Omron EJ1G-TC2A-QNH, EJ1G-TC4B-QQ, EJ1G-TC2B-QNH, EJ1G-TC4A-QQ, EJ1G-HFUA-NFLK Datasheet

...
Modular Temperature Controller for Gradient Temperature Control EJ1G 1
Modular Temperature Controller for Gradient Temperature Control
EJ1G
Gradient Temperature Control to Achieve Consistent Layer Temperature
• Perform gradient temperature control ranging from 2 to 32 channels.
• Set gradient temperature control or 2-PID control for each group.
• Reduce design work for ladder programming with programless connections to Programmable Controllers. (The same feature as Standard-control EJ1 Models.)
• Connect directly to the G3ZA Multi-channel Power Controller using optimum cycle control for high-accuracy control with minimal noise.
Refer to the “Safety Precautions” on page 18.
Ordering Information
Temperature Controllers
Gradient Temperature Control
Note: 1. An End Unit is required to connect an HFU to a Basic Unit. A Gradient Temperature Control HFU and a Gradient Temperature Control
Basic Unit must be used together to achieve gradient temperature control. The Gradient Temperature Control HFU and Gradient Temperature Control Basic Unit are used exclusively for gradient temperature control, but the End Unit is the same as that used for the Standard-control EJ1 Models. The Basic Unit cannot communicate externally by itself.
2. Heating/cooling control is not supported for gradient temperature control.
3. When using the heater burnout alarm, use a Current Transformer (E54-CT1 or E54-CT3) (sold separately).
Name Power
supply
voltage
No. of
con-
trol
points
Control outputs 1 and 2
Control outputs 3 and 4
Auxiliary
output
Functions Communications
functions
Input type Terminal Model
Heater
burnout
alarm
Event
inputs
Basic Unit (gradient tempera­ture control) (See note
1.)
24 VDC supplied from the End Unit
2 Voltage
output: 2 points (for SSR drive) (See note
2.)
Transistor output: 2 points (sourcing)
None 2
(See note 3.)
None G3ZA connection
port: RS-485 From End Unit:
Por t A : R S- 48 5
Thermocou­ple, platinum resistance thermometer, analog voltage, and analog current select­able for each channel.
M3 terminal EJ1G-TC2A-QNH
Screw-less clamp
EJ1G-TC2B-QNH
4 Voltage out-
put: 2 points (for SSR drive) (See note 2.)
None M3 terminal EJ1G-TC4A-QQ
Screw-less clamp
EJ1G-TC4B-QQ
HFU (gradient tempera­ture con­trol) (See note
1.)
None None None Transistor
output: 4 points (sourcing)
4 From End Unit:
Por t A : R S- 48 5 Port C: RS-485 or RS-232C selectable.
No input M3 terminal EJ1G-HFUA-NFLK
Screw-less clamp
EJ1G-HFUB-NFLK
From End Unit: Por t A : R S- 48 5
Port C: RS-422
M3 terminal EJ1G-HFUA-NFL2
Screw-less clamp
EJ1G-HFUB-NFL2
End Unit (See note
1.)
24 VDC Transistor
output: 2 points (sourcing)
None Port A: RS-485
Connector: Port A
M3 terminal EJ1C-EDUA-NFLK
Refer to the following manual for precautionary information and other information necessary to use the EJ1G: EJ1G Modular Temperature Controller Operation Manual (Cat. No. H143)
2 Modular Temperature Controller for Gradient Temperature Control EJ1G
Accessories (Order Separately)
Current Transformer (CT)
G3ZA Connecting Cable
Rail Mounting Equipment
CX-Thermo Support Software Ver. 3.1
Note: CX-Thermo Support Software version 3.2 (available soon) is
required to set the EJ1G Modular Temperature Controller for Gradient Temperature Control.
USB-Serial Conversion Cable
Specifications
Ratings
Note: Inputs are fully multi-input. Therefore, platinum resistance thermometer, thermocouple, infrared thermosensor, and analog input can be
selected.
