• Four kinds of 45-mm wide Units are
available:
A 3-safety contact model, a 5-safety
contact model, and models with 3 safety contacts and 2 OFF-delay safety
contacts.
Also available are 17.5-mm wide Expansion Units with 3 safety contacts
and 3 OFF-delay safety contacts.
• Two hand controller (type III C, EN 574)
• Simple expansion connection.
• OFF-delay models have 15-step OFFdelay settings.
• Conforms to EN standards. (BG approval)
• Approved by UL and CSA.
• Both DIN track mounting and screw
mounting are possible.
• Suitable for PNP OSSD outputs of
safety sensors, F3SN, F3SH, F3S-B,
F3S-TGR, F3SL
The G9SA Series Offers a Complete
Line-up of Compact Units.
Ordering Information
Emergency-stop Units
Main contactsAuxiliary contactNumber of input channelsRated voltageModelCategory
3PST-NOSPST-NC1 channel or 2 channels possible
5PST-NOSPST-NC1 channel or 2 channels possible
Emergency-stop OFF-delay Units
Main contacts
3PST-NODPST-NOSPST-NC
Note: The following 15-step OFF-delay time settings are available:
T075: 0.5, 1, 1.5, 2, 2.5, 3, 3.5, 4, 4.5, 5, 5.5, 6, 6.5, 7, and 7.5 s
T15: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, and 15 s
T30: 2, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, and 30 s
Two-hand Controller
Main contactsAuxiliary contactNumber of input channelsRated voltageModelCategory
3PST-NOSPST-NC2 channels
Expansion Unit
The Expansion Unit connects to a G9SA-301, G9SA-501, G9SA-
Main contactsAuxiliary contactModelCategory
OFF-delay
contacts
3PST-NOSPST-NCG9SA-EX3014
Auxiliary
contact
Number of
input channels
1 channel
or 2 channels
possible
OFF-delay
time
7.5 s
15 s
30 s
24 VAC/VDC
100 to 240 VAC
24 VAC/VDC
100 to 240 VAC
Rated voltageModelCategory
24 VAC/VDC
100 to 240 VAC
24 VAC/VDC
100 to 240 VAC
24 VAC/VDC
100 to 240 VAC
24 VAC/VDC
100 to 240 VAC
321, or G9SA-TH301.
G9SA-301
G9SA-501
G9SA-321-T075
G9SA-321-T15
G9SA-321-T30
G9SA-TH3014 (IIIc, EN574)
Main contacts:
4
4
OFF-delay
contacts:
3
G9SA
G-109G9SA
Expansion Units with OFF-delay Outputs
The Expansion Unit connects to a G9SA-301, G9SA-501, G9SA-321, or G9SA-TH301.
Main contact formAuxiliary contactOFF-delay timeModelCategory
7.5 sG9SA-EX031-T075
3PST-NOSPST-NC
30 sG9SA-EX031-T30
Note: The following 15-step OFF-delay time settings are available:
T075: 0.5, 1, 1.5, 2, 2.5, 3, 3.5, 4, 4.5, 5, 5.5, 6, 6.5, 7, and 7.5 s
T15: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, and 15 s
T30: 2, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, and 30 s
Model Number Legend
315 sG9SA-EX031-T15
G9SA-######-####
1 2 3 4 5 6
1. Function
None: Emergency stop
EX: Expansion Unit
TH: Two-hand Controller
Operating voltage range85% to 110% of rated power supply voltage
Power consumption
(See note.)
Note: When an Expansion Unit is connected, the power consumption is increased by 2 VA/2 W max.
Inputs
ItemG9SA-301/321-T#/TH301G9SA-501
Input current (See note.) 40 mA max.60 mA max.
Note: When an Expansion Unit is connected, the input current is increased by 30 mA max.
