Omron G3PE-245B DC12-24, G3PE-215B DC12-24, G3PE-215BL DC12-24, G3PE-225BL DC12-24, G3PE-235BL DC12-24 User Manual

...
1
New Product
Solid State Relays for Heaters
Single-phase G3PE
Compact, Slim-profile SSRs with Heat Sinks. Models with No Zero Cross for a Wide Range of Applications.
• Models also available with no zero cross
• Improved surge dielectric strength for output circuits.
• Compact with a slim profile.
• Mount to DIN Track or with screws.
• Certification pending for UL, CSA, and EN (TÜV certification).
Ordering Information
List of Models
* The applicable load current depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in Engineering
Data on page 3.
Number of
phases
Isolation
method
Operation
indicator
Rated input
voltage
Zero cross
function
Applicable load * Model
Single-phase
Phototriac coupler
Yes (yellow) 12 to 24 VDC
Yes
15 A, 100 to 240 VAC G3PE-215B DC12-24 25 A, 100 to 240 VAC G3PE-225B DC12-24 35 A, 100 to 240 VAC G3PE-235B DC12-24 45 A, 100 to 240 VAC G3PE-245B DC12-24
No
15 A, 100 to 240 VAC G3PE-215BL DC12-24 25 A, 100 to 240 VAC G3PE-225BL DC12-24 35 A, 100 to 240 VAC G3PE-235BL DC12-24 45 A, 100 to 240 VAC G3PE-245BL DC12-24
Yes
15 A, 200 to 480 VAC G3PE-515B DC12-24 25 A, 200 to 480 VAC G3PE-525B DC12-24 35 A, 200 to 480 VAC G3PE-535B DC12-24 45 A, 200 to 480 VAC G3PE-545B DC12-24
No
15 A, 200 to 480 VAC G3PE-515BL DC12-24 25 A, 200 to 480 VAC G3PE-525BL DC12-24 35 A, 200 to 480 VAC G3PE-535BL DC12-24 45 A, 200 to 480 VAC G3PE-545BL DC12-24
Refer to Safety Precautions on page 18.
Single-phase G3PE
2
Specifications
Certification
UL508 (pending), CSA22.2 No.14 (pending), and EN60947-4-3 (pending)
Note: The G3PE-2@@B (L) Series has already been certified for the above standards.
Ratings
Input (at an Ambient Temperature of 25°C)
Output
* The applicable load current depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in Engineering
Data on page 3.
Characteristics
Item
Model
Rated voltage
Operating voltage
range
Rated input current
Voltage level
Must operate voltage Must release voltage
G3PE-@@@B
12 to 24 VDC 9.6 to 30 VDC
7 mA max.
9.6 VDC max. 1.0 VDC max.
G3PE-@@@BL 15 mA max.
Model
G3PE-215B(L) G3PE-225B(L) G3PE-235B(L) G3PE-245B(L) G3PE-515B(L) G3PE-525B(L) G3PE-535B(L) G3PE-545B(L)
Item Rated load voltage 100 to 240 VAC (50/60 Hz) 200 to 480 VAC (50/60 Hz) Load voltage range 75 to 264 VAC (50/60 Hz) 180 to 528 VAC (50/60 Hz)
Applicable load current *0.1 to 15 A
(at 40°C)
0.1 to 25 A
(at 40°C)
0.5 to 35 A
(at 25°C)
0.5 to 45 A
(at 25°C)
0.1 to 15 A
(at 40°C)
0.1 to 25 A
(at 40°C)
0.5 to 35 A
(at 25°C)
0.5 to 45 A
(at 25°C)
Inrush current resistance
150 A
(60 Hz,
1cycle)
220 A
(60 Hz,
1 cycle)
440 A
(60 Hz, 1 cycle)
150 A
(60 Hz,
1 cycle)
220 A
(60 Hz,
1cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t (reference value)
121A
2
s 260A2s 1,260A2s 128A2s 1,350A2s 6,600A2s
Applicable load (resistive load)
3 kW
(at 200 VAC)
5 kW
(at 200 VAC)
7 kW
(at 200 VAC)
9 kW
(at 200 VAC)
6 kW
(at 400 VAC)
10 kW
(at 400 VAC)
14 kW
(at 400 VAC)
18 kW
(at 400 VAC)
Model
G3PE
-215B
G3PE
-225B
G3PE
-235B
G3PE
-245B
G3PE
-215BL
G3PE
-225BL
G3PE
-235BL
G3PE
-245BL
Item Operate time 1/2 of load power source cycle + 1 ms max. 1 ms max. Release time 1/2 of load power source cycle + 1 ms max. Output ON voltage drop 1.6 V (RMS) max. Leakage current 10 mA max. (at 200 VAC) Insulation resistance 100 M min. (at 500 VDC) Dielectric strength 2,500 VAC, 50/60 Hz for 1 min Vibration resistance 10 to 55 to10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) (Mounted to DIN track) Shock resistance Destruction: 294 m/s2 (Mounted to DIN track)
Ambient storage temperature
30 to 100°C (with no icing or condensation)
Ambient operating temperature
30 to 80°C (with no icing or condensation)
Ambient operating humidity
45% to 85%
Weight Approx. 240 g Approx. 400 g Approx. 240 g Approx. 400 g
Model
G3PE
-515B
G3PE
-525B
G3PE
-535B
G3PE
-545B
G3PE
-515BL
G3PE
-525BL
G3PE
-535BL
G3PE
-545BL
Item Operate time 1/2 of load power source cycle + 1 ms max. 1 ms max. Release time 1/2 of load power source cycle + 1 ms max. Output ON voltage drop 1.8 V (RMS) max. Leakage current 20 mA max. (at 480 VAC) Insulation resistance 100 M min. (at 500 VDC) Dielectric strength 2,500 VAC, 50/60 Hz for 1 min Vibration resistance 10 to 55 to10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) (Mounted to DIN track) Shock resistance Destruction: 294 m/s2 (Mounted to DIN track)
Ambient storage temperature
30 to 100°C (with no icing or condensation)
Ambient operating temperature
30 to 80°C (with no icing or condensation)
Ambient operating humidity
45% to 85%
Weight Approx. 240 g Approx. 400 g Approx. 240 g Approx. 400 g
Single-phase G3PE
3
Engineering Data
Input Voltage vs. Input Impedance and Input Voltage vs. Input Current G3PE-2@@B G3PE-2@@BL G3PE-5@@B
G3PE-5@@BL
Load Current vs. Ambient Temperature G3PE-215B(L), G3PE-225B(L) G3PE-515B(L), G3PE-525B(L)
G3PE-235B(L), G3PE-245B(L) G3PE-535B(L), G3PE-545B(L)
Inrush Current Resistance: Non-repetitive
Keep the inrush current to below the inrush current resistance value (i.e., below the broken line) if it occurs repetitively.
