350219-DE
146 6.00
Voltage Reference
Dimensions Weight
kg
A
B2 C2 D E F
200 V
AX-RAO11500026-DE 120 70 120 80 52 5.5 1.78 AX-RAO07600042-DE 120 70 120 80 52 5.5 1.78 AX-RAO04100075-DE 120 80 120 80 62 5.5 2.35 AX-RAO03000105-DE 120 80 120 80 62 5.5 2.35 AX-RAO01830180-DE 180 85 190 140 55 6 5.5 AX-RAO01150220-DE 180 85 190 140 55 6 5.5 AX-RAO00950320-DE 180 85 205 140 55 6 6.5
400 V
AX-RAO16300038-DE 120 70 120 80 52 5.5 1.78 AX-RAO11800053-DE 120 80 120 80 52 5.5 2.35 AX-RAO07300080-DE 120 80 120 80 62 5.5 2.35 AX-RAO04600110-DE 180 85 190 140 55 6 5.5 AX-RAO03600160-DE 180 85 205 140 55 6 6.5
Reference D
diameter
Motor
KW
Dimensions Weight
kg
L W H X Y m AX-FER2102-RE 21 < 2.2 85 22 46 70 - 5 0.1 AX-FER2515-RE 25 < 15 105 25 62 90 - 5 0.2
DC Reactor
Output AC Reactor
Chokes
X
Ø
YW
L
H
Ø
d
m
JX 5
Page 6
Installation
Standard connections
3-phase 200 VAC 1-phase 200 VAC 3-phase 400 VAC
Frequency meter
Frequency setting unit 1 to 2 kΩ
Power supply input 4 to 20 mA DC
For Source logic
R (L1)
S (L2)
T/N (L3)
P24
5
4
3
2
1
PCS
L
AM
10 VDC
H
O
OI
L
4.7 kΩ
250 Ω
Inverter
10 kΩ
U/T1
V/T2
W/T3
PD/+1
P/+
N/-
AL1
AL2
AL0
11
CM2
Motor
Note: To connect the DC reactor, remove the short-circuit bar.
DC reactor
Relay output
Common
RY
24 VDC
Terminal Block Specifications
Terminal Name Function (signal level)
R/L1, S/L2, T/N/L3
U/T1, V/T2, W/T3
PD/+1, P/+
P/+, N/-
Main circuit power supply input Used to connect line power to the drive.
Inverter output Used to connect the motor
External DC reactor terminal Normally connected by the short-circuit bar. Remove the short-circuit bar between +1 and
Regenerative braking unit connection terminal
Grounding For grounding (grounding should conform to the local grounding code.)
6 Frequency inverters
Drives with single-phase 200 V input power use only terminals R/L1 and N (T/L3), terminal S/L2 is not available for these units
P/+2 when a DC reactor is connected.
Connect optional regenerative braking units (If a braking torque is required)
Page 7
Control Circuit
Type No.
PCS
P24
Digital
input
signals
Analog input
Digital output
Monitor
signal
signals
Signal
1
2
3
4
5
L
H
O
OI
L
AL2
AL1
AL0
11
CM2
AM
Signal name Function Signal level
External power supply terminal for input signal (input)
Input power supply
Internal 24 VDC 24 VDC internal power supply 24 VDC ±10% 30mA
Multi-function Input selection 1 Factory setting: Forward/ Stop
Multi-function Input selection 2 Factory setting: Reverse/ Stop
Multi-function Input selection 3 Factory setting: Fault reset
Multi-function Input selection 4 Factory setting: Emergency stop fault
Multi-function Input selection 5 Factory setting: Multi-step speed reference 1
Multi-function Input selection common -- --
Frequency reference power supply 10 VDC 10 mA max
Voltage frequency reference signal 0 to 10 VDC (10 KΩ)
Current frequency reference signal 4 to 20 mA (250 Ω)
Frequency reference common --
NC output
NO output
Relay Output common
Multi-function output terminal Factory setting: Frequency arrival signal at a constant speed
Output signal common --
