Omron F3S-B302P, F3S-B122P, F3S-B362P, F3S-B422P, F3S-B482P Instruction Manual

...
F3S-B Series Safety Light Curtain
Instruction Manual
Cat. No. E502-E2-01
F3S-B
3
Introduction
Thank you for purchasing the F3S-B series Safety Light Curtain. Always heed the following points when using the F3S-B:
Make sure that personnel operating the F3S-B are knowledgeable about the machine on which it is
installed
Read this manual completely and be sure you understand the information provided before attempting
to operate the F3S-B
Keep the manual in a secure and convenient location and refer to it as necessary.
Regulations and Standards
(1) The F3S-B has not received the type approval provided by Article 44-2 of the Industrial Safety and
Health Law of Japan. Therefore, it cannot be used in Japan as a safety device for pressing or shearing machines provided by article 42 of that law.
(2) The F3S-B is electro-sensitive protective equipment (ESPE) in accordance with European Union (EU)
Machinery Directive Annex IV, B. Safety Components, Item 1. The F3S-B complies with the following regulations and standards.
EU regulations and technical standards:
Machinery Directive: No. 98/37/EC EMC Directive: No. 89/336/EEC EN 61496-1 (06/98) (Type 2 ESPE), IEC 61496-2 (1997) (Type 2 AOPD)
IEC standards
IEC 61496-1 (1997) (Type 2 ESPE), IEC 61496-2 (1997) (Type 2 AOPD)
(3) The F3S-B received the following approvals from the EU accredited bodies.
- Certificate of a Notified Body for EC Type-Examination referred to in the EU Machinery Directive Annex IV, from TÜV Hannover/Sachsen-Anhalt e.V.
- Certificate of a Competent Body referred to in the EU EMC Directive, from Technischer Überwa­chungs-Verein Nord
(4) The F3S–B received the following approvals from the third–party testing laboratory UL.
– UL Listed (UL508, IEC61496-1 and –2) – UL Listed to Canadian safety standards (CSA C22.2 No. 14 and No.0.8, IEC61496-1 and –2) – Programmable system certificate (UL1998, IEC61496–1)
(5) The following standards are referenced when designing the F3S–B. To comply with these standards,
be sure to design and use in accordance with all regulations and standards related to them. Contact an expert agency such as TÜV and UL if any of the above points are unclear.
– EN415–4 – OSHA 29 CFR 1910. 212 – ANSI/RIA 15.06 (Risk reduction category : R2B)
Precaution on Safety
! General conventions for safe use
The following conventions are used for precautionary items in this manual in order to ensure safe and proper use of the F3S-B. Items listed here are critical for safety and must be heeded at all times.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
!
!!
!
Indicates prohibited actions.
F3S-B
4
WARNING
The F3S-B is a TYPE 2 Electro-sensitive protective equipment, intended to be used as or with the safety related part of control system to category 2,1, or B as defined in the European standard EN954-1. Do not use the F3S-B in category 3 or 4 systems. Do not use the F3S-B on machines that cannot be stopped by electrical control in case of an emergency. Install protective structures around the machine so that you must pass through the detection zone to reach a hazardous part of the machine (see “2-1 Installation Conditions”). Install the F3S-B so that some part of the operator’s body remains in the detection zone at all times when the operator works in a hazardous area (see “2-1 Installation Conditions”). Failure to do so may result in serious injury. A qualified person, as determined by local regulations, must confirm that installation, inspection and maintenance are implemented correctly. Always maintain the safety distance between the F3S-B and a hazardous part of a machines (see “2-1 Installation Conditions”). Do not install the F3S-B in a location affected by wall reflections (see “2-1 Installation Conditions”).
Do not short the output lines to the +24 V line. Doing so will cause the output to be always ON, creating a hazardous situation. Do not connect the F3S-B to a power supply with voltage higher than 24 VDC + 20 %. Do not connect the F3S-B to an AC power supply.
Be sure to conduct inspections regularly (see “6 Maintenance”). The F3S-B cannot be used in applications where hazardous projectiles may exit the protected zone. Do not disassemble, repair or modify the F3S-B. Do not use the F3S-B in flammable or explosive environments. DC power supply units must satisfy all of the conditions below so that the F3S-B can comply with the applicable standards IEC 61496-1 and UL 508.