G3PE-215B(L), G3PE-515B(L) G3PE-225B(L), G3PE-525B(L) G3PE-235B(L), G3PE-245B(L)
G3PE-535B(L), G3PE-545B(L)
10
9
8
7
6
5
4
3
2
1
0
0 5
10 15 20 25 30 35
Input voltage (V)
Input current
Input impedance
Input current (mA)
Input impedance (k)
Ta = 25°C
15 14 13 12 11 10
9 8 7 6 5 4 3 2 1 0
0 5
10 15 20 25 30 35
Input voltage (V)
Input current
Input impedance
Input current (mA)
Input impedance (k)
Ta = 25°C
10
9
8
7
6
5
4
3
2
1
0
0 5
10 15 20 25 30 35
Input voltage (V)
Input current
Input impedance
Input current (mA)
Input impedance (k)
Ta = 25°C
15 14 13 12 11 10
9 8 7 6 5 4 3 2 1 0
0 5
10 15 20 25 30 35
Input voltage (V)
Input current
Input impedance
Input current (mA)
Input impedance (k)
Ta = 25°C
30
25
20
15
10
7
0
Load current (A)
30 20
0 20 40 60 80 100
Ambient temperature (°C)
G3PE-225B(L) G3PE-525B(L)
G3PE-215B(L) G3PE-515B(L)
30 20
0 20 40 60 80 100
18 17 14
25
50 45
40
35
30
20
10
0
G3PE-245B(L) G3PE-545B(L)
G3PE-235B(L)
G3PE-535B(L)
Load current (A)
Ambient temperature (°C)
250
200
150
100
50
0
Inrush current (A. Peak)
Energized time (ms)
10 30 50
100
300 500 1,000 3,000 5,000
250
200
150
100
50
0
10 30 50
100
300 500 1,000 3,000 5,000
Inrush current (A. Peak)
Energized time (ms)
500
400
300
200
100
0
10 30 50
100
300 500 1,000 3,000 5,000
Inrush current (A. Peak)
Energized time (ms)
Single-phase G3PE
4
Close Mounting (3 or 8 SSRs) G3PE-215B(L) G3PE-225B(L) G3PE-235B(L) G3PE-245B(L)
G3PE-515B(L) G3PE-525B(L) G3PE-535B(L) G3PE-545B(L)
Close Mounting Example
40 20 0 20 40 60 80 100 Ambient temperature (°C)
Load current (A)
5.7
20
15 13
12
10
5
0
3 Relays
8 Relays
40 20 0 20 40 60 80 100
8
30
25
20 19
15
5
10
7
0
Ambient temperature (°C)
Load current (A)
8 Relays
3 Relays
40 20 0 20 40 60 80 100
40
30 28 26
10
20
11
0
25
Ambient temperature (°C)
Load current (A)
8 Relays
3 Relays
50
40
31 30 29
10
20
11
0
40 20
0 20 40 60 80 100
25
Ambient temperature (°C)
Load current (A)
8 Relays
3 Relays
5.7
20
15 13
12
10
5
0
40 20
0 20 40 60 80 100
Ambient temperature (°C)
Load current (A)
3 Relays
8 Relays
7
30
25
20
16
17
15
5
10
6
0
Ambient temperature (°C)
Load current (A)
3 Relays
8 Relays
40 20
0 20 40 60 80 100
40 20 0 20 40 60 80 100
40
30 28 26
10
20
11
0
25
Ambient temperature (°C)
Load current (A)
3 Relays
8 Relays
50
40
31 30 29
10
20
11
0
40 20
0 20 40 60 80 100
25
Ambient temperature (°C)
Load current (A)
3 Relays
8 Relays
DIN Trac
k
Single-phase G3PE
5
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Solid State Relays
G3PE-215B(L) G3PE-225B(L) G3PE-515B(L) G3PE-525B(L)
Two , M 4
68
4.2
6.3
Two , M3.5
Note: Without terminal cover.
24
13
±0.2
Two ,
4.6 dia.
100 max.
90
±0.2
84
22.5 max.
Elliptical hole:
4.6 × 5.6
Note: With terminal cover.
4.5
(90)
(85)
(100)
90
±0.3
Three, 4.5 dia. or M4
Mounting Holes
13
±0.3
1
2
A1
A2
(+)
()
G3PE-5@@B
1
2
A1
A2
(+)
()
G3PE-2@@B
Terminal Arrangement/Internal Circuit Diagram
Output side
tiucric reggirT
IInput side
IInput side
Output side
tiucric reggirT
t
iu cr
i c t
u pn I
ti u cr ic t u pn I
G3PE-235B(L) G3PE-245B(L) G3PE-535B(L) G3PE-545B(L)
24
68
13.5
6
44.5 max.
84
Two , M 5
Two , M3.5
Note: Without terminal cover.
25
±0.2
4.6 dia.
100 max.
90
±0.2
Elliptical hole:
4.6 × 5.6
Note: With terminal cover.
(90)
(85)
(100)
90
±0.3
Three, 4.5 dia. or M4
Mounting Holes
25
±0.3
1
2
A1
A2
(+)
()
G3PE-5@@B
1
2
A1
A2
(+)
()
G3PE-2@@B
Terminal Arrangement/Internal Circuit Diagram
Output side
tiucric reggirT
IInput side
IInput side
Output side
tiucric reggirT
t
iu cr
i c t
u pn I
ti u cr ic t u pn I
New Product
6
Solid State Contactors for Heaters
Three-phase G3PE
Compact, Slim-profile SSRs with Heat Sinks. Solid State Contactors for Three-phase Heaters Reduced Installation Work with DIN Track Mounting.
• RoHS compliant.
• Improved surge dielectric strength for output circuits.
• Slim design with 3-phase output and built-in heat sinks.
• DIN Track mounting types and screw mounting types are available. All DIN Track mounting types mount to DIN Track (applicable DIN Track: TR35-15Fe (IEC 60715)).
• Certification pending for UL, CSA, and EN (TÜV certification).
Ordering Information
List of Models
Models with Built-in Heat Sinks
*1. The applicable load current depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in Engineering
Data on page 10.
*2. The applicable DIN Track is the TR35-15Fe (IEC 60715). For details, refer to the mounting information in the Safety Precautions.
Refer to Safety Precautions on page 18.
