J-34 Solid State Relays G3PA
Safety Precautions
■ Precautions for Correct Use
Please observe the following precautions to prevent failure to
operate, malfunction, or undesirable effect on product performance.
Load Connection
For an AC load, use a power supply rated at 50 or 60 Hz.
The maximum operating frequency is 10 Hz.
The G3PA-(VD) has a built-in varistor for overvoltage protection.
At a low applied voltage, such as 24 VAC, the load current is not fully
supplied. When the Unit is switched ON, the voltage required to
power the Unit deprives the output signal of the necessary voltage
level and thus creates loss time. The lower the load voltage is, the
greater the loss time is. This condition, however, will not create any
serious problems.
For a DC or L load, a diode should be connected in parallel the load
to absorb the counter electromotive force of the load.
When attaching a heat sink to the G3PA-(VD), in order to facilitate
heat dissipation, apply silicone grease or equivalent heat-conductive
grease on the heat sink. (Toshiba Silicone, Shinetsu Silicone, etc.)
Tighten the mounting screws of the heat sink with a torque of 0.78 to
0.98 N·m.
Noise Terminal Voltage according to
EN55011
The G3PA-(VD) complies with EN55011 standards when a capacitor
is connected to the load power supply as shown in the following
circuit diagram.
Recommended Capacitor: 1 µF, 250 VAC
Mounting
Loss time
SSR
Input
Load
Load power
supply
G3PA-(VD)
Output
Load
Input
DIN track
G3PA
G3PA
Panel
DIN track
Panel
The rated ambient
temperature is
40°C. (30°C for
400 V.)
Vertical mounting
Close mounting
Horizontal mounting
• Screw or DIN track
mounting is possible.
• Vertical mounting should
usually be used.
• Close mounting is also
possible.
• Close mounting is possible for
up to 3 G3PA SSRs. (If there
are 4 or more SSRs, mount at
intervals of 10 mm min.)
Reduce the load current by
10% for G3PA-210B-VD,
-220B-VD, -240B-VD and by
20% for G3PA-260B-VD, 420B-VD(-2), -430B-VD(-2),
-450B-VD-2.
• Leave a distance of 80 mm
• With vertical mounting,
reduce the load current by
30%. (Refer to the Load
Current vs. Ambient
Temperature graph.)
80 mm
Note: Leave a distance of 60 mm min. between SSRs and ducts (especially above the SSR).
↔
↔
↔
Vertical
Vertical
Vertical