• Downsizing achieved through optimum design of heat sink.
• Mounting possible via screws or via DIN track.
• Close mounting possible for linking terminals. (Except for G3PA260B-VD and G3PA-450B-VD-2.)
• Applicable with 3-phase loads.
• Replaceable power element cartridges.
• Comply with VDE 0160 (finger protection), with a dielectric
strength of 4,000 V between input and load.
• Comply with VDE 0805, IEC 950.
• Certified by UL, CSA, and VDE (reinforced insulation).
Model Number Structure
■ Model Number Legend
G3PA-@@@@-@-@
123 4 5 6 7
1. Basic Model Name
G3PA:Solid State Relay
2. Rated Load Power Supply Voltage
2:200 VAC
4:400 VAC
3. Rated Load Current
10:10 A
20:20 A
30:30 A
40:40 A
50:50 A
60:60 A
4. Terminal Type
B:Screw terminals
5. Zero Cross Function
Blank:Equipped with zero cross function
L:Not equipped with zero cross function
6. Certification
VD:Certified by UL, CSA, and VDE
7. Special Specifications
Blank:Standard models
2:480-V models
SSR
Solid State RelaysG3PAJ-21
Page 2
Ordering Information
■ List of Models
ModelIsolationZero cross functionIndicatorRated output loadRated input voltage
G3PA-210B-VDPhototriac
G3PA-220B-VD20 A at 24 to 240 VAC
G3PA-240B-VD40 A at 24 to 240 VAC
G3PA-260B-VD60 A at 24 to 240 VAC
G3PA-210BL-VDNo10 A at 24 to 240 VAC
G3PA-220BL-VD20 A at 24 to 240 VAC
G3PA-240BL-VD40 A at 24 to 240 VAC
G3PA-260BL-VD60 A at 24 to 240 VAC
G3PA-210B-VDYes10 A at 24 to 240 VAC24 VAC
G3PA-220B-VD20 A at 24 to 240 VAC
G3PA-240B-VD40 A at 24 to 240 VAC
G3PA-260B-VD60 A at 24 to 240 VAC
G3PA-420B-VD20 A at 180 to 400 VAC12 to 24 VDC
G3PA-430B-VD30 A at 180 to 400 VAC
G3PA-420B-VD-220 A at 200 to 480 VAC
G3PA-430B-VD-230 A at 200 to 480 VAC
G3PA-450B-VD-250 A at 200 to 480 VAC
Note: When ordering, specify the rated input voltage.
coupler
Replacement Parts
YesYes10 A at 24 to 240 VAC5 to 24 VDC
NameCarry currentLoad voltage rangeModelApplicable SSRVDE
Power Device
Cartridge
10 A19 to 264 VACG32A-A10-VD DC5-24G3PA-210B-VD DC5-24Yes
G3PA-210B-VD5 to 24 VDC4 to 30 VDC7 mA max.4 VDC max.1 VDC min.
G3PA-220B-VD
G3PA-240B-VD
G3PA-260B-VD
G3PA-210BL-VD5 to 24 VDC4 to 30 VDC20 mA max.4 VDC max.1 VDC min.
G3PA-220BL-VD
G3PA-240BL-VD
G3PA-260BL-VD
G3PA-210B-VD24 VAC19.2 to 26.4 VAC1.4 kΩ±20%19.2 VAC max.4.8 VAC min.
G3PA-220B-VD
G3PA-240B-VD
G3PA-260B-VD
G3PA-420B-VD12 to 24 VDC9.6 to 30 VDC7 mA max.9.2 VDC max.1 VDC min.
G3PA-430B-VD
G3PA-420B-VD-2
G3PA-430B-VD-2
G3PA-450B-VD-2
range
Input current
impedance
Voltage level
Must operate voltageMust release voltage
Output
ModelApplicable load
Rated load voltageLoad voltage rangeLoad currentInrush current
G3PA-210B(L)-VD24 to 240 VAC (50/60 Hz)19 to 264 VAC (50/60 Hz)0.1 to 10 A150 A (60 Hz, 1 cycle)
G3PA-220B(L)-VD0.1 to 20 A220 A (60 Hz, 1 cycle)
G3PA-240B(L)-VD0.5 to 40 A440 A (60 Hz, 1 cycle)
G3PA-260B(L)-VD0.5 to 60 A440 A (60 Hz, 1 cycle)
G3PA-420B-VD180 to 400 VAC (50/60 Hz) 150 to 440 VAC (50/60 Hz) 0.5 to 20 A220 A (60 Hz, 1 cycle)
G3PA-430B-VD0.5 to 30 A440 A (60 Hz, 1 cycle)
G3PA-420B-VD-2200 to 480 VAC (50/60 Hz) 180 to 528 VAC (50/60 Hz) 0.5 to 20 A220 A (60 Hz, 1 cycle)
G3PA-430B-VD-20.5 to 30 A440 A (60 Hz, 1 cycle)
G3PA-450B-VD-20.5 to 50 A440 A (60 Hz, 1 cycle)
Refer to Engineering Data for further details.
