Use wires of the applicable sizes specified above. The length of the exposed conductor should be 7 mm for a G3RV-SL700 series, 12 mm for a
G3RV-SL500 series.
G3RV-SL700
7 mm
G3RV-SL500
12 mm
Fig. 1 Exposed Conductor Length
Wiring Procedure for G3RV-SL500 series
● Wiring
Insert the exposed conductor into the connection hole.
No other tools are required.
Note: In case of wiring stranded wires without ferrules screwdriver
should be inserted before inserting the wire.
Screwdriver should be removed after fully insertion of the wire.
● Removing
Insert the specified screwdriver into the release hole.
Removing wire.
Removing screwdriver.
Slim Relay G3RV11
Precautions
Screwdriver
Precautions for Connection
• Do not move the screwdriver up, down, or from side to side while it
is inserted in the hole. Doing so may cause damage to internal
components (e.g., deformation of the clamp spring or cracks in the
housing) or cause deterioration of insulation.
• Do not insert the screwdriver at an angle. Doing so may break the
side of socket and result in a short-circuit.
• Do not insert two or more wires in the hole. Wires may come in
contact with the spring causing a temperature rise or be subject to
sparks.
• If lubricating liquid, such as oil, is present on the tip of screwdriver,
the screwdriver may fall out resulting in injury to the operator.
• Inser t the screwdriver into the bottom of the hole. It may not be
possible to connect cables properly if the screwdriver is inserted
incorrectly.
General Precautions
• Do not use the product if it has been dropped on the ground.
Dropping the product may adversely affect performance.
• Confirm that the socket is securely attached to the mounting track
before wiring. If the socket is mounted insecurely it may fall and
injure the operator.
• Ensure that the socket is not charged during wiring and
maintenance. Not doing so may result in electric shock.
• Do not pour water or cleansing agents on the product. Doing so
may result in electric shock.
• Do not use the socket in locations subject to solvents or alkaline
chemicals.
• Do not use the socket in locations subject to ultraviolet light (e.g.,
direct sunlight). Doing so may result in markings fading, rust,
corrosion, or resin deterioration.
• Do not dispose the product in fire.
Removing from Mounting Rail
To remove the socket from the mounting rail, insert the tip of
screwdriver in the fixture rail, and move it in the direction shown
below.
• Insert the screwdriver along the hole wall as shown below.
12Slim Relay G3RV
Definition of Precautionary Information
Indicates a potentially hazardous situation which,
WARNING
CAUTION
Minor hazard by electric shock may occasionally occur.
Do not touch the G3RV's terminal (Charging part) while
the power supply turned on.
The G3RV may occasionally rupture in case of a short
circuit.
To protect against shor t-circuit accident, install a
protective device, such as a quick-burning fuse or a
circuit breaker or the like, on the power supply.
Minor hazard by electric shock may occasionally occur.
Do not touch the G3RV's main circuit terminals
immediately after the power is turned OFF.
The internal snubber circuit is charged.
* 202S,SL,G3RV-A(L) Type only
Minor hazard by burns may occasionally occur.
Do not touch the G3RV or the heat sink either while the
power supply is ON, or immediately after the power is
turned OFF.
The G3RV and the heat sink will be hot.
if not avoided, will result in minor or moderate
injury, or may result in serious injury or death.
Additionally there may be significant property
damage.
A potentioally hazardous situation by misuse,
may result in property damage only accident.
CAUTION
Precautions for Safe Use
● Transpporting
Do not use or store the G3RV in the following transporting.
of Doing so may result in damage, mulfunction, or detericration
of performance characteristics.
• Conditions under which the G3RV will be exposed to water.
• High temperatures or high humidity.
• Without proper packing.
● Operating and Strage Locations
Do not use or store the G3RV, in the following locations. Doing so
may result in damage, mulfunction, or detericration of
performance characteristic.
• Locations subject to rain or water drops.
• Locations subject to exposure to water, or oil, or chemicals.
• Locations subject to high temperatures or high humidity.
• Locations subject to ambient temperatures outside the range
from -30 to +100 centigrade.
• Locations subject to relative humidity outside the range 45% to
85%.
• Locations subject to corrosive or ammable gasses.
• Locations subject to dust (especially iron dust) or salts.
• Locations subject to barrier.
● Handring
• Must need an air convection for G3RV or the heat convection air
producess a heating on G3RV abnormal and causes a
short-circuit failure and burning.
• Do not use the G3RV with terminal bending due to dropping etc.
Bent terminal may poorly tting electrical contacts, leading to
trouble.
• Do not carry out the mounting work with hand stained with oil or
metal powder. Otherwise, trouble may be caused.