The power supply voltage must be within rating (24 VDC ± 20 %).
The power supply is connected only to the F3S-B and to the devices related to the electro-sensitive
protective function of the F3S-B, such as a safety controller and muting sensors, and it has enough rated current for all the devices. The power supply is not connected to other devices or machines.
The power supply uses double or reinforced insulation between the primary and secondary circuits
The power supply has automatic reset characteristics (voltage drop) to protect overcurrent.
The power supply maintains an output holding time of at least 20 ms.
FG (frame ground terminal) must be connected to PE (protective earth) when using a commercially
available switching regulator.
The power supply must have output characteristics required for the power source for Class 2 Circuit
or Limited Voltage/Current Circuit as defined in UL508 (see “2-3-1 Remark”).
The power supply must conform to regulatory requirements and standards, regarding EMC and elec-
trical equipment safety, of the country where the F3S-B is installed and where machinery will be op­erated, for example: The EMC Directive (industrial environment) and the Low Voltage Directive in EU.
Do not use the F3S-B in a retroreflective configuration. Otherwise detection may fail.
F3S-B
5
Notice
For your safety, always pay attention to the following: # Installation Environment
Do not install the F3S-B in the following environments:
Areas exposed to intense interference light such as direct sunlight.
Areas with high-humidity where condensation is likely to occur.
Areas exposed to corrosive gases.
Areas exposed to vibration or shock levels higher than specification provisions.
Areas where the light curtain may come in direct contact with water.
Do not use radio equipment, such as cellular phones, walkie-talkies, or transceivers with high power,
near the F3S-B.
# Wiring and Mounting
Be sure to route the F3S-B cable separate from high-potential power lines or through an exclusive
conduit.
Be sure to turn OFF the power prior to wiring. Otherwise, the diagnostic function may prevent the
sensor from operating.
When using cables with a connector other than the F39-JB series cable, make sure the connector is
rated IP54 or higher.
The F3S-B will start operating in two seconds after the power is turned ON. Make sure that no op-
eration faults will occur in the control system during this time.
The emitter and receiver are to be mounted in parallel and facing one another.
# Loads must satisfy all the conditions below.
Is not short-circuited.
Is not used with current higher than the rating.
Is reinforced insulated or double insulated as shown in the following figure to prevent the output
from being subjected to a hazardous voltage when the load is a relay. The insulation shown in the figure below should insulate against hazardous voltage levels (230 VAC, etc.), not simply against 24 VDC.
Emitter
Receiver
Relay monitoring input
0 V
+24 V
Output
0 V
+24 V
Power supply unit
Reinforced insulation or double insulation
k1
Reinforced insulation or double insulation between the coil and contacts, between contacts
K1
Motor, etc.
Hazardous voltage level
k1
Hazardous voltage level
# Two control outputs must be used.
# The procedures of installation and inspection in this manual should be read carefully.
# Do not use any solvents such as paint thinners, benzene or acetone to clean the F3S-B because they
will dissolve resin and paint.
# Do not use screw-locking adhesives (screw lock) to secure the cap unit or connector cap screws be-
cause the adhesive may cause the resin to deteriorate and crack.
# The F3S-B can not detect transparent or semi-transparent materials.
# After unpacking the emitter and receiver, install them facing each other.
# Be sure to dispose of the F3S-B as industrial waste.
F3S-B
6
PRIOR TO USE
Make sure the following items were supplied with each F3S-B, contact your nearest OMRON representative or distributor if any item is missing.
