Omron G3PA-260B-VD, G3PA-210B-VD, G3PA-210BL-VD, G3PA-220BL-VD, G3PA-240BL-VD User Manual

...
Solid State Relays G3PA J-21
SSR
Solid State Relays
G3PA
Extremely Thin Relays Integrated with Heat Sinks
• Downsizing achieved through optimum design of heat sink.
• Close mounting possible for linking terminals. (Except for G3PA­260B-VD and G3PA-450B-VD-2.)
• Applicable with 3-phase loads.
• Replaceable power element cartridges.
• Comply with VDE 0160 (finger protection), with a dielectric strength of 4,000 V between input and load.
• Comply with VDE 0805, IEC 950.
• Certified by UL, CSA, and VDE (reinforced insulation).
Model Number Structure
Model Number Legend
1. Basic Model Name
G3PA: Solid State Relay
2. Rated Load Power Supply Voltage
2: 200 VAC 4: 400 VAC
3. Rated Load Current
10: 10 A 20: 20 A 30: 30 A 40: 40 A 50: 50 A 60: 60 A
4. Terminal Type
B: Screw terminals
5. Zero Cross Function
Blank: Equipped with zero cross function L: Not equipped with zero cross function
6. Certification
VD: Certified by UL, CSA, and VDE
7. Special Specifications
Blank: Standard models 2: 480-V models
123 4 5 6 7
G3PA-@@@@-@-@
J-22 Solid State Relays G3PA
Ordering Information
List of Models
Note: When ordering, specify the rated input voltage.
Replacement Parts
Other Units (Order Separately)
Units that Enable 2-line Switching of 3-phase Power
Model Isolation Zero cross function Indicator Rated output load Rated input voltage
G3PA-210B-VD Phototriac
coupler
Yes Yes 10 A at 24 to 240 VAC 5 to 24 VDC G3PA-220B-VD 20 A at 24 to 240 VAC G3PA-240B-VD 40 A at 24 to 240 VAC G3PA-260B-VD 60 A at 24 to 240 VAC G3PA-210BL-VD No 10 A at 24 to 240 VAC G3PA-220BL-VD 20 A at 24 to 240 VAC G3PA-240BL-VD 40 A at 24 to 240 VAC G3PA-260BL-VD 60 A at 24 to 240 VAC G3PA-210B-VD Yes 10 A at 24 to 240 VAC 24 VAC G3PA-220B-VD 20 A at 24 to 240 VAC G3PA-240B-VD 40 A at 24 to 240 VAC G3PA-260B-VD 60 A at 24 to 240 VAC G3PA-420B-VD 20 A at 180 to 400 VAC 12 to 24 VDC G3PA-430B-VD 30 A at 180 to 400 VAC G3PA-420B-VD-2 20 A at 200 to 480 VAC G3PA-430B-VD-2 30 A at 200 to 480 VAC G3PA-450B-VD-2 50 A at 200 to 480 VAC
Name Carry current Load voltage range Model Applicable SSR VDE
certification
Power Device Cartridge
10 A 19 to 264 VAC G32A-A10-VD DC5-24 G3PA-210B-VD DC5-24 Yes
G32A-A10L-VD DC5-24 G3PA-210BL-VD DC5-24 G32A-A10-VD AC24 G3PA-210B-VD AC24
20 A G32A-A20-VD DC5-24 G3PA-220B-VD DC5-24
G32A-A20L-VD DC5-24 G3PA-220BL-VD DC5-24 G32A-A20-VD AC24 G3PA-220B-VD AC24
40 A G32A-A40-VD DC5-24 G3PA-240B-VD DC5-24
G32A-A40L-VD DC5-24 G3PA-240BL-VD DC5-24 G32A-A40-VD AC24 G3PA-240B-VD AC24
60 A G32A-A60-VD DC5-24 G3PA-260B-VD DC5-24
G32A-A60L-VD DC5-24 G3PA-260BL-VD DC5-24
G32A-A60-VD AC24 G3PA-260B-VD AC24 20 A 150 to 440 VAC G32A-A420-VD DC12-24 G3PA-420B-VD DC12-24 30 A G32A-A430-VD DC12-24 G3PA-430B-VD DC12-24 20 A 180 to 528 VAC G32A-A420-VD-2 DC12-24 G3PA-420B-VD-2 DC12-24 30 A G32A-A430-VD-2 DC12-24 G3PA-430B-VD-2 DC12-24 50 A G32A-A450-VD-2 DC12-24 G3PA-450B-VD-2 DC12-24
Name Current flow Model Applicable SSR
Short-circuit Unit 10 A G32A-D20 G3PA-210B-VD, G3PA-210BL-VD
20 A G3PA-220B-VD, G3PA-220BL-VD
G3PA-420B-VD, G3PA-420B-VD-2 30 A G32A-D40 G3PA-430B-VD, G3PA-430B-VD-2 40 A G3PA-240B-VD, G3PA-240BL-VD
Solid State Relays G3PA J-23
SSR
Specifications
Ratings (at an Ambient Temperature of 25°C)
Input
Output
Refer to Engineering Data for further details.
