Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with a tolerance of ±10%.
2. Operating characteristics are measured at a coil temperature of 23°C.
3. The maximum voltage is the highest voltage that can be imposed on the relay coil.
Contact Ratings
■
LoadResistive load
Rated load0.5 A at 125 VAC;
Contact materialAg (Au-Alloy)
Rated carry current3 A
Max. switching voltage250 VAC, 220 VDC
Max. switching current2 A1 A
Max. switching power125 VA, 60 W62.5 VA, 30 W
Failure rate (reference value)0.01 mA at 10 mVDC
SetArmature OFF 0.0150.040.050.070.160.281.14
Armature ON0.010.0250.0350.050.120.20.752.9
Reset Armature OFF 0.010.0250.0350.050.120.20.752.9
Armature ON0.0150.040.050.070.160.281.14
ItemG6A-274P-ST(40)-US
(cosφ = 1)
2 A at 30 VDC
Inductive load
(cosφ = 0.4; L/R = 7 ms)
0.3 A at 125 VAC;
1 A at 30 VDC
ItemG6AK-274P-ST(40)-US/G6AU-274P-ST-US
LoadResistive load
Rated load0.5 A at 125 VAC;
Contact materialAg (Au-Alloy)
Rated carry current3 A
Max. switching voltage250 VAC, 220 VDC
Max. switching current2 A1 A
Max. switching power125 VA, 60 W62.5 VA, 30 W
Failure rate (reference value) (See note.) 0.01 mA at 10 mVDC
Note: P level: λ60 = 0.1 x 10–6/operation
This value was measured at a switching frequency of 60 operations/min and the criterion of contact resistance is 50 Ω. This value
may vary depending on the switching frequency and operating environment. Always double-check relay suitability under actual operating conditions.
(cosφ = 1)
2 A at 30 VDC
Inductive load
(cosφ = 0.4; L/R = 7 ms)
0.25 A at 125 VAC;
1 A at 30 VDC
111
Page 4
■ Characteristics
Contact resistance (See note 1.)50 mΩ max.
Operate (set) time (See note 2.)Single-side stable types:
Release (reset) time (See note 2.)Single-side stable types:
1,000 VAC, 50/60 Hz for 1 min between contacts of different polarity
1,000 VAC, 50/60 Hz for 1 min between contacts of same polarity
250 VAC, 50/60 Hz for 1 min between set and reset coils
Malfunction: 10 to 55 to 10 Hz, 1.65-mm single amplitude (3.3-mm double amplitude)
2
Destruction: 1,000 m/s
Malfunction: 500 m/s
Electrical: 500,000 operations min. (at 1,800 operations/hr)
Using the Relay in a circuit where the Relay will be ON continuously for long periods (without switching) can lead to unstable
contacts because the heat generated by the coil itself will affect
the insulation, causing a film to develop on the contact surfaces.
We recommend using a latching relay (magnetic-holding relay) in
this kind of circuit. If a single-side stable model must be used in
this kind of circuit, we recommend using a fail-safe circuit design
that provides protection against contact failure or coil burnout.
Relay Handling
When washing the product after soldering the Relay to a PCB,
use a water-based solvent or alcohol-based solvent, and keep the
solvent temperature to less than 40°C. Do not put the Relay in a
cold cleaning bath immediately after soldering.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. K020-E1-09
114
Double-swicthing load in two poles
Double-switching in two poles as shown in the figure below, one
pole and two pole interval may become MBB(Make Before
Break) mechanically according to the timing of the point of contact switching (By the short-circuit mode), and the malfunction
might be caused.
In such a circuit, direct electric switching should be avoided, and
concern for contact to be carried after the contact of Relay absolutely switches in condition of no load.
Contacts
Load
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.