Diameter Model
5.8 dia. E54-CT1
12.0 dia. E54-CT3
Cable length Model
5 m EJ1C-CBLA050
Name Model
Mounting Rail PFP-100N
PFP-50N
Model
EST2-2C-MV3
Model
E58-CIFQ1
Basic Unit/EJ1G-TC
Item Type EJ1G-TC4 EJ1G-TC2
Power supply voltage 24 VDC
Operating voltage range 85% to 110% of rated voltage
Power consumption 5 W max. (at maximum load) 4 W max. (at maximum load)
Input (See note.) Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII
ES1B Infrared Thermosensor: 10 to 70
°C, 60 to 120°C, 115 to 165°C, 140 to 260°C
Analog input: 4 to 20 mA, 0 to 20 mA, 1 to 5 V, 0 to 5 V, 0 to 10 V Platinum resistance thermometer: Pt100, JPt100
Input impedance Current input: 150
max., voltage input: 1 M min.
Control outputs
Vol t a g e o u tput Output voltage: 12 VDC
±15%, max. load current: 21 mA (PNP models with short-circuit protection circuit)
Transistor output --- Max. operating voltage: 30 V, max. load current: 100 mA
Number of input and control points
Input points: 4, Control points: 4 Input points: 2, Control points: 2
Setting method Via communications
Ambient temperature range Operating:
10°C to 55°C, Stored: 25°C to 65°C (with no icing or condensation)
Ambient humidity range Operating: 25% to 85% (with no condensation)
Modular Temperature Controller for Gradient Temperature Control EJ1G 3
Characteristics
Note: 1. The indication of K thermocouples in the 200 to 1,300°C range, T and N thermocouples at a temperature of 100°C or less, and U and
L thermocouples at any temperature is
±2°C ±1 digit maximum. The indication of B thermocouples at a temperature of 400°C or less is
unrestricted. The indication of R and S thermocouples at a temperature of 200
°C or less is ±3°C ±1 digit max.
W = (
±0.5% of indication value (PV) or ±3°C, whichever is greater) ±1 digit max. PLII = (±0.5% of indication value (PV) or ±2°C, whichever
is greater)
±1 digit max.
2. Ambient temperature:
10°C to 23°C to 55°C
Voltage range:
15% to +10% of rated voltage
3. “EU” stands for Engineering Unit. The location of the decimal point depends on the setting of decimal point position B. If the decimal point location is set to 0 (****), however, it will be treated as if it were set to 1 (***.*).
4. B, R, and S sensors: 0.2
°C/ max. (100 max.)
Indication accuracy Thermocouple input/platinum resistance thermometer input:
(
±0.5% of indication value (PV) or ±1°C, whichever is greater) ±1 digit max. (See note 1.)
Analog input:
±0.5% FS ±1 digit max.
CT input:
±5% FS ±1 digit max.
Temperature variation influence (See note 2.)
Thermocouple input (R, S, B): (
±1% of indication value (PV) or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: (
±1% of indication value (PV) or ±4°C, whichever is greater) ±1 digit max.
K thermocouple at
100°C max: ±10°C max.
Platinum resistance thermometer: (
±1% of indication value (PV) or ±2°C, whichever is greater) ±1 digit max.
Analog input:
±1% FS ±1 digit max.
Voltage variation influence (See note 2.)
Proportional band (P) 0.1 to 999.9 EU (in units of 0.1 EU) (See note 3.)
Integral time (I) 1 to 3,999 s (in units of 1 s)
Derivative time (D) 0.0 to 999.9 s (in units of 0.1 s)
Control period 0.5 s, 1 to 99 s (in units of 1 s)
Alarm output setting range
1,999 to 9,999 (The location of decimal point depends on the setting of decimal point position B.)
Sampling period 250 ms
Influence of signal source resistance
Thermocouple: 0.1
°C (0.2°F)/ max. (100 max per line) (See note 4.)