Model Rated voltage Operating Voltage
range
Input current
impedance
Voltage level
Must operate voltage Must release voltage G3PA-210B-VD 5 to 24 VDC 4 to 30 VDC 7 mA max. 4 VDC max. 1 VDC min. G3PA-220B-VD G3PA-240B-VD G3PA-260B-VD G3PA-210BL-VD 5 to 24 VDC 4 to 30 VDC 20 mA max. 4 VDC max. 1 VDC min. G3PA-220BL-VD G3PA-240BL-VD G3PA-260BL-VD G3PA-210B-VD 24 VAC 19.2 to 26.4 VAC 1.4 kΩ±20% 19.2 VAC max. 4.8 VAC min. G3PA-220B-VD G3PA-240B-VD G3PA-260B-VD G3PA-420B-VD 12 to 24 VDC 9.6 to 30 VDC 7 mA max. 9.2 VDC max. 1 VDC min. G3PA-430B-VD G3PA-420B-VD-2 G3PA-430B-VD-2 G3PA-450B-VD-2
Model Applicable load
Rated load voltage Load voltage range Load current Inrush current G3PA-210B(L)-VD 24 to 240 VAC (50/60 Hz) 19 to 264 VAC (50/60 Hz) 0.1 to 10 A 150 A (60 Hz, 1 cycle) G3PA-220B(L)-VD 0.1 to 20 A 220 A (60 Hz, 1 cycle) G3PA-240B(L)-VD 0.5 to 40 A 440 A (60 Hz, 1 cycle) G3PA-260B(L)-VD 0.5 to 60 A 440 A (60 Hz, 1 cycle) G3PA-420B-VD 180 to 400 VAC (50/60 Hz) 150 to 440 VAC (50/60 Hz) 0.5 to 20 A 220 A (60 Hz, 1 cycle) G3PA-430B-VD 0.5 to 30 A 440 A (60 Hz, 1 cycle) G3PA-420B-VD-2 200 to 480 VAC (50/60 Hz) 180 to 528 VAC (50/60 Hz) 0.5 to 20 A 220 A (60 Hz, 1 cycle) G3PA-430B-VD-2 0.5 to 30 A 440 A (60 Hz, 1 cycle) G3PA-450B-VD-2 0.5 to 50 A 440 A (60 Hz, 1 cycle)
J-24 Solid State Relays G3PA
Characteristics
Item G3PA-
210B(L)-VD
G3PA-
220B(L)-VD
G3PA-
240B(L)-VD
G3PA-
260B(L)-VD
G3PA-
420B-VD
G3PA-
420B-VD-2
G3PA-
430B-VD
G3PA-
430B-VD-2
G3PA-
450B-VD-2
Operate time 1/2 of load power source cycle + 1 ms max. (DC Input, -B models)
1 1/2 of load power source cycle + 1 ms max. (AC Input) 1 ms max. (-BL models)
Release time 1/2 of load power source cycle + 1 ms max. (DC Input)
1 1/2 of load power source cycle + 1 ms max. (AC Input)
Output ON voltage drop
1.6 V (RMS) max. 1.8 V (RMS) max.
Leakage current
5 mA max. (at 100 VAC) 10 mA max. (at 200 VAC)
10 mA max. (at 100 VAC) 20 mA max. (at 200 VAC)
20 mA max. (at 400 VAC)
20 mA max. (at 480 VAC)
20 mA max. (at 400 VAC)
20 mA max. (at 480 VAC)
I
2
t 260 A2s 1,260 A2s260 A
2
s 1,800 A2s 1,800 A2s 1,800 A2s
Insulation resistance
100 M min. (at 500 VDC)
Dielectric strength
4,000 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction: 10 to 55 to 10 Hz, 0.375–mm single amplitude (Mounted to DIN track)
Shock resistance
Destruction: 300 m/s
2
(mounted to DIN track)
Ambient temperature
Operating: –30°C to 80°C (with no icing or condensation) Storage: –30°C to 100°C (with no icing or condensation)
Certified standards
UL508, CSA C22.2 (No.14, No.950), EN60950 File No. 5915ÜG
UL508, CSA C22.2 (No.14), EN60947­4-3 File No. 6642ÜG
UL508, CSA C22.2 (No.14), EN60947-4-3 File No. 133127ÜG
UL508, CSA C22.2 (No.14), EN60947­4-3 File No. 6642ÜG
UL508, CSA C22.2 (No.14), EN60947-4-3 File No. 133127ÜG
Ambient humidity
Operating: 45% to 85%
Weight Approx.
260 g
Approx. 340 g
Approx. 460 g
Approx. 900 g
Approx. 290 g
Approx. 290 g
Approx. 410 g
Approx. 410 g
Approx. 900 g
Solid State Relays G3PA J-25
SSR
Operation
Replacement Parts
G32A-A Power Device Cartridge
The G32A-A Power Device Cartridge (a Triac Unit) can be replaced with a new one. When the temperature indicator has changed from pink to red, the triac circuitry may have malfunctioned possibly by an excessive flow of current, in which case, dismount the damaged cartridge for replacement.
The damaged cartridge can be replaced with a new one without disconnecting the wires from the G3PA. Improve the heat radiation efficiency of the G3PA before replacing the cartridge. The G32A-A Power Device Cartridge can withstand an excessive current for a short period of time, such as may be caused accidentally by the
short circuitry of the load, in which case the temperature indicator will not turn red. Be sure to turn OFF the power supply when replacing the Cartridge. Supplying power with the Cartridge removed may result in malfunction.
Appearance
Replacing Power Device Cartridges
When replacing Power Device Cartridges, use the specified model. Using a Power Device Cartridge other than the specified one will result in faulty operation and destruction of the elements.
G32A-A10(L)-VD G32A-A20(L)-VD G32A-A40(L)-VD G32A-A60(L)-VD
G32A-A420-VD(-2)
G32A-A430-VD(-2) G32A-A450-VD-2