Omron G7Z DATASHEET

New Product News
Power Relays
G7Z
High-capacity Power Relays Capable of Carrying and Switching 40 A at 440 VAC
High
Compact
Insulation
Load switching for
400-VAC systems
Low
Noise
Approx. 70 dB
40%
smaller than
contactors (IEC-
AC1, 50-A
specifications)
Low Power
Consumption
Less than 4 W DC
Capacity
IEC-AC1 40-A rating
4-pole power fully applied:
160 A
RoHS
Compliant
Mirror Contacts
for
Safety Function
Simple
Mounting
High-capacity Power Relays for Use in Contactor Current Ranges
G7Z
Customers want to use contactors with greater ease for AC 1 class (IEC load) switching, and the G7Z Power Relays were developed to meet those needs. As the No.1 leader in production performance in Relays, OMRON has implemented crossover technologies for the new design of the G7Z. Along with providing switching in the conventional contactor range of 40 A with the size and convenience of a conventional relay, we have also achieved an ecological relay-the user-friendly, high-capacity G7Z.
Number of poles
45 mm
62 mm
84 mm
60 mm
High Capacity and
High Insulation
Continuously apply 40 A at 440 VAC,
or apply up to a maximum of 160 A
by using 4-pole parallel connections
for full power application.*
The Relays are highly insulated to
support load switching
of 40 A at 440 VAC
* Always consult with your OMRON representative
before using the maximum current of 160 A.
Compact Size
Downsizing of approximately 40% volume compared with contactors.*
Contributes to space savings in control panels.
* IEC-AC1 50-A specifications
Safety Function with Mirror Contacts
EN 60947-4-1 certification for mirror contact mechanisms has been obtained by
using a combination of a relay and auxiliary contact blocks (5 VDC, 1 mA),
enabling application in feedback circuits of safety circuits.
G7Z
4 poles
3 poles 2 poles
1 pole
Up to 20 A 25 A 30 A 40 A
G7J
Expansion of relay range
Conventional usage division
Contactor current range
Current capacity
Application Example: General Safety Circuit
G9SA-301 (24-V AC/DC) (two limit switch input channels with manual reset)
Feedback loop
Open
TH
SA
Control
circuit
Feedback circuit
Low Noise and
Low Power Consumption
Low noise of approx. 70 dB compared with the approx.
100 dB for contactors.* Low power consumption of less
than 4 W DC. Environmentally friendly specifications.
* IEC-AC1 50-A specifications
DIN Track Mountable
The Relay can be easily mounted right on a DIN Track.
Power Relays Contactors
Power Relays
G7Z
Multi-pole Power Relay fo r Contactor Current Range Capable of Carrying and Switching 40 A at 440 VAC
• One pole, 40 A can be carried and switched.
• The maximum load capa city of 160 A when usi ng 4-pole parallel connections.
• All materials used are compliant with the RoHS Directive
• EN 60947-4-1 certification for mirror contact mechanisms has been obtained b y us ing a co mbin ation of t he rela y and auxi liary contact blocks.
Note: Refer to the Precautions for Correct Use on page 9.
Model Number Structure
Model Number Legend
Relay with Auxiliary Contact Block
G7Z-@-@@
123
1. Relay Contact Configuration
4A: 4PST-NO 3A1B: 3PST-NO/SPST-NC 2A2B: DPST-NO/DPST-NC
2. Co ntact Configuration of Auxiliary Contacts
20: DPST-NO 11: SPST-NO/SPST-NC 02: DPST-NC
3. Contact Mechanism of Auxiliary Contacts
Z: Bifurcated crossbar contact
Auxiliary Contact Block
G73Z-@@
1 2
1. Co ntact Configuratio n of Auxiliary Contacts
20: DPST-NO 11: SPST-NO/SPST-NC 02: DPST-NC
2. Co ntact Mechanism of Auxiliary Contacts
Z: Bifurcated crossbar contact
Configuration
Structure Contact configuratio n Screw terminals
Classification Relay Auxiliary Contact
Relay with Auxilia ry Contact Block
Auxiliary Contact Block 2 poles --- DPST-NO G73Z-20Z
Note: 1. Relay contact terminals are M5, and the coil terminals are M3.5.
