Note: 1. Consult your OMRON representative for details.
2. Approval for CSA C22.2 No. 14 is authorized by the UL
mark.
EN60947-5-1 (approved
direct opening)
(See note 1.)
Approved Standard Ratings
TÜV (EN60947-5-1)
Utilization
Item
Rated operating current (I
Rated operating voltage (U
Note: Use a 10-A fuse type gI or gG that conforms to IEC269 as a short-circuit
protection device. This fuse is not built into the Switch.
category
) 3 A0.27 A
e
e
UL/CSA (UL508, CSA C22.2 No. 14)
A300
Rated
voltage
120 VAC 10 A60 A6 A7,200 VA 720 VA
240 VAC30 A3 A
Carry currentCurrentVolt-amperes
Solenoid Coil Characteristics
Item24 VDC110 VAC230 VAC
Rated operating
voltage (100% ED)
Current consumption
InsulationClass F (130° C max.)
24 VDC +10%/
−15%
Approx.
200 mA
AC-15DC-13
) 240 V250 V
MakeBreakMakeBreak
110 VAC ±10% 230 VAC ±10%
Approx. 50 mA Approx. 30 mA
Indicator Characteristics
ItemLED
Rated voltage10 to 115 VAC/VDC
Current leakageApprox. 1 mA
Color (LED)Orange
D4NL
G-155D4NL
Characteristics
Degree of protection (see note 2)IP67 (EN60947-5-1)
Durability
(see note 3)
Mechanical1,000,000 operations min.
Electrical500,000 operations min. for a resistive load of 3 A at 250 VAC (see note 4)
Operating speed0.05 to 0.5 m/s
Operating frequency30 operations/minute max.
Rated frequency50/60 Hz
Contact gap2 x 2 mm min
Direct opening force (see note 5)60 N min. (EN60947-5-1)
Direct opening travel (see note 5)10 mm min. (EN60947-5-1)
Holding force (see note 6)1,300 N min.
Insulation resistance100 MΩ min. (at 500 VDC)
Minimum applicable load (see note 7)Resistive load of 1 mA at 5 VDC (N-level reference value)
Rated insulation voltage (Ui)300 V (EN60947-5-1)
Rated open thermal current (Ith)10 A (EN60947-5-1)
Impulse withstand voltage (EN60947-5-1)Between terminals of the same polarity2.5 kV
Conditional short-circuit current100 A (EN60947-5-1)
Pollution degree (operating environment)3 (EN60947-5-1)
Protection against electric shockClass II (double insulation)
Contact resistance25 mΩ max. per contact (initial value)
Vibration resis-
Malfunction10 to 55 Hz, 0.75-mm single amplitude
tance
Shock resistanceDestruction
Malfunction
Ambient temperatureOperating:−10° C to 55° C with no icing
Ambient humidityOperating:95% max.
WeightApprox. 370 g (D4NL-IAFA-B)
Note: 1. The above values are initial values.
2. The degree of protection is tested using the method specified by the standard (EN60947-5-1). Confirm that sealing properties are suffi-
cient for the operating conditions and environment beforehand. Although the switch box is protected from dust or water penetration, do
not use the D4NL in places where foreign material may penetrate through the key hole on the head, otherwise Switch damage or malfunctioning may occur.
3. The durability is for an ambient temperature of 5°C to 35° C and an ambient humidity of 40% to 70%. For more details, consult your OM-
RON representative.
4. If the ambient temperature is greater than 35° C, do not pass the 3-A, 250-VAC load through more than 2 circuits.
5. These figures are minimum requirements for safe operation.
6. This figure is based on the GS-ET-19 evaluation method.
7. This value will vary with the switching frequency, environment, and reliability level. Confirm that correct operation is possible with the actual
load beforehand.
(This applies for the Switch only. The degree of protection for the key hole is IP00.)
Between terminals of different polarities4 kV
Between other terminals and uncharged metallic parts 6 kV
1,000 m/s
300 m/s
2
min.
2
min. (100 m/s2 min. for the lock monitor switch)
G-156Safety Sensors / Components
Connections
Indicator
Internal Circuit Diagram
10 to 115 VAC/VDC
Circuit Connection Example
• Terminals 12 and 41 are connected internally and so connect termi-
nals 11 and 42 for safety-circuit input. (GS-ET-19)
• Connect terminals 21 and 22 and terminals 51 and 52 in series
when using as safety-circuit input (redundancy circuit for terminals
11 and 12 and terminals 41 and 42 above). Connect the terminals
individually when using as auxiliary-circuit input (e.g., terminals 21
and 22 for safety-door open/closed monitoring and terminals 51
and 52 for monitoring the lock status).
• In the connection example on the right, terminals 21 and 22 and
terminals 51 and 52 are used as auxiliary-circuit input.
R
D
Z
R
Constant-current diode
51
LED
11
21
33
E1 (+)
Indicator
(Orange)
O1O2
1241
42
52
22
34
E2 (−)
Safety
circuit
Auxiliary
circuit
Auxiliary
circuit
Auxiliary
circuit
• Direct opening contacts used as safety-circuit input are indicated
with the mark. Terminals 11 and 12 and terminals 21 and 22
are direct opening contacts.
• Connect the indicators in parallel to the auxiliary circuits or termi-
nals E1 and E2.
If an indicator is connected in parallel to a direct opening contact,
when the indicator breaks, a short-circuit current will be generated,
possibly resulting in an installation malfunction.
• Do not switch standard loads for more than 2 circuits at the same
time. Otherwise, the level of insulation may decrease.
• The 24-VDC solenoid has polarity. Be sure to connect terminals
with the correct polarity.
D4NL
G-157D4NL
Operation Method
Operation Principles
Mechanical
lock models
Operation Key
Solenoid
Solenoid
lock models
Operation Key
Plunger
OFF
Spring
Lock plate
OFF
Spring
Lock plate
Solenoid
OFF
When the Operation Key is inserted, it is
locked by the lock spring. The door will stay
locked even if there is a power interruption.
OFF
If the solenoid is OFF, the door will not be
locked when the Operation Key is inserted.
This means that the door can be opened
and closed easily when replacing workpieces or parts.
ON
The solenoid is released only when the
lock is turned ON.
ON
The door is locked only when the solenoid
is turned ON. This means that the door will
be unlocked if there is a power interruption
and so this model cannot be used in systems that would maintain a hazardous
state (e.g., systems requiring toxic gases,
high temperatures, or gears that would
continue to turn due to inertia).
Nomenclature
Structure
Operation key hole
Terminal 42
Terminal 41
Shorting pin (12-41)
Terminal 12
Terminal 11
Door open/closed
detection switch
Terminal 21
Terminal 22
Terminal 31/33
Terminal 32/34
Release key
Note: Terminal numbers vary with the model.
Conduit opening
(vertical)
Solenoid
Terminal E1 (+)
Terminal E2 (−)
Terminal 01
Indicator
Terminal 02
Lock monitor switch
Conduit opening
(horizontal)
Terminal 52/54
Terminal 51/53
The head can be
mounted in 3 directions.
Standard Release Key
(Bottom View)
UNLOCKLOCKUNLOCKLOCK
Back-mounting is also possible.
Two conduits
(horizontal and vertical)
Special release key
Special Release Key
(Bottom View)