● Mounting
• Mount the G3RV in the speci ed orientation. If the G3RV is
mounted in any other orientation, abnormal heat generation
may cause output elements to short or may cause burning.
• Be sure to prevent the ambient temperature from rising due to
the heat radiation of the G3RV. If the G3RV is mounted a panel,
install a fan so that the interior of the panel is fully inside
ventilated.
• Be sure that the G3RV clicks into place when mounting it to DIN
Track. The G3RV may fall if it is not mounted correctly.
● Wiring
• Use a wire an adequate size for current to be applied. Abnormal
heating of wire may cause burning.
• Do not use any wires with damaged sheaths. These may caus
electric shock leakage.
• Con rm it wire for G3RV is not used in pipe or duct for high
voltage power supply.Induction will be generated and cause
malfunction or damages.
• Be sure to conduct wiring with the power supply turned OFF.
Touching the terminals when they are charged may occationally
result in minor electric shock.
● Using
• Select a load within the rated range. Inappropriate load may
cause misoperation, trouble or burning.
• Select the power supply within the rated frequency range.
Inappropriate power frequency may cause misoperation, trouble
or burning.
Precautions for Correct Use
● G3RV uses electronics parts mounting on PCB, so that any
dropping and vibration, physical shock beyond the standard level
should beprevented, otherwise the initial characteristic will be not
injured.
● Terminal screw must be tightened with regulation torque. Less
convection air produces a heating on G3RV abnormal and causes
a short-circuit failure and burning.
(M2.5, 0.4 N•m)
● Do not supply a high voltage/current to the input and output. Short
circuit failure or burning must be occured on G3RV.
● Do not use or store the G3RV, in the following locations. Doing so
may result in damage, malfunction, or deterioration of
performance characteristic.
• Locations subject to static electricity or other forms of noise.
• Locations subject to strong electromagnetic elds.
• Locations subject to possible exposure to radioactivity.
Slim Relay G3RV13
● Mounting
<SSR Mounting Pitch (Panel Mountin)>
60mm min.
Duct
<Ventilation Outside the Control Panel>
Be aware of air flow
Duct
SSR
Air inlet
SSR
Ventllation
outlet
SSR
SSR
Vertical
direction
80mm min.
30mm min.
<Relations between SSR and duct (Depth of duct)>
Counter measure(1)Duct DepthCounter measure(2)
The recommended width is
Vertical
direction
1/2 as large as the depth of
SSR or less
Duct or air flow
obstruction
SSR
Metal
base
Duct or air flow
obstruction
The depth
of SSR
SSR
Duct or air flow
obstruction
Air flow
* If the air inlet or air outlet has a lter, clean the lter regularly to
prevent it from cogging to ensure an e cient ow of air.
* Do no locate any objects around the air inlet or air outlet, otherwise
the objects may obstruct the proper ventilation of the control panel.
* A heat exchanger, if used, should be located in front the G3RVs to
ensure the eciency or the heat exchanger.
* Please reduce the ambient temperature of G3RVs. The rated load
current of a G3RV is measured at an ambient temperature of 25°C.
* A G3RV uses semiconductor in the output element.
This causes the temperature inside the control panel to increase
due to heating resulting from the passeage of electrical current
through the load. To the restrict heating, attach a fan to the
ventilation outlet or air inlet of the control panel to ventilate the
panel. This will reduce the ambient temperature of the G3RVs and
thus increase reliability.
(Generally, each 10°C reduction in temperature will double the
expected life.)
● EMI
• This is a class A product. In residential areas it may cause redio
interference, in which case the user may be required to take
adequate measures to reduce interference.
Suitability for Use
OMRON shall not be responsible for conformity with any standards,
codes, or regulations that apply to the combination of the products in
the customer's application or use of the product.
Take all necessary steps to determine the suitability of the product
for the systems, machines, and equipment with which it will be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS
RISKTO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A
WHOLE HAS BEEN DESIGNEDTOADDRESSTHE RISKS, ANDTHATTHE OMRON
PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE
WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
SSR
See also Product catalog for Warranty and Limitation of Liability.
Duct or air flow obstructionDuct or air flow
Do not surrounded the SSR
with the duct in the depth
direction, or otherwise the
heat radiation of the S5R
will be adversely affected.
obstruction
Use a short duct in
the depth direction.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. J180-E1-01
In the interest of product improvement, specifications are subject to change without notice.
14Slim Relay G3RV
Duct or air flow obstruction
If the height of the ducts
can not be lowered, place
the SSR or a metal base so
that they are not
surrounded by the ducts.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.