Number of
phases
Insulation
method
Operation
indicator
Rated input
voltage
Zero cross
function
Type Applicable load *1
Number of
poles
Model
Three-phase
Phototriac
coupler
Yes (yellow) 12 to 24 VDC Yes
DIN track
mounting *2
15 A, 100 to 240 VAC
3 G3PE-215B-3N DC12-24 2 G3PE-215B-2N DC12-24
25 A, 100 to 240 VAC
3 G3PE-225B-3N DC12-24 2 G3PE-225B-2N DC12-24
35 A, 100 to 240 VAC
3 G3PE-235B-3N DC12-24 2 G3PE-235B-2N DC12-24
45 A, 100 to 240 VAC
3 G3PE-245B-3N DC12-24 2 G3PE-245B-2N DC12-24
15 A, 200 to 480 VAC
3 G3PE-515B-3N DC12-24 2 G3PE-515B-2N DC12-24
25 A, 200 to 480 VAC
3 G3PE-525B-3N DC12-24 2 G3PE-525B-2N DC12-24
35 A, 200 to 480 VAC
3 G3PE-535B-3N DC12-24 2 G3PE-535B-2N DC12-24
45 A, 200 to 480 VAC
3 G3PE-545B-3N DC12-24 2 G3PE-545B-2N DC12-24
Screw
mounting
15 A, 100 to 240 VAC
3 G3PE-215B-3 DC12-24 2 G3PE-215B-2 DC12-24
25 A, 100 to 240 VAC
3 G3PE-225B-3 DC12-24 2 G3PE-225B-2 DC12-24
35 A, 100 to 240 VAC
3 G3PE-235B-3 DC12-24 2 G3PE-235B-2 DC12-24
45 A, 100 to 240 VAC
3 G3PE-245B-3 DC12-24 2 G3PE-245B-2 DC12-24
15 A, 200 to 480 VAC
3 G3PE-515B-3 DC12-24 2 G3PE-515B-2 DC12-24
25 A, 200 to 480 VAC
3 G3PE-525B-3 DC12-24 2 G3PE-525B-2 DC12-24
35 A, 200 to 480 VAC
3 G3PE-535B-3 DC12-24 2 G3PE-535B-2 DC12-24
45 A, 200 to 480 VAC
3 G3PE-545B-3 DC12-24 2 G3PE-545B-2 DC12-24
Three-phase G3PE
7
Models with Externally Attached Heat Sinks
* The rated load current depends on the heat sink or radiator that is mounted. It also depends on the ambient temperature. For details, refer to
Load Current vs. Ambient Temperature.
Accessories (Order Separately)
Heat Sink
Number of
phases
Insulation
method
Operation
indicator
Rated input
voltage
Zero cross
function
Type Applicable load *
Number of poles
Model
Three-phase
Phototriac
coupler
Yes (yellow) 12 to 24 VDC Yes
Externally at­tached heat sinks
15 A, 100 to 240 VAC
3 G3PE-215B-3H DC12-24 2 G3PE-215B-2H DC12-24
25 A, 100 to 240 VAC
3 G3PE-225B-3H DC12-24 2 G3PE-225B-2H DC12-24
35 A, 100 to 240 VAC
3 G3PE-235B-3H DC12-24 2 G3PE-235B-2H DC12-24
45 A, 100 to 240 VAC
3 G3PE-245B-3H DC12-24 2 G3PE-245B-2H DC12-24
15 A, 200 to 480 VAC
3 G3PE-515B-3H DC12-24 2 G3PE-515B-2H DC12-24
25 A, 200 to 480 VAC
3 G3PE-525B-3H DC12-24 2 G3PE-525B-2H DC12-24
35 A, 200 to 480 VAC
3 G3PE-535B-3H DC12-24 2 G3PE-535B-2H DC12-24
45 A, 200 to 480 VAC
3 G3PE-545B-3H DC12-24 2 G3PE-545B-2H DC12-24
Heat resistance Rth (s-a) (°C/W) Model
1.67 Y92B-P50
1.01 Y92B-P100
0.63 Y92B-P150
0.43 Y92B-P200
0.36 Y92B-P250
Three-phase G3PE
8
Specifications
Certification
UL508 (pending), CSA22.2 No.14 (pending), and EN60947-4-3 (pending)
Ratings (at an Ambient Temperature of 25°C)
Operating Circuit (All Models)
Main Circuit of Models with Built-in Heat Sinks
*1. The applicable load current depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in Engineering
Data on page 10.
*2. Applicable Load
Use the following formula to calculate the maximum total capacity of a heater load for a three-phase balanced load with delta connections.
Maximum load capacity = Load current × Load voltage × √3 Example: 15 A × 200 V × √3 = 5,196 W ≅ 5.1 kW Example: 15 A × 400 V × √3
= 10,392 W 10.3 kW
Main Circuit of Models with Externally Attached Heat Sinks
* The rated load current depends on the heat sink or radiator that is mounted. It also depends on the ambient temperature.
For details, refer to Load Current vs. Ambient Temperature in Engineering Data on page 10.
Item Model Same for all models
Rated operating voltage 12 to 24 VDC Operating voltage range 9.6 to 30 VDC Rated input current (impedance) 10 mA max. (24 VDC) Must-operate voltage 9.6 VDC max. Must-release voltage 1 VDC min. Insulation method Phototriac Operation indicator Yellow LED
Model G3PE-
215B-
3(N)
G3PE­215B-
2(N)
G3PE-
225B-
3(N)
G3PE-
225B-
2(N)
G3PE-
235B-
3(N)
G3PE­235B-
2(N)
G3PE-
245B-
3(N)
G3PE-
245B-
2(N)
G3PE-
515B-
3(N)
G3PE-
515B-
2(N)
G3PE-
525B-
3(N)
G3PE-
525B-
2(N)
G3PE-
535B-
3(N)
G3PE-
535B-
2(N)
G3PE-
545B-
3(N)
G3PE-
545B-
2(N)
Item
Rated load voltage 100 to 240 VAC 200 to 480 VAC
Operating voltage range
75 to 264 VAC 180 to 528 VAC
Rated load current *1 15 A (at 40°C) 25 A (at 40°C) 35 A (at 25°C) 40 A (at 25°C) 15 A (at 40°C) 25 A (at 40°C) 35 A (at 25°C) 40 A (at 25°C) Minimum load current 0.2 A 0.5 A
Inrush current resistance (peak value)
150 A
(60 Hz, 1 cycle)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t (reference value)
121A2s 260A2s 1,260A2s 260A2s 1,260A2s
Applicable load (resistive load: AC1 class) *2
5.1 kW
(at 200 VAC)
8.6 kW
(at 200 VAC)
12.1 kW
(at 200 VAC)
15.5 kW
(at 200 VAC)
12.5 kW
(at 480 VAC)
20.7 kW
(at 480 VAC)
29.0 kW
(at 480 VAC)
37.4 kW
(at 480 VAC)
Model G3PE-
215B-
3H
G3PE­215B-
2H
G3PE-
225B-
3HH
G3PE-
225B-
2H
G3PE-
235B-
3H
G3PE­235B-
2H
G3PE-
245B-
3H
G3PE-
245B-
2H
G3PE-
515B-
3H
G3PE-
515B-
2H
G3PE-
525B-
3H
G3PE-
525B-
2H
G3PE-
535B-
3H
G3PE-
535B-
2H
G3PE-
545B-
3H
G3PE-
545B-
2H
Item
Rated load voltage 100 to 240 VAC 200 to 480 VAC
Operating voltage range
75 to 264 VAC 180 to 528 VAC
Rated load current * 15 A (at 40°C) 25 A (at 40°C) 35 A (at 25°C) 40 A (at 25°C) 15 A (at 40°C) 25 A (at 40°C) 35 A (at 25°C) 40 A (at 25°C) Minimum load current 0.2 A 0.5 A
Inrush current resistance (peak value)
150 A
(60 Hz, 1 cycle)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t (reference value)
121A2s 260A2s 1,260A2s 260A2s 1,260A2s
Applicable load (resistive load: AC1 class)
Refer to Engineering Data on page 10.