Contacts
Item
Rated load250 VAC, 5 A
Rated carry current 5 A
Characteristics
ItemG9SA-301/TH301G9SA-501/321-T#G9SA-EX301/EX031-T#
Contact resistance (see note 1)100 mΩ
Operating time30 ms max. (not including bounce time)
Response time (see note 2)10 ms max. (not including bounce time)
Insulation resistance (see note 3)100 MΩ min. (at 500 VDC)
Between different outputs
Dielectric
strength
Vibration resistance10 to 55 Hz, 0.75-mm double amplitude
Shock
resistance
Durability
Minimum permissible load (reference value)5 VDC, 1 mA
Between inputs and outputs
Between power inputs and outputs
Between power inputs and other inputs
(only for 100 to 240-V models)
Destruction300 m/s
Malfunction100 m/s
Mechanical5,000,000 operations min. (at approx. 7,200 operations/hr)
Electrical100,000 operations min. (at approx. 1,800 operations/hr)
24 VAC/VDC:24 VAC, 50/60 Hz, or 24 VDC
100 to 240 VAC:100 to 240 VAC, 50/60 Hz
24 VAC/VDC: 1.8 VA/1.7 W max.
100 to 240 VAC: 9 VA max.
G9SA-301/501/321-T#/TH301/EX301/EX031-T#
Resistive load (cos φ =1)
2,500 VAC, 50/60 Hz for 1 min
Operating:-25°C to 55°C (with no icing or condensation)
Storage:-25°C to 85°C (with no icing or condensation)
Operating:35% to 85%
Storage:35% to 85%
EMI: EN55011 group 1 class A
EMS: EN50082-2 group 1
24 VAC/VDC: 2.8 VA/2.6 W max.
100 to 240 VAC: 11 VA max.
2
2
24 VAC/VDC: 3.5 VA/3.3 W max.
100 to 240 VAC: 12.5 VA max.
Approx. 130 g
G9SA
Note: 1. The contact resistance was measured with 1 A at 5 VDC using the voltage-drop method.
2. The response time is the time it takes for the main contact to open after the input is turned OFF.
3. The insulation resistance was measured with 500 VDC at the same places that the dielectric strength was checked.
4. Weight shown is for 24-VAC/VDC type. For 100 to 240-VAC type, add approximately 20 g.
G-111G9SA
Application Examples
G9SA-301 (24 VAC/VDC) with 2-channel Limit Switch Input/Auto-reset
Feedback loop
Open
Timing Chart
Limit switches
S1 and S2
K1 and K2
(NC)
K1 and K2
(NO)
KM1 and KM2
(NC)
KM1 and KM2
(NO)
Control
circuit
G9SA-301 (24 VAC/VDC) with 2-channel Limit Switch Input/Manual-reset
Feedback loop
Open
S1: Safety Limit Switch
S2: Limit switch
KM1 and KM2: Magnetic Contactor
M: 3-phase motor
Note: This circuit achieves EN954-1
Safety Category 4.
with direct opening mechanism
(D4N or D4B)
Timing Chart
Limit switches
S1 and S2
Reset switch
S3
K1 and K2
(NC)
K1 and K2
(NO)
KM1 and KM2
(NC)
KM1 and KM2
(NO)
PC input
PC output
KM3
Control
circuit
G-112Safety Sensors / Components
S1: Safety Limit Switch
S2: Limit switch
S3: Reset switch
KM1 and KM2: Magnetic Contactor
KM3: Solid-state Contactor
M: 3-phase motor
Note: This circuit achieves EN954-1
with direct opening mechanism
(D4N or D4B)
Safety Category 4.
G9SA-301 (100 to 240 VAC) with 2-channel Limit Switch Input/Auto-reset
Limit switches
S1 and S2
K1 and K2
(NC)
K1 and K2
Feedback loop
Open
(NO)
KM1 and KM2
(NC)
KM1 and KM2
(NO)
Timing Chart
Control
circuit
S1: Safety Limit Switch
S2: Limit switch
KM1 and KM2: Magnetic Contactor
M: 3-phase motor
Note: This circuit achieves EN954-1
with direct opening mechanism
(D4N or D4B)
Safety Category 4.
G9SA-301 (24 VAC/VDC) with 2-channel Emergency Stop Switch Input/Manual-reset
Timing Chart
Emergency
stop switch S1
Reset switch
S2
Feedback loop
K1 and K2
(NC)
K1 and K2
(NO)
KM1 and KM2
(NC)
KM1 and KM2
(NO)
PC input
PC output
KM3
Control
circuit
S1: Emergency stop switch
S2: Reset switch
KM1 and KM2: Magnetic Contactor
KM3: Solid-state Contactor
M: 3-phase motor
Note: This circuit achieves EN954-1
with direct opening mechanism
(A165E or A22E)
Safety Category 4.