Platinum resistance thermometer: 0.4
°C (0.8°F)/ max. (10 max per line)
Insulation resistance 20 M
min. (at 500 VDC)
Dielectric strength 600 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity
Vibration resistance
10 to 55 Hz, 20 m/s
2
for 2 hours each in X, Y, and Z directions
Shock resistance
150 m/s
2
max., 3 times each in 6 directions
Weight 180 g
Degree of protection Rear case: IP20, Terminal section: IP00
Memory protection EEPROM (non-volatile memory) (number of writes: 100,000)
Standards Approved standards UL61010C-1, CSA C22.2 No.1010-1
Conformed standards
EN61010-1 (IEC61010-1): Pollution level 2, overvoltage category II
EMC Directive EMI: EN61326
EMI Radiated: EN55011 Group1 class A EMI Conducted: EN55011 Group1 class A EMS: EN61326 ESD Immunity: EN61000-4-2 Radiated Electromagnetic Field Immunity: EN61000-4-3 Burst immunity/Noise Immunity: EN61000-4-4 Conducted Disturbance Immunity: EN61000-4-6 Surge Immunity: EN61000-4-5 Commercial Frequency Immunity: EN61000-4-8 Voltage Dip/Interrupting Immunity: EN61000-4-11
4 Modular Temperature Controller for Gradient Temperature Control EJ1G
Communications Specifications
Note: 1. Connection from the EJ1C-EDU
2. A special cable (EJ1C-CBLA050) must be purchased separately for the G3ZA connection.
3. For the number of Units that can be connected, refer to “Connection Precautions” on page 9.
4. When performing gradient temperature control, the number of control channels is limited by the group setting. For details, refer to
“Gradient Group Settings” on page 11.
Current Transformer (CT) Rating
Characteristics of the Heater Burnout Alarm and Heater Short Alarm (TC2 Models Only)
Note: 1. When the control output ON time is 100 ms or less, heater
burnout detection and heater current measurement are not performed.
2. When the control output OFF time is 100 ms or less, heater short alarm and leakage current measurement are not performed.
Item Port A Terminal/ Port A Connector
(See note 1.)
G3ZA Connection Port
(See note 2.)
Transmission path connection RS-485 (multipoint)
Communications method RS-485 (two-wire, half duplex)
Synchronization method Star t-stop synchronization
Baud rate 38.4 kbps fixed 57.6 kbps fixed
Transmission code ASCII
Data bit length 7 bits
Stop bit length 2 bits
Error detection Vertical parity (even)
Block check character (BCC): with CompoWay/F
Flow control
None
Interface RS-485
Retry function
None
Communications response wait time 1 to 99 ms (default: 1 ms) ---
Number of Units that can be connected in parallel (See notes 3 and 4.)
16 Units (model numbers with TC4: 64 channels, model numbers with TC2: 32 channels) Communications connection via port A on the End Unit
8 Units (Communications connection via G3ZA port on the Basic Unit)
Dielectric strength
1,000 VAC for 1 min
Vibration resistance
50 Hz, 98 m/s
2
Weight E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g
Accessories (E54-CT3 only)
Armatures (2), plugs (2)
Maximum heater current
100 A AC
Input current indication accuracy
±5%FS ±1 digit max.
Heater burnout alar m setting range
0.1 to 99.9 A (in units of 0.1 A)
0.0 A: Heater burnout alarm output turns OFF.
100.0 A: Heater burnout alarm output turns ON. Min. detection ON time: 100 ms (See note 1.)
Heater short alarm setting range
0.1 to 99.9 A (in units of 0.1 A)
0.0 A: Heater short alarm output turns ON.
100.0 A: Heater short alarm output turns OFF. Min. detection OFF time: 100 ms (See note 2.)
Modular Temperature Controller for Gradient Temperature Control EJ1G 5
Input Ranges
Sensor inputs are fully multi-input. Therefore, platinum resistance thermometer, thermocouple, infrared thermosensor, and analog input can be selected. Inputs can be set for each channel using multi-inputs.
