Omron G3PB-215B-3N-VD, G3PB-235B-2N-VD, G3PB-215B-2N-VD, G3PB-225B-2N-VD, G3PB-245B-2N-VD User Manual

...
1
Solid-state Contactor (New Heat Sink Construction)
G3PB
Space and working time saved with new heat sink construction. Series now includes 480-VAC models to allow use in a greater range of applications.
Slim design with 3-phase output and built-in heat sinks.
New heat sink construction with smaller mounting section.
DIN
track mounting supported as standard. (Screw
mounting is also possible.) Conforms
to international standards (IEC, UL, and
CSA).
RC
X
VDE
Ordering Information
Models with Built-in Heat Sinks
Applicable
phase
Number
of
poles
Zero-cross
function
Main circuit voltage Applicable heater capacity
(with Class-1 AC resistive
load)
Model
3
3
Yes
100 to 240 V
AC
5.1 kW max. (15 A)
G3PB-215B-3N-VD
32es
00 o 0
C
5a(5)
G3PB-215B-2N-VD
3
8.6 kW max. (25 A)
G3PB-225B-3N-VD
2
86 a ( 5 )
G3PB-225B-2N-VD
3
12.1 kW max. (35 A)
G3PB-235B-3N-VD
2
a (35 )
G3PB-235B-2N-VD
3
15.5 kW max. (45 A)
G3PB-245B-3N-VD
2
55 a ( 5 )
G3PB-245B-2N-VD
3
200 to 480 V
AC
12.5 kW max. (15 A)
G3PB-515B-3N-VD
2
00 o 80
C
5a(5)
G3PB-515B-2N-VD
3
20.7 kW max. (25 A)
G3PB-525B-3N-VD
2
0a(5)
G3PB-525B-2N-VD
3
29.0 kW max. (35 A)
G3PB-535B-3N-VD
2
9 0 a (35 )
G3PB-535B-2N-VD
3
37.4 kW max. (45 A)
G3PB-545B-3N-VD
2
3a(5)
G3PB-545B-2N-VD
G3PB
G3PB
2
Specifications
Ratings (at an Ambient Temperature of 25°C)
Operating Circuit (Common)
Item Common
Rated
operating voltage 12 to 24 VDC
Operating voltage range
9.6 to 30 VDC
Rated input current (Impedance)
10 mA max. (at 24 VDC)
Must-operate voltage
9.6 VDC max.
Reset voltage
1 VDC min.
Insulation method
Phototriac coupler
Operation indicator
Y
ellow LED
Main Circuit of Models with Built-in Heat Sinks
Item G3PB-
215B-
3N-VD
G3PB-
215B-
2N-VD
G3PB-
225B-
3N-VD
G3PB-
225B-
2N-VD
G3PB-
235B-
3N-VD
G3PB-
235B-
2N-VD
G3PB-
245B-
3N-VD
G3PB-
245B-
2N-VD
Rated
voltage
100 to 240 V
AC
Operating voltage range
75 to 264 V
AC
Rated carry current (see note)
15 A 25 A 35 A 45 A
Minimum load current
0.2 A 0.5 A
Inrush current resistance (peak value)
150 A (60 Hz, 1 cycle)
220 A (60 Hz, 1 cycle)
440 A (60 Hz, 1 cycle)
Permissible I2t (half 60-Hz wave)
121 A2s
260 A2s
1,260 A2s
Item G3PB-
515B-
3N-VD
G3PB-
515B-
2N-VD
G3PB-
525B-
3N-VD
G3PB-
525B-
2N-VD
G3PB-
535B-
3N-VD
G3PB-
535B-
2N-VD
G3PB-
545B-
3N-VD
G3PB-
545B-
2N-VD
Rated voltage
200 to 480 V
AC
Operating voltage range
180 to 528 V
AC
Rated carry current (see note)
15 A 25 A 35 A 45 A
Minimum load current
0.5 A
Inrush current resistance (peak value)
220 A (60 Hz, 1 cycle)
440 A (60 Hz, 1 cycle)
Permissible I2t (half 60-Hz wave)
260 A2s
1,260 A2s
Note: Rated
carry current varies depending on the ambient temperature. For details, refer to
Load Current vs. Ambient T
emperature
in
Engi
-
neering
Data.
