CXONE-AL@@C-V4/
CXONE-AL@@D-V4
Face Plate Auto-Builder for NS
(Ver. 3.1)
Operation Manual
Revised October 2010
iv
Notice:
r
f
OMRON products are manufactured for use according to proper procedures by a qualified operator
and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed
the information provided with them. Failure to heed precautions can result in injury to people or damage to property.
!DANGERIndicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury. Additionally, there may be severe property damage.
!WARNINGIndicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury. Additionally, there may be severe property damage.
!CautionIndicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to
an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means
“word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PLC” means Programmable Controller. “PC” is used, however, in some Programming Device displays to mean Programmable Controller.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of
information.
OMRON, 2003
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, o
by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission o
OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without
notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility
for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in
this publication.
Note Indicates information of particular interest for efficient and convenient opera-
tion of the product.
1,2,3...1. Indicates lists of one sort or another, such as procedures, checklists, etc.
This manual describes the installation and operation of the CXONE-AL@@C-V4/CXONE-AL@@D-V4
Face Plate Auto-Builder for NS. The Face Plate Auto-Builder for NS is a software package used to
automatically build project files for the CS1W-LC001 Loop Control Unit, the CS1W-LCB01 and CS1WLCB05 Loop Control Boards, CS1D-CPU@@P Process-control CPU Units, and CJ1W-CPU@@P Loop
Control CPU Units used with NS-series Programmable Terminals. These files are based on the tag
files created using CX-Process Tool.
The project files that are created are configured using the Face Plate Screens for the Loop Control
Unit.
Please read this manual carefully and be sure you understand the information provided before
attempting to install and operate the Face Plate Auto-Builder for NS. Please read the following manuals
carefully and be sure you understand the information provided before setting up the Loop Control Unit/
Board and NS-series PT System
Manuals Related to the Loop Control Unit/Board
Product Manual nameCat. No. Contents
CXONE-AL@@C-V4/
CXONE-AL@@D-V4
Face Plate AutoBuilder for NS
CX-Process Monitor
Operation Manual
CX-Process Monitor Plus
Operation Manual
Loop Control Unit
Operation Manual
Loop Control Board
Operation Manual
Loop Control Unit
Function Block Reference
Manual
Loop Control Board
Function Block Reference
Manual
W418 (this manual) Installation and operation procedure for
Face Plate Auto-Builder for NS.
W372Installation and operation procedures
for the CX-Process Tool.
W463Provides an outline of the CX-One FA
Integrated Tool Package and the installation procedure. Refer to this manual
when installing software contained in
the CX-One FA Integrated Tool Package.
W373Installation and operation procedures
for the CX-Process Monitor.
W428Installation and operation procedures
for the CX-Process Monitor Plus.
W374Installation and operation procedures
for the Loop Control Unit (except for
function blocks).
W406Installation and operation procedures
for the Loop Control Boards (except for
function blocks).
W418 (this manual) Installation and operation procedure for
Face Plate Auto-Builder for NS.
W372Installation and operation procedures
for the CX-Process Tool.
W373Installation and operation procedures
for the CX-Process Monitor.
W428Installation and operation procedures
for the CX-Process Monitor Plus.
V088Operating procedures for the CX-
Designer.
V083Setup procedures for NS-series PTs.
V073Descriptions of NS-series PT functions.
!WARNING Failure to read and understand the information provided in this manual may result in per-
sonal injury or death, damage to the product, or product failure. Please read each section
in its entirety and be sure you understand the information provided in the section and
related sections before attempting any of the procedures or operations given.
x
Read and Understand this Manual
Please read and understand this manual before using the product. Please consult your OMRON
representative if you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a
period of one year (or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NONINFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE
PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which
liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS
REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS
WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO
CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
xi
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the
combination of products in the customer's application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying
ratings and limitations of use that apply to the products. This information by itself is not sufficient for a
complete determination of the suitability of the products in combination with the end product, machine,
system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not
intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses
listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or
uses not described in this manual.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical
equipment, amusement machines, vehicles, safety equipment, and installations subject to separate
industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED
FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any
consequence thereof.
xii
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other
reasons.
It is our practice to change model numbers when published ratings or features are changed, or when
significant construction changes are made. However, some specifications of the products may be changed
without any notice. When in doubt, special model numbers may be assigned to fix or establish key
specifications for your application on your request. Please consult with your OMRON representative at any
time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when
tolerances are shown.
PERFORMANCE DATA
Performance data given in this manual is provided as a guide for the user in determining suitability and does
not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must
correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and
Limitations of Liability.
ERRORS AND OMISSIONS
The information in this manual has been carefully checked and is believed to be accurate; however, no
responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
xiii
xiv
PRECAUTIONS
The information contained in this section is important for the safe and reliable application of the Face Plate AutoBuilder for NS. You must read this section and understand the information contained before attempting to set up or
operate the Face Plate Auto-Builder for NS and PLC system.
This manual is intended for the following personnel, who must also have
knowledge of electrical systems (an electrical engineer or the equivalent) and
instrumentation systems.
• Personnel in charge of installing FA systems.
• Personnel in charge of designing FA systems.
• Personnel in charge of managing FA systems and facilities.
2General Precautions
The user must operate the product according to the performance specifications described in the operation manuals.
Before using the product under conditions which are not described in the
manual or applying the product to nuclear control systems, railroad systems,
aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, petrochemical plants, and other systems,
machines, and equipment that may have a serious influence on lives and
property if used improperly, consult your OMRON representative.
Make sure that the ratings and performance characteristics of the product are
sufficient for the systems, machines, and equipment, and be sure to provide
the systems, machines, and equipment with double safety mechanisms.
This manual provides information for using the Face Plate Auto-Builder for
NS. Be sure to read this manual before attempting to use the Face Plate AutoBuilder for NS and keep this manual close at hand for reference during operation.
!WARNING It is extremely important that a PLC and all PLC Units/Boards be used for the
specified purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. Your must consult with
your OMRON representative before applying a PLC System to the abovementioned applications.
3Safety Precautions
!Caution When updating the CSV tag file generated by the CX-Process Tool Software
to use with the Face Plate Auto-Builder for NS, be sure to confirm that the
data is consistent with the program in the Loop Control Board/Unit. If the output project is not confirmed, unexpected operation may result.
4Application Precautions
Observe the following points when using the Face Plate Auto-Builder for NS.
!Caution Confirm operation of any user programs that you develop before running the
programs.
!Caution Confirm the operation of screen data and host programs before using the pro-
grams for actual applications.
xvi
1-1Features of the Face Plate Auto-Builder for NS . . . . . . . . . . . . . . . . . . . . . . . 2
Features of the Face Plate Auto-Builder for NSSection 1-1
1-1Features of the Face Plate Auto-Builder for NS
The Face Plate Auto-Builder for NS is a software package that automatically
builds project files for NS-series Programmable Terminals that are used for
monitoring and tuning CS1W-LC001 Loop Control Units, CS1W-LCB01,
CS1W-LCB05 Loop Control Boards, CS1D-CPU@@P Process-control CPU
Units, and CJ1W-CPU@@P Loop Control CPU Units.
Based on a CSV tag file created using the CX-Process Tool, the software
automatically builds a NS-series project file configured with Face Plate
Screens for the Loop Control Unit/Board and Process-control CPU Units.
1-1-1Features
• By simply specifying the tag file created using the CX-Process Tool, the
software automatically builds a project file for an OMRON NS-series Programmable Terminal. The project file is configured with Face Plate
Screens of the Loop Control Unit/Board and Process-control CPU Units.
• When using a Loop Control Unit/Board and Process-control CPU Unit
containing NS system version 4 or later, up to 100 loops of function block
(e.g., PID Control) monitoring and tuning can be performed on an NSseries Programmable Terminal. With any other NS system version, up to
32 loops of function block monitoring and tuning can be performed.
• Face Plate Screens can be built for the following function blocks of Loop
Control Unit or Board.
