Omron G3FD, G3F-203SN-VD, G3F-202SN-VD, G3F-203S-VD, G3F-203SLN-VD User Manual

...
214 Solid State Relays G3@-VD G3F/G3FD
Solid State Relays G3@-VD
G3F/G3FD
Refer to Warranty and Application Considerations (page 1), Safety Precautions (page 4), and Technical and Safety Information (page 6).
International Standards for G3F Series, Same Profile as MY Power Relays
• Certified by UL, CSA, and VDE (model numbers wi th a suffix of “-VD”).
• Socket type, same size as MY Power Relays.
• Operation indicator provided to confirm input (model numbers with “N” before the suffix).
Model Number Structure
Mode l Number Legend
1. Basic Model Name
G3F: Solid State Relay
2. Rated Load Power Supply Voltage
2: 200 VAC
3. Rated Load Current
02: 2 A 03: 3 A
4. Terminal Type
S: Plug-in terminals
5. Zero Cross Function
Blank: Equipped with zero cross functions L: Not equipped with zero cross function
6. Operation Indicator
Blank: Not equipped with operation indicator N: Equipped with operation indicator
7. Certification
VD: Certified by UL, CSA, and VDE
1. Basic Model Name
G3F: Solid State Relay
2. Load Power Supply T ype
D: DC
3. Rated Load Power Supply Voltage
X: 50 VDC 1: 100 VDC
4. Rated Load Current
02: 2 A 03: 3 A
5. Terminal Type
S: Plug-in terminals
6. Operation Indicator
Blank: Not equipped with operation indicator N: Equipped with operation indicator
7. Certification
VD: Certified by UL, CSA, and VDE
1
2
34
56
7
G3F-@@@@@-@
1
2
34
56
7
G3FD-@@@@-@
Solid State Relays G3@-VD G3F/G3FD 215
Ordering Information
List of Models
Note: 1. Product is labelled “250 VAC”.
2. Product is labelled “50 VDC”.
3. When ordering, specify the rated input voltage.
Accessories (Order Separately)
Connecting Sockets
Refer to page 297 for details.
Specifications
Rati ngs (at an Ambient Temperature of 25°C)
Input
Isolation Zero cross
function
Indicator Rated output load Rated input voltage Model
Photocoupler Yes Yes 3 A at 100 to 240 VAC (See note 1.) 5 to 24 VDC G3F-203SN-VD
2 A at 100 to 240 VAC (See note 1.) 100/110 VAC G3F-202SN-VD
200/220 VAC
Phototriac coupler No 3 A at 100 to 240 VAC (See note 1.) 5 VDC G3F-203SLN-VD
12 VDC 24 VDC
Photocoupler 3 A at 4 to 48 VDC (See note 2.) 5 to 24 VDC G3FD-X03SN-VD
2 A at 5 to 110 VDC 100/110 VAC G3FD-102SN-VD
200/220 VAC
5 to 24 VDC Photocoupler Yes No 3 A at 100 to 240 VAC (See note 1.) 4 to 24 VDC G3F-203S-VD Phototriac coupler No 5 VDC G3F-203SL-VD
12 VDC
24 VDC Photocoupler 3 A at 4 to 48 VDC (See note 2.) 4 to 24 VDC G3FD-X03S-VD
2 A at 5 to 110 VDC G3FD-102S-VD
Item PYF08A-E PY08 PY08-02 PY08QN(2)
Connecting Front connecting Back connecting Mounting method/
Terminal type
Track mounted/ screw terminals
Solder terminals PCB terminals Wrapping terminals
Hold-down clip PYC-A1 PYC-P
Model Rated voltage Operating voltage Impedance Voltage level
Must operate voltage Must release voltage
G3F-203SN-VD 5 to 24 VDC 4 to 28 VDC 15 mA max. (See note.) 4 VDC max. 1 VDC min. G3F-202SN-VD 100/110 VAC 75 to 125 VAC 41 k
Ω±20% 75 VAC max. 20 VAC min.
200/220 VAC 150 to 250 VAC 72 k
Ω±20% 150 VAC max. 40 VAC min.