Solid State RelaysG3PAJ-23
SSR
Page 4
■ Characteristics
ItemG3PA-
Operate time 1/2 of load power source cycle + 1 ms max. (DC Input, -B models)
Release time 1/2 of load power source cycle + 1 ms max. (DC Input)
Output ON
voltage drop
Leakage
current
2
t260 A2s1,260 A2s260 A
I
Insulation
resistance
Dielectric
strength
Vibration
resistance
Shock
resistance
Ambient
temperature
Certified
standards
Ambient
humidity
WeightApprox.
210B(L)-VD
1 1/2 of load power source cycle + 1 ms max. (AC Input)
1 ms max. (-BL models)
1 1/2 of load power source cycle + 1 ms max. (AC Input)
1.6 V (RMS) max.1.8 V (RMS) max.
5 mA max. (at 100 VAC)
10 mA max. (at 200 VAC)
100 MΩ min. (at 500 VDC)
4,000 VAC, 50/60 Hz for 1 min
Destruction: 10 to 55 to 10 Hz, 0.375–mm single amplitude (Mounted to DIN track)
Destruction: 300 m/s
Operating: –30°C to 80°C (with no icing or condensation)
Storage: –30°C to 100°C (with no icing or condensation)
The G32A-A Power Device Cartridge (a Triac Unit) can be replaced with a new one. When the temperature indicator has changed from pink to red,
the triac circuitry may have malfunctioned possibly by an excessive flow of current, in which case, dismount the damaged cartridge for replacement.
The damaged cartridge can be replaced with a new one without disconnecting the wires from the G3PA.
Improve the heat radiation efficiency of the G3PA before replacing the cartridge.
The G32A-A Power Device Cartridge can withstand an excessive current for a short period of time, such as may be caused accidentally by the
short circuitry of the load, in which case the temperature indicator will not turn red.
Be sure to turn OFF the power supply when replacing the Cartridge. Supplying power with the Cartridge removed may result in malfunction.
When replacing Power Device Cartridges, use the specified model. Using a Power Device Cartridge other than the specified one will result in faulty
operation and destruction of the elements.
SSR
Solid State RelaysG3PAJ-25
Page 6
■ Replacement Procedure
G32A-A10(L)-VD/G32A-A20(L)-VD/G32-A420-VD(-2)
Use the special tool (provided) to extract the cartridge for replacement with a new one.
Extraction
Follow the procedures below to dismount the Power Device
Cartridge from the G3PA.
Switch off the power.
1.
2. Remove the terminal cover.
3. Hook the indented part of the cartridge with the tool and pull up
on the cartridge to remove it.
Remover
Hook here with
Remover.
Mounting
Follow the procedures below to mount the Power Device Cartridge
on the G3PA.
1. Apply silicone grease (provided with the G32A-A) to the entire
surface of the heat sink.
2. Make sure that there is no dust or pieces of wire on the heat sink
of the G32A-A or the G3PA.
3. Insert the cartridge into the opening of the G3PA so that the
letters on the cartridge and those on the G3PA are in the same
direction and side A and side B are even.
4. Attach the terminal cover.
5. Switch on the power and check the G3PA to be sure it works
The G32A Power Device Cartridge is mounted and secured with screws to the G3PA Unit.
Extraction
Follow the procedures below to dismount the G32A-A Power Device
Cartridge from the G3PA.
Switch off the power.
1.
2. Remove the terminal cover.
3. Loosen the two centered screws on the sides to dismount the
cartridge. The screws are connected to terminals 1 and 2.
Loosen
Loosen
4. Loosen the screws on both the corners.
Loosen
Loosen
Mounting
1. Apply silicone grease to the entire surface of the heat sink.
Apply silicone grease here.
2. Make sure that there is no dust or pieces of wire on the heat sink
of the G32A-A or the G3PA.
5. Hold the indented part of both the corners to dismount the
cartridge.
J-26Solid State Relays G3PA
Page 7
3. Insert the cartridge into the opening of the G3PA so that side A
and side B are even.
Side A
Side B
■ Linking Terminal Connection
• Connecting with linking terminal for G3PA-210B(L)-VD, -220B(L)-
VD, -240B(L)-VD and G3PA-420B-VD(-2), G3PA-430B-VD(-2).
SSR1SSR2SSR1SSR2
4. Tighten the screws on both the corners with a tightening torque of
0.59 to 0.78 N·m.