2-position ON/OFF (Block Model 001)
3-position ON/OFF (Block Model 002)
Basic PID (Block Model 011)
Advanced PID (Block Model 012)
Indication and Operation (Block Model 032)
Indicator (Block Model 034)
Segment Program 2 (Block Model 157)
Segment Program 3 (Block Model 158)
Indication and Setting (Block Model 031)
Ratio Setting (Block Model 033)
High/Low Alarm (Block Model 111)
Timer (Block Model 205)
Counter (Block Model 208)
ON/OFF Valve Manipulator (Block Model 221)
Motor Manipulator (Block Model 222)
Reversible Motor Manipulator (Block Model 223)
Motor Opening Manipulator (Block Model 224)
Blended PID (Block Model 013)
Batch Flowrate Capture (Block Model 014)
2
System RequirementsSection 1-2
1-2System Requirements
The following hardware and software is required to install and operate the
Face Plate Auto-Builder for NS.
1-2-1Computer
■ Computer
IBM PC/AT or compatible
■ CPU
Intel CPU (Core, Pentium, or Celeron family)
For Windows Vista: 1 GHz min.
For any other OS: 333 MHz min. required, 1 GHz min. recommended
■ Memory
For Windows Vista: 1 GB min.
For any other OS: 256 MB min. required, 512 MB min. recommended
1-2-2OS
Windows XP Professional (Service Pack 3) (see note), Windows Vista (Ultimate or Business), or Windows 7 is required.
Note: The 64-bit versions are not supported.
1-3Application Environment
The Face Plate Auto-Builder for NS uses tag files created with the following
software.
CX-Process Tool
■ Using a Loop Control Board
CX-Process Tool Ver. 3.0 or later
■ Using a Loop Control Unit
CX-Process Tool Ver. 2.0 or later
Projects built with the Face Plate Auto-Builder for NS are used with the follow-
ing hardware and software.
Loop Control Unit,
Loop Control Board,
Loop Control CPU
Unit, or Processcontrol CPU Unit
Note1. CX-Process Tool Ver. 3.2 or later must be used to output any EM banks
CS1W-LC001 Ver. 2.0 or later
CS1W-LCB01/05 Ver. 1.0 or later
CJ1G-CPU@@P Ver. 2.0 or later
CS1D-CPU@@P Ver. 1.0 or later
other than bank 0 to the area allocated for the Loop Control Board’s HMI.
2. Backup cannot be performed during operation with versions of the CS1WLCB01/05 Loop Control Boards earlier than version 1.5 or CS1W-LC001
Loop Control Units. With other Units/Boards, data can be backed up during
operation from the detail setting screens for the Segment Program 2 face
plate that is built.
NS-DesignerNS-Designer Ver. 2.0 or later
3
Upgrades Made for Version 2.0Section 1-4
CX-DesignerCX-Designer Ver. 1.0 or later
NS-series PT
(Programmable
Terminals)
The following models of NS-series PT, Ver. 2.0 or later:
Note Other connection combinations not listed here may cause malfunctions.
Supported communications
1:N NT Links
1:N NT Links
1-4Upgrades Made for Version 2.0
The functional changes made between version 1.1 and version 2.0 of the
Face Plate Auto-Builder for NS are described in this section.
methods
Maximum Number of
Loops Increased from 32
to 100
System Version Setting
for NS Project To Build
NS8 SupportProject data can be built for the NS8.
EM Multi-bank SupportWith CS-Process Ver. 3.2 or later, EM banks 0 to C can be specified for output
Multi-node Support (Up to
32 Nodes)
Automatic Building of
Segment Program 2 Detail
Setting Screens
Accompanying upgrades to the NS-series PT system software, the number of
loops that can be used for monitoring and tuning on the NS-series PT has
been increased from 32 to 100 with Face Plate Auto-Builder for NS Ver. 2.0.
Note Set the NS-series project system to version 4 or later.
The output version of the project data after building can be specified.
to the Loop Control Board’s HMI. (Previously only bank 0 was supported.)
With version 2.0, function block data using EM banks 0 to C created with CXProcess Ver. 3.2 can be converted to NS-series projects.
An NS-series project file that monitors more than one Loop Control Unit/
Board from single NS-series PT can be built from and CS-Process project
using multiple nodes.
When a Segment Program 2 function block is used, detail setting screens to
set Segment Program 2 parameters (time width-output setting screen and
weight width setting screen) are automatically generated.
4
Upgrades Made for Version 3.0Section 1-5
1-5Upgrades Made for Version 3.0
The functional changes made between version 2.0 and version 3.0 of the
Face Plate Auto-Builder for NS are described in this section.
Additional Support for
Function Blocks
Automatic Comments for
Unit and Scaling Settings
Face plates can be built for the following function blocks in addition to the
function blocks supported for version 2.0.
• Indication and Setting (Block Model 031)
• Ratio Setting (Block Model 033)
• High/Low Alarm (Block Model 111)
• Timer (Block Model 205)
• Counter (Block Model 208)
• ON/OFF Valve Manipulator (Block Model 221)
• Motor Manipulator (Block Model 222)
• Reversible Motor Manipulator (Block Model 223)
• Motor Opening Manipulator (Block Model 224)
• Blended PID (Block Model 013)
• Batch Flowrate Capture (Block Model 014)
Comments are automatically entered for automatically allocated unit and scaling settings when a project is generated. This prevents mistakes in editing
automatically allocated unit and scaling settings when editing projects.
1-6Upgrades Made for Version 3.1
The functional changes made between version 3.0 and version 3.1 of the
Face Plate Auto-Builder for NS are described in this section.
Additional Support for
Function Block
Output in NS System
Version 6.6 and NSRuntime Version 1.0
Formats
Face plates can be built for the following function block in addition to the function blocks supported for version 3.0.
• Segment Program 3 (Block Model 158)
Projects can be output in NS System version 6.6 and NS-Runtime version 1.0.
2-1-2Installing the Face Plate Auto-Builder for NS . . . . . . . . . . . . . . . . . 8
2-2Uninstalling the Face Plate Auto-Builder for NS . . . . . . . . . . . . . . . . . . . . . . 11
SECTION 2
Setup
7
Installation MethodSection 2-1
2-1Installation Method
Install the Face Plate Auto-Builder for NS from the installer of CX-One. Refer
to the included CX-One Setup Manual (W463) for details.
2-1-1Installation Precautions
• Before installing the Face Plate Auto-Builder for NS, close all Windows
programs.
• Do not install on a compressed drive. If a file on a compressed drive is
corrupted, it cannot be recovered.
• Do not cancel installation during setup. Doing so may result in some files
already copied remaining in the installation directory.
• Do not turn OFF the power or reset the personal computer during installation. Doing so may damage data in the computer.
• If Windows 2000 is used, be user to use Service Pack 4 or later. To check
the Service Pack version number, from the Start Menu select Settings -Control Panel - System. The System Properties Window will appear.
Click the General Tab. The Service Pack version is displayed under Sys-tem. If the Service Pack version is not displayed, it is not installed. Refer
to the Microsoft Website for details on compatibility.
• For Windows login users, log in as the administrator or user with administrative authority. A filter preventing unauthorized users is provided and will
cause an access error to occur.
• After installation, Windows must be restarted. Use the Installation Wizard
Dialog Box to restart, if required.
2-1-2Installing the Face Plate Auto-Builder for NS
Step 1: Execute the following setup wizard program from the CD.
<CD-ROM drive> \Face Plate Auto-Builder for NS\DISK1\SETUP.EXE.
Step 2: Start installation of the Face Plate Auto-Builder for NS by clicking the
Next Button.
8
Installation MethodSection 2-1
Step 3: Read the License Agreement thoroughly. If you agree with the terms,
select I accept the terms of the license agreement, and click the Next But-
ton to proceed.
Step 4: Specify the drive and directory in which the program files will be
installed.
The default setting is C: \Program Files\OMRON\CX-One\FP Auto-Builder.
To change the directory, click the Browse Button, and select the directory.
Check the installation directory and then click the Next Button.
9
Installation MethodSection 2-1
Step 5: Select the program folder.
Specify the location for the new shortcut to be added to the program folder
under the Start Menu. Check the setting and select the Next Button.
Step 6: Preparations for executing the installation have been completed.
10
Click the Install Button.
Installation will start from the install program.To check or change installation
details, click the Back Button. To cancel installation, click the Cancel Button.
Step 7: The following dialog box will be displayed when installation has been
completed. Click the Finish Button.
Uninstalling the Face Plate Auto-Builder for NSSection 2-2
2-2Uninstalling the Face Plate Auto-Builder for NS
Step 1: Select Add/Remove Programs from the Control Panel.
