Omron G3PE-245B DC12-24, G3PE-215B DC12-24, G3PE-215BL DC12-24, G3PE-225BL DC12-24, G3PE-235BL DC12-24 User Manual

...
1
New Product
Solid State Relays for Heaters
Single-phase G3PE
Compact, Slim-profile SSRs with Heat Sinks. Models with No Zero Cross for a Wide Range of Applications.
• Models also available with no zero cross
• Improved surge dielectric strength for output circuits.
• Compact with a slim profile.
• Mount to DIN Track or with screws.
• Certification pending for UL, CSA, and EN (TÜV certification).
Ordering Information
List of Models
* The applicable load current depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in Engineering
Data on page 3.
Number of
phases
Isolation
method
Operation
indicator
Rated input
voltage
Zero cross
function
Applicable load * Model
Single-phase
Phototriac coupler
Yes (yellow) 12 to 24 VDC
Yes
15 A, 100 to 240 VAC G3PE-215B DC12-24 25 A, 100 to 240 VAC G3PE-225B DC12-24 35 A, 100 to 240 VAC G3PE-235B DC12-24 45 A, 100 to 240 VAC G3PE-245B DC12-24
No
15 A, 100 to 240 VAC G3PE-215BL DC12-24 25 A, 100 to 240 VAC G3PE-225BL DC12-24 35 A, 100 to 240 VAC G3PE-235BL DC12-24 45 A, 100 to 240 VAC G3PE-245BL DC12-24
Yes
15 A, 200 to 480 VAC G3PE-515B DC12-24 25 A, 200 to 480 VAC G3PE-525B DC12-24 35 A, 200 to 480 VAC G3PE-535B DC12-24 45 A, 200 to 480 VAC G3PE-545B DC12-24
No
15 A, 200 to 480 VAC G3PE-515BL DC12-24 25 A, 200 to 480 VAC G3PE-525BL DC12-24 35 A, 200 to 480 VAC G3PE-535BL DC12-24 45 A, 200 to 480 VAC G3PE-545BL DC12-24
Refer to Safety Precautions on page 18.
Single-phase G3PE
2
Specifications
Certification
UL508 (pending), CSA22.2 No.14 (pending), and EN60947-4-3 (pending)
Note: The G3PE-2@@B (L) Series has already been certified for the above standards.
Ratings
Input (at an Ambient Temperature of 25°C)
Output
* The applicable load current depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in Engineering
Data on page 3.
Characteristics
Item
Model
Rated voltage
Operating voltage
range
Rated input current
Voltage level
Must operate voltage Must release voltage
G3PE-@@@B
12 to 24 VDC 9.6 to 30 VDC
7 mA max.
9.6 VDC max. 1.0 VDC max.
G3PE-@@@BL 15 mA max.
Model
G3PE-215B(L) G3PE-225B(L) G3PE-235B(L) G3PE-245B(L) G3PE-515B(L) G3PE-525B(L) G3PE-535B(L) G3PE-545B(L)
Item Rated load voltage 100 to 240 VAC (50/60 Hz) 200 to 480 VAC (50/60 Hz) Load voltage range 75 to 264 VAC (50/60 Hz) 180 to 528 VAC (50/60 Hz)
Applicable load current *0.1 to 15 A
(at 40°C)
0.1 to 25 A
(at 40°C)
0.5 to 35 A
(at 25°C)
0.5 to 45 A
(at 25°C)
0.1 to 15 A
(at 40°C)
0.1 to 25 A
(at 40°C)
0.5 to 35 A
(at 25°C)
0.5 to 45 A
(at 25°C)
Inrush current resistance
150 A
(60 Hz,
1cycle)
220 A
(60 Hz,
1 cycle)
440 A
(60 Hz, 1 cycle)
150 A
(60 Hz,
1 cycle)
220 A
(60 Hz,
1cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t (reference value)
121A
2
s 260A2s 1,260A2s 128A2s 1,350A2s 6,600A2s
Applicable load (resistive load)
3 kW
(at 200 VAC)
5 kW
(at 200 VAC)
7 kW
(at 200 VAC)
9 kW
(at 200 VAC)
6 kW
(at 400 VAC)
10 kW
(at 400 VAC)
14 kW
(at 400 VAC)
18 kW
(at 400 VAC)
Model
G3PE