Three-phase G3PE
9
Characteristics
Models with Built-in Heat Sinks
* The leakage current of phase S will be approximately 3 times larger if the 2-element model is used.
Models with Externally Attached Heat Sinks
* The leakage current of phase S will be approximately 3 times larger if the 2-element model is used.
Heat Sinks
Model G3PE-
215B-
3(N)
G3PE-
215B-
2(N)
G3PE­225B-
3(N)
G3PE-
225B-
2(N)
G3PE-
235B-
3(N)
G3PE-
235B-
2(N)
G3PE-
245B-
3(N)
G3PE-
245B-
2(N)
G3PE-
515B-
3(N)
G3PE-
515B-
2(N)
G3PE-
525B-
3(N)
G3PE-
525B-
2(N)
G3PE-
535B-
3(N)
G3PE-
535B-
2(N)
G3PE­545B-
3(N)
G3PE-
545B-
2(N)
Item
Operate time
1/2 of load power source cycle + 1 ms max.
Release time
1/2 of load power source cycle + 1 ms max.
Output ON voltage drop
1.6 V (RMS) max. 1.8 V (RMS) max.
Leakage current *
10 mA max. (at 200 VAC) 20 mA max. (at 480 VAC)
Insulation resistance
100 M min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
DIN Track mounting: 10 to 55 to 10 Hz, 0.175-mm single amplitude (0.35-mm double amplitude)
Screw mounting: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Shock resis­tance
294 m/s2 (reverse mounting: 98 m/s2)
Ambient storage tem­perature
30 to 100°C (with no icing or condensation)
Ambient op­erating tem­perature
30 to 80°C (with no icing or condensation)
Ambient op­erating hu­midity
45% to 85%
Weight Approx. 1.25 kg
Ap-
prox.
1.45 kg
Ap-
prox.
1.25 kg
Ap-
prox.
1.65 kg
Ap-
prox.
1.45 kg
Ap-
prox.
2.0 kg
Ap-
prox.
1.65 kg
Approx. 1.25 kg
Ap-
prox.
1.45 kg
Ap-
prox.
1.25 kg
Ap-
prox.
1.65 kg
Ap-
prox.
1.45 kg
Ap-
prox.
2.0 kg
Ap-
prox.
1.65 kg
Model G3PE-
215B-
3H
G3PE-
215B-
2H
G3PE­225B-
3H
G3PE-
225B-
2H
G3PE-
235B-
3H
G3PE-
235B-
2H
G3PE-
245B-
3H
G3PE-
245B-
2H
G3PE-
515B-
3H
G3PE-
515B-
2H
G3PE-
525B-
3H
G3PE-
525B-
2H
G3PE-
535B-
3H
G3PE-
535B-
2H
G3PE­545B-
3H
G3PE-
545B-
2H
Item
Operate time
1/2 of load power source cycle + 1 ms max.
Release time
1/2 of load power source cycle + 1 ms max.
Output ON voltage drop
1.6 V (RMS) max. 1.8 V (RMS) max.
Leakage current *
10 mA max. (at 200 VAC) 20 mA max. (at 480 VAC)
Insulation resistance
100 M min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Shock resis­tance
Destruction: 294 m/s
2
Ambient storage tem­perature
30 to 100°C (with no icing or condensation)
Ambient op­erating tem­perature
30 to 80°C (with no icing or condensation)
Ambient op­erating hu­midity
45% to 85%
Weight Approx. 300 g
Model Weight
Y92B-P50 Approx. 450 g Y92B-P100 Approx. 450 g Y92B-P150 Approx. 600 g Y92B-P200 Approx. 850 g Y92B-P250 Approx. 1,200 g
Three-phase G3PE
10
Engineering Data
Input Voltage vs. Input Impedance and Input Voltage vs. Input Current
G3PE-2@@B-@@
G3PE-5@@B-@@
5 10 15 20 25 30 35
10
9
8
7
6
5
4
3
2
1
0
Input voltage (V)
Input current
Input impedance
Input current (mA)
Input impedance (k)
15 14 13 12 11 10
9 8 7 6 5 4 3 2 1 0
0 5
10 15 20 25 30 35
Ta = 25°C
Input voltage (V)
Input current
Input impedance
Input current (mA)
Input impedance (k)
Load Current vs. Ambient Temperature
Models with Built-in Heat Sinks G3PE-215B-3(N), G3PE-225B-3(N)
G3PE-215B-2(N), G3PE-225B-2(N) G3PE-515B-3(N), G3PE-525B-3(N) G3PE-515B-2(N), G3PE-525B-2(N)
G3PE-235B-3(N), G3PE-245B-3(N) G3PE-235B-2(N), G3PE-245B-2(N) G3PE-535B-3(N), G3PE-545B-3(N) G3PE-535B-2(N), G3PE-545B-2(N)
30
25
20
15
10
7
0
30 20 0 20 40 60 80 100
G3PE-225B-3(N) G3PE-225B-2(N) G3PE-525B-3(N) G3PE-525B-2(N)
G3PE-215B-3(N) G3PE-215B-2(N) G3PE-515B-3(N) G3PE-515B-2(N)
Load current (A)
Ambient temperature (°C)
50
45
40
35
30
20
14
10
0
30 20 0 20 40 60 80 100
18
G3PE-245B-3(N) G3PE-245B-2(N) G3PE-545B-3(N) G3PE-545B-2(N)
G3PE-235B-3(N) G3PE-235B-2(N) G3PE-535B-3(N) G3PE-535B-2(N)
25
Load current (A)
Ambient temperature (°C)
Models with Externally Attached Heat Sinks G3PE-215B-3H(-2H)
G3PE-225B-3H(-2H) G3PE-515B-3H(-2H) G3PE-525B-3H(-2H)
G3PE-235B-3H(-2H) G3PE-245B-3H(-2H) G3PE-535B-3H(-2H) G3PE-545B-3H(-2H)
30 20 0 20 40 60 80 100
G3PE-225B-3H(-2H) G3PE-525B-3H(-2H)
G3PE-215B-3H(-2H) G3PE-515B-3H(-2H)
10
8
6
4
2
0
5
Load current (A)
Ambient temperature (°C)
30 20 0 20 40 60 80 100
G3PE-235B-3H(-2H) G3PE-245B-3H(-2H) G3PE-535B-3H(-2H) G3PE-545B-3H(-2H)
10
8
6
4
2
0
25
Load current (A)
Ambient temperature (°C)
Three-phase G3PE
11
Models with Externally Attached Heat Sinks Heat Resistance Rth (Junction/SSR Back Surface)
Heat Resistance of Heat Sinks
Note: If a commercially available heat sink is used, use one that has
a heat resistance equal to or lower than a standard OMRON Heat Sink.
Inrush Current Resistance: Non-repetitive
Keep the inrush current to below the inrush current resistance value (i.e., below the broken line) if it occurs repetitively.