Select Face Plate Auto-Builder for NS from the list of applications, and
click the Change/Remove Button.
Step 2: Click the OK Button. The Face Plate Auto-Builder for NS will be uninstalled.
Step 3: When the uninstall process has been completed, the following screen
will be displayed. Click the Finish Button.
11
Uninstalling the Face Plate Auto-Builder for NSSection 2-2
This section describes the operation flow through execution of the project that
has been created using the Face Plate Auto-Builder for NS.
The following settings must be set from CX-Process Tool before executing
Face Plate Auto-Builder for NS.
Compile CSV Tag Files Using CX-Process Tool
(Refer to the CX-Process Tool Operation Manual (W372).)
Use the CX-Process Tool to compile (create) a CSV tag file for the Loop
Control Unit/Board.
1. Use the CX-Process Tool to create a program for the Loop Control Unit/Board.
Register and connect each function block, and register the Send/Receive All
Blocks block (for Loop Control Units only).
2. Set a CSV tag for each function block.
3. After setting the CSV tags, create the CSV tag file.
Note: Supported by CX-Process Tool Ver. 2.0 or later only.
Automatically Build NS Project Using Face Plate Auto-Builder for NS
(Refer to Section 4 Basic Operations.)
Specify the CSV tag file compiled using the CX-Process Tool to enable
the NS Face Plate Screen Project to be automatically built.
Note: Specify a new project for the project to be built automatically.
If an existing project is specified, the communications settings, numeric
unit and scale settings, and data log settings will be changed to the
default values when a new project is created.
Read Project and Transfer to the NS-series PT Using CX-Designer
Using as a New Project
Load the project file created by Face Plate Auto-Builder for NS to
the CX-Designer.
Loading Face Plates into an Existing Project
Refer to 4-2 Merging Projects.
Edit screens or create new screens, as required.
(Automatically built project files can be used as is.)
Set the initial settings for communications between the NS-series PT and PLC
in the CX-Designer System Settings.
After confirming project details, transfer the project file to the NS-series PT.
Start Operation of Loop Control Unit/Board + NS-series PT System
After connecting the Loop Control Unit/Board (CS series) and NS-series PT,
check operations, and then start operating the system.
Start the Face Plate Auto-Builder for NS by selecting Programs\OMRON\CXOne/Face Plate Auto-Builder for NS\Face Plate Auto-Builder for NS from
the Windows Start Menu. The following parameter setting screen will be displayed, when the Face Plate Auto-Builder for NS starts.
CSV Tag File
Set the folder location and file name of the CSV tag file from which the project
will be built. Click the Browse (1) Button to display a dialog box for selecting
the CSV tag file.
Project Name
Set the name of the CX-Designer project file to be created (up to 38 characters).
Output Folder
Set the folder that will output the CX-Designer project file. Click the Browse
(2) Button to display a dialog box for selecting the folder that will output the
project.
■ Build Conditions
PT Model/Project Version
Select the model of the NS-series PT and the system version.
ModelProject version
(system version)
NS7NS System Version 232
NS8NS System Version 4 or Version 6.6100 (See note.)
NS10NS System Version 232
NS System Version 4 or Version 6.6100 (See note.)
NS12 (Default) NS System Version 232
NS System Version 4 or Version 6.6100 (See note.)
NS-RuntimeNS System Version 6.6100 (See note.)
Number of changeable
function blocks
16
Basic OperationSection 4-1
NoteA maximum of 85 Segment Program 3 blocks can be created. Con-
version will not be possible if there are more than 85 Segment Program 3 blocks registered in the CSV tag file.
Enable for Making Detail Setting Screen of Segment Program 2 (Project
Version 4 or Later)
If this option is selected and a Segment Program 2 function block is used,
detail setting screens (time width-output setting screen and wait width setting
screen) to set the Segment Program 2 parameters will be built automatically.
Note The capacity of the NS-series PT may be exceeded if a large quantity of
screens are generated automatically. An error will occur when transferring the
project if the capacity is exceeded. If this occurs, delete the detail setting
screens and wait screens. When deleting detail setting screens and wait
screens, always delete the parts from the screen first and then delete the
screens using the screen maintenance function. (It will not be possible to
delete the screens using the screen maintenance function if there are parts
remaining on the screens.) Tool - Resource Report can be used from the
CX-Designer to see if the capacity has been exceeded.
Screen Number Offset
Set the first screen number in the NS-series PT.
Project versionVersion 2Version 4Version 6.6
Range0 to 37990 to 35990 to 3599
Default0
Starting from the specified screen number offset, screen numbers are
assigned to the Control Screens (up to 25 screens) and Tuning Screens (up to
100 screens) in that order.
Unit Number Offset
Set the first number allocated from the Unit and Scale No. data in the NSseries PT.
Project versionVersion 2Version 4Version 6.6
Range12 to 80012 to 70012 to 700
Default12
Unit and Scale No. data items for the NS-series PT Numeral Display and Input
objects are created automatically by the Face Plate Auto-Builder for NS from
the scaling upper/lower limit and unit characters.
If version 2 is selected, up to 69 Unit and Scale No. data items will be created
from the first number tag set here. If version 4 or version 6.6 is selected, up to
207 Unit and Scale No. data items will be created (when using Segment Program 3, up to 632 Unit and Scale No. data items will be created). (See note.)
Refer to the following illustration for details.
NoteThe number of data items shown here will be created when the
maximum of 85 Segment Program 3 blocks are registered in addition to 15 other blocks, making a total of 100 blocks.
17
Basic OperationSection 4-1
The NS System uses
Allocation of Unit and Scaling Settings
Start of unit and scaling
settings to be set (default: 12)
These 100 are allocated regardless
of the number of registered
function blocks
These 100 are allocated regardless
of the number of registered
function blocks
Two allocated for Segment
Program 2. Numbers 999 and
1000 are always allocated
regardless of the start number
setting. (Applies only when the
detailed setting screen of
Segment Program 2 is used.)
the first 11.
Five are always
allocated.
One is allocated for each
registered function block
(PV scaling settings).
One is allocated for each
registered function block
(DV scaling settings).
The total number of freely set values for
bank data registered for Segment Program 3
(only in version 6.6 and NS-Runtime).
Refer to 5-4 Engineering Units for details on unit and scale settings.
Comments are automatically entered for unit and scaling settings automati-
cally allocated by the Face Plate Auto-Builder for NS. Unit and scaling settings
for which comments have been automatically entered are automatically generated by the Face Plate Auto-Builder for NS; do not change the settings
when constructing screens.
Data Log Number Offset
Specify the first number allocated to the data log group in the NS-series PT.
The maximum value of the data log used by the Face Plate Auto-Builder for
NS is 100 for NS system version 4 and higher and 32 for other versions.
18
Basic OperationSection 4-1
Message ID Number Offset
Specify the first number allocated for confirmation messages in the NS-series
PT. There are two confirmation messages used by the Face Plate AutoBuilder for NS. These two messages are automatically created when a project
is generated.
■ Button
Build
Click this button to start automatic screen building.
Quit
Click this button to exit the Face Plate Auto-Builder for NS.
Version
Click this button to display the Version Information Dialog Box for the Face
Plate Auto-Builder for NS.
Step 3: Register Host
Names
1,2,3...1. Select the host to be set in the Host Registration Dialog Box and click the
When all settings have been completed in step 2, click the Build Button. The
following dialog box will be displayed.
This window is used to make the host settings to create an NS-series project
file from a CX-Process project that uses multiple nodes. With the NS-series
PT, nodes are registered as hosts. Host settings are described next.
Settings Button. The following dialog box will be displayed.
19
Basic OperationSection 4-1
2. Set the required items. The settings and display is described in the following table.
ItemMeaning
CSV tag file
settings
Settings registered in
CX-Designer
Network
address
Node addressDisplays the node address given in the CSV tag file.
Communica-
tions connection method
Host nameSet the host name.
Network
address
Node addressSet the node address of the node (host) as viewed
Displays the network address given in the CSV tag
file.
Set the node (host) connection method.
Any of the following three methods can be set: Serial
port A, serial port B, Ethernet/CLK
Example: If the node is connected to serial port A,
select Serial port A.
Note: The host name, network address, and node
address cannot be set if serial port A or serial B is
selected.
