Omron D4BL User Manual

Guard Lock Safety-door Switch
D4BL
Release Protective Cover Locks Using Controller Signals or Pushbutton Switches after the Cutting Tool Stops Moving Due to Inertia
• A mechanical lock is applied automatically when the Operation Key is inserted. A high level of safety is achieved using a mechanism where the lock is only released when voltage is applied to the solenoid.
• Conforms to EN (TÜV) standards corresponding to the CE marking.
• Approved by UL, CSA, BIA, SUVA and CCC standards.
• The Switch contact is opened by a direct opening mechanism (NC contacts only) when the protective cover is opened. Direct opening mechanism that is EN-approved is indicated by on the Switch.
• Auxiliary release key ensures easy maintenance and unlocks the door in the case of a power failure.
• Tough aluminum die-cast body incorporating a switch box with degree of protection satisfying IP67, UL, and CSA TYPE6P, 13.
• Equipped with a horizontal and vertical conduit opening.
• Models incorporating easy-to-see indicators for monitoring and those using an adjustable Operation Key for a double door are available.
• The mounting direction of the head can be changed to allow the Operation Key to be inserted from four directions.
Note: Be sure to read the “Safety Precautions” on page A-78 and the
“Precautions for All Safety Door Switches” on page A-2.
Switches
D4BL
Safety Door

Model Number Structure

Model Number Legend
Switch
D4BL - -
1234 5
1. Conduit Size (2-conduit)
1: PG13.5 2: G1/2 3: 1/2-14NPT
2. Built-in Switch (with Safety Switch and Lock Monitor Switch Contacts)
C: 1NC/1NO (slow-action) + 1NC (slow-action) D: 2NC (slow-action) + 1NC (slow-action)
3. Head Mounting Direction
R: Four mounting directions possible (right-side mounting at shipping)
Operation Key (Order Separately)
D4BL - K
1
1. Operation Key Type
1: Horizontal mounting 2: Vertical mounting 3: Adjustable mounting (Horizontal)
4. Door Lock and Release (Auxiliary Release Key is Incorporated by All Models)
A: Mechanical lock/24-VDC solenoid release B: Mechanical lock/110-VAC solenoid release G: 24-VDC Solenoid lock/Mechanical release
5. Indicator
Blank: Without indicator A: 10 to 115 VAC or VDC driving (with orange
and green LED indicator unit)
Guard Lock Safety-door Switch D4BL A-67

Ordering Information

List of Models
Switches
Switches
Safety Door
D4BL
Lock
method
Mechanical lock
Solenoid lock
Conduit
size
PG13.5 24 VDC D4BL-1CRA D4BL-1CRA-A D4BL-1DRA D4BL-1DRA-A
G1/2 24 VDC D4BL-2CRA D4BL-2CRA-A D4BL-2DRA D4BL-2DRA-A
1/2­14NPT
Pg 13.5 24 VDC D4BL-1CRG D4BL-1CRG-A D4BL-1DRG D4BL-1DRG-A G1/2 24 VDC D4BL-2CRG D4BL-2CRG-A D4BL-2DRG D4BL-2DRG-A 1/2-
14NPT
Vol tage
for
solenoid
110 VAC D4BL-1CRB D4BL-1CRB-A D4BL-1DRB D4BL-1DRB-A
110 VAC D4BL-2CRB D4BL-2CRB-A D4BL-2DRB D4BL-2DRB-A 24 VDC D4BL-3CRA D4BL-3CRA-A D4BL-3DRA D4BL-3DRA-A 110 VAC D4BL-3CRB D4BL-3CRB-A D4BL-3DRB D4BL-3DRB-A
24 VDC D4BL-3CRG D4BL-3CRG-A D4BL-3DRG D4BL-3DRG-A
Without indicator
Operation Keys (Order Separately)
Mounting type Model
Horizontal mounting
Vertical mounting
D4BL-K1
D4BL-K2
1NC/1NO+ 1NC
(Slow-action)
With LED indicator
1NC/1NO+ 1NC
(Slow-action)
Without indicator
2NC+ 1NC
(Slow-action)
With LED indicator
2NC+ 1NC
(Slow-action)
Adjustable mounting (Horizontal)
D4BL-K3