G3PE-215B-3(N)(H) G3PE-215B-2(N)(H)
G3PE-225B-3(N)(H), G3PE-525B-3(N)(H) G3PE-225B-2(N)(H), G3PE-525B-2(N)(H) G3PE-515B-3(N)(H), G3PE-515B-2(N)(H),
G3PE-235B-3(N)(H), G3PE-535B-3(N)(H) G3PE-235B-2(N)(H), G3PE-535B-2(N)(H) G3PE-245B-3(N)(H), G3PE-545B-3(N)(H) G3PE-245B-2(N)(H), G3PE-545B-2(N)(H)
250
200
150
100
50
0
10 30 50
100 300 500 1,000 3,000 5,000
Inrush current (A. Peak)
Energized time (ms)
250
200
150
100
50
0
10 30 50
100 300 500 1,000 3,000 5,000
Inrush current (A. Peak)
Energized time (ms)
500
400
300
200
100
0
10 30 50
100 300 500 1,000 3,000 5,000
Inrush current (A. Peak)
Energized time (ms)
Heat Sink Area vs. Load Current (40°C and 80°C)
G3PE-225B-3H G3PE-525B-3H
Note: The heat sink area is the combined
area of all surfaces of the heat sink that radiate heat. For the G3PE-525B-3H, when a current of 18 A flows through the SSR at 40°C, the graph shows that a heat sink area of about 2,500 cm
2
would be required. Therefore, if the heat sink is square, one side of an aluminum plate in the heat sink must be 36 cm or longer (√2,500
(cm2)/2 =
36 cm (rounded to a whole number)).
Load current (A)
0 10 20 30 40
Heat s ink area ( cm
2
)
30,000
50,000
10,000
5,000
3,000
1,000
500
300
100
Ambient temperature + 80°C
Ambient temperature + 40°C
Aluminum plate t = 3.0
0 10 20 30 40
30,000
50,000
10,000
5,000
3,000
1,000
500
300
100
Load current (A)
Heat s ink area ( cm
2
)
Ambient temperature + 80°C
Ambient temperature + 40°C
Aluminum plate t = 3.0
Model Rth (°C/W)
G3PE-215B-3H 1.05 G3PE-225B-3H 0.57 G3PE-235B-3H 0.57 G3PE-245B-3H 0.57
Model Rth (°C/W)
Y92B-P50 1.67 Y92B-P100 1.01 Y92B-P150 0.63 Y92B-P200 0.43 Y92B-P250 0.36
Three-phase G3PE
12
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Solid State Relays
68
68
32.2
20
Six, M4
0.5 20
Two, 4.6-dia. mounting holes
Four, 8 dia.
Two, M3.5
100
max.
84.5
max.
90
64
80 max.
19.1
64
±0.3
90
±0.3
Four, 4.5 dia. or M4
23.2
120 max.
35
max.
24
Two, R2.3 mounting holes
A1
A2
Input circuit
Input circuit
Input circuit
Input circuit
A1
A2
Terminal Arrangement/Internal Circuit Diagram
G3PE-2@5B-2N
G3PE-215B-3N
L1/R
T1/U T2/V T3/W
L2/S L3/T
L1/R
T1/U T2/V T3/W
L2/S L3/T
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
(+)
()
(+)
()
(+)
()
(+)
()
G3PE-5@5B-2N
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PE-515E-3N
Note: Without terminal cover. Note: With terminal cover.
Mounting Holes
Models with DIN Track Mounting
G3PE-215B-3N G3PE-215B-2N G3PE-225B-2N G3PE-515B-3N G3PE-515B-2N G3PE-525B-2N
120
max.
84.5
max.
110100
64
80 max.
68
68
32.2
20
Six, M5 (35-A type) Six, M4 (25-A type)
0.5 20
24
19.1
64
±0.3
110
±0.3
23.2
120 max.
35
max.
Two, 4.6-dia. mounting holes
Four, 8 dia.
Two, M3.5
Four, 4.5 dia. or M4
Two, R2.3 mounting holes
A1
A2
A1
A2
Terminal Arrangement/Internal Circuit Diagram
G3PE-235B-2N
G3PE-225B-3N
L1/R
T1/U T2/V T3/W
L2/S L3/T
L1/R
T1/U T2/V T3/W
L2/S L3/T
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PE-535B-2N
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PE-525B-3N
Input circuit
(+)
()
Input circuit
(+)
()
Input circuit
(+)
()
Input circuit
(+)
()
Models with DIN Track Mounting
G3PE-225B-3N G3PE-235B-2N G3PE-525B-3N G3PE-535B-2N
Note: Without terminal cover. Note: With terminal cover.
Mounting Holes
Three-phase G3PE
13
A1
A2
A1
A2
Terminal Arrangement/Internal Circuit Diagram
G3PE-245B-2N
G3PE-235B-3N
L1/R
T1/U T2/V T3/W
L2/S L3/T
L1/R
T1/U T2/V T3/W
L2/S L3/T
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PE-545B-2N
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PE-535B-3N
Input circuit
(+)
()
Input circuit
(+)
()
Input circuit
(+)
()
Input circuit
(+)
()
140
max.
84.5
max.
130120
64
80 max.
68
68
32.2
20
0.5 20
24
19.1
64
±0.3
130
±0.3
23.2
120 max.
35
max.
Six, M5
Two, 4.6-dia. mounting holes
Four, 8 dia.
Two, M3.5
Four, 4.5 dia. or M4
Two, R2.3 mounting holes
Models with DIN Track Mounting
G3PE-235B-3N G3PE-245B-2N G3PE-535B-3N G3PE-545B-2N
Note: Without terminal cover. Note: With terminal cover.
Mounting Holes
140
max.
84.5
max.
130120
64
80 max.
110 max.
68
68
32.2
20
0.5 20
24
19.1
64
±0.3
130
±0.3
23.2
120 max.
35
max.
Six, M5
Two, 4.6-dia. mounting holes
Four, 8 dia.
Two, M3.5
Four, 4.5 dia. or M4
Two, R2.3 mounting holes
A1
A2
Terminal Arrangement/Internal Circuit Diagram
G3PE245B-3N
L1/R
T1/U T2/V T3/W
L2/S L3/T
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PE-545B-3N
Input circuit
(+)
()
Input circuit
(+)
()
Models with DIN Track Mounting
G3PE-245B-3N G3PE-545B-3N
Note: Without terminal cover. Note: With terminal cover.
Mounting Holes
Three-phase G3PE
14
24
68
0.5 20 20
68
32.2
Two, M3.5
Six, M4
90
50
80 max.
84.5 max.
100 max.
4.6 dia.
4.6 × 5.6 elliptical hole
50
±0.3
90
±0.3
Two, 4.5 dia. or M4
Mounting Holes
55 max.
35
max.
23.2
19.1
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PE-215B-2
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PE-515B-2
Terminal Arrangement/Internal Circuit Diagram
Input circuit
(+)
()
Input circuit
(+)
()
DIN Track or screw mounting
Models with Screw Mounting
G3PE-215B-2 G3PE-515B-2
Note: Without terminal cover.
Note: With terminal cover.