-215B
G3PE
-225B
G3PE
-235B
G3PE
-245B
G3PE
-215BL
G3PE
-225BL
G3PE
-235BL
G3PE
-245BL
Item Operate time 1/2 of load power source cycle + 1 ms max. 1 ms max. Release time 1/2 of load power source cycle + 1 ms max. Output ON voltage drop 1.6 V (RMS) max. Leakage current 10 mA max. (at 200 VAC) Insulation resistance 100 M min. (at 500 VDC) Dielectric strength 2,500 VAC, 50/60 Hz for 1 min Vibration resistance 10 to 55 to10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) (Mounted to DIN track) Shock resistance Destruction: 294 m/s2 (Mounted to DIN track)
Ambient storage temperature
30 to 100°C (with no icing or condensation)
Ambient operating temperature
30 to 80°C (with no icing or condensation)
Ambient operating humidity
45% to 85%
Weight Approx. 240 g Approx. 400 g Approx. 240 g Approx. 400 g
Model
G3PE
-515B
G3PE
-525B
G3PE
-535B
G3PE
-545B
G3PE
-515BL
G3PE
-525BL
G3PE
-535BL
G3PE
-545BL
Item Operate time 1/2 of load power source cycle + 1 ms max. 1 ms max. Release time 1/2 of load power source cycle + 1 ms max. Output ON voltage drop 1.8 V (RMS) max. Leakage current 20 mA max. (at 480 VAC) Insulation resistance 100 M min. (at 500 VDC) Dielectric strength 2,500 VAC, 50/60 Hz for 1 min Vibration resistance 10 to 55 to10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) (Mounted to DIN track) Shock resistance Destruction: 294 m/s2 (Mounted to DIN track)
Ambient storage temperature
30 to 100°C (with no icing or condensation)
Ambient operating temperature
30 to 80°C (with no icing or condensation)
Ambient operating humidity
45% to 85%
Weight Approx. 240 g Approx. 400 g Approx. 240 g Approx. 400 g
Single-phase G3PE
3
Engineering Data
Input Voltage vs. Input Impedance and Input Voltage vs. Input Current G3PE-2@@B G3PE-2@@BL G3PE-5@@B
G3PE-5@@BL
Load Current vs. Ambient Temperature G3PE-215B(L), G3PE-225B(L) G3PE-515B(L), G3PE-525B(L)
G3PE-235B(L), G3PE-245B(L) G3PE-535B(L), G3PE-545B(L)
Inrush Current Resistance: Non-repetitive
Keep the inrush current to below the inrush current resistance value (i.e., below the broken line) if it occurs repetitively.
G3PE-215B(L), G3PE-515B(L) G3PE-225B(L), G3PE-525B(L) G3PE-235B(L), G3PE-245B(L)
G3PE-535B(L), G3PE-545B(L)
10
9
8
7
6
5
4
3
2
1
0
0 5
10 15 20 25 30 35
Input voltage (V)
Input current
Input impedance
Input current (mA)
Input impedance (k)
Ta = 25°C
15 14 13 12 11 10
9 8 7 6 5 4 3 2 1 0
0 5
10 15 20 25 30 35
Input voltage (V)
Input current
Input impedance
Input current (mA)
Input impedance (k)
Ta = 25°C
10
9
8
7
6
5
4
3
2
1
0
0 5
10 15 20 25 30 35
Input voltage (V)
Input current
Input impedance
Input current (mA)
Input impedance (k)
Ta = 25°C
15 14 13 12 11 10
9 8 7 6 5 4 3 2 1 0
0 5
10 15 20 25 30 35
Input voltage (V)
Input current
Input impedance
Input current (mA)
Input impedance (k)
Ta = 25°C
30
25
20
15
10
7
0
Load current (A)
30 20
0 20 40 60 80 100
Ambient temperature (°C)
G3PE-225B(L) G3PE-525B(L)
G3PE-215B(L) G3PE-515B(L)
30 20
0 20 40 60 80 100
18 17 14
25
50 45
40
35
30
20
10
0
G3PE-245B(L) G3PE-545B(L)
G3PE-235B(L)
G3PE-535B(L)