Input type Platinum resistance
thermometer
Name Pt100 JPt100
Tem ­pera­ture range (
°C)
2300
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
100.0
200.0
850
500.0 500.0
100.0 1 00.0
0.0 0.0
200 199.9 199.9
Setting number
01234
Input type Thermocouple ES1B Infrared
Thermosensor
Analog input
Name K J T E L U N R S B W PL
II
10 to 70 °C
60 to
120
°C
115
to
165
°C
140
to
260
°C
4 to
20
mA
0 to
20
mA
1 to
5 V
0 to
5 V
0 to
10 V
Tem ­pera­ture range (
°C)
2300
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
100.0
200.0
2300
Any of the following ranges, by scaling:
1999 to 9999
199.9 to 999.9
19.99 to 99.99
1.999 to 9.999
1800
1700 1700
1300 1300 1300
850 850
600
500.0
400.0 400 400.0 400 400.0
260
120 165
90
100
0 00 000000
20.0 100 20.0 100
200 200 199.9 200 199.9 −200
Setting number
5 6 7 8 9 1011121314151617181920212223242526272829
Applicable standards by input type are as follows: K, J, T, E, N, R, S, B: JIS C1602-1995, IEC584-1 L: Fe-CuNi, DIN 43710-1985 U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990 PL II: According to Platinel II Electromotive Force
Table by Engelhard Cor p. JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997 IEC 751
Shaded ranges indicate default settings.
6 Modular Temperature Controller for Gradient Temperature Control EJ1G
Ratings
Note: 1. Auxiliary outputs can be allocated using auxiliary output allocations.
2. Allocated using the digital input allocation function.
Characteristics
EJ1G-HFU
Power supply voltage 24 VDC
Operating voltage range 85% to 110% of rated voltage
Power consumption 2 W max. (at maximum load)
Auxiliary outputs (See note 1.)
Outputs 4
Transistor outputs Max. operating voltage: 30 VDC, Max. load current: 50 mA
Event inputs (See note 2.)
Inputs 4
Inputs with contacts ON: 1 k
max., OFF: 100 k min.
Inputs without contacts ON: Residual voltage of 1.5 V max., OFF: Leakage current of 0.1 mA max.
Short-circuit current: Approx. 4 mA (per contact)
Programless connection
Programless downloading (EJ1G writes data to a PLC)
Number of parameters that can be set: 300
Programless uploading (EJ1G reads data from a PLC)
Number of parameters that can be set: 300
Applicable PLCs OMRON: SYSMAC CS/CJ Series, Mitsubishi Electric: MELSEC-Q/QnAS Series
Control method 2-PID control (with autotuning), gradient temperature control (with gradient tuning function)
Other functions 2-point input shift, SP ramp, manual manipulated variable, manipulated variable limiter,
interference overshoot adjustment, heater burnout alarm, RUN/STOP, banks, I/O allocations, etc.
Ambient temperature range Operating:
10°C to 55°C
Storage:
25°C to 65°C (with no icing or condensation)
Ambient humidity range Operating: 25% to 85% (with no condensation)
Insulation resistance 20 M
min. (at 500 VDC)
Dielectric strength 600 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity
Vibration resistance
10 to 55 Hz, 20 m/s
2
for 2 hours each in X, Y, and Z directions
Shock resistance
150 m/s
2
max., 3 times each in 6 directions
Weight 160 g
Degree of protection Rear case: IP20, Terminal section: IP00
Memory protection EEPROM (non-volatile memory) (number of writes: 100,000)
Standards Approved standards UL61010C-1, CSA C22.2 No.1010-1
Conformed standards EN61010-1 (IEC61010-1): Pollution level 2, overvoltage category II
EMC Directive Refer to page 3.
Modular Temperature Controller for Gradient Temperature Control EJ1G 7
Communications Characteristics: Port C
Communications are not possible from port B on the End Unit. A connection is made between ports B when using distributed placement.
Note: 1. The communications method can be switched between RS-485 and RS-232C. Another model must be used for RS-422 communications.
2. For the number of Units that can be connected, refer to “Connection Precautions” on page 9.
3. When performing gradient temperature control, the number of control channels is limited by the group setting. For details, refer to “Gradient Group Settings”
on page 11.
Ratings
Characteristics
Communications
Note: Port A connector communications and port A terminal communications cannot be used at the same time.
Transmission path connection RS-485/RS-422: Multi-point, RS-232C: Point-to-point (See note 1.)