F3S-B unit (emitter qty. 1, receiver qty. 1)
Mounting brackets (top and bottom) qty. 4
Sixteen M3 x 10 tapping screws
Four L-shaped brackets
Sixteen M3 washers
Mounting brackets (intermediate) qty. 2
(Supplied with types which have a protective height of 1050 mm or longer)
Mounting plates qty. 4
(Supplied with types which have a protective height of 1050 mm or longer)
Test Rod Ø 30 mm qty. 1
(Supplied with F3S-B2P and BM2P)
Instruction manual (this manual) qty. 1
(Supplied with F3S-BP and BMP)
Two M4×10 screws
Two M6×8 screws
Two L-shaped intermediate brackets
Two U-shaped intermediate brackets
F3S-B
7
TABLE OF CONTENTS
DESCRIPTION ................................................................................................................ Section 1 ............................ 8
1-1 Basics .................................................................................................................................................. 8
1-2 Features............................................................................................................................................... 8
1-3 Standard Functions.............................................................................................................................. 8
1-3-1 Start/restart interlock................................................................................................................ 8
1-3-2 Testing ..................................................................................................................................... 8
1-3-3 Instability Output ...................................................................................................................... 9
1-4 Optional Functions ............................................................................................................................... 9
1-4-1 Start Interlock........................................................................................................................... 9
1-4-2 Relay Monitoring ...................................................................................................................... 9
1-4-3 Blanking ................................................................................................................................... 9
1-5 Detection zone ................................................................................................................................... 10
1-6 Configuration variation ....................................................................................................................... 10
1-6-1 Stand-alone type.................................................................................................................... 10
1-6-2 Series connection types......................................................................................................... 11
1-7 Ratings and Performance .................................................................................................................. 12
1-8 Indicators ........................................................................................................................................... 13
1-9 Table of Types ................................................................................................................................... 14
1-10 Table of Response Time.................................................................................................................. 15
1-10-1 Stand-alone type................................................................................................................... 15
1-10-2 Series connection types........................................................................................................ 15
WIRING and MOUNTING ............................................................................................Section 2.......................... 16
2-1 Installation Conditions........................................................................................................................ 16
2-1-1 Detection Zone and Intrusion Path ........................................................................................ 16
2-1-2 Safety Distance...................................................................................................................... 16
2-1-3 Distance from Reflective Surfaces......................................................................................... 19
2-1-4 How to Prevent Mutual Interference ...................................................................................... 19
2-2 Dimensional Drawings ....................................................................................................................... 21
2-2-1 F3S-B..................................................................................................................................... 21
2-2-2 Mounting Bracket (Top and Bottom)...................................................................................... 25
2-2-3 Mounting Plate ....................................................................................................................... 25
2-2-4 Mounting Bracket (Intermediate) ........................................................................................... 26
2-3 Wiring................................................................................................................................................. 27
2-3-1 Power Supply Units and Loads.............................................................................................. 27
2-3-2 Wiring Diagram ...................................................................................................................... 28
2-3-3 Wiring Procedure ................................................................................................................... 29
ADJUSTMENT ................................................................................................................Section 3..........................30
3-1 Adjustment Procedure ....................................................................................................................... 30
3-2 Check List .......................................................................................................................................... 30
I/O CIRCUIT....................................................................................................................Section 4 .......................... 32
APPLICATIONS.............................................................................................................. Section 5..........................33
5-1 Application (1) .................................................................................................................................... 33
5-2 Application (2) .................................................................................................................................... 33
MAINTENANCE .............................................................................................................Section 6 .......................... 34
6-1 Daily Inspections................................................................................................................................ 34
6-2 Inspection Every Six Month ............................................................................................................... 34
6-3 Cleaning............................................................................................................................................. 34
ACCESSORIES (OPTIONAL) ....................................................................................... Section 7 ..........................35
TROUBLESHOOTING................................................................................................... Section 8 .......................... 36
F3S-B
8
DESCRIPTION Section 1
1-1 Basics
WARNING
Use the F3S-B only in category 2, 1, or B appli­cations as defined in pr EN 1050 or EN 954-1. Do not use the F3S-B in category 3 or 4 sys­tems.
The F3S-B Safety Light Curtain is a multi-axis transmissive-type light array which uses microprocessor technology.
It is used to stop a machine before the hazard is reached when any part of the detection zone is interrupted.
It consists of an IR (infrared) Emitter and a Re­ceiver. Optional devices are available for the sys­tem with further safety requirements.
1-2 Features
Self-test
Optical resolution of 30, 55 or 80 mm in diame-
ter
Detection distance from 0.3 to 5.0 m
Max. protective height of 1,650 mm
TÜV approvals and CE marking
UL listed to U.S. and Canadian safety standard
IP 65 enclosure rating
Start/restart interlock function selectable
Blanking, Start Interlock, Relay monitoring func-
tions optionally available
Series connection types available
1-3 Standard Functions
1-3-1 Start/restart interlock
This function keeps the F3S-B in the OFF-state after power ON and every interruption of the detection zone. To reset this condition, 17 VDC to Vs (nominal 24 VDC) must be applied to the Interlock selection input of the emitter for 15 to 2500 ms. Otherwise the OFF-state continues even if nothing interrupts the detection zone.
