187
Unit Descriptions
DeviceNet Wireless Link
WD30
■ Wireless Interface Specifications
Note: 1. The actual transmission distance depends on many factors in the installation environment.
2. The wireless system is not suitable for applications requiring real-time control.
■ DeviceNet Interface Specifications (Summary)
Note: FINS message communications are not supported. Explicit messages must be handled in the ladder program. Refer to the WD30 DeviceNet
Wireless Units Operation Manual for details.
■ I/O Points
Note: Relay Stations can be used to create up to 3 levels and DeviceNet Slaves can be connected in each level. Terminators are required when
Slaves are connected to a Relay Station or Slave Station. Refer to the WD30 DeviceNet Wireless Units Operation Manual for details on Terminator installation.
Item Specifications
Wave type Spread Spectrum (direct sequence; DS-SS)
Communication method Simplex (half duplex)
Frequency band 2.4 GHz (2401 MHz to 2480.2 MHz)
Number of channels 34 channels (based on frequency division)
Antenna power 10 mW
Data transfer speed between wireless units 100 kbps
Transmission distance (See note 1.) Indoors: 60 m (approx. 50 m with magnetic base antennas)
Outdoors: 300 m (unobstructed)
Relay stations 3 repeaters max.
Max. number of sets in the same area (See note 1.) 10 sets max.
Max. number of wireless Slaves 64 max.
Item Specifications
Communications functions
(See note.)
Master/Slave connections Remote I/O functions and Explicit message communications functions
Self-diagnostic functions Unit WDT error, hardware errors (such as memory and CAN errors), and setting er-
rors
DeviceNet communications Duplicate node address errors, Bus OFF detection, and connection timeout
Device profiles Communication control unit Refer to Appendix A of the WD30 DeviceNet Wireless Units Operation Manual
for various DeviceNet IDs (vendor, device type = communication adapter, product code, product revision, product name, serial number, status, and I/O unit
IDs.)
Name Number of I/O points (words used)
DeviceNet Wireless Master 1,600 inputs max. (100 words)
1,600 outputs max. (100 words)
DeviceNet Wireless Slave 512 inputs max. (32 words)