J-18 Solid State Relays G3NE
Ordering Information
■ List of Models
Note: When ordering, specify the input voltage.
■ Accessories (Order Separately)
Heat Sinks
The following heat sinks are thin and can be DIN-track mounted.
See Dimensions for details.
Specifications
■ Ratings (at an Ambient Temperature of 25°C)
Input
Note: Each model has 5-VDC, 12-VDC, and 24-VDC input versions.
Output
Note: 1. The load current varies depending on the ambient temperature. Refer to Load Current vs. Ambient Temperature under Engineering Data
for details.
2. These values apply when using a dedicated heat sink or a radiation plate of specified size.
Isolation Zero cross
function
Indicator Rated output load Rated input voltage Model
Phototriac Yes No 5 A at 100 to 240 VAC 5, 12, 24 VDC G3NE-205T-US
G3NE-205T-2-US
10 A at 100 to 240 VAC G3NE-210T-US
G3NE-210T-2-US
20 A at 100 to 240 VAC G3NE-220T-US
G3NE-220T-2-US
No 5 A at 100 to 240 VAC G3NE-205TL-US
G3NE-205TL-2-US
10 A at 100 to 240 VAC G3NE-210TL-US
G3NE-210TL-2-US
20 A at 100 to 240 VAC G3NE-220TL-US
G3NE-220TL-2-US
Model Applicable SSR
Y92B-N50 G3NE-205T(L)(-2)-US/-210T(L)(-2)-US
Y92B-N100 G3NE-220T(L)(-2)-US
Rated voltage Operating voltage Voltage level Input impedance
Must operate Must release With zero cross function Without zero cross function
5 VDC 4 to 6 VDC 4 VDC max. 1 VDC min. 250 Ω±20% 300 Ω±20%
12 VDC 9.6 to 14.4 VDC 9.6 VDC max. 600 Ω±20% 800 Ω±20%
24 VDC 19.2 to 28.8 VDC 19.2 VDC max. 1.6 kΩ±20%
Model Applicable load
Rated load voltage Load voltage range Load current
(See note 1.)
Inrush current
With heat sink Without heat sink
G3NE-205T(L)(-2)-US 100 to 240 VAC 75 to 264 VAC 0.1 to 5 A 0.1 to 5 A 60 A (60 Hz, 1 cycle)
G3NE-210T(L)(-2)-US 0.1 to 10 A
(See note 2.)
0.1 to 5 A 150 A (60 Hz, 1 cycle)
G3NE-220T(L)(-2)-US 0.1 to 20 A
(See note 2.)
0.1 to 5 A 220 A (60 Hz, 1 cycle)