Safety Relay G7SA
Slim Safety Relays Conforming to EN
Standards
The forcibly guided contact in the G7SA assures
safe operation (EN50205 Class A, approved by
VDE.)
Ideal for use in safety circuits in press machinery,
machine tools, and other production machinery.
Four-pole and six-pole Relays are available.
The Relay’s terminal arrangement simplifies PWB
pattern design.
Reinforced
Reinforced insulation between some poles.
UL, CSA approval.
CE marking.
Note: Be
Ordering Information
Safety Relays
Standard Flux-tight
insulation between inputs and outputs.
sure to refer to the
Type Sealing Poles Contacts Rated
Precautions
on page
4 poles
6 poles
131.
3PST-NO, SPST-NC
DPST-NO, DPST-NC
5PST-NO, SPST-NC G7SA-5A1B
4PST-NO, DPST-NC G7SA-4A2B
3PST-NO, 3PST-NC G7SA-3A3B
24 VDC
RC
voltage
G7SA-3A1B
G7SA-2A2B
VDE
X
Model
Safety Relay Sockets
Track-mounting T
Back-mounting
rack mounting and screw mounting
possible
PCB terminals
Model Number Legend
G7SA-jAjB
12
1. NO
2. NC Contact Poles
Contact Poles
2: DPST-NO
3: 3PST-NO
4: 4PST-NO
5: 5PST-NO
1: SPST-NC
2: DPST-NC
3: 3PST-NC
Type LED
No
Yes
No
indicator
Poles Rated
4 poles
6 poles
4 poles
6 poles
4 poles
6 poles
---
24 VDC
---
voltage
Model
P7SA-10F
P7SA-14F
P7SA-10F-ND
P7SA-14F-ND
P7SA-10P
P7SA-14P
132
G7SA
Specifications
Ratings
Coil
Rated
voltage
24 VDC
Rated
current
4 poles: 15 mA
6 poles: 20.8 mA
Coil resistance
4 poles: 1,600
6 poles: 1,152
Must-operate
Ω
75% max. (V)
Ω
voltage
Must-release
voltage
10% min. (V)
Max.
voltage
1
10% (V)
G7SA
Power consumption
4 poles:
Approx. 360 mW
6 poles: Approx. 500 mW
Note: 1.
The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of
2.
Performance characteristics are based on a coil temperature of 23
3. The
value given for the maximum voltage is for voltages applied instantaneously to the Relay coil (at an ambient temperature of
23°C)
and not continuously
.
°C.
±15%.
Contacts
Load
Rated load
Rated carry current
Max. switching voltage
Max. switching current
Max. switching capacity (reference value)
Resistive load (cos φ =1)
6 A at 250 V
6 A
250 V
6 A
1,500 V
AC, 6 A at 30 VDC
AC, 125 VDC
A, 180 W
Characteristics
Safety Relay Sockets
Model Continuous
P7SA-14j
Note: 1.
If the P7SA-1jF is used between 55 and 85°C, reduce the continuous current (from 6A) by 0.1 A for every degree.
2.
Measurement conditions: Measurement of the same points as for the dielectric strength at 500 VDC.
3.
When using the P7SA-1jF-ND at 24 VDC, use at an ambient operating temperature from –25 to 55
6 A (see note 1)
Safety Relays
Contact
resistance
Operating time (see note 2)
Response time (see note 2) 10 ms max. (The response time is the time it takes for the normally open contacts to open
Release time (see note 2)
Maximum operating
frequency
Insulation resistance
Dielectric strength (see notes 3, 4)
V
ibration resistance
Shock resistance
Life expectancy
Min. permissible load (see note 5)
(reference value)
Ambient temperature (see note 6)
Ambient humidity
Weight
Approved standards
Note: 1.
The values listed above are initial values.
Mechanical
Rated load
Destruction
Malfunction
Mechanical
Electrical
current
2,500 V
100 mΩ max. (The contact resistance was measured with 1 A at 5 VDC using the
voltage-drop method.)
20 ms max.
after the coil voltage is turned OFF
20 ms max.
36,000 operations/hr
1,800 operations/hr
100 MΩ min. (at 500 VDC)
(The insulation resistance was measured with a 500-VDC megger at the same places that the
dielectric strength was measured.)
Between coil contacts/dif
(2,500 V
AC between poles 3–4 in 4-pole Relays or poles 3–5, 4–6, and 5–6 in 6-pole Relays.)
Between contacts of same polarity: 1,500 VAC, 50/60 Hz for 1 min
10 to 55 Hz, 1.5-mm double amplitude
1,000 m/s
100 m/s
10,000,000 operations min. (at approx. 36,000 operations/hr)
100,000 operations min. (at the rated load and approx. 1,800 operations/hr)
5 VDC, 1 mA
Operating: –40°
Storage: –40°
Operating:
Storage:
4 poles: Approx. 22 g
6 poles: Approx. 25 g
EN61810-1 (IEC61810-1), EN50205, UL508, CSA22.2 No. 14
2
2
Dielectric strength
AC for 1 min. between poles
.)
ferent poles: 4,000 V
C to 85°C (with no icing or condensation)
C to 85°C (with no icing or condensation)
35% to 85%
35% to 85%
AC, 50/60 Hz for 1 min
Insulation resistance
100 MΩ min. (see note 2)
°C.
133