Ambient temperatureOperating/Storage: −25 to 70°C (with no icing or condensation)
Ambient humidityOperating/Storage: 35% to 95% (with no condensation)
Temperature influence±10% max. of sensing distance at 23°C in the temperature range of −25 to 70°C
Voltage influence±1% max. of sensing distance at rated voltage in the rated voltage ±15% range
Insulation resistance50 MΩ min. (at 500 VDC) between current-carrying parts and case
Dielectric strength1000 VAC, 50/60 Hz for 1 minute between current-carrying parts and case
Vibration resistance
(destruction)
Shock resistance
(destruction)
Degree of protectionIEC IP67, in-house standard for oil resistance
Connection methodPre-wired Models (Standard cable length: 2 m)
Weight (packed state)Approx. 65 gApprox. 150 gApprox. 210 g
Materials
AccessoriesInstruction sheet
*1. Use the E2E2 within the range in which the setting indicator (green LED) is ON (except D2 Models).
*2. The response frequency is an average value. Measurement conditions are as follows: standard sensing object, a distance of twice the standard sensing object, and
a set distance of half the sensing distance.
Switching
capacity
Residual voltage 3 V max. (Load current: 100 mA, Cable length: 2 m)
CaseBrass
Sensing surface PBT
Clamping nutsNickel-plated brass
Toothed washer Zinc-plated iron
Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to Engineering Data on
page 5.)
Iron,
12 × 12 × 1 mm
1 kHz800 Hz500 Hz400 Hz100 Hz
12 to 24 VDC (10 to 30 VDC), ripple (p-p): 10% max.
Ambient temperatureOperating/Storage: −40 to 85°C (with no icing or condensation)
Ambient humidityOperating/Storage: 35% to 95% (with no condensation)
Temperature influence
Voltage influence±1% max. of sensing distance at rated voltage in the rated voltage ±15% range
Insulation resistance50 MΩ min. (at 500 VDC) between current-carrying parts and case
Dielectric strength1,000 VAC, 50/60 Hz for 1 minute between current carry parts and case
Vibration resistance
(destruction)
Shock resistance
(destruction)
Degree of protectionIEC IP67, in-house standard for oil resistance
Connection methodPre-wired Models (Standard cable length: 2 m) and Connector Models
Weight (packed state)Approx. 75 gApprox. 160 gApprox. 220 g
Materials
AccessoriesInstruction sheet
*1. The response frequency is an average value. Measurement conditions are as follows: standard sensing object, a distance of twice the standard sensing object, and
a set distance of half the sensing distance.
*2. A full-wave rectification power supply of 24 VDC
Load currentNPN open-collector output, 200 mA max. (55 VDC max.)
Residual voltage 2 V max. (Load current: 200 mA, Cable length: 2 m)
CaseBrass
Sensing surface PBT
Clamping nutsNickel-plated brass
Toothed washer Zinc-plated iron
Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to Engineering Data on
page 5.)
Iron,
12 × 12 × 1 mm
12 to 24 VDC (10 to 55 VDC), ripple (p-p): 10% max.
C1 Models: NO
C2 Models: NC
±15% max. of sensing distance at 23°C in the temperature range of −40 to 85°C
±10% max. of sensing distance at 23°C in the temperature range of −25 to 70°C
10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions
1,000 m/s
M12M18M30
Iron,
15 × 15 × 1 mm
400 Hz600 Hz200 Hz400 Hz100 Hz
Refer to the timing charts under I/O Circuit Diagrams on page 8 for details.
Set distance0 to 1.6 mm0 to 4 mm0 to 4 mm0 to 8 mm0 to 8 mm0 to 14 mm
Differential travel10% max. of sensing distance
Sensing object
Standard sensing object
Response frequency
Power supply voltage (operating voltage range) *1
Leakage current1.7 mA max.