• Serial Port A Settings
Host name: SERIALA
Network address: 111
Node address: 1
• Serial port B Settings
Host name: SERIALB
Network address: 112
Node address: 1
Note: When Ethernet/CLK is selected, the PLC type
registered in the CX-Designer will always be SYSMAC-CS1.
• The host name must be all-caps.
• The host name can be up to 16 characters long.
• The same host name can be used only once.
• The host name, network address, and node
address cannot be set if serial port A or serial B is
selected as the communications connection
method.
Set the network address of the node (host) as viewed
from the NS-series PT.
The network address will be 111 or 112 if serial port
A or serial B is selected as the communications connection method.
from the NS-series PT.
The node address will be 1 if serial port A or serial B
is selected as the communications connection
method.
Step 4: Load the
Project File
Step 5: Transfer the
Settings to the NSseries PT
20
Use CX-Designer to read the automatically built project files.
Use CX-Designer to edit the project files as required.
Transfer the settings from CX-Designer to the NS-series PT (or save the settings to a Memory Card and install the Memory Card in the NS-series PT).
Start the system, and perform monitoring/tuning of the Loop Control Unit/
Board from the NS-series PT.
Note An error message saying that the file is too large and to check the product
data (0088) may be displayed when transferring a project from the CXDesigner to the NS-series PT. If this message appears, clear the selection of
Merging ProjectsSection 4-2
the Transfer with the symbol table Option in the Send Options of the CX-
Designer, and then resend the project.
4-2Merging Projects
4-2-1Merge Using the CX-Designer
Use the CX-Designer with the following procedure to merge an NS project
output using the Face Plate Auto-Builder for NS with an existing NS project.
Individually Copying
Screens
Selected screens can be copied. Screens can be copied from a project output
using Face Plate Auto-Builder for NS to an existing project by starting two
copies of the CX-Designer. Screens cannot be copied, however, if the system
version of the project copy destination is older than that of the project copy
source.
1,2,3...1. Select the screen to be copied from the Project Workspace and press the
Ctrl+C Keys. Alternatively, right-click and select Copy from the pop-up
menu. Click the screens while pressing the Shift Key or Ctrl Key to select
multiple screens at the same time.
2. Select the category in which to paste in the Project Workspace.
3. Press the Ctrl + V Keys. Alternatively, right-click and select Paste from the
pop-up menu.
4. Specify the number of the first screen after pasting, then click the OK Button.
5. If the Reuse screen with sheet option has been set, specify the number of
the first sheet after pasting, and then click the OK Button. (This operation
is necessary only if the Reuse screen with sheet option has been set.)
Pasting Parts, Such As
Face Plates, into Separate
Projects
The screen will not be copied if the number of sheets after copying exceeds
ten.
Once copying has completed, a file in the format of projectname.txt will be
created in the folder where the project file (i.e., ipp file) is saved. The screen
numbers before copying and after copying can be checked.
Copied or cut parts can be pasted to separate projects. Common settings that
the part references are also copied at the same time. (Refer to the note below
regarding common settings.) Parts cannot be copied, however, if the system
version of the project copy destination is older than that of the project copy
source.
21
Merging ProjectsSection 4-2
1,2,3...1. Start two copies of the CX-Designer, and then open the copy source
project in one and the copy destination project in the other.
2. Copy or cut the part in the copy source CX-Designer project.
3. Paste the part into the copy destination CX-Designer project.
4. Alternatively, drag the part from the copy source CX-Designer project to
the copy destination CX-Designer project.
5. If multiple hosts are registered to the project at the reuse destination, select an appropriate host after copying for the communications addresses
used with the parts.
Note Common Settings
The following settings, which are referred to by function parts, are also copied
to the project of the copy destination.
• Alarm/event settings (alarm/event indication, alarm/event summary and
log)
• Data log settings (data log graph)
• Data block settings (data block tables)
• Unit and scale settings (unit-set value settings, inputs, and thumb rotary
switches)
• Dialog box settings (function parts for which specifying a confirmation
message has been set)
These settings will be added with numbers changed to not overlap settings
already at the copy source. Unused communications addresses at the copy
destination will be added to the symbol tables.
Note1. Switch from the face plate on the Control Screen to the relevant Tuning
Screen by using the Command Button. The number of the screen switched
to may deviate depending on the method of screen copying.
2. When copying individual screens and parts, unit and scale settings except
for comments will be regarded as identical unit and scale settings if the settings are identical, and the allocation of unit and scale numbers will
change. To change the scaling information of function blocks, change the
scaling settings using the CX-Process Tool, and copy after again outputting the project with Face Plate Auto Builder for NS.
4-2-2Merging Using the NS Project Merge Tool
22
The following settings are required for the Face Plate Auto-Builder for NS,
when merging the built project with other projects using the NS Project Merging Tool.
For details on merging projects, refer to the NS Project Merging Tool Opera-tion Manual.
The NS Project Merge Tool is provided with the CX Designer.
Merging ProjectsSection 4-2
Execute the “Setup.exe” file in \Utility\English\ProjectMergeTool\disk1 on the
CDROM to install it.
When merging projects, make the following settings when building the project
on the Face Plate Auto-Builder for NS so that the same resources are not
used by both projects. Confirm the build conditions in 4.1 Basic Operation for
details on settings.
• First screen number
• First unit number
• First data log number
• First confirmation message number
Note Observe the following precaution when merging projects with the NS Project
Merge Tool.
• The NS Project Merge Tool does not support version 6.6 projects. Follow
the procedure described in 4-2-1 Merge Using the CX-Designer to merge
version 6.6 projects.
• The SMART Active Parts will not function if a project (called project A)
that was output with the Enable for Making Detail Setting Screen of Seg-ment Program 2 option selected is merged with a project (called project
B) in which SMART Active Parts were pasted.
Use the following procedure to successfully merge projects like these.
1,2,3...1. Delete all of the SMART Active Parts from project B.
2. Save project B.
3. Merge the two projects with project A as the base project and project B as
the merge project.
4. Paste the SMART Active Parts into the merged project.
The Face Plate Auto-Builder for NS creates two types of screens: Control
Screens and Tuning Screens.
Control ScreensControl Screens display a row of multiple face plates.
Control Screens are created from the beginning of the CSV tag file for up to
100 loops for system version 4 or later and for up to 32 loops for other system
versions.
For NS12 PTs, six face plates are created in a single screen, and for NS10,
NS8, and NS7 PTs, four face plates are created in a single screen.
The following screen is a Control Screen when using an NS12 PT.
Click the >> Button in the top right corner of the screen to move to the next
Control Screen page, and click the << Button to move to the previous page.
Tuning ScreensTuning Screens are adjustment screens for individual tag names (i.e., function
blocks) and are configured from the parameter settings, such as face plate,
realtime trend, and alarms.
Click the Tuning Button at the top of each face plate arranged in a row in the
Control Screens to move to the Tuning Screen of the corresponding tag name
(function block).
The following Tuning Screen is an example of when an NS12 PT is used.
Click the Back Button in the top right corner of the Tuning Screen to return to
the Control Screen.
26
Created ScreensSection 5-1
Screen Building
Order (Screen
Number Order)
Control Screens are built first, followed by Tuning Screens, as shown in the
following table. Building starts from the screen number specified as the screen
number offset, and continues in sequence without skipping any screen numbers. (The screen number offset can be specified between 0 and 3,799 (System Version 2), 0 and 3,599 (System Version 4 or later). The default is 0.)
ScreenDetails
A Control Screens
(up to 8 screens)
B Tuning Screens
(up to 32 screens)
Up to 100 face plates for system version 4 or later and up to
32 face plates for other system versions are built for the function blocks to be converted that are detected when searched
from the beginning of the CSV tag file.
The function blocks detected first are built with the smaller
numbers at the left of the screen, and are arranged in order to
the right. Six face plates are created for NS12 PTs and four
face plates are created for the NS10 and NS7 PTs, after which
building is shifted to the next screen.
The Control Screens are built for all the function blocks.
Up to100 face plates for system version 4 or later and up to 32
face plates for other system versions are built sequentially for
the function blocks to be converted that are detected when
searched from the beginning of the CSV tag file. The Tuning
Screens are built for all the function blocks.
Note In the screens built using the Face Plate Auto-Builder for NS, the face plates
(in both Control Screens and Tuning Screens) are built in groups. Parts other
than face plates are not grouped.