5. Tighten the screws on both the sides with a tightening torque of
0.59 to 0.78 N·m.
6. Attach the terminal cover.
7. Switch on the power and check the G3PA to be sure it works
properly.
• Connecting with linking terminal for G32A.
SSRG32A UnitSSRG32A Unit
1. When SSRs are close
mounted, loosen the
M3.5 Sems screw and
flip the linking terminal
down.
Connect the terminal with power off.
Refer to the instruction manual for
the G32A-A Power Device Car tridge
to replace the G3PA's triac par t.
2. Insert the linking
terminal securely
into the center of
the screw and
tighten the screw.
Linking terminal
Linking terminal
1. When SSR are close
mounted, loosen the
M3.5 Sems screw on
the G32A and flip the
linking terminal down.
G3PA-420B-VD
Linking
terminal
Linking
terminal
*
* The cover will not fit if
the terminal protrudes.
2. Insert the linking terminal
securely into the center
of the screw and tighten
the screw. Ensure that
the linking terminal does
not protrude.
SSR
When the temperature indicator has turned from pink to red, the G32-A-A Power Device Cartridge
may have malfunctioned, in which case the cartridge must be replaced with a new one.
Use the terminal cover to prevent accidents
due to electric shock.
Solid State RelaysG3PAJ-27
Page 8
Engineering Data
Load Current vs. Ambient Temperature
Vertical Mounting
Panel
Ground
G3PA-210B(L)-VD, G3PA-220B(L)-VD
G3PA-220B(L)-VD
25
G3PA-210B(L)-VD
15
Load current (A)
Ambient temperature (°C)Ambient temperature (°C)Ambient temperature (°C)
Note: All units are in millimeters unless otherwise indicated.
G3PA-210B(L)-VD
Without Terminal
Cover
Linking
terminal B2
Two , M 4
Linking terminal B1
With Terminal
Cover
Two ,
M3.5
4.6 x 5.6 elliptical
hole
100 max.
4.6 dia.
Mounting
Holes
Two, 4.5 dia. or M4 holes
Terminal
Arrangement/
Internal Connections
Input circuit
Trigger circuit
G3PA-220B(L)-VD
G3PA-240B(L)-VD
Without Terminal
Cover
Linking terminal B1
Linking terminal B2
Two , M 4
Without Terminal
Cover
Linking
terminal B1
Linking
terminal B2
Two , M 5
Two ,
M3.5
4.6 x 5.6 elliptical
hole
100 max.
With Terminal
Cover
Two ,
M3.5
4.6 x 5.6 elliptical
hole
With Terminal
Cover
4.6 dia.
4.6 dia.
Mounting
Holes
Two, 4.5 dia. or M4 holes
Mounting
Holes
Two, 4.5 dia. or M4 holes
Terminal
Arrangement/
Internal Connections
Input circuit
Trigger circuit
Terminal
Arrangement/
Internal Connections
Input circuit
Trigger circuit
100 max.
J-32Solid State Relays G3PA
Page 13
G3PA-260B(L)-VD
G3PA-450B-VD-2
With Terminal
Cover
100 max.
G3PA-420B-VD, G3PA-420B-VD-2
4.6 x 5.6
elliptical hole
110 max.
4.6 dia.
Without Terminal
Cover
Two , M 5
Two, M3.5
Mounting Holes
Two, 4.5 dia. or M4 holes
Terminal Arrangement/
Internal Connections
Input circuit
Trigger circuit
Without Terminal
Cover
Two, M4
Linking
terminal
+B1
67
Linking
terminal
−B2
2.2
8.8
13.2
G3PA-430B-VD, G3PA-430B-VD-2
Without Terminal
Cover
Two, M5
Linking
terminal
+B1
67
Linking
terminal
−B2
18
13
7.6
90±0.2
100
38
max.
8.6
Two, M3.5
4.5 x 5.6 elliptic hole
7.6
100
90±0.2
38
max.
13
4.6 x 5.6
elliptic hole
With Terminal
Cover
4.6 dia.
80
25±0.2
37 max.
90
91
100 max.
4.5
With Terminal
Mounting Holes
Two, 4.5 dia. or M4
90±0.3
Mounting Holes
Cover
4.6 dia.
Two, 4.5 dia. or M4
Terminal Arrangement/
Internal Connections
Input circuit
Trigger circuit
Terminal Arrangement/
Internal Connections
SSR
80
35±0.2
47 max.
100 max.
4.5
90±0.3
35±0.3
Trigger circuit
Input circuit
89
91
Solid State RelaysG3PAJ-33
Page 14
Safety Precautions
■ Precautions for Correct Use
Please observe the following precautions to prevent failure to
operate, malfunction, or undesirable effect on product performance.