2. Auxiliary contact block terminals are M3.5.
4 poles + 2 poles
4PST-NO DPST-NO G7Z-4A-20Z
3PST-NO/SPST-NC DPST-NO G7Z-3A1B-20Z
DPST-NO/DPST-NC DPST-NO G7Z-2A2B-20Z
Block
SPST-NO/SPST-NC G7Z-4A-11Z DPST-NC G7Z-4A-02Z
SPST-NO/SPST-NC G7Z-3A1B-11Z DPST-NC G7Z-3A1B-02Z
SPST-NO/SPST-NC G7Z-2A2B-11Z DPST-NC G7Z-2A2B-02Z
SPST-NO/SPST-NC G73Z-11Z DPST-NC G73Z-02Z
4 Power Relays G7Z
Ordering Information
Relay with Auxiliary Contact
Block
Relay with Auxiliary Contact Block (for Screw Terminals)
Contact configuratio n Rated voltage Model
Relay Auxiliary contact
4PST-NO DPST-NO 12, 24 VDC G7Z-4A-20Z
3PST-NO/ SPST-NC
DPST-NO/ DPST-NC
block
SPST-NO/SPST-NC 12, 24 VDC G7Z-4A-11Z DPST-NC 12, 24 VDC G7Z-4A-02Z DPST-NO 12, 24 VDC G7Z-3A1B-20Z SPST-NO/SPST-NC 12, 24 VDC G7Z-3A1B-11Z DPST-NC 12, 24 VDC G7Z-3A1B-02Z DPST-NO 12, 24 VDC G7Z-2A2B-20Z SPST-NO/SPST-NC 12, 24 VDC G7Z-2A2B-11Z DPST-NC 12, 24 VDC G7Z-2A2B-02Z
Specifications
Ratings
Coil Ratings
Accessories (Order Separately)
Auxiliary Contact Block
Contact
configuration
DPST-NO G73Z-20Z SPST-NO/SPST-NC G73Z-11Z DPST-NC G73Z-02Z
Model
Item Rated current Coil resistance Must operate
Rated voltage Percentage of rated voltage 12 VDC 333 mA 39 24 VDC 154 mA 156
Note: 1. Rated current and coil resistance were measured at a coil temperature of 23°C with coil resistance of ±15%.
2. Operating characteristic s were measured at a coil temperature of 23
3. The maximum allowable voltage is the maximum value of the fluctuation range for the Relay coil operating power supply and was measured at an ambient
temperature of 23 There is, however, no continuous allowance.
°C.
75% max. 10% min. 110% Approx. 3.7 W
voltage
Must release
voltage
°C.
Maximum
voltage
Power
consumption
Contact Ratings
Relay
Model G7Z-4A-@Z, G7Z-3A1B-@Z,
Item Load Resistive
Contact structure Double break Contact materia l Ag alloy Rated load NO 40 A at
Rated carry current NO 40 A 22 A 5 A
Maximum contact voltage 480 VAC 125 VDC Maximum contact
current Maximum switching
capacity Failure rate P value (reference
value)
Note: The ratings for the auxiliary contact block mounted on the G7Z are the
same as those for the G73Z auxiliary contact block.
440 VAC
NC 25 A at
440 VAC
NC 25 A 10 A 5 A
NO 40 A NC 25 A NO 17,600 VA 9,680 VA 550 W NC 1 1,00 0 VA 4,400 VA 550 W
2 A at 24 VDC
load
G7Z-2A2B-@Z
Inductive
load cos
φ =
0.3
22 A at 440 VAC
10 A at 440 VAC
Resistive
load L/R = 1
ms
5 A at 110 VDC
5 A at 110 VDC
Auxiliary Contact Block
Model G73Z-20Z, G73Z-11Z, G73Z-02Z
Item Load Resistive
Contact structure Double break Contact material Au clad + Ag Rated load 1 A at
Rated carry current 1 A Maximum contact voltage 480 VAC 125 VDC Maximum contact current 1 A Maximum switching capacity 440 VA 220 VA 110 W Failure rate P value (reference
value)
load
440 VAC
1 mA at 5 VDC
Inductive
load cos
0.3
0.5 A at 440 VAC
φ =
Resistive
load L/R = 1
ms
5 A at 110 VDC
Powe r Re la ys G7Z 5
Loading...