This function can be selected/deselected as follows; Active mode: By not connecting the Interlock selection input line or by connecting it to 0V line before turning the power ON. Inactive mode (Automatic start): By connecting the Interlock selection input line to the Instability output line before turning the power ON (see “2-3-2 Wiring diagram”).
Note: The switch to reset the start/restart interlock condition has to be installed out of the hazardous area.
When the start/restart interlock is reset, the hazardous area must be visibly free.
1-3-2 Testing
Self-test after Power-ON
After the power is turned ON, the F3S-B performs a complete self-test within 2 seconds. If no failure is found, the F3S-B goes into normal operation.
Self-test during Normal Operation
The F3S-B periodically checks all safety related functions at least every 2 seconds. All components and memories are tested in this periodic check.
F3S-B
9
External Test
If your application requires periodic testing more often than every 2 seconds an external control system is able to initiate an external test with the External test function. If a signal of 17 VDC to Vs is applied to the External test input at least 15 ms, a self-test starts and the outputs turn to the OFF­state in 15 ms. If no failure is detected, the outputs return to the ON-state after a maximum of 150 ms.
Failure detection and restoration
When a failure is detected through the tests above, the F3S-B keeps the outputs in the OFF-state and the indicators show the type of failure, refer to section “8 Troubleshooting”. After the failure is eliminated, in most cases the F3S-B operation will be restored automatically.
1-3-3 Instability Output
When the received light is insufficient, the instability output and the instability indicator turn ON. In normal operation, both are OFF. See also “1-8 Indicators”. This output makes it possible for customers to monitor deterioration of optical performance due to aging or other factor, such as reduction of LED power, misalignment between the emitter and receiver, or dust on the lens. Also, when a failure is detected, or the F3S-B is connected with the F39-E1 interface unit, the instability output turns ON as well.
Note: After the power is turned ON, the instability
output goes to the ON-state for approxi­mately 150 ms as shown in the timing chart for Interlock mode selection.
1-4 Optional Functions
These functions can be activated by the optional function software, F39-U1E (see the F39-U1E manual for detailed information).
Note: The F39-U1E Optional Function Software is used with the F39-E1 Interface Unit, a PC (running
Microsoft
Windows
95, Windows98 or Windows NT
), the F39-JB1C Interface Cable, and a RS-
232C cable.
1-4-1 Start Interlock
When the Start interlock function is used, the F3S-B does not go to the ON-state automatically after power ON. Interrupting one or more axes resets the start interlock condition, so the F3S-B can start normal op­eration.
1-4-2 Relay Monitoring
MPCEs (Machine Primary Control Elements) are usually relays or contactors used to control hazardous movement directly. The state of the MPCEs can be checked with the Relay monitoring function. A voltage of 17 VDC to Vs has to be applied to the Relay monitoring input through the NC contacts of the MPCEs when the F3S-B control outputs are in the OFF-state (see “2-3-2 Wiring diagram”). To ensure this logic relation, the MPCEs must be safety approved types, with forcibly guided contacts.
1-4-3 Blanking
With this function, one or more axes can be disabled. To select the blanking axes, a manual setting func­tion or teaching function is available. This function is useful when part of the F3S-B detection zone is inter­rupted.
External test in
p
ut
Control out
p
uts
H
H
L
(open)
L
(open)
> 15 ms
Approx. 15 ms
150 ms max.
Power supply
Instability output
H
H
L
L
Approx. 150 ms
Approx. 30 ms
2 s max.
(Startup waiting time)
F3S-B available
F3S-B
10
1-5 Detection zone
Protective height
The F3S-B can detect in the area indicated by “Protective height” in the figure below. The protective height is from “the Optical-axis line mark above the indicator area” to “the end of the yellow metal case”.
Optical-axis line mark
The center line for optical axes is indicated by the triangle mark. This position is a reference line for meas­uring safety distance.
Emitter
Receiver
Optical-axis pitch
1
n-1
n
2
Optical resolution
No. of optical axes
Protective height
Limit position for detection
Detection distance
Optical-axis line mark
1-6 Configuration variation
1-6-1 Stand-alone type
This is the most common configuration, and it is used to protect a hazardous part of a machine when ap­proached from one direction only.