27
Screen TitlesSection 5-2
5-2Screen Titles
Screen titles are assigned to each screen that is built, as shown in the following table.
ScreenScreen title assignment method
Control ScreensControl Screen <Sequential number from 1>
Example: Control Screen 1, Control Screen 2, etc.
Tuning ScreensTuning Screen - <Tag No. >
Tag No.
Example: Tuning Screen−TIC0000.
5-3Tuning Screen Realtime Trends
Up to 100 Tuning Screens for system version 4 or later and up to 32 Tuning
Screens for other system versions can be built using the Face Plate AutoBuilder for NS. The NS-series data log is also generated for creating a realtime trend graph for the Tuning Screens. Up to 100 data logs for system version 4 or later and up to 32 data logs for other system versions are used and
data logs are created from the following details, according to the order the
face plates are built.
• Data log setting group name: Group (number) (Example: Group 1, Group
2, etc.)
• Data collection cycle: 1 s
• Log count: 533 records
• Log period: Logging is performed while data log object is displayed only.
(It is cleared when screens are switched.)
• Log address: (Refer to information on individual function blocks for details
on logging the SP, MV, and PV for the tag ITEM.)
Note The NS project file built with the Face Plate Auto-Builder for NS create build-
ing results after returning the communications settings, unit and scale setting,
and data log settings to the default values for creating new projects. Specify a
new project name in the name for the project file being built.
5-4Engineering Units
Values such as the SP and PV for Basic PID must be scaled to engineering
units.
In the following explanations, places where engineering units are indicated
must be scaled as defined in this section.
With the data in tag ITEMs for engineering units, such as PV and SP for Basic
PID, the value stored and used in the PLC or in communications for the scaling lower limit (0%) is 0, and for the scaling upper limit (100%) is 10,000 (e.g.,
5,000 for scaling of 50%, −1,500 for −15%, etc.).
When the value of a tag ITEM for an engineering unit is displayed or set on
the PT screen, the value must be displayed or set as the actual amount (engineering unit value) after scaling.
Scaling is performed by referencing the CSV tag file's scaling upper limit, scaling lower limit, decimal point position (scaling decimal point position), and unit
characters.
28
Percent DataSection 5-5
In a CSV tag file, the scaling upper limit, scaling lower limit, and decimal point
position are stored for every tag ITEM. The scaling upper limit, scaling lower
limit, and decimal point position are, however, the default values registered by
the user in for individual tag names (i.e., function blocks) from the CX-Process
Tool. Therefore, for the same tag name (function block), the scaling upper
limit, scaling lower limit, decimal point position, and unit characters are all the
same for the tag ITEM, i.e., the engineering unit is the same.
For example, when the scaling upper limit value=500, scaling lower limit
value=0, and decimal point position=1 the values in the PLC or communications are scaled to the values shown in the following table.
Scaling is based on the CSV tag file, according to the Integer Decimal setting
and Unit and Scale No. data for NS-series Numeral Display and Input objects.
The Integer Decimal is automatically set based on the decimal point position
in the CSV tag file.
Unit and Scale No. data items are created based on the scaling upper/lower
limit, and unit characters for tag names from the beginning of the CSV tag file.
Up to 66 sets of these items can be created for system version 2.0 and up to
207 can be created for system version 4.0 (632 if Segment Program 3 blocks
are set). When building, use the Unit Number Offset setting to specify which
of the Unit and Scale No. data items will be allocated. (System version 2 setting range: 12 to 800, System version 4 setting range: 12 to 700, System version 6.6 setting range: 12 to 700 (upper limit changes if Segment Program 3
blocks are set).
When the Tag ITEMs are required to display with the engineering units, the
units from the CSV tag file are used.
Note In NS project files built with the Face Plate Auto-Builder for NS, the following
5-5Percent Data
two Unit and Scale settings are always registered: 0.01 multiplier, 0 offset,
and 0.1 multiplier, 0 offset.
Due to face plate design restrictions, when the decimal point position is 6 or
higher, only 5 decimal places will be displayed.
Data such as the MV for Basic PID is referred to as percent data, and is displayed using a base of 0.00% to 100.00%.
and used in the PLC or communications are 0 for 0%, and 10,000 for 100%
(e.g., the value for 50% is 5,000, and for −15% is −1,500).
When the values of tag ITEMs for percent data are displayed on the PT
screen or receive a set value, the values are displayed using two decimal
Percent data is set by registering a setting in a Numeral Display and Input
objects with the integer set to four digits and the decimal to two digits. The
conversion rate/offset for the unit and scale setting is set to a multiplier of
0.01.
5-6Read Address and Write Address
Even if the tag ITEM is the same for the read address that is read and displayed from the PLC to the NS-series PT and the write address that is written
to the PLC from the NS-series PT, the addresses are different.
For example, the following table shows the addresses when Basic PID is
used.
Tag ITEMRead addressWrite address
SPDetermined by the I/O mem-
ory area type, address, and
bit position of SP in the CSV
tag file.
MV, R/L_SW, A/
M_SW, P, I, D,
HH_SP, H_SP, L_SP,
LL_SP, etc.
Determined by the I/O memory area type, address, and
bit position of each tag ITEM
in the CSV tag file.
Determined by the I/O memory area type, address, and
bit position of SP_W in the
CSV tag file, plus the offset
(write data).
Determined by the I/O memory area type, address, and
bit position of each tag ITEM
in the CSV tag file, plus the
offset (write data).
Note If any values in the receive area (i.e., I/O memory in the CPU Unit) have not
changed, Receive All Blocks in the Loop Control Unit will not receive any data
from the CPU Unit. Therefore, after changing the mode from MAN to AUTO
and then back to MAN mode, such as for Basic PID, and 2-position ON/OFF,
and after changes to the MV set values, the MV value change operation will
not function unless there is a change between the current MAN and previous
MAN mode in the MV write value (receive area value) from the NS-series PT.
In this case, perform an operation to change the MV write value (receive area
value) from the NS-series PT once, and then perform processing.
The following precaution is required for the Loop Control Unit.
When using an NS project file built with the Face Plate Auto-Builder for NS,
the NS-series PT communicates with the Loop Control Unit via the memory of
the CPU Unit, using the Send/Receive All Blocks block in the Loop Control
Unit. Therefore, compared with accessing the Loop Control Unit using the CXProcess Tool or CX-Process Monitor software, the communications response
is slower.
30
Work MemorySection 5-7
5-7Work Memory
The Face Plate Auto-Builder for NS creates the following macros using the
internal memory in the PT for purposes such as checking statuses of changed
SP data and changed MV data.
PT memoryApplication and places used
$B32760Used to temporarily read tag ITEM R/L_SW.
Used in the macro for the SP Change Button in the face plate.
Used in the macro for the Numeral Display and Input object in
the Change SP Data Screen.
$B32761Used to temporarily read tag ITEM A/M_SW.
Used in the macro for the MV Change Button in the face plate.
Used in the macro for the Numeral Display and Input object in
the Change MV Data Screen.
$B32762Used to temporarily read tag ITEM CAS_SET.
Used in the macro for the SP Change Button in the face plate.
Used in the macro for the Numeral Display and Input object in
the Change SP Data Screen.
$B32763Used to temporarily read tag ITEM MV (2-position ON/OFF).
Used in the macro for the MV Operation Button in the face
plate.
$B32764Used to temporarily read tag ITEM MVH (3-position ON/OFF).
Used in the macro for the MV Operation Button in the face
plate.
$B32765Used to temporarily read tag ITEM MVL (3-position ON/OFF).
Used in the macro for the MV Operation Button in the face
plate.
$B32766Used to temporarily read tag ITEM S1 (Segment Program 2).
Used in the macro for the START/STOP Button in the face
plate.
$B32767Used to temporarily read tag ITEM S2 (Segment Program 2).
Used in the macro for the CONT/PAUSE Button in the face
plate.
$W2047Used to write word data.
Used for numeric settings such as those for SP, MV, alarm set
values, and PID.
$W32700Used to display tag ITEMs Q1 and Q2 (for 013 Blended PID).
$W32706Used to display tag ITEM B0 (for 014 Batch Flowrate Cap-
$W32708Used to display tag ITEM BP (for 014 Batch Flowrate Cap-
$W32710Used to display tag ITEM B1 (014 Batch Flowrate Capture).