Control
output
IndicatorsOperation indicator (red)
Operation mode
(with sensing object approaching)
Ambient temperature *1, 2Operating/Storage: −40 to 85°C (with no icing or condensation)
Ambient humidityOperating/Storage: 35% to 95% (with no condensation)
Temperature influence
Voltage influence±1% max. of sensing distance at rated voltage in the rated voltage ±15% range
Insulation resistance50 MΩ min. (at 500 VDC) between current-carrying parts and case
Dielectric strength4,000 VAC, 50/60 Hz for 1 minute between current carry parts and case
Vibration resistance
(destruction)
Shock resistance
(destruction)
Degree of protectionIEC IP67, in-house standard for oil resistance
Connection methodPre-wired Models (Standard cable length: 2 m) and Connector Models
Weight (packed state)Approx. 65 gApprox. 150 gApprox. 210 g
Materials
AccessoriesInstruction sheet
*1. When supplying 24 VAC to any of the above models, make sure that the operating ambient temperature range is at least −25°C to 85°C.
*2. When using an M18 or M30 Connector Model at an ambient temperature between 70 and 85°C, make sure that the Sensor has a control output (load current) of 5
to 200 mA max.
Load current *25 to 200 mA5 to 300 mA
Residual voltage Refer to Engineering Data on page 5.
CaseBrass
Sensing surface PBT
Clamping nutsNickel-plated brass
Toothed washer Zinc-plated iron
Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to Engineering Data on
page 5.)
Iron,
12 × 12 × 1 mm
25 Hz
24 to 240 VAC (20 to 264 VAC), 50/60 Hz
Y1 Models: NO
Y2 Models: NC
±15% max. of sensing distance at 23°C in the temperature range of −40 to 85°C,
±10% max. of sensing distance at 23°C in the temperature range of −25 to 70°C
10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions
1,000 m/s
M12M18M30
Iron,
15 × 15 × 1 mm
Refer to the timing charts under I/O Circuit Diagrams on page 8 for details.
2
10 times each in X, Y, and Z directions
Iron,
18 × 18 × 1 mm
Iron,
30 × 30 × 1 mm
Iron,
30 × 30 × 1 mm
Iron,
54 × 54 × 1 mm
4
E2E2
Engineering Data
(Typical)
Sensing Area
Shielded Models
E2E2-X@D@E2E2-X@C@/-X@Y@
12
10
Distance X (mm)
8
6
4
Y
2
0
−20 −15 −10 −5 0 5 10 15 20
X
E2E2-X10
E2E2-X7
E2E2-X3
Distance Y (mm)
12
10
Distance X (mm)
8
6
4
2
0
−10−50 51015−15
Y
X
Unshielded Models
E2E2-X@MD@E2E2-X@MC@/-X@MY@
30
25
Distance X (mm)
20
15
10
5
E2E2
-X20M
E2E2
-X14M
Y
X
E2E2
-X8M
30
25
Distance X (mm)
20
15
10
5
Y
X
E2E2-X10
E2E2-X5
E2E2
-X2
Distance Y (mm)
E2E2-X18M
E2E2-X10M
E2E2-X5M
0
−20−100102030−30
Distance Y (mm)
0
−20−100102030−30
Distance Y (mm)
Leakage CurrentResidual Output Voltage
E2E2-X@D@E2E2-X@Y@E2E2-X@D@
1.0
0.8
0.6
Leakage current (mA)
0.4
0.2
0 5 10 15 20 25 30
Power supply voltage (V)
1.4
1.2
1.0
Leakage current (mA)
0.8
0.6
0.4
0.2
Proximity
Sensor (OFF)
0 50 100 150 200 250 300
Protective
resistance
mA
V
Power supply voltage (V)
AC
power
6
5
4
Residual output voltage (V)
3
2
1 3 5 10 30 50 100
Load current (mA)
5
E2E2
E2E2-X@Y@ at 24 VACE2E2-X@Y@ at 100 VACE2E2-X@Y@ at 200 VAC
This product is not designed or rated for
ensuring safety of persons either directly or
indirectly.
Do not use it for such purposes.