Communications method RS-485/RS-422 (two-wire, half duplex), RS-232C
Synchronization method Start-stop synchronization
Baud rate 9.6, 19.2, 38.4, 57.6, or 115.2 kbps
Transmission code ASCII
Data bit length 7 or 8 bits
Stop bit length 1 or 2 bits
Error detection Vertical parity (none, even, or odd)
Block check character (BCC) with CompoWay/F
Flow control None
Interface RS-485, RS-422, RS-232C (See note 1.)
Retry function None
Communications response wait time 1 to 99 ms (default: 5 ms)
Number of Units that can be connected in parallel (See notes 2 and 3.)
16 Units (model numbers with TC4: 64 channels, model numbers with TC2: 32 channels)
End Unit/EJ1C-EDU
Power supply voltage 24 VDC
Operating voltage range 85% to 110% of rated voltage
Auxiliary output Outputs 2
Transistor outputs Max. operating voltage: 30 VDC, Max. load current: 50 mA
Ambient temperature range Operating:
10°C to 55°C
Storage:
25°C to 65°C (with no icing or condensation)
Ambient humidity range Operating: 25% to 85% (with no condensation)
Insulation resistance 20 M
min. (at 500 VDC)
Dielectric strength 600 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity
Vibration resistance
10 to 55 Hz, 20 m/s
2
for 2 hours each in X, Y, and Z directions
Shock resistance
150 m/s
2
max., 3 times each in 6 directions
Weight 70 g
Degree of protection End Unit case: IP20, Terminal section: IP00
Standards Approved standards UL61010C-1, CSA C22.2 No.1010-1
Conformed standards EN61010-1 (IEC61010-1): Pollution level 2, overvoltage category II
EMC Directive Same as for the Basic Unit. Refer to page 3.
Por t A Basic Unit Communications (Refer to “Communications Specifications” on page 4.)
Port A connector (See note.) E58-CIFQ1
8 Modular Temperature Controller for Gradient Temperature Control EJ1G
Unit Configuration Example
Basic Configuration for Gradient Temperature Control
Systems can be built with host PLCs using programless communications.
Distributed placement is possible by using multiple EJ1C-EDU End Units.
Basic Configuration for Connection to G3ZA Multi-channel Power Controllers
Up to 8 G3ZA Controllers can be connected to each Basic Unit.
COM1 COM2 COM3
PWR RUN ERR ALM
SW1
ON
SW2
21345678
EJ1-TC4
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
COM1 COM2 COM3
PWR RUN ERR ALM
SW1
ON
SW2
21345678
EJ1-TC4
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
COM1 COM2 COM3
PWR RUN ERR ALM
SW1
ON
SW2
21345678
EJ1-TC4
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
COM1 COM2 COM3
PWR RUN ERR ALM
SW1
ON
SW2
21345678
EJ1-HFU
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
GTC
PC
EJ1G-HFU
PLC
EJ1G-TC4
or
EJ1G-TC2 EJ1C-EDU
Por t B
Use port B for configurations with distributed placement.
Port A (connector): USB connection can be made with the E58-CIFQ1 (sold separately).
CX-Thermo for setting
Por t C
SW2
SW1
ERROR
OCC
SD/RD
READY
SW2
SW1
ERROR
OCC
SD/RD
READY
SW2
SW1
ERROR
OCC
SD/RD
READY
PC
COM1 COM2 COM3
PWR RUN ERR ALM
SW1
ON
SW2
21345678
EJ1-TC4
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
COM1 COM2 COM3
PWR RUN ERR ALM
SW1
ON
SW2
21345678
EJ1-TC4
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
COM1 COM2 COM3
PWR RUN ERR ALM
SW1
ON
SW2
21345678
EJ1-TC4
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
COM1 COM2 COM3
PWR RUN ERR ALM
SW1
ON
SW2
21345678
EJ1-HFU
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
GTC
G3ZA G3ZAG3ZA
EJ1G-HFU
PLC
EJ1G-TC4
or
EJ1G-TC2 EJ1C-EDU
Por t B
Use port B for configurations with distributed placement.
Port A (connector): USB connection can be made with the E58-CIFQ1 (sold separately).
CX-Thermo for setting
G3ZA connecti­on port
G3ZA connection port
Por t C
G3ZA connection port