G9SA
G-113G9SA
G9SA-321-T# (24 VAC/VDC) with 2-channel Limit Switch Input/Manual-reset
Feedback loop
Open
S1: Safety Limit Switch
S2: Limit switch
S3: Reset switch
KM1 and KM2: Magnetic Contactor
M: 3-phase motor
with direct opening mechanism
(D4N or D4B)
Timing Chart
Limit switches
S1 and S2
Reset switch
S3
K1 and K2
(NC)
K1 and K2
(NO)
K3 and K4
(NC)
K3 and K4
(NO)
KM1 and KM2
(NC)
KM1 and KM2
(NO)
Operation
instruction
Motor rotation
OFF-delay time
Off delay
timer
Control
circuit
Operation
instruction
Note: This circuit achieves EN954-1 Safety Category 4.
The OFF-delay output, however, achieves EN954-1
Safety Category 3.
Motor controller
G-114Safety Sensors / Components
G9SA-321-T# (24 VAC/VDC) + G9SA-EX031-T# with 2-channel Limit Switch Input/Manual-reset
Feedback loop
Open
Off delay
Off delay
timer
Control
circuit
timer
S1: Safety Limit Switch
S2: Limit switch
S3: Reset switch
KM1, KM2,
KM3, and KM4: Magnetic Contactor
M1, M2: 3-phase motor
with direct opening mechanism
(D4N or D4B)
Timing Chart
Limit switches
S1 and S2
Reset switch
S3
G9SA-321-T#
K1 and K2 (NC)
G9SA-321-T#
K1 and K2 (NO)
G9SA-321-T#
K3 and K4 (NC)
G9SA-321-T#
K3 and K4 (NO)
KM1 and KM2
(NC)
KM1 and KM2
(NO)
Operation
instruction
Motor M1
rotation
G9SA-EX031
K1 and K2 (NC)
G9SA-EX-031
K1 and K2 (NO)
KM3 and KM4
(NC)
KM3 and KM4
(NO)
Operation
instruction
Motor M2
rotation
OFF-delay time 1
OFF-delay time 2
Operation
instruction
Operation
instruction
Note: This circuit achieves EN954-1 Safety Category 4.
The OFF-delay output, however, achieves EN954-1
Safety Category 3.
Motor controller
Motor controller
G9SA
G-115G9SA
G9SA-301 (24 VAC/VDC) with 2-channel Safety Area Sensor/Manual-reset
Timing Chart
F3SN-A Incident
Interrupted
Reset switch S1
K1 and K2
(NC)
K1 and K2
(NO)
KM1 and KM2
(NC)
KM1 and KM2
(NO)
PC input
PC output
KM3
F3SN-A:Safety area sensor
S1:Reset switch
KM1 and KM2: Magnetic Contactor
KM3:Solid-state Contactor
M:3-phase motor
E1:24-VDC Power Supply
Note: This circuit achieves EN954-1
Safety Category 4.
Feedback loop
Shield
EmitterReceiver
F3SN-A
F3SH-A
RS-485(A) (Gray)
RS-485(B) (Pink)
(Red)
Open
EDM input (Red)
0V (Blue)
Interlock selection
input (White)
Reset input (Yellow)
Test input (Green)
Open
+24V (Brown)
+24V (Brown)
Auxiliary (Yellow)
Open
OSSD2 (White)
OSSD1 (Green)
Open
Shield
0V (Blue)
KM3
E1
Control
circuit
G-116Safety Sensors / Components
G9SA-TH301 (24 VDC) with 2-hand Inputs/Auto-reset
(See note 1.)
Feedback loop
Control circuit
Timing Chart
S11 (NC)
S11 (NO)
S12 (NC)
S12 (NO)
KM1 and KM2
(NC)
KM1 and KM2
(NO)
Input time difference operates only
when the difference is 0.5 s max.
S11, S12:Two-hand pushbutton switches
KM1 and KM2: Magnetic Contactor
Note: 1. Use a 1NC+1NO switch for S11
and S12.