Sensing object
Operation indicator
(red)
Control output
Sensing object
Operation indicator
(red)
Control output
Not present
Not present
Present
ON
OFF
ON
OFF
Present
ON
OFF
ON
OFF
Proximity
Sensor
main
circuit
Brown
Blue
E2E2
Load
Precautions for Correct Use
Do not use this product under ambient conditions that exceed
the ratings.
● Design
Influence of Surrounding Metal
When mounting the Sensor within a metal panel, ensure that
the clearances given in the following table are maintained.
ModelItem
DC 2-Wire Models
E2E2-X@D@
DC 3-Wire Models
E2E2-X@C@
AC 2-Wire Models
E2E2-X@Y@
Shielded
Unshielded
Shielded
Unshielded
l000
d121830
D00 0
m82040
n182745
l152230
d407090
D152230
m204070
n407090
l000
d121830
D00 0
m82040
n182745
l152230
d405590
D152230
m204070
n365490
M12M18M30
l
m
(Unit: mm)
D
d dia.
n
m
l
9
E2E2
Mutual Interference
When installing Sensors face-to-face or
side-by-side, ensure that the minimum
distances given in the following table
A
are maintained.
Mutual Interference
ModelItem
A
Shielded
DC 2-Wire Models
E2E2-X@D@
Unshielded
DC 3-Wire Models
E2E2-X@C@
AC 2-Wire Models
E2E2-X@Y@
Note: Values in parentheses apply to Sensors operating at different frequencies.
Shielded
Unshielded
B
A
B
A3050100
B203570
A120200300
B100110200
M12M18M30
30
(20)
20
(12)
120
(60)
100
(50)
● Mounting
Tightening Torque
Do not tighten the nut with excessive force.
A washer must be used with the nut.
The following strengths assume washers are being used.
ModelTorque
M1230 N·m
M1870 N·m
M30180 N·m
50
(30)
35
(18)
200
(100)
110
(60)
Relationship between Sizes and
B
(Unit: mm)
100
(50)
70
(35)
300
(100)
200
(100)
Models
SizeModel
Shielded
M12
Unshielded
Shielded
M18
Unshielded
Shielded
M30
Unshielded
E2E2-X3D@
E2E2-X2C@
E2E2-X2Y@
E2E2-X8MD@
E2E2-X5MC@
E2E2-X5MY@
E2E2-X7D@
E2E2-X5C@
E2E2-X5Y@
E2E2-X14MD@
E2E2-X10MC@
E2E2-X10MY@
E2E2-X10D@
E2E2-X10C@
E2E2-X10Y@
E2E2-X20MD@
E2E2-X18MC@
E2E2-X18MY@
10
E2E2
S
(Unit: mm)
DimensionsUnless otherwise specified, the tolerance class IT16 is used for dimensions in this data sheet.
hieldedUnshielded
E2E2-X3D@/E2E2-X2C@/E2E2-X2Y@
21 dia.
17
4
M12 × 1
*1. 4-dia. vinyl-insulated round cable with 2 conductors
(Conductor cross section: 0.3 mm
Standard length: 2 m
4-dia. vinyl-insulated round cable with 3 conductors
(Conductor cross section: 0.3 mm
Standard length: 2 m
The cable can be extended to up to 200 m (Separate metal conduit.)
*2. D Models: Operation indicator (red) and setting indicator (green),
C/Y Models: Operation indicator (red)
60
55
10
Two clamping nuts
Toothed washer
E2E2-X7D@/E2E2-X5C@/E2E2-X5Y@
29 dia.
24
4
M18 × 1
*1. 6-dia. vinyl-insulated round cable with 2 conductors
(Conductor cross section: 0.5 mm
Standard length: 2 m
6-dia. vinyl-insulated round cable with 3 conductors
(Conductor cross section: 0.5 mm
Standard length: 2 m
The cable can be extended to up to 200 m (Separate metal conduit.)