Specifications

Standards and EC Directives
Conforms to the following EC Directives:
Machinery Directive Low Voltage Directive EN1088
Approved Standards
Agency Standard File No.
TÜV Rheinland EN60947-5-1
BIA GS-ET-19 Mechanical lock:
SUVA SUVA E6186/2.d UL UL508 E76675 CSA CSA C22.2, No.14 LR45746 CQC (CCC) GB14048.5 2003010305073836
Note: Ask your OMRON representative for information on approved
models.
R9451050 (Direct opening:
approved)
9402293 Solenoid lock: 1998 20462-01
A-68 Guard Lock Safety-door Switch D4BL
Approved Standard Ratings
TÜV (EN60947-5-1), CCC (GB14048.5)
Item Standard model Indicator model Utilization category AC-15 AC-15 Rated operating current (I
Rated operating voltage (U
Use a 10-A fuse type gI or gG that conforms to IEC60269 as a short-circuit protection device.
UL/CSA (UL508, CSA C22.2 No. 14)
) 3 A 6 A
e
) 250 V 115 V
e
Safety Door
Switches
A300
Rated voltage Carry current Current Volt-amperes
Make Break Make Break
120 VAC 10 A 60 A 6 A 7,200 VA 720 VA 240 VAC 30 A 3 A
Note: The UL/CSA approved rating for products with indicators (-A) is 6 A/115 VAC.
Characteristics
Degree of protection (See note 2.) IP67 (EN60947-5-1) (This applies for the Switch only. The degree of protection for the key hole is
Durability (See note 3.) Mechanical: 1,000,000 operations min.
Operating speed 0.05 to 0.5 m/s Operating frequency 30 operations/min max. Rated frequency 50/60 Hz Contact gap 2 x 2 mm min. Operating characteristics Direct opening force: 19.61 N min. (EN60947-5-1) (See note 4.)
Lock holding strength 700 N min. (GS-ET-19) Insulation resistance 100 M Rated insulation voltage (U
Conventional enclosed thermal current (I
)
the
Dielectric strength (U
Conditional short-circuit current 100 A (EN60947-5-1) Pollution degree (operating
environment) Protection against electric shock Class I (with ground terminal) Switching overvoltage 1,500 V max. (EN60947-5-1) Contact resistance 50 m Vibration resistance Malfunction: 10 to 55 Hz, 0.35-mm single amplitude Shock resistance
Ambient temperature Operating: –10 Ambient humidity Operating: 95% max. Weight Approx. 800 g
Note: 1. The above values are initial values.
2. The degree of protection is tested using the method specified by the standard (EN60947-5-1). Confirm that sealing properties are
sufficient for the operating conditions and environment beforehand. Although the switch box is protected from dust, oil or water penetration, do not use the D4BL in places where dust, oil, water, or chemicals may enter through the key hole on the head, otherwise Switch damage or malfunctioning may occur.
3. The durability is for an ambient temperature of 5
4. These figures are minimum requirements for safe operation.
) 300 V (EN60947-5-1)
i
) Impulse dielectric strength (U
imp
IP00.)
Electrical: 500,000 operations min. (10-A resistive load at 250 VAC)
Direct opening travel: 20 mm min. (EN60947-5-1) (See note 4.) All stroke: 23 mm min.
min. (at 500 VDC)
10 A (EN60947-5-1)
) 4 kV (EN60947-5-1) between terminals of different polarity, between
each terminal and ground, and between each terminal and non-current-carrying metal part;
2.5 kV between solenoid and ground (EN60947-5-1)
3 (EN60947-5-1)
max. (initial value)
Destruction: 1,000 m/s Malfunction: 300 m/s
°C to 55°C (with no icing)
°C to 35°C and an ambient humidity of 40% to 70%.
imp
2
min. (IEC68-2-27)
2
min. (IEC68-2-27)
D4BL
Guard Lock Safety-door Switch D4BL A-69
Solenoid Coil Characteristics
Item 24-VDC mechanical lock models 110-VAC mechanical lock models 24-VDC solenoid lock models
Rated operating voltage
24 VDC
+10%
(100% ED) 110 VAC ±10% (50/60 Hz) 24 VDC (100% ED)
15%
+10%
15%
Current consumption Approx. 300 mA Approx. 98 mA Approx. 300 mA Insulation Class F (130
Indicator Characteristics
Safety Door
Switches
°C or less)
Item LED Rated voltage 10 to 115 VAC/VDC Current leakage Approx. 1 mA Color (LED) Orange, green
D4BL