Analog frequency monitor/Analog output current monitor
...At sink logic Internal power supply output terminal for input signal (output) ...At source logic
Factory default relay settings Under normal operation: AL2-AL0 Closed Under abnormal operation or power shutdown: AL1-AL0 Open
Factory setting: Analog frequency monitor 0 to 10 VDC 1 mA
24 VDC ±10%
250 VAC 2.5 A 30 VDC 3 A
250 VAC 1 A 30 VDC 1 A
27 VDC 50 mA max
Side by side mounting
JX 7
Page 8
Input AC Reactor
Power supply
JX
DC reactor
R/L1
+1 P/+2
MCCB
S/L2
T/L3
AC reactor
Power supply
Max. applicable
motor output kW
0.1 to 1.5 AX-RAI02800080-DE 8.0 2.8 0.4 to 1.5 AX-RAI07700042-DE
2.2 to 3.7 AX-RAI00880175-DE 17.5 0.88 2.2 to 4.0 AX-RAI03500090-DE 9.0 3.5
5.5 to 7.5 AX-RAI00350335-DE 33.5 0.35 5.5 to 7.5 AX-RAI01300170-DE
3 phase 200 V class 400 V class
Reference
Current value AInductancemHMax. applicable
MCCB
V
W
motor output kW
X
YZS/L2
R/L1U
T/L3
JX
Reference
Current value AInductance
4.2 7.7
17.0 1.3
DC Reactor
Max. applicable
motor output kW
0.2 AX-RC21400016-DE 1.6 21.4 -
0.4 AX-RC10700032-DE 3.2 10.7 0.4 AX-RC43000020-DE
0.7 AX-RC06750061-DE 6.1 6.75 0.7 AX-RC27000030-DE 3.0 27.0
1.5 AX-RC03510093-DE 9.33.51 1.5 AX-RC14000047-DE
2.2 AX-RC02510138-DE 13.8 2.51 2.2 AX-RC10100069-DE 6.9 10.1
3.7 AX-RC01600223-DE 22.3 1.60 4.0 AX-RC06400116-DE 11.6 6.40
5.5 AX-RC01110309-DE 30.9 1.11 5.5 AX-RC04410167-DE 16.7 4.41
7.5 AX-RC00840437-DE 43.7 0.84 7.5 AX-RC03350219-DE 21.9 3.35
Output AC
Max. applicable
motor output kW
Reactor
0.1 to 0.4 AX-RAO11500026-DE 2.6 11.50 0.4 to 1.5 AX-RAO16300038-DE
0.75 AX-RAO07600042-DE 4.2 7.60 2.2 AX-RAO11800053-DE 5.3 11.80
1.5 AX-RAO04100075-DE 7.5 4.10 4.0 AX-RAO07300080-DE
2.2 AX-RAO03000105-DE 10.5 3.00 5.5 AX-RAO04600110-DE 11.0 4.60
3.7 AX-RAO01830160-DE 16.0 1.83 7.5 AX-RAO03600160-DE 16.0 3.60
5.5 AX-RAO01150220-DE 22.0 1.15
7.5 AX-RAO00950320-DE 32.0 0.95
200 V class 400 V class
Reference
Reference
Current value AInductancemHMax. applicable
200 V class 400 V class
Current value AInductancemHMax. applicable
motor output kW
motor output kW
Reference
Reference
Current value AInductance
2.0 43.0
4.7 14.0
Current value AInductance
3.8 16.30
8.0 7.30
mH
mH
mH
8 Frequency inverters
Page 9
Ordering information
Choke
A
BB
LCD 5 lines remote operator
Remote operator extension cable
A
A
CC C C
A
Output reactor
B
D
A
USB cable
CX-Drive CX-On e
MCCB
JX
Filter
AC reactor
Motor
Ground
Power supply
DC reactor
* Only needed for 3 phase 200 V or to comply C1 on 3 phase 400 V models
*
JX
Voltage class Max. applicable motor output kW Rated output current (A) Standard
Single-phase 200 V
Three-phase 200 V
Three-phase
400 V
Specifications Model
0.2 1.4 JX-AB002-EF
0.4 2.6 JX-AB004-EF
0.75 4 JX-AB007-EF
1.5 7.1 JX-AB015-EF
2.2 10 JX-AB022-EF
0.2 1.4 JX-A2002-E
0.4 2.6 JX-A2004-E
0.75 4 JX-A2007-E
1.5 7.1 JX-A2015-E
2.2 10 JX-A2022-E
3.7 15.9 JX-A2037-E
5.5 24 JX-A2055-E
7.5 32 JX-A2075-E
0.4 1.5 JX-A4004-EF
0.75 2.5 JX-A4007-EF
1.5 3.8 JX-A4015-EF
2.2 5.5 JX-A4022-EF
4.0 8.6 JX-A4040-EF
5.5 13 JXA4055-EF
7.5 16 JXA4075-EF
JX 9
Page 10
A Line filters