A1
A2
A1
A2
G3PE-225B-2
G3PE-215B-3
L1/R
T1/U T2/V T3/W
L2/S L3/T
L1/R
T1/U T2/V T3/W
L2/S L3/T
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PE-525B-2
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PE-515B-3
Terminal Arrangement/Internal Circuit Diagram
Input circuit
(+)
()
Input circuit
(+)
()
Input circuit
(+)
()
Input circuit
(+)
()
60
80 max.
100
110.5 max.
90
80
84.5 max.
5
24
0.5 20 20
32.2
60
±0.3
100
±0.3
Four, 4.5 dia. or M4
70 max.
35
max.
Four, R2.5
Two, M3.5
Six, M4
Mounting Holes
23.2
19.1
68
68
For screw mounting only
Models with Screw Mounting
G3PE-215B-3 G3PE-225B-2 G3PE-515B-3 G3PE-525B-2
Note: Without terminal cover. Note: With terminal cover.
Three-phase G3PE
15
84.5 max.
90
80 max.
90
100
110.5 max.
110.5 max.
5
24
0.5 20 20
32.2
90
±0.3
100
±0.3
Four, 4.5 dia. or M4
70 max.
35
max.
Four, R2.5
Two, M3.5
Six, M5 (G3PE-@35B-2) Six, M4 (G3PE-@25B-3)
Mounting Holes
23.2
19.1
68
68
For screw mounting only
A1
A2
A1
A2
G3PE-235B-2
G3PE-225B-3
L1/R
T1/U T2/V T3/W
L2/S L3/T
L1/R
T1/U T2/V T3/W
L2/S L3/T
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PE-535B-2
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PE-525B-3
Terminal Arrangement/Internal Circuit Diagram
Input circuit
(+)
()
Input circuit
(+)
()
Input circuit
(+)
()
Input circuit
(+)
()
Models with Screw Mounting
G3PE-225B-3 G3PE-235B-2 G3PE-525B-3 G3PE-535B-2
Note: Without terminal cover. Note: With terminal cover.
A1
A2
A1
A2
G3PE-245B-2
G3PE-235B-3
L1/R
T1/U T2/V T3/W
L2/S L3/T
L1/R
T1/U T2/V T3/W
L2/S L3/T
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PE-545B-2
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PE-535B-3
Terminal Arrangement/Internal Circuit Diagram
Input circuit
(+)
()
Input circuit
(+)
()
Input circuit
(+)
()
Input circuit
(+)
()
84.5 max.
90
80 max.
110 120
130.5 max.
130.5 max.
5
24
0.5 20 20
32.2
90
±0.3
120
±0.3
Four, 4.5 dia. or M4
70 max.
35
max.
Four, R2.5
Two, M3.5
Six, M5
Mounting Holes
23.2
19.1
68
68
For screw mounting only
Models with Screw Mounting
G3PE-235B-3 G3PE-245B-2 G3PE-535B-3 G3PE-545B-2
Note: Without terminal cover. Note: With terminal cover.
Three-phase G3PE
16
84.5 max.
150
80 max.
110 120
130.5 max.
190.5 max.
5
24
0.5 20 20
32.2
150
±0.3
120
±0.3
Four, 4.5 dia. or M4
70 max.
35
max.
Four, R2.5
Two, M3.5
Six, M5
Mounting Holes
23.2
19.1
68
68
A1
A2
G3PE-245B-3
L1/R
T1/U T2/V T3/W
L2/S L3/T
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PE-545B-3
Terminal Arrangement/Internal Circuit Diagram
Input circuit
(+)
()
Input circuit
(+)
()
For screw mounting only
Models with Screw Mounting
G3PE-245B-3 G3PE-545B-3
Note: Without terminal cover. Note: With terminal cover.
35
max.
23.2
19.1
80
84.5 max.
80 max.
24
0.5 20 20
32.2
68
Four, 8 dia.
Four, 4.5 dia.
Two, M3.5
Four, 4.5 dia. or M4
68
±0.3
68
±0.3
Mounting Holes
Six, M4 (G3PE-@15B-@H/-@25B-@H) Six, M5 (G3PE-@35B-@H/-@45B-@H)
9
8 dia.
4.5 dia.
68
Models with Externally Attached Heat Sinks
G3PE-215B-3H G3PE-215B-2H G3PE-225B-3H G3PE-225B-2H G3PE-235B-3H G3PE-235B-2H G3PE-245B-3H G3PE-245B-2H G3PE-515B-3H G3PE-515B-2H G3PE-525B-3H G3PE-525B-2H G3PE-535B-3H G3PE-535B-2H G3PE-545B-3H G3PE-545B-2H
Note: Without terminal cover.
Note: With terminal cover.
A1
A2
A1
A2
G3PE-2@5B-2H
G3PE-2@5B-3H
L1/R
T1/U T2/V T3/W
L2/S L3/T
L1/R
T1/U T2/V T3/W
L2/S L3/T
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PE-5@5B-2H
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PE-5@5B-3H
Terminal Arrangement/Internal Circuit Diagram
Input circuit
(+)
()
Input circuit
(+)
()
Input circuit
(+)
()
Input circuit
(+)
()
Three-phase G3PE
17
Accessories (Order Separately)
Heat Sink
Y92B-P50 (Mounts to DIN Track.) For G3PE-215B-2H and G3PE-515B-2H
Heat Sink
Y92B-P100 For G3PE-215B-3H, G3PE-225B-2H, G3PE-515B-3H, and G3PE-525B-2H
Heat Sink
Y92B-P150 For G3PE-225B-3H, G3PE-235B-2H, G3PE-525B-3H, and G3PE-535B-2H
Heat Sink
Y92B-P200 For G3PE-235B-3H, G3PE-245B-2H, G3PE-535B-3H, and G3PE-545B-2H
Heat Sink
Y92B-P250 For G3PE-245B-3H and G3PE-545B-3H
68 90
68
50
80 max.
80.5 max.
55 max.
100 max.
4.6 dia.
4.6 × 5.6 elliptical hole
50
±0.3
90
±0.3
Two, 4.5 dia. or M4
Mounting Holes
68
110.5 max.
60
68
Four, M4
100
80.5 max.
70 max.
Four, R2.5
60
±0.3
100
±0.3
Four, 4.5 dia. or M4
Mounting Holes
5
90
±0.3
100
±0.3
Four, 4.5 dia. or M4
Mounting Holes
68
90
68
100
110.5 max.
110.5 max.
70 max.
Four, M4
5
Four, R2.5
Mounting Holes
68
120
70 max.
68
120
130.5 max.
Four, M4
90
±0.3
120
±0.3
90
130.5 max.
5
Four, 4.5 dia. or M4
Four, R2.5
5
68
68
47.6
Four, M4M4-D10
M4-D10
120
120
130.5 max.
190.5 max.
70 max.
150
150
±0.3
120
±0.3
Four, 4.5 dia. or M4
Mounting Holes
Four, R2.5
G3PE
18
Safety Precautions
Refer to Safety Precautions for All Solid State Relays.