Load current (A)
Ambient temperature (°C)
250
200
150
100
50
0
Inrush current (A. Peak)
Energized time (ms)
10 30 50
100
300 500 1,000 3,000 5,000
250
200
150
100
50
0
10 30 50
100
300 500 1,000 3,000 5,000
Inrush current (A. Peak)
Energized time (ms)
500
400
300
200
100
0
10 30 50
100
300 500 1,000 3,000 5,000
Inrush current (A. Peak)
Energized time (ms)
Single-phase G3PE
4
Close Mounting (3 or 8 SSRs) G3PE-215B(L) G3PE-225B(L) G3PE-235B(L) G3PE-245B(L)
G3PE-515B(L) G3PE-525B(L) G3PE-535B(L) G3PE-545B(L)
Close Mounting Example
40 20 0 20 40 60 80 100 Ambient temperature (°C)
Load current (A)
5.7
20
15 13
12
10
5
0
3 Relays
8 Relays
40 20 0 20 40 60 80 100
8
30
25
20 19
15
5
10
7
0
Ambient temperature (°C)
Load current (A)
8 Relays
3 Relays
40 20 0 20 40 60 80 100
40
30 28 26
10
20
11
0
25
Ambient temperature (°C)
Load current (A)
8 Relays
3 Relays
50
40
31 30 29
10
20
11
0
40 20
0 20 40 60 80 100
25
Ambient temperature (°C)
Load current (A)
8 Relays
3 Relays
5.7
20
15 13
12
10
5
0
40 20
0 20 40 60 80 100
Ambient temperature (°C)
Load current (A)
3 Relays
8 Relays
7
30
25
20
16
17
15
5
10
6
0
Ambient temperature (°C)
Load current (A)
3 Relays
8 Relays
40 20
0 20 40 60 80 100
40 20 0 20 40 60 80 100
40
30 28 26
10
20
11
0
25
Ambient temperature (°C)
Load current (A)
3 Relays
8 Relays
50
40
31 30 29
10
20
11
0
40 20
0 20 40 60 80 100
25
Ambient temperature (°C)
Load current (A)
3 Relays
8 Relays
DIN Trac
k
Single-phase G3PE
5
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Solid State Relays
G3PE-215B(L) G3PE-225B(L) G3PE-515B(L) G3PE-525B(L)
Two , M 4
68
4.2
6.3
Two , M3.5
Note: Without terminal cover.
24
13
±0.2
Two ,
4.6 dia.
100 max.
90
±0.2
84
22.5 max.
Elliptical hole:
4.6 × 5.6
Note: With terminal cover.
4.5
(90)
(85)
(100)
90
±0.3
Three, 4.5 dia. or M4
Mounting Holes
13
±0.3
1
2
A1
A2
(+)
()
G3PE-5@@B
1
2
A1
A2
(+)
()
G3PE-2@@B
Terminal Arrangement/Internal Circuit Diagram
Output side
tiucric reggirT
IInput side
IInput side
Output side
tiucric reggirT
t
iu cr
i c t
u pn I
ti u cr ic t u pn I
G3PE-235B(L) G3PE-245B(L) G3PE-535B(L) G3PE-545B(L)
24
68
13.5
6
44.5 max.
84
Two , M 5
Two , M3.5
Note: Without terminal cover.
25
±0.2
4.6 dia.
100 max.
90
±0.2
Elliptical hole:
4.6 × 5.6
Note: With terminal cover.
(90)
(85)
(100)
90
±0.3
Three, 4.5 dia. or M4
Mounting Holes
25
±0.3
1
2
A1
A2
(+)
()
G3PE-5@@B
1
2
A1
A2
(+)
()
G3PE-2@@B
Terminal Arrangement/Internal Circuit Diagram
Output side
tiucric reggirT
IInput side
IInput side
Output side
tiucric reggirT
t
iu cr
i c t
u pn I
ti u cr ic t u pn I
New Product
6
Solid State Contactors for Heaters
Three-phase G3PE
Compact, Slim-profile SSRs with Heat Sinks. Solid State Contactors for Three-phase Heaters Reduced Installation Work with DIN Track Mounting.
• RoHS compliant.
• Improved surge dielectric strength for output circuits.
• Slim design with 3-phase output and built-in heat sinks.
• DIN Track mounting types and screw mounting types are available. All DIN Track mounting types mount to DIN Track (applicable DIN Track: TR35-15Fe (IEC 60715)).