Used to calculate tag ITEMs Q1, Q2, PR, BM, BMU, SM,
SMU, SP, and SPU (for 014 Batch Flowrate Capture). Used by
the macro when loading face plate screens.
Used to display tag ITEM SP (for 033 Ratio Setting). Used for
the Numerical Display and display objects of the face plate.
Used to calculate tag ITEMs SP and K1 (for 033 Ratio Setting). Used in the macro of the face plate Word Buttons.
Used for numerical input and display object of integrated values.
ture). Used for numerical input and display parts overshoot
amounts.
ture). Used for numerical input and display parts of pre-batch.
Used for numerical input and display parts of flow speed limit
amounts.
31
Work MemorySection 5-7
PT memoryApplication and places used
$W32760 to
$W32762
$W32712 to
$W32759
$W32764 to
$W32767
Note Do not use the above areas of the internal memory in the PT for any other
purpose.
Used to calculate tag ITEMs Q1, Q2, PR, BM, BMU, SM,
SMU, SP, and SPU (for 014 Batch Flowrate Capture). Used by
the macro of the face plate Word Buttons.
Used to display tag ITEMs Q1, Q2, PR, BM, BMU, SM, SMU,
SP, and SPU. Used for the Numerical Display and input object
of the face plate.
Used to write tag ITEMs Q1, Q2, PR, BM, BMU, SM, SMU,
SP, and SPU (for 014 Batch Flowrate Capture). Used in the
macro for the Numeral Display and Input object of the face
plate.
The following diagram shows a face plate for Basic PID built using the Face
Plate Auto-Builder for NS in an 800×600 screen resolution.
The whole face is built using 580×133 dots.
2
3
45
7
9
13
14
25
20
21
22
1
6
8
10
1112
16
17
18
15
19
In the graphic display, 24 is
displayed as follows:
23
24
1: Tuning Screen Button
Touch this button to switch to the Tuning Screen for the corresponding tag
name. This button is created as a Command Button.
The Tuning Screen Button is not provided in the face plates in the Tuning
Screen.
2: Tag Name
The tag name in the CSV tag file is set as a label and displayed as a Text
object (up to 16 characters).
3: Tag Comment
The tag comment in the CSV tag file is set as a label and displayed as a Text
object (up to 16 characters).
4: Status Display 1
Either AUTO, MAN, or CAS status is displayed. The status character string
displayed is determined by the combination of values for tag ITEMs R/L_SW
and A/M_SW.
DisplayR/L_SE (ITEM 026)A/M_SW (ITEM 086)
MAN00
(No characters displayed) 10
AUTO01
CAS11
These buttons are created as ON/OFF Buttons using a Select Shape of type 3
to switch the graphic displaying AUTO, MAN, and CAS characters.
Control Flag input is disabled.
35
Basic PID (Block Model 011)Section 6-1
5: Status Display 2
Either PV error indication or MV error indication status is displayed. The status character string displayed is determined by the combination of values for
tag ITEMs PV_ABN and MV_ABN.
ON/OFF Buttons using a Select Shape of type 3 are used to switch the
graphic displaying PV error indication and MV error indication characters.
Control Flag input is disabled.
6: Alarm Status Display
This field displays the status of alarms that have occurred. The Bit Lamp
object is used to display normal operation in gray and alarm states in red.
Statuses such as LL (low/low alarm) are displayed in the rough font.
Refer to the following table of tag ITEMs for addresses.
Alarm typeTag ITEM
LL (Low/low alarm) LL (ITEM 016)
L (Low alarm) L (ITEM 015)
H (High alarm) H (ITEM 014)
HH (High/high alarm) HH (ITEM 013)
DV (Deviation alarm) DVA (ITEM 042)
MH (High MV limit) MHA (ITEM 078)
ML (Low MV limit) MLA (ITEM 079)
7: PV
The fixed string “PV” is displayed as a Text object.
8: PV Numerical Value Display
A Numeral Display and Input object is used to display the value of tag ITEM
PV (ITEM 007) in engineering units.
A Control Flag is set to disable input.
9: SP
The fixed text “SP” is displayed as a Text object.
10: SP Numerical Value Display and Input
A Numeral Display and Input object is used to display the value of tag ITEM
SP (ITEM 029) in engineering units. Touch this field to display a ten-key pad
below it.
Writing is performed for tag ITEM SP_W (ITEM 023) using the Before Writing
Numeral/String macro condition.
• LL and HH are displayed in red, and L and H are displayed in light blue
(color code 219).
• The maximum value displayed is 11500 (115%) and the minimum value
displayed is −1500 (−15%).
• The zero point is specified to be displayed.
13: PV Bar Display
The tag ITEM PV (ITEM 007) is displayed using a Level Meter object. The
meter color is green, the maximum value displayed is 11500 (115%), and the
minimum value displayed is −1500 (−15%). The bar is set to display the zero
point.
14: SP Bar Display
The tag ITEM SP (ITEM 029) is displayed using a Level Meter object. The
meter color is yellow, the maximum value displayed is 11500 (115%), and the
minimum value displayed is −1500 (−15%). The bar is set to display the zero
point.
37
Basic PID (Block Model 011)Section 6-1
15: Bar Scale Display
The PV bar and SP bar displays include fixed marks in the graphic indicating
0%, 50%, and 100%. The numerical values for 0% and 100% are displayed
with engineering units using Text objects in the rough font.
16: Switch to CAS Button
This button switches operation to Remote and Auto (CAS) mode. Values are
displayed in red during Remote and Auto mode.
This button is created as a momentary ON/OFF Button using a Simple Rectangle (Type 3) and the display color is determined according to the following
table.
Display colorR/L_SW (ITEM 026) A/M_SW (ITEM 086)
Yellow0 (Local)0 (Manual)
1 (Remote)0 (Manual)
0 (Local)1 (Auto)
Red1 (Remote)1 (Auto)
The label displays “CAS” in the rough font.
By setting a Touch OFF Timing macro as shown below, the display will switch
A Control Flag is used to reference the tag ITEM CAS_SET (ITEM 024) and if
the value is 1, the object is set for no display and to disable input.
17: Switch to AUTO Button
This button is set as a momentary ON/OFF Button using a Simple Rectangle
(Type 3), and the display color is determined according to the following table.
Display colorR/L_SW (ITEM 026) A/M_SW (ITEM 086)
Yellow0 (Local)0 (Manual)
1 (Remote)0 (Manual)
0 (Local)1 (Auto)
Red1 (Remote)1 (Auto)
The label displays “AUTO” in the rough font.
By setting a Touch OFF Timing macro as shown below, the display will switch
The value for tag ITEM MV_IDX (ITEM 098) is displayed as a Level Meter
object. The leftmost side is 0%, the rightmost side is 100%, and the color of
the bar is brown.
21: MV Bar Display
The value for tag ITEM MV (ITEM 089) is displayed as a Level Meter object.
The leftmost side is 0%, the rightmost side is 100%, and the color of the bar is
blue (color code 209).
22: MV
The fixed string “MV” is displayed as a Text object.
23: MV Numeral Value Display and Input
A Numeral Display and Input object is used to display the value of tag ITEM
MV (ITEM 089) as percent data. When touched, a ten-key pad is displayed
under this field.
Writing is performed for tag ITEM MV (ITEM 089) using the Before Writing
Numeral/String macro condition, as follows:
$W2047=GETNUMVAL () ;
WRITECMEM ([MV],$W2047,1) ;
The upper and lower limits of the data range are ±320.00%.
When the ten-key pad is displayed, the tag ITEM A/M_SW (ITEM 086) is ref-
erenced, and if the value is 1, a message is displayed indicating that the MV
cannot be set, and input is disabled.
This function is set using the following macro as a Touch ON Timing macro for
Word Buttons.
READCMEM ($B32761,[A/M_SW],1) ;
40
if ($B32761==1)
MSGBOX (“Cannot set.”,“MV change”,0) ;
endif
24: Up/Down Buttons to Change MV
These Buttons are used to increase or decrease the value of tag ITEM MV
(ITEM 089).
Basic PID (Block Model 011)Section 6-1
The increment is set to 0, and actual increase or decrease of the value is performed from the macro.
ButtonIncrement
100 (1%)
10 (0.1%)
−10 (−0.1%)
−100 (−1%)
A Select Shape graphic is used for the Button display.