*2. D Models: Operation indicator (red) and setting indicator (green),
C/Y Models: Operation indicator (red)
65
60
10
Two clamping nuts
Toothed washer
9
Indicators *2
2
, Insulator diameter: 1.3 mm),
2
, Insulator diameter: 1.3 mm),
12
Indicators *2
2
, Insulator diameter: 1.9 mm),
2
, Insulator diameter: 1.9 mm),
E2E2-X8MD@/E2E2-X5MC@/E2E2-X5MY@
21 dia.
17
*1
9 dia.
M12 × 1
*1. 4-dia. vinyl-insulated round cable with 2 conductors
(Conductor cross section: 0.3 mm
Standard length: 2 m
4-dia. vinyl-insulated round cable with 3 conductors
(Conductor cross section: 0.3 mm
Standard length: 2 m
The cable can be extended to up to 200 m (Separate metal conduit.)
*2. D Models: Operation indicator (red) and setting indicator (green),
C/Y Models: Operation indicator (red)
60
55
47
Two clamping nuts
Toothed washer
9
10
Indicators *2
2
, Insulator diameter: 1.3 mm),
2
, Insulator diameter: 1.3 mm),
*1
E2E2-X14MD@/E2E2-X10MC@/E2E2-X10MY@
29 dia.
24
*1
10
14.8 dia.
M18 × 1
*1. 6-dia. vinyl-insulated round cable with 2 conductors
(Conductor cross section: 0.5 mm
Standard length: 2 m
6-dia. vinyl-insulated round cable with 3 conductors
(Conductor cross section: 0.5 mm
Standard length: 2 m
The cable can be extended to up to 200 m (Separate metal conduit.)
*2. D Models: Operation indicator (red) and setting indicator (green),
C/Y Models: Operation indicator (red)
65
60
4
Two clamping nuts
Toothed washer
12
10
Indicators *2
2
, Insulator diameter: 1.9 mm),
2
, Insulator diameter: 1.9 mm),
*1
E2E2-X10D@/E2E2-X10C@/E2E2-X10Y@
42 dia.
36
5
M30 × 1.5
*1. 6-dia. vinyl-insulated round cable with 2 conductors
(Conductor cross section: 0.5 mm
Standard length: 2 m
6-dia. vinyl-insulated round cable with 3 conductors
(Conductor cross section: 0.5 mm
Standard length: 2 m
The cable can be extended to up to 200 m (Separate metal conduit.)
*2. D Models: Operation indicator (red) and setting indicator (green),
C/Y Models: Operation indicator (red)
70
65
Two clamping nuts
Toothed washer
10
2
, Insulator diameter: 1.9 mm),
2
, Insulator diameter: 1.9 mm),
12
Indicators *2
*1
E2E2-X20MD@/E2E2-X18MC@/E2E2-X18MY@
42 dia.
36
13
26.8 dia.
M30 × 1.5
*1. 6-dia. vinyl-insulated round cable with 2 conductors
(Conductor cross section: 0.5 mm
Standard length: 2 m
6-dia. vinyl-insulated round cable with 3 conductors
(Conductor cross section: 0.5 mm
Standard length: 2 m
The cable can be extended to up to 200 m (Separate metal conduit.)
*2. D Models: Operation indicator (red) and setting indicator (green),
C/Y Models: Operation indicator (red)
5
70
65
Two clamping nuts
Toothed washer
2
, Insulator diameter: 1.9 mm),
2
, Insulator diameter: 1.9 mm),
10
12
*1
Indicators *2
Mounting Hole Dimensions
Dimension
F (mm)
F
Note 1. Two clamping nuts and one toothed washer are provided with each Sensors.
2. The model number is laser-marked on the cable section and milled section.
M12M18M30
+0.5
12.5 dia.18.5 dia.30.5 dia.
0
+0.5
0
+0.5
0
In the interest of product improvement, specifications are subject to change without notice.
11
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
•
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
•
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
•
Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2009 All Right Reserved.
2009.1
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.