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. I110E-EN-01C
Voltage Model JX-@ Reference Rated current (A) Weight (kg)
1-Phase 200 VAC
3-Phase 200 VAC
3-Phase 400 VAC
Inverter
AB002 / AB004 AX-FIJ1006-RE 6 0.5
AB007 AX-FIJ1010-RE 10 0.6
AB015 / AB022 AX-FIJ1026-RE 26 0.8
A2002 / A2004 / A2007 AX-FIJ2006-RE 6 1.0
A2015 / A2022 / A2037 AX-FIJ2020-RE 20 1.3
A2055 / A2075 AX-FIJ2040-RE 40 2.3
A4004 / A4007 /A4015 AX-FIJ3005-RE 5 0.9
A4022 /A4040 AX-FIJ3011-RE 11 1.1
A4055 / A4075 AX-FIJ3020-RE 20 1.7
Line filter Rasmi
A Input AC Reactors
Voltage Model JX-@ Reference
3-Phase 200 VAC
1-Phase 200 VAC
3-Phase 400 VAC
Inverter
A2002 / A2004 / A2007 AX-RAI02800080-DE
A2015 / A2022 / A2037 AX-RAI00880175-DE
A2055 / A2075 AX-RAI00350335-DE
AB002 / AB004
AB015 / AB022
A4004 / A4007 / A4015 AX-RAI07700042-DE
A4022 / A4040 AX-RAI03500090-DE
A4055 / A4075 AX-RAI01300170-DE
AC Reactor
Under developmentAB007
A DC Reactors
200V single phase
Inverter
JX-AB002 AX-RC10700032-DE JX-A2002 AX-RC21400016-DE -
JX-AB004 AX-RC06750061-DE JX-A2004 AX-RC10700032-DE JX-A4004 AX-RC43000020-DE
JX-AB007 AX-RC03510093-DE JX-A2007 AX-RC06750061-DE JX-A4007 AX-RC27000030-DE
JX-AB015 AX-RC02510138-DE JX-A2015 AX-RC03510093-DE JX-A4015 AX-RC14000047-DE
JX-AB022 AX-RC01600223-DE JX-A2022 AX-RC02510138-DE JX-A4022 AX-RC10100069-DE
-
DC Reactor
Inverter
JX-A2037 AX-RC01600223-DE JX-A4040 AX-RC06400116-DE
JX-A2055 AX-RC01110309-DE JX-A4055 AX-RC04410167-DE
JX-A2075 AX-RC00840437-DE JX-A4075 AX-RC03350219-DE
200V 3-phase 400V 3-phase
DC Reactor
Inverter
DC Reactor
A Chokes
Model Diameter Description
AX-FER2102-RE 21 For 2.2 KW motors or below
AX-FER2515-RE 25 For 7.5 KW motors or below
A Output AC Reactors
Voltage Model JX-@ Reference
200 VAC
400 VAC
Inverter
A2001 / A2002 / A2004
AB001 / AB002 / AB004
A2007/AB007 AX-RAO07600042-DE
A2015 / AB015 AX-RAO04100075-DE
A2022 / AB022 AX-RAO03000105-DE
A2037 AX-RAO01830160-DE
A2055 AX-RAO01150220-DE
A2075 AX-RAO00950320-DE
A4004 / A4007 / A4015 AX-RAO16300038-DE
A4022 AX-RAO11800053-DE
A4040 AX-RAO07300080-DE
A4055 AX-RAO04600110-DE
A4075 AX-RAO03600160-DE
AC Reactor
AX-RAO11500026-DE
B Accessories
Types Model Description Functions
AX-OP05-E
3G3AX-CAJOP300-EE
Digital
operator
3G3AX-OP01
4X-KITMINI
3G3AX-PCACN2
3G3AX-CTB020-EE
3G3AX-CTR150-EE
Accessories
*1
Please note, for JX inverters models, the operator will only display 2 lines of text.
LCD remote
operator
Remote operator
cable
LED remote
operator
Mounting kit for
LED operator
USB converter /
USB cable
RJ45 T-Branch
cable
RJ45 Terminator
resistor
5 Line LCD remote operator
with copy function,
cable length max. 3m.
3 meters cable for connecting
remote operator
LED remote operator, cable
length max. 3m
Mounting kit for LED operator
on panel
RJ45 to USB connection
cable
T cable for RS-422
connection
Terminator resistor for
RS-422 connection
D Computer software
Types Model Description Installation
CX-drive
Software
CX-One
Computer
software
Computer
software
Configuration and monitoring
software tool
Configuration and monitoring
software tool
*1
10 Frequency inverters
Loading...