The upper and lower limits of the data range are ±320.00%. These buttons
are not set to loop back when the upper or lower limit is exceeded.
When increasing or decreasing the MV value, the tag ITEM A/M_SW (ITEM
086) is referenced. If the value is 1, a message is displayed indicating that the
MV value cannot be set, and input is disabled.
This function is set using the following macro as a Touch OFF Timing macro
for Word Buttons.
READCMEM ($B32761,[A/M_SW],1) ;
if ($B32761==1)
MSGBOX (“Cannot set.”,”MV change”,0) ;
RETURN (1) ;
READCMEM ($W2047,[MV],1) ;
$W2047=$W2047+10; *1*1: +10 is the increment/decrement for each button.
IF ($W2047 > 32000)
$W2047 = 32000;
ENDIF
IF ($W2047 < -32000)
$W2047 = -32000;
ENDIF
WRITECMENE ([MV],$W2047,1) ;
endif
25: MV Bar Scale Display
The MV bar display and MV index position include fixed marks in the graphic
indicating 0%, 50%, and 100%.
The following diagram shows a face plate for Basic PID built using the Face
Plate Auto-Builder for NS in a 640×480 screen resolution.
The whole face is built using 458×142 dots.
41
Basic PID (Block Model 011)Section 6-1
The display and operation of each object in the face plate is the same as the
version for 800×600 screen resolution.
6-1-2Tuning Screens
The following screen is a Tuning Screen for Basic PID built using the Face
Plate Auto-Builder for NS in an 800×600 screen resolution.
2
1
4
5
3
9
8
6
7
42
Basic PID (Block Model 011)Section 6-1
1: Status
This button is used to switch between the statuses for Stop Block Operation
Command (tag ITEM MT_ST (ITEM 000)), Alarm Stop Switch (tag ITEM AOF
(ITEM 017)), and AT Command/AT Executing (tag ITEM AT (ITEM 035)).
Each button is built as an alternate ON/OFF Button, and using an Alternate
Simple Rectangle (Type 2), as shown in the following table.
ButtonTag
ITEM
Stop block
operation
command
Alarm
stop
switch
AT command/ AT
executing
MT_ST
(ITEM
000)
AOF
(ITEM
017)
AT
(ITEM
035)
The read address is set as the display address and the write address is set as
write address 1.
Color
(OFF)
GrayYellowOperating Operation
GrayYellowAlarm ON Alarm dis-
GrayYellowAT OFFAT ONYes
Color
(ON)
Label
(OFF)
Label
(ON)
stopped
abled
Ye s
“OK?”
Ye s
“OK?”
“The MV will
change is AT is
executed/stopped.
OK?”
Write
confirmation
message
2: Alarm Set Values
The alarm set values are displayed and set with engineering units. The following table shows the tag ITEMs used for setting alarm set values.
Alarm typeAlarm set value tag ITEM
LL (Low/low alarm) LL_SP (ITEM 011)
L (Low alarm) L_SP (ITEM 010)
H (High alarm) H_SP (ITEM 009)
HH (High/high alarm) HH_SP (ITEM 008)
DV (Deviation alarm) DVA_SP (ITEM 041)
Numeral Display and Input objects are used to create these fields, and a tenkey pad is displayed when a field is touched. The following table shows the
upper and lower limits of the setting ranges.
Alarm typeUpper limitLower limit
LL (Low/low alarm) −15% in the corresponding
engineering units
L (Low alarm) −15% in the corresponding
engineering units
H (High alarm) −15% in the corresponding
HH (High/high
alarm)
DV (Deviation alarm) 0% in the corresponding engi-
engineering units
−15% in the corresponding
engineering units
neering units
115% in the corresponding
engineering units
115% in the corresponding
engineering units
115% in the corresponding
engineering units
115% in the corresponding
engineering units
115% in the corresponding
engineering units
The engineering unit displayed for the unit as a Text object.
Data is written to the write address of each tag ITEM using the Before Writing
Numeral/String macro.
These fields are used to display and set each parameter. The following table
shows the tag ITEMs used to set these parameters.
ParameterTag ITEM
P (Proportional band) P (ITEM 054)
I (Integral time) I (ITEM 055)
D (Differential time) D (ITEM 056)
MH (High MV limit) MH_LMT (ITEM 076)
ML (Low MV limit) ML_LMT (ITEM 077)
MV index positionMV_IDX (ITEM 098)
Numeral Display and Input objects are used to create these fields, and a tenkey pad is displayed when a field is touched. The following table shows the
upper and lower limits of the setting ranges.
ParameterUpper limitLower limit
P (Proportional band) 0.1999.9
I (Integral time) 09999
D (Differential time) 09999
MH (High MV limit) −320.00320.00
ML (Low MV limit) −320.00320.00
MV index position−15.00115.00
The following table shows the units that are displayed. These units are fixed.
ParameterUnit
P (Proportional band)%
I (Integral time)S
D (Differential time)S
MH (High MV limit)%
ML (Low MV limit)%
MV index position%
The following values are used in communications between the PLC and NSseries PT.
ParameterValues used in PLC device/communications
P (Proportional band)1 to 9999 (10 x display value)
I (Integral time)0 to 9999 (same as display value)
D (Differential time)0 to 9999 (same as display value)
MH (High MV limit)Percent data
ML (Low MV limit)Percent data
MV index positionPercent data
Data is written to the write address of each tag ITEM using a Before Writing
Numeral/String macro, as follows:
Decimal Point Position of I (Integral Time) and D (Differential Time):
The decimal point position of I and D changes according to the decimal point
position in the CSV tag file. The decimal point position is changed by changing the scale setting number. When the value of the decimal point position for
the CSV tag file is 0, the scale setting number is set to not be changed, and
when the value is 1, the scale setting is set to a factor of 0.1.
4: Realtime Trend Graph
The tag ITEMs PV (ITEM 007), SP (ITEM 029), and MV (ITEM 089) are displayed in graph format. Each tag ITEM is depicted by a line in the graph
according to the following table.
The line color of each tag ITEM is indicated using a Text object and a Rectangle (PV: Green; SP: Yellow; MV: Light blue).
Maximum
value
Line styleMarkerStep
display
6: Switch to Control Screen Button
Touch this button to switch to the Control Screen that includes the tag name of
the Tuning Screen. This button is created as a Command Button.
7: Realtime Trend Graph Scale
Fixed marks on the vertical axis of the realtime trend graph indicate the gradations equivalent to 0%, 25%, 50%, 75%, and 100%. The value for each mark
is displayed in engineering units using a Text object.
8: Unit
The unit character string for the engineering unit is displayed as a Text object.
9: Face Plate Control
The contents is the same as that provided in the explanations in 6.1Basic
PID (Block Model 011) except that there is no Tuning Screen Button.
The following screen is a Tuning Screen for Basic PID built using the Face
Plate Auto-Builder for NS in a 640×480 screen resolution.
45
Advanced PID (Block Model 012)Section 6-2
The unit display for the alarm set values is restricted to a maximum of four
characters.
6-2Advanced PID (Block Model 012)
This section describes only the differences between the Advanced PID and
Basic PID (Block Model 011). For details on the areas not covered here, refer
to 6-1 Basic PID (Block Model 011).
6-2-1Face Plates
The face plates are exactly the same as for Basic PID (Block Model 011).
46
Advanced PID (Block Model 012)Section 6-2
6-2-2Tuning Screens
The Tuning Screens are almost the same as for Basic PID (Block Model 011)
except for the addition of a manual reset parameter setting.
Manual reset
The details of the manual reset parameter are as follows:
ParameterAlarm set value tag ITEM
Man. resetMRT (ITEM 057)
A Numeral Display and Input is used to create this field, and a ten-key pad is
displayed when the field is touched. The following table shows the upper and
lower limits of the setting range.
ParameterUpper limitLower limit
Man. reset−320.00320.00
The following table shows the unit display, which is fixed.
ParameterUnit
Man. reset%
The following values are used in communications between the PLC and NSseries PT.
ParameterValues used in PLC device/
communications
Man. resetPercent data
Data is written to the write address of tag ITEM MRT using the Before Writing
Numeral/String macro, as follows:
The Tuning Screen for Advanced PID built with the Face Plate Auto-Builder for
NS in a 640×480 screen resolution is almost the same as for Basic PID, except
for the addition of a manual reset parameter setting.