!CAUTION
Minor electrical shock may occasionally occur. Do not touch the G3PE terminal section (i.e., current­carrying parts) while the power is being supplied. Also, always attach the cover terminal.
The G3PE may rupture if short-circuit current flows. As protection against accidents due to short­circuiting, be sure to install protective devices, such as fuses and no-fuse breakers, on the power supply side.
Minor electrical shock may occasionally occur. Do not touch the main circuit terminals on the SSR immediately after the power supply has been turned OFF. Shock may result due to the electrical charge stored in the built-in snubber circuit.
Minor burns may occasionally occur. Do not touch the SSR or the heat sink while the power is being supplied or immediately after the power supply has been turned OFF. The SSR and heat sink become extremely hot.
OMRON constantly strives to improve quality and reliability. SSRs, however, use semiconductors, and semiconductors may commonly malfunction or fail. In particular, it may not be possible to ensure safety if the SSRs are used outside the rated ranges. Therefore, always use the SSRs within the ratings. When using an SSR, always design the system to ensure safety and prevent human accidents, fires, and social harm in the event of SSR failure. System design must include measures such as system redundancy, measures to prevent fires from spreading, and designs to prevent malfunction.
Transport
Do not transport the G3PE under the following conditions. Doing so may result in damage, malfunction, or deterioration of performance characteristics.
Conditions in which the G3PE may be subject to water.
Conditions in which the G3PE may be subject to high temperature
or high humidity.
Conditions in which the G3PE is not packaged.
Operating and Storage Environments
Do not use or store the G3PE in the following locations. Doing so may result in damage, malfunction, or deterioration of performance characteristics.
Locations subject to rainwater or water splashes.
Locations subject to exposure to water, oil, or chemicals.
Locations subject to high temperature or high humidity.
Do not store in locations subject to ambient storage temperatures outside the range 30 to 100°C.
Do not use in locations subject to relative humidity outside the
range 45% to 85%.
Locations subject to corrosive gases.
Locations subject to dust (especially iron dust) or salts.
Locations subject to direct sunlight.
Locations subject to shock or vibration.
Installation and Handling
Do not block the movement of the air surrounding the G3PE or heat
sink. Abnormal heating of the G3PE may result in shorting failures of the output elements or burn damage.
Do not use the G3PE if the heat radiation fins have been bent by
being dropped. Doing so may result in malfunction due to a reduction in the heat radiation performance.
Do not handle the G3PE with oily or dusty (especially iron dust)
hands. Doing so may result in malfunction.
Attach a heat sink or radiator when using an SSR. Not doing so
may result in malfunction due to a reduction in the heat radiation performance.
Installation and Mounting
Mount the G3PE in the specified direction. Otherwise excessive
heat generated by the G3PE may cause short-circuit failures of the output elements or burn damage.
Make sure that there is no excess ambient temperature rise due to
the heat generation of the G3PE. If the G3PE is mounted inside a panel, install a fan so that the interior of the panel is fully ventilated.
Make sure the DIN track is securely mounted. Otherwise, the
G3PE may fall.
When mounting the heat sink, do not allow any foreign matter
between the heat sink and the mounting surface. Foreign matter may cause malfunction due to a reduction in the heat radiation performance.
If the G3PE is mounted directly in a control panel, use aluminum,
steel plating, or similar material with a low heat resistance as a substitute for a heat sink. Using the G3PE mounted in wood or other material with a high heat resistance may result in fire or burning due to heat generated by the G3PE.
Installation and Wiring
Use wires that are suited to the load current. Otherwise, excessive
heat generated by the wires may cause burning.
Do not use wires with a damaged outer covering.
Otherwise, it may result in electric shock or ground leakage.
Do not wire any wiring in the same duct or conduit as power or
high-tension lines. Otherwise, inductive noise may damage the G3PE or cause it to malfunction.
When tightening terminal screws, prevent any non-conducting
material from becoming caught between the screws and the tightening surface. Otherwise, excessive heat generated by the terminal may cause burning.
Do not use the G3PE with loose terminal screws. Otherwise,
excessive heat generated by the wire may cause burning.
For the G3PE models with a carry current of 35 A or larger, use M5
crimp terminals that are an appropriate size for the diameter of the wire.
Always turn OFF the power supply before performing wiring. Not
doing so may cause electrical shock.
Installation and Usage
Select a load within the rated values. Not doing so may result in
malfunction, failure, or burning.
Select a power supply within the rated frequencies. Not doing so
may result in malfunction, failure, or burning.
The G3PE provides a circuit to prevent photocoupler damage by
forcibly arcing the output element for surge voltages applied to the load. The G3PE therefore cannot be used for motor loads. Doing so may result in load motor malfunction.
Precautions for Safe Use
G3PE
19
The SSR in operation may cause an unexpected accident. Therefore it is necessary to test the SSR under the variety of conditions that are possible. As for the characteristics of the SSR, it is necessary to consider differences in characteristics between individual SSRs. The ratings in this catalog are tested values in a temperature range between 15°C and 30°C, a relative humidity range between 25% and 85%, and an atmospheric pressure range between 86 and 106 kPa. It will be necessary to provide the above conditions as well as the load conditions if the user wants to confirm the ratings of specific SSRs.
Causes of Failure
Do not drop the G3PE or subject it to abnormal vibration or shock
during transportation or mounting. Doing so may result in deterioration of performance, malfunction, or failure.
Tighten each terminal to the torque specified below. Improper
tightening may result in abnormal heat generation at the terminal, which may cause burning.
Do not supply overvoltage to the input circuits or output circuits.
Doing so may result in failure or burning.
Do not use or store the G3PE in the following conditions. Doing so
may result in deterioration of performance.
Locations subject to static electricity or noise
Locations subject to strong electric or magnetic fields
Locations subject to radioactivity
Mounting
The G3PE is heavy. Firmly mount the DIN Track and secure both
ends with End Plates for DIN Track mounting models. When
mounting the G3PE directly to a panel, firmly secure it to the panel. Screw diameter: M4 Tightening torque: 0.98 to 1.47 N·m
Note: Make sure that the load current is 50% of the rated load current
when the G3PE is mounted horizontally. For details on close mounting, refer to the related information under performance characteristics. Mount the G3PE in a direction so that the markings read naturally.
The G3PE-2N/-3N (DIN Track mounting models) can be mounted
on the following TR35-15Fe (IEC 60715) DIN Tracks.
Wiring
When using crimp terminals, refer to the terminal clearances
shown below.
Make sure that all lead wires are thick enough for the current.
For three-element and two-element models, the output terminal will
be charged even when the Relay is OFF. Touching the terminal may result in electric shock. To isolate the Relay from the power supply, install an appropriate circuit breaker between the power supply and the Relay. Always turn OFF the power supply before wiring the Unit.
Terminal L2 and terminal T2 of a 2-element model are internally
connected to each other. Connect terminal L2 to the ground terminal of the power supply. If terminal L2 is connected to a terminal other than the ground terminal, cover all the charged terminals, such as heater terminals, to prevent electric shock and ground faults.