Input
SSR
Load
Load power
supply
Load Connection
For an AC load, use a power supply rated at 50 or 60 Hz.
The maximum operating frequency is 10 Hz.
The G3PA-(VD) has a built-in varistor for overvoltage protection.
At a low applied voltage, such as 24 VAC, the load current is not fully
supplied. When the Unit is switched ON, the voltage required to
power the Unit deprives the output signal of the necessary voltage
level and thus creates loss time. The lower the load voltage is, the
greater the loss time is. This condition, however, will not create any
serious problems.
Loss time
For a DC or L load, a diode should be connected in parallel the load
to absorb the counter electromotive force of the load.
Mounting
Vertical mounting
When attaching a heat sink to the G3PA-(VD), in order to facilitate
heat dissipation, apply silicone grease or equivalent heat-conductive
grease on the heat sink. (Toshiba Silicone, Shinetsu Silicone, etc.)
Tighten the mounting screws of the heat sink with a torque of 0.78 to
0.98 N·m.
Noise Terminal Voltage according to
EN55011
The G3PA-(VD) complies with EN55011 standards when a capacitor
is connected to the load power supply as shown in the following
circuit diagram.
Load
Input
G3PA-(VD)
Recommended Capacitor: 1 µF, 250 VAC
• Screw or DIN track
mounting is possible.
• Vertical mounting should
usually be used.
↔
Vertical
Panel
Output
• Close mounting is also
possible.
• Close mounting is possible for
↔
up to 3 G3PA SSRs. (If there
The rated ambient
temperature is
40°C. (30°C for
400 V.)
Close mounting
G3PA
G3PA
Horizontal mounting
DIN track
↔
80 mm
DIN track
Panel
Vertical
are 4 or more SSRs, mount at
intervals of 10 mm min.)
Reduce the load current by
10% for G3PA-210B-VD,
-220B-VD, -240B-VD and by
Vertical
20% for G3PA-260B-VD, 420B-VD(-2), -430B-VD(-2),
-450B-VD-2.
• Leave a distance of 80 mm
• With vertical mounting,
reduce the load current by
30%. (Refer to the Load
Current vs. Ambient
Temperature graph.)
Note: Leave a distance of 60 mm min. between SSRs and ducts (especially above the SSR).
J-34Solid State Relays G3PA
Page 15
Close Mounting
SSR Mounting Pitch
Panel Mounting (At a rated ambient temperature of 40°C).
Duct or airflow obstruction
SSR
Mounting direction
Vertical direction
80 mm min.
Space between
SSRs
Close Mounting
min.
Relationship between SSRs and Ducts
Duct Height
Mounting surface
Do not surround the SSR
with ducts, otherwise the
heat radiation of the SSR
will be adversely affected.
Countermeasure (1)Countermeasure (2)
50 mm max.
Mounting surface
(A height of no
more than half
the SSR's height is
recommended.)
G3PA
Duct or
airflow
obstruction
G3PA
Vertical
direction
Duct or
airflow
obstruction
Use short ducts.
60 mm min.
Between duct
or airflow
obstruction
and SSR
30 mm min.
Mounting surface
If the ducts cannot be
shortened, place the SSR
on a metal base so that it
is not surrounded by the
ducts.
Airflow
An SSR uses a semiconductor in the output element. This causes
the temperature inside the control panel to increase due to heating
resulting from the passage of electrical current through the load. To
restrict heating, attach a fan to the ventilation outlet or air inlet of the
control panel to ventilate the panel. This will reduce the ambient
temperature of the SSRs and thus increase reliability. (Generally,
each 10 °C reduction in temperature will double the expected life.)
Load current (A)10 A20 A30 A40 A60 A
Required number of fans
0.160.310.470.620.93
per SSR
Example: For 10 SSRs with load currents of 20 A,
0.31 x 10 = 3.1
Thus, 4 fans would be required.
Size of fans: 92 mm
2
, Air volume: 0.7 m3/min,
Ambient temperature of control panel: 30 °C
If there are other instruments that generate heat in the control
panel other than SSRs, additional ventilation will be required.
G3PA
Ventilation
Be aware of air flow
Duct or
air flow
obstruction
G3PA
G3PA
Air inlet
If the air inlet or air outlet has a filter, clean the filter regularly to
prevent it from clogging and ensure an efficient flow of air.
Do not locate any objects around the air inlet or air outlet, otherwise
the objects may obstruct the proper ventilation of the control panel.
A heat exchanger, if used, should be located in front of the SSR Units
to ensure the efficiency of the heat exchanger.
Please reduce the ambient temperature of SSRs.
The rated load current of an SSR is measured at an ambient
temperature of 25 or 40 °C.
Ventilation
outlet
G3PA
SSR
Solid State RelaysG3PAJ-35
Page 16
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.