• Certification pending for UL, CSA, and EN (TÜV certification).
Ordering Information
List of Models
Models with Built-in Heat Sinks
*1. The applicable load current depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in Engineering
Data on page 10.
*2. The applicable DIN Track is the TR35-15Fe (IEC 60715). For details, refer to the mounting information in the Safety Precautions.
Refer to Safety Precautions on page 18.
Number of
phases
Insulation
method
Operation
indicator
Rated input
voltage
Zero cross
function
Type Applicable load *1
Number of
poles
Model
Three-phase
Phototriac
coupler
Yes (yellow) 12 to 24 VDC Yes
DIN track
mounting *2
15 A, 100 to 240 VAC
3 G3PE-215B-3N DC12-24 2 G3PE-215B-2N DC12-24
25 A, 100 to 240 VAC
3 G3PE-225B-3N DC12-24 2 G3PE-225B-2N DC12-24
35 A, 100 to 240 VAC
3 G3PE-235B-3N DC12-24 2 G3PE-235B-2N DC12-24
45 A, 100 to 240 VAC
3 G3PE-245B-3N DC12-24 2 G3PE-245B-2N DC12-24
15 A, 200 to 480 VAC
3 G3PE-515B-3N DC12-24 2 G3PE-515B-2N DC12-24
25 A, 200 to 480 VAC
3 G3PE-525B-3N DC12-24 2 G3PE-525B-2N DC12-24
35 A, 200 to 480 VAC
3 G3PE-535B-3N DC12-24 2 G3PE-535B-2N DC12-24
45 A, 200 to 480 VAC
3 G3PE-545B-3N DC12-24 2 G3PE-545B-2N DC12-24
Screw
mounting
15 A, 100 to 240 VAC
3 G3PE-215B-3 DC12-24 2 G3PE-215B-2 DC12-24
25 A, 100 to 240 VAC
3 G3PE-225B-3 DC12-24 2 G3PE-225B-2 DC12-24
35 A, 100 to 240 VAC
3 G3PE-235B-3 DC12-24 2 G3PE-235B-2 DC12-24
45 A, 100 to 240 VAC
3 G3PE-245B-3 DC12-24 2 G3PE-245B-2 DC12-24
15 A, 200 to 480 VAC
3 G3PE-515B-3 DC12-24 2 G3PE-515B-2 DC12-24
25 A, 200 to 480 VAC
3 G3PE-525B-3 DC12-24 2 G3PE-525B-2 DC12-24
35 A, 200 to 480 VAC
3 G3PE-535B-3 DC12-24 2 G3PE-535B-2 DC12-24
45 A, 200 to 480 VAC
3 G3PE-545B-3 DC12-24 2 G3PE-545B-2 DC12-24
Three-phase G3PE
7
Models with Externally Attached Heat Sinks
* The rated load current depends on the heat sink or radiator that is mounted. It also depends on the ambient temperature. For details, refer to
Load Current vs. Ambient Temperature.
Accessories (Order Separately)
Heat Sink
Number of
phases
Insulation
method
Operation
indicator
Rated input
voltage
Zero cross
function
Type Applicable load *
Number of poles
Model
Three-phase
Phototriac
coupler
Yes (yellow) 12 to 24 VDC Yes
Externally at­tached heat sinks
15 A, 100 to 240 VAC
3 G3PE-215B-3H DC12-24 2 G3PE-215B-2H DC12-24
25 A, 100 to 240 VAC
3 G3PE-225B-3H DC12-24 2 G3PE-225B-2H DC12-24
35 A, 100 to 240 VAC
3 G3PE-235B-3H DC12-24 2 G3PE-235B-2H DC12-24
45 A, 100 to 240 VAC
3 G3PE-245B-3H DC12-24 2 G3PE-245B-2H DC12-24
15 A, 200 to 480 VAC
3 G3PE-515B-3H DC12-24 2 G3PE-515B-2H DC12-24
25 A, 200 to 480 VAC
3 G3PE-525B-3H DC12-24 2 G3PE-525B-2H DC12-24
35 A, 200 to 480 VAC
3 G3PE-535B-3H DC12-24 2 G3PE-535B-2H DC12-24
45 A, 200 to 480 VAC
3 G3PE-545B-3H DC12-24 2 G3PE-545B-2H DC12-24
Heat resistance Rth (s-a) (°C/W) Model
1.67 Y92B-P50
1.01 Y92B-P100
0.63 Y92B-P150
0.43 Y92B-P200
0.36 Y92B-P250
Three-phase G3PE
8
Specifications
Certification
UL508 (pending), CSA22.2 No.14 (pending), and EN60947-4-3 (pending)
Ratings (at an Ambient Temperature of 25°C)
Operating Circuit (All Models)
Main Circuit of Models with Built-in Heat Sinks
*1. The applicable load current depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in Engineering
Data on page 10.