Fuses
Use a quick-burning fuse on the output terminals to prevent
accidents due to short-circuiting. Use a fuse with equal or greater performance than those given in the following table.
Recommended Fuse Capacity
Precautions for Correct Use
Terminals Screw terminal diameter Tightening torque
Input terminals M3.5 0.59 to 1.18 N·m
Output
terminals
M4 0.98 to 1.47 N·m M5 1.57 to 2.45 N·m
Manufacturer Thickness 1.5 mm 2.3 mm Schneider AM1-DE200 ---
WAGO
210-114, 210-197
210-118
PHOENIX NS35/15 NS35/15-2.3
Panel
Vertical Direction
Mounted on a
vertical surface
Panel
Mounted on a
horizontal surface
Rated G3PE output
current
Applicable SSR
Fuse
(IEC 60269-4)
15 A G3PE@15B Series
32 A
25 A G3PE@25B Series 35 A G3PE@35B Series
63 A
45 A G3PE@45B Series
7 mm
13 mm
10 mm 13 mm
12 mm
M4 (15A, 25A) M5 (35A, 45A)
12.9 mm
12.4 mm
10 mm
7.0 mm
M3.5
15-A and 25-A Models 35-A and 45-A Models
M5 (35 A, 45 A)
M4 (15 A, 25 A)
Output Terminal Section for Three-phase Models
Output Terminal Section for Single-phase Models
Input Terminal Section
G3PE
20
EMC Connection
Make EMC connections according to the following figure.
Connect a capacitor to the load power supply.
The input cable must be no longer than 3 m.
EMI
This is a Class A product (for industrial environments). In a domestic environment, the G3PE may cause radio interference, in which case the user may be required to take appropriate measures.
Noise and Surge Effects
If noise or an electrical surge occurs that exceeds the malfunction withstand limit for the G3PE output circuit, the output will turn ON for a maximum of one half cycle to absorb the noise or surge. Confirm that turning the output ON for a half cycle will not cause a problem for the device or system in which the G3PE is being used prior to actual use. The G3PE malfunction withstand limit is shown below.
Malfunction withstand limit (reference value): 500 V
Note: This value was measured under the following conditions.
Noise duration: 100 ns and 1 µs Repetition period: 100 Hz Noise application time: 3 min
Mounting Models with Externally Attached Heat Sinks
Before attaching an external Heat Sink or Radiator to the Unit,
always apply silicone grease, such as Toshiba Silicone's YG6260 or Sinetsu Silicone's G746, to the mounting surface to enable proper heat radiation.
Tighten the screws to the following torque to secure the Unit and
external Heat Sink or Radiator to enable proper heat dissipation.
Tightening torque: 2.0 N·m
Mounting to Control Panel
The G3PE is heavy. Firmly mount the DIN track and secure both ends with End Plates for DIN-track-mounting models. When mounting the G3PE directly to a panel, firmly secure it to the panel. If the panel is airtight, heat from the SSR will build up inside, which may reduce the current carry ability of the SSR or adversely affect other electrical devices. Be sure to install ventillation holes on the top and bottom of the panel.
SSR Mounting Pitch (Panel Mounting)
Single-phase Model
Three-phase Models
G3PE
Input Output
3 m max.
Load
Recommended Capacitor (Film Capacitor) G3PE-2@@B Series: 1 µF, 250 VAC G3PE-5@@B Series: 0.5 µF, 500 VAC
SSR
10 mm min.
30 mm min.
80 mm min.
60 mm min.
Duct or other object blocking airflow
Vertical Direction
Between duct and G3PE
Between duct and G3PE
Mounting direction
Host and slave
60 mm min.
30 mm min.
G3PE
G3PE G3PE
G3PE
80 mm min.
80 mm min.
Duct or other object blocking airflow
Duct or other object blocking airflow
Between duct and G3PE
Between duct and G3PE
Host and slave
G3PE
21
Relationship between the G3PE and Ducts or Other Objects Blocking Airflow
Ventilation Outside the Control Panel
Note: 1. If the air inlet or air outlet has a filter, clean the filter regularly
to prevent it from clogging to ensure an efficient flow of air.
2. Do not locate any objects around the air inlet or air outlet, otherwise the objects may obstruct the proper ventilation of the control panel.
3. A heat exchanger, if used, should be located in front of the G3PE to ensure the efficiency of the heat exchanger.
G3PE Ambient Temperature
The rated current of the G3PE is measured at an ambient temperature of 40°C. The G3PE uses a semiconductor to switch the load. This causes the temperature inside the control panel to increase due to heating resulting from the flow of electrical current through the load. The G3PE reliability can be increased by adding a ventilation fan to the control panel to dispel this heat, thus lowering the ambient temperature of the G3PE. (Arrhenius's law suggests that life expectancy is doubled by each 10°C reduction in ambient temperature.)
Example: For 10 G3PE SSRs with load currents of 15 A,
0.23 × 10 = 2.3 Thus, 3 fans would be required.
Note: 1. Size of fans: 92 mm × 92 mm, Air volume: 0.7 m
3
/min,
Ambient temperature of control panel: 30°C
2. If there are other instruments that generate heat in the control panel in addition to SSRs, more ventilation will be required.
3. Ambient temperature: The temperature that will allow the SSR to cool by convection or other means.
SSR rated current (A) 15 A 25 A 35 A 45 A
Required number of fans per SSR
0.23 0.39 0.54 0.70
Duct or other object blocking airflow
Duct
Duct
Duct Duct Duct
Vertical Direction
50 mm max.
Airflow
Base
SSR SSR
SSR
Incorrect Example Countermeasure 1 Countermeasure 2
Mounting surface
Mounting surface
Mounting surface
If the depth direction of the G3PE is obstructed by ducts, the heat radiation will be adversely affected.
(No more than 1/2 the SSR depth is recom­mended.)
Use ducts that have a shallow depth, to provide a sufficient ventilation area.
If the ducts cannot be made lower, place the G3PE on a metal base so that it is not surrounded by the ducts.
SSR
Air inlet
Be aware of airflow
Ventilation outlet (Axial Fan)
SSR
SSR
Duct or other object blocking airflow
G3PE
22
Warranty and Application Considerations
Read and Understand this Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE
PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will be used.
Know and observe all prohibitions of use applicable to this product. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Disclaimers
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with your OMRON representative at any time to confirm actual specifications of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
G3PE
23
Authorized Distributor:
In the interest of product improvement, specifications are subject to change without notice.
Cat. No. J174-E1-01
OMRON Industrial Automation Global: www.ia.omron.com
Printed in Japan
0708 (0708)
OMRON Corporation
Industrial Automation Company
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp The Netherlands Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg, IL 60173-5302 U.S.A. Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2), Alexandra Technopark, Singapore 119967 Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower, 200 Yin Cheng Zhong Road, PuDong New Area, Shanghai, 200120, China Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
Control Devices Division H.Q. Strategy Planning Division
Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 Japan Tel: (81) 75-344-7109/Fax: (81) 75-344-7149
© OMRON Corporation 2008 All Rights Reserved.
Loading...