2. This circuit achieves EN954-1
Safety Category 4.
Typ III C (EN 574)
0.5 s max.
G9SA
G-117G9SA
G9SA-501 (24 VAC/VDC) and G9SA-EX301 with 2-channel Limit Switch Input/Manual-reset
Feedback loop
Open
Control
circuit
S1: Safety Limit Switch
S2: Limit switch
S3: Reset switch
KM1 and KM2: Magnetic Contactor
M: 3-phase motor
with direct opening mechanism
(D4N or D4B)
Timing Chart
Limit switches S1
and S2
Reset switch
S3
G9SA-501
K1, K2, K3 and
K4 (NC)
G9SA-501
K1, K2, K3, and
K4 (NO)
G9SA-EX301
K1 and K2 (NC)
G9SA-EX301
K1 and K2 (NO)
KM1 and KM2
(NC)
KM1 and KM2
(NO)
Note: This circuit achieves EN954-1 Safety Category 4.
G-118Safety Sensors / Components
Dimensions
Note: All units are in millimeters unless otherwise indicated. The diagrams are drawn in perspective.
Note: 1. Use terminals A and B to switch reset mode.
A to B open: Manual reset
A to B closed: Auto-reset
2. Use terminals C and D to switch input conditions.
C to D open: DPDT input.
C to D closed: DPST-NC input. (Make sure T11 and
T21 are open.)
3. Use terminal T23 with + common 2-channel input.
When using T23, make sure that T21 and T22 are
open. For 1-channel input, make sure T12 and T23 are
closed.
4. With 100 to 240-VAC type, be sure to connect PE to a
protective ground. With 24-VAC/VDC type, if the power
supply is not connected to a protective ground, be sure
to connect PE to a protective ground.
5. With 24-VAC/VDC type, the power supply terminals A1
and A2 have polarities. A2 is the negative pole.
Control
circuit
Control
circuit
Off delay
timer
Control
circuit
G-120Safety Sensors / Components
Precautions
Do not touch the terminal area of the Relays or the socket terminal
area (charged area) while power is ON. Electric shock will result.
Wiring
Turn OFF the G9SA before wiring the G9SA. Do not touch the terminals of the G9SA while the power is turned ON, because the terminals are charged and may cause an electric shock.
Use the following to wire the G9SA.
Stranded wire: 0.75 to 1.5 mm
Solid wire:1.0 to 1.5 mm
Tighten each screw to a torque of 0.78 to 1.18 N·m, or the G9SA
may malfunction or generate heat.
External inputs connected to T11 and T12 or T21 and T22 of the
G9SA-301 must be no-voltage contact inputs.
PE is a ground terminal.
When a machine is grounded at the positive, the PE terminal should
not be grounded.
2
2
Mounting Expansion Units
Turn OFF the G9SA before connecting the Expansion Unit.
When an Expansion Unit is being used, remove the connector cover
from the G9SA Safety Relay Unit (G9SA-301, G9SA-501, G9SA321#, or G9SA-TH301) and insert the connector of the Expansion
Unit’s connector cable.
Applicable Safety Category (EN954-1)
G9SA-series Relays meet the requirements of Safety Category 4 of
the EN954-1 standards when they are used as shown in the examples provided by OMRON. The Relays may not meet the standards
in some operating conditions. The OFF-delay output of models
G9SA-321-T# and EX031-T#, however, conform to Safety Category
3.
The applicable safety category is determined from the whole safety
control system. Make sure that the whole safety control system
meets EN954-1 requirements.
Mounting Multiple Units
When mounting multiple Units close to each other, the rated current
will be 3 A. Do not apply a current higher than 3 A.
Connecting Inputs
If using multiple G9SA models, inputs cannot be made using the
same switch. This is also true for other input terminals.
G9SAG9SA
Earth Short
A positive thermistor is built into the G9SA circuits, so you can detect
earth short breakdowns and breakdown shorts between channel 1
and channel 2. If the short breakdown is canceled, reset is automatic.
G9SA
G-121G9SA
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. J121-E2-03A-X
In the interest of product improvement, specifications are subject to change without notice.