Receiver
Emitter
Indicator area
Extension cable
Protective height
F3S-B
11
1-6-2 Series connection types
When your application requires an additional pro­tective zone, for example, to prevent someone from staying behind a primary detection zone, the F3S-B may be connected in series. The system consists of a master unit, a slave unit, and a series connection cable, type F39-JB1B (refer to “2-3-2 Wiring diagram” and “7 Accessories (Optional)”). The series connection allows up to 96 axes and
2.4 m of protective height in total.
Series connection types have the same character­istics as a stand-alone types. When the detection zone of the master unit or that of the slave unit is interrupted, the outputs of the master unit go to the OFF-state. However, please note that a slave unit does not have indicators.
Note: Both the master unit and the slave unit need
to be ordered separately.
Protective height
Slave unit
Master unit
Series connection cable
Extension cable
Protective height
Indicator area
Emitters
Receivers
F3S-B
12
1-7 Ratings and Performance
Type
Item
F3S-BP (*1)
Stand-alone
F3S-BMP (*1) Master unit for series connection
F3S-BS (*1) Slave unit for series connection
No. of optical axes
12 to 66 6 to 33 4 to 22 12 to 66 6 to 33 4 to 22 12 to 30 6 to 15 4 to10
Optical-axis pitch
25 mm 50 mm 75 mm 25 mm 50 mm 75 mm 25 mm 50 mm 75 mm Non-transparent:  in diameter
Optical resolution
(Detection capability)
30 mm 55 mm 80 mm 30 mm 55 mm 80 mm 30 mm 55 mm 80 mm
Protective height
300 / 450 / 600 / 750 / 900 / 1,050 / 1,200 / 1,350 / 1,500 / 1,650 mm
300 / 450 / 600 / 750 mm
Detection distance
0.3 to 5.0 m
Response time
ON to OFF : See “1-10 Table of Response Time” OFF to ON (*2): Default 100 ms (selectable with F39-U1E, 80 to 400 ms)
Startup waiting time
2 s max.
Supply voltage: Vs
24 VDC ± 20% (including 5 Vp-p ripple)
Current consumption
400 mA max. (under no-load conditions)
Light source
Infrared LED (880 nm wavelength). Lifetime: 50,000 hrs. at 25 °C.
Effective aperture angle
Within ± 5° for the emitter and receiver at a detection distance of at least 3 m according to IEC 61496-2
Operating mode
Light ON
Control output
Two PNP transistor outputs, operational current (load current) 200 mA max., re­sidual voltage 2 V max. (except for voltage drop due to cable extension)
Instability output
PNP transistor output (not safety-related control output), load current 100 mA max., residual voltage 2 V max. (except for voltage drop due to cable extension)
Protection circuit
Output short-circuit protection, power supply reverse connection protection Mode selection before power ON by connecting “Interlock selection input” line to:
Active : No connection or 0 to 2.5 VDC, 3 mA max. Inactive : Instability output line Reset of start/restart interlock by connecting “Interlock selection input” line to:
Start/restart interlock function
Interlock reset : 17 VDC to Vs, 20 mA max. Duration time 15 to 2,500 ms Mode selection by connecting “External test input” line to: Active : 17 VDC to Vs, 10 mA max. Duration time at least 15 ms
External test function
Inactive : No connection or 0 to 2.5 VDC, 2 mA max. Default inactive, selectable with F39-U1E Relay monitoring input line with NC contact connected, Available level : 17 VDC to Vs, 10 mA max. Allowed relay delay time (*2) : Selectable between 20 and 300 ms
Relay monitoring function (Optional)
Termination when not selected : No connection or 0 to 2.5 VDC, 2 mA max.
Start interlock function (Optional)
Default inactive, selectable with F39-U1E
Blanking function (Optional)
Default inactive, selectable with F39-U1E
Indicators
See “1-8 Indicators” No indicators For Extension cable : 8 pins, M12 connector
Connection method
For Series connection cable : 6 pins, M12 connector
Ambient temperature
During operation : –10 to 55 °C (with no freezing) During storage : –25 to 70 °C
Ambient humidity
During operation : 35 to 85 %RH (with no condensation) During storage : 35 to 95 %RH
Insulation resistance
20 M min. (at 500 VDC)
Dielectric strength voltage
1,000 VAC 50/60 Hz for 1 min