*2. Applicable Load
Use the following formula to calculate the maximum total capacity of a heater load for a three-phase balanced load with delta connections.
Maximum load capacity = Load current × Load voltage × √3 Example: 15 A × 200 V × √3 = 5,196 W ≅ 5.1 kW Example: 15 A × 400 V × √3
= 10,392 W 10.3 kW
Main Circuit of Models with Externally Attached Heat Sinks
* The rated load current depends on the heat sink or radiator that is mounted. It also depends on the ambient temperature.
For details, refer to Load Current vs. Ambient Temperature in Engineering Data on page 10.
Item Model Same for all models
Rated operating voltage 12 to 24 VDC Operating voltage range 9.6 to 30 VDC Rated input current (impedance) 10 mA max. (24 VDC) Must-operate voltage 9.6 VDC max. Must-release voltage 1 VDC min. Insulation method Phototriac Operation indicator Yellow LED
Model G3PE-
215B-
3(N)
G3PE­215B-
2(N)
G3PE-
225B-
3(N)
G3PE-
225B-
2(N)
G3PE-
235B-
3(N)
G3PE­235B-
2(N)
G3PE-
245B-
3(N)
G3PE-
245B-
2(N)
G3PE-
515B-
3(N)
G3PE-
515B-
2(N)
G3PE-
525B-
3(N)
G3PE-
525B-
2(N)
G3PE-
535B-
3(N)
G3PE-
535B-
2(N)
G3PE-
545B-
3(N)
G3PE-
545B-
2(N)
Item
Rated load voltage 100 to 240 VAC 200 to 480 VAC
Operating voltage range
75 to 264 VAC 180 to 528 VAC
Rated load current *1 15 A (at 40°C) 25 A (at 40°C) 35 A (at 25°C) 40 A (at 25°C) 15 A (at 40°C) 25 A (at 40°C) 35 A (at 25°C) 40 A (at 25°C) Minimum load current 0.2 A 0.5 A
Inrush current resistance (peak value)
150 A
(60 Hz, 1 cycle)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t (reference value)
121A2s 260A2s 1,260A2s 260A2s 1,260A2s
Applicable load (resistive load: AC1 class) *2
5.1 kW
(at 200 VAC)
8.6 kW
(at 200 VAC)
12.1 kW
(at 200 VAC)
15.5 kW
(at 200 VAC)
12.5 kW
(at 480 VAC)
20.7 kW
(at 480 VAC)
29.0 kW
(at 480 VAC)
37.4 kW
(at 480 VAC)
Model G3PE-
215B-
3H
G3PE­215B-
2H
G3PE-
225B-
3HH
G3PE-
225B-
2H
G3PE-
235B-
3H
G3PE­235B-
2H
G3PE-
245B-
3H
G3PE-
245B-
2H
G3PE-
515B-
3H
G3PE-
515B-
2H
G3PE-
525B-
3H
G3PE-
525B-
2H
G3PE-
535B-
3H
G3PE-
535B-
2H
G3PE-
545B-
3H
G3PE-
545B-
2H
Item
Rated load voltage 100 to 240 VAC 200 to 480 VAC
Operating voltage range
75 to 264 VAC 180 to 528 VAC
Rated load current * 15 A (at 40°C) 25 A (at 40°C) 35 A (at 25°C) 40 A (at 25°C) 15 A (at 40°C) 25 A (at 40°C) 35 A (at 25°C) 40 A (at 25°C) Minimum load current 0.2 A 0.5 A
Inrush current resistance (peak value)
150 A
(60 Hz, 1 cycle)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t (reference value)
121A2s 260A2s 1,260A2s 260A2s 1,260A2s
Applicable load (resistive load: AC1 class)
Refer to Engineering Data on page 10.