G3PB
G3PB
3
Characteristics
Models with Built-in Heat Sinks
Item G3PB-
215B-
3N-VD
G3PB-
215B-
2N-VD
G3PB-
225B-
3N-VD
G3PB-
225B-
2N-VD
G3PB-
235B-
3N-VD
G3PB-
235B-
2N-VD
G3PB-
245B-
3N-VD
G3PB-
245B-
2N-VD
Operate
time
1/2 of load power source cycle + 1 ms max. (DC input)
Release time
1/2 of load power source cycle + 1 ms max. (DC input)
Output ON voltage drop
1.6 V (RMS) max.
Leakage current (see note)
10 mA (at 200 V
AC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 V
AC, 50/60 Hz for 1 min
V
ibration resistance
10 to 55 Hz, 0.175-mm single amplitude
Shock resistance
294 m/s2 (98 m/s2 with reverse mounting)
Ambient temperature
Operating: –30°
C to 80°C (with no icing or condensation)
Storage: –30°
C to 100°C (with no icing or condensation)
Ambient humidity
Operating: 45% to 85%
Weight
Approx. 1.25 kg Approx. 1.45 kg Approx. 1.65 kg
Approx. 2.0 kg
Approved standards
UL508, CSA22.2 No. 14, EN60947-4-3 (IEC947-4-3) approved by VDE (From April 2001)
EMC Emission EN55011 Group 1 Class B
Immunity ESD
IEC947-4-3, EN61000-4-2
4 kV contact discharge 8 kV air discharge
Immunity Electromagnetic
IEC947-4-3, EN61000-4-3
10 V/m (80 MHz to 1 GHz)
Immunity EFT
IEC947-4-3, EN61000-4-4
2 kV AC power-signal line
Immunity
Surge transient
IEC947-4-3, EN61000-4-5
Normal mode
±1 kV
, Common mode
±2 kV
Immunity
RF disturbance
IEC947-4-3, EN61000-4-6
10 V (0.15 to 80 MHz)
Immunity Dips
IEC947-4-3, EN61000-4-1
1
3
Note:
The leakage current of phase S will be approximately
times larger if the 2-element model is applied.
G3PB
G3PB
4
Item G3PB-
515B-
3N-VD
G3PB-
515B-
2N-VD
G3PB-
525B-
3N-VD
G3PB-
525B-
2N-VD
G3PB-
535B-
3N-VD
G3PB-
535B-
2N-VD
G3PB-
545B-
3N-VD
G3PB-
545B-
2N-VD
Operate time
1/2 of load power source cycle + 1 ms max. (DC input)
Release time
1/2 of load power source cycle + 1 ms max. (DC input)
Output ON voltage drop
1.8 V (RMS) max.
Leakage current (see note)
20 mA (at 480 V
AC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 V
AC, 50/60 Hz for 1 min
V
ibration resistance
10 to 55 Hz, 0.175-mm single amplitude
Shock resistance
294 m/s2 (98 m/s2 with reverse mounting)
Ambient temperature
Operating: –30°
C to 80°C (with no icing or condensation)
Storage: –30°
C to 100°C (with no icing or condensation)
Ambient humidity
Operating: 45% to 85%
Weight
Approx. 1.25 kg Approx. 1.45 kg Approx. 1.65 kg
Approx. 2.0 kg
Approved standards
UL508, CSA22.2 No. 14, EN60947-4-3 (IEC947-4-3) approved by VDE (From April 2001)
EMC Emission EN55011 Group 1 Class B
Immunity ESD
IEC947-4-3, EN61000-4-2
4 kV contact discharge 8 kV air discharge
Immunity Electromagnetic
IEC947-4-3, EN61000-4-3
10 V/m (80 MHz to 1 GHz)
Immunity EFT
IEC947-4-3, EN61000-4-4
2 kV AC power-signal line
Immunity
Surge transient
IEC947-4-3, EN61000-4-5
Normal mode
±1 kV
, Common mode
±2 kV
Immunity
RF disturbance
IEC947-4-3, EN61000-4-6
10 V (0.15 to 80 MHz)
Immunity Dips
IEC947-4-3, EN61000-4-1
1
3
Note:
The leakage current of phase S will be approximately
times larger if the 2-element model is applied.
Loading...