Connections

Contact Form (Diagrams Show State with Key Inserted and Lock Engaged)
Model Contact Operating pattern Remarks
D4BL-@C@@-@ 1NC/1NO+1NC
D4BL-@D@@-@ 2NC+1NC
31
32 11
Zb
12
Zb
24
12
22
Operation Key insertion comple­tion position
Operation Key insertion comple­tion position
23
113231
21
Lock position
Stroke
Lock position
Stroke
Extraction completion position
Extraction completion position
ON
ON
Only NC contacts 11-12 and 31-32 have an approved direct opening mechanism.
The terminals 11-12 and 23-24 can be used as unlike poles.
NC contacts 11-12, 21-22, and 31-32 have an approved direct opening mechanism.
The terminals 11-12 and 21-22 can be used as unlike poles.
Note: The EN-approved direct opening mechanism is indicated by on the Switch.
Contact Form 2NC + 2NC
(Safety circuit side)
(Monitor circuit side)
Indicator Unit
Dimensions Internal Circuit
Four terminal plates
(7)
(16)
(16)
(35) 26.2
(61.2)
Two, 7 dia.
26.8
0.3
5.6
Two LED indicators
53.2 57.2
2 10.6
(12.6)
10 to 115 VAC/DC
R
Z
D
R
Constant-current diode
LED
A-70 Guard Lock Safety-door Switch D4BL
Circuit Connection Example
Terminals 11 and 32 are connected internally and so connect terminals 12 and 31 for safety-circuit input. (GS-ET-19).
When using indicators, connect them to the auxiliary circuit side (monitor circuit) or the solenoid input terminals as shown below.
The indicators can be used to confirm the open/closed status of the door, the ON/OFF status of the power supply, and the ON/OFF status of the
solenoid.
Do not connect the indicators in parallel with the direct opening contact. If the indicators are broken, a short-circuit current may flow, causing
equipment to malfunction.
The 24-VDC solenoid terminals have polarity. Confirm the polarity before wiring.
Be sure to use a special pushbutton switch to stop and start machinery and release locks.
Safety Door
Switches
1. Orange: Lights when the solenoid turns ON. Green: Lights when the door opens.
(Power supply side)
E1 (+)
1211 32
23 24
Auxiliary circuit (monitor circuit)
31
Safety circuit
Solenoid
LED (orange)
LED (green)
(Ground side)
E2 (−)
3. Orange: Lights when the solenoid turns ON. Green: Lights when door closes.
(Power supply side)
E1 (+)
1211 32
31
21 22
Solenoid
LED (orange)
LED (green)
E2 (−)
2. Orange: Lights when the solenoid turns ON. Green: Lights when power turns ON.
(Power supply side)
E1 (+)
1211 32
23 24
Auxiliary circuit (monitor circuit)
31
Safety circuit
Solenoid
LED (orange)
LED (green)
(Ground side)
E2 (−)
4. Orange: Lights when the solenoid turns ON. Green: Lights when power turns ON.
(Power supply side)
E1 (+)
1211 32
31
2221
LED (orange)
LED (green)
Solenoid
E2 (−)
D4BL
Auxiliary circuit (monitor circuit)
Safety circuit (Ground side)
Auxiliary circuit (monitor circuit)
Safety circuit (Ground side)
Guard Lock Safety-door Switch D4BL A-71