47
Two-position ON/OFF (Block Model 001)Section 6-3
Manual reset
6-3Two-position ON/OFF (Block Model 001)
6-3-1Face Plates
This section describes only the differences between the 2-position ON/OFF
and Basic PID (Block Model 011). For details on the areas not covered here,
refer to 6-1 Basic PID (Block Model 011).
The face plates are almost the same as for Basic PID (Block Model 011)
except that MV has two positions.
3
4
In the graphic display, 2 is
1
2
displayed as follows:
48
Two-position ON/OFF (Block Model 001)Section 6-3
1: MV Status Display
The status is displayed according to the contact information of tag ITEM MV
(ITEM 093), as shown in the following table.
LampColor
Red: MV (ITEM 093) is OFF.
Green: MV (ITEM 093) is ON.
Red: MV (ITEM 093) is ON.
Green: MV (ITEM 093) is OFF.
These objects are created as rectangular Bit Lamp objects.
2: Switch to MV Buttons
These buttons switch the Contact information of tag ITEM MV (ITEM 093).
ButtonOperation
Turns OFF MV (ITEM 093).
Turns ON MV (ITEM 093).
These buttons are created as momentary ON/OFF Buttons, using a Select
Shape of type 1, and with no write address set. (Macros are used to write
data.)
The button surface is displayed according to the Select Shape graphic.
When the button is touched, the tag ITEM A/M_SW (ITEM 086) is referenced,
and if the value is 1, a message is displayed indicating that setting is not possible, and setting is disabled.
This function is set using the following macro as a Touch OFF Timing macro
for ON/OFF Buttons.
for 0.
for 1.
3: Status Display 2
The MV error indication (tag ITEM MV_ABN) is not provided with 2-position
ON/OFF, so the PV error status is only displayed. The status character string
displayed is determined by the value of tag ITEM PV_ABN.
DisplayPV_ABN (ITEM 019)
(No characters
displayed)
PV error indication1
0
49
Two-position ON/OFF (Block Model 001)Section 6-3
This field is created as an ON/OFF Button using a Select Shape of type 2 to
switch to display of PV error indication characters. Control Flag input is disabled.
4: Alarm Status Display
MH and ML are not provided with 2-position ON/OFF. The other settings are
the same as for Basic PID.
The following diagram is a face plate for 2-position ON/OFF built with the Face
Plate Auto-Builder for NS in a 640×480 screen resolution. The whole face is
built using 458×142 dots.
The display and operation of each object in the face plate is the same as the
version for 800×600 screen resolution.
6-3-2Tuning Screens
The Tuning Screens for 2-position ON/OFF are almost the same as for Basic
PID (Block Model 011), except for the following differences.
1. A setting field for each parameter is not provided.
2. AT is not supported.
3. MV is not included in the realtime trend graph.
4. The face plate is for 2-position ON/OFF.
50
Three-position ON/OFF (Block Model 002)Section 6-4
The following screen is a Tuning Screen for 2-position ON/OFF built using the
Face Plate Auto-Builder for NS in a 640×480 screen resolution.
The display and operation of each object in the face plate is the same as the
version for 800×600 screen resolution.
A setting field for each parameter is not provided, so up to eight characters can
be displayed for the unit character string for 2-position ON/OFF, instead of the
four characters for Basic PID.
6-4Three-position ON/OFF (Block Model 002)
This section describes only the differences between the 3-position ON/OFF
and Basic PID (Block Model 011). For details on the areas not covered here,
refer to 6-1 Basic PID (Block Model 011).
6-4-1Face Plates
The face plates are almost the same as for Basic PID (Block Model 011)
except that the format of MV has three positions.
51
Three-position ON/OFF (Block Model 002)Section 6-4
3
4
In the graphic display, 2 is
1
2
1: MV Status Display
The status is displayed according to the contact information of tag ITEM MVH
(ITEM 093) and MVL (ITEM 095), as shown in the following table.
LampColor
Red: MVH (ITEM 093) is OFF and MVL (ITEM 095) is ON.
Green: Other combinations
displayed as follows:
Red: MVH (ITEM 093) is OFF and MVL (ITEM 095) is OFF.
Green: Other combinations
Red: MVH (ITEM 093) is ON and MVL (ITEM 095) is OFF.
Green: Other combinations
These lamps are built as ON/OFF Buttons using Simple Rectangles (Type 3).
A Control Flag is set to disable input.
2: Switch to MV Buttons
These buttons switch the contact information of tag ITEM MV (ITEM 093).
ButtonOperation
Turns OFF MVH (ITEM 093) and turns
ON MVL (ITEM 095).
Turns OFF MVH (ITEM 093) and turns
OFF MVL (ITEM 095).
Turns ON MVH (ITEM 093) and turns
OFF MVL (ITEM 095).
These buttons are created as momentary ON/OFF Buttons using a Select
Shape of type 1, and with no write address set. (Macros are used to write
data.)
The button is displayed as a Select Shape graphic.
When the buttons are touched, tag ITEM A/M_SW (ITEM 086) is referenced,
and when the value is 1, a message is displayed indicating that the value cannot be set, and setting is disabled.
52
Three-position ON/OFF (Block Model 002)Section 6-4
This function is set using the following macro as a Touch OFF Timing macro
for ON/OFF Buttons.
RE ADCME M($B32761,[A/M _SW],1);
if($B32761==1)
MSGBOX("Can not set.","MV cha nge.",0);
RETURN(1);
else
$B32764=0;
$B32765=0;
WRITE CME M([MVH ],$B3 276 4,1);
WRITE CME M([MVL ],$B 327 65,1);
endif
When this button is
pressed, $B32764=0
and $B32765=1.
When this button is
pressed, $B32764=0
and $B32765=0.
When this button is
pressed, $B32764=1
and $B32765=0.
Note When the Switch to MV Button for 3-position ON/OFF is operated, the MV sta-
tus display may fluctuate temporarily due to the macro execution order and
execution time. The MV status display will eventually stabilize.
3: Status Display 2
The MV error indication (tag ITEM MV_ABN) is not provided with 3-position
ON/OFF, so the PV error status is displayed only.
The status character string displayed is determined according to the value of
tag ITEM PV_ABN.
DisplayPV_ABN (ITEM 019)
(No characters displayed.) 0
PV error indication1
This field is created as an ON/OFF Button using a Select Shape of type 1 and
switches to display PV error indication characters. Control Flag input is disabled.
4: Alarm Status Display
MH and ML are not provided with 3-position ON/OFF. The other settings are
the same as for Basic PID.
The following diagram shows a face plate for 3-position ON/OFF built with the
Face Plate Auto-Builder for NS in a 640×480 screen resolution. The whole
face is built using 458×142 dots.
53
Three-position ON/OFF (Block Model 002)Section 6-4
The display and operation of each object in the face plate is the same as the
version for 800×600 screen resolution.
6-4-2Tuning Screens
The Tuning Screens for 3-position ON/OFF are almost the same as for Basic
PID (Block Model 011), except for the following differences.
1. A setting field for each parameter is not provided.
2. AT is not supported.
3. MV is not included in the realtime trend graph.
4. MV is not included in the realtime trend graph.
5. 4.The face plate is for 3-position ON/OFF.
54
The following screen is a Tuning Screen for 3-position ON/OFF built using the
Face Plate Auto-Builder for NS in a 640×480 screen resolution.
Indication and Operation (Block Model 032)Section 6-5
The display and operation of each object in the face plate is the same as the
version for 800×600 screen resolution.
A setting field for each parameter is not provided, so up to eight characters can
be displayed for the unit character string for 3-position ON/OFF, instead of the
four characters for Basic PID.
6-5Indication and Operation (Block Model 032)
This section describes only the differences between the Indication and Setting
and Basic PID (Block Model 011). For details on the areas not covered here,
refer to 6-1 Basic PID (Block Model 011).
6-5-1Face Plates
The face plates are almost the same as for Basic PID (Block Model 011),
except for the following aspects.
• The SP is X1 (Auto input) and read-only (no SP Change Button provided).
• A deviation alarm (DV) is not provided.
• Remote mode is not supported.
55
Indication and Operation (Block Model 032)Section 6-5
1
2
3
5
4
The actual graphic display is shown below.
1: Status Display
Either AUTO or MAN is displayed. CAS (Remote and Auto) mode is not supported, which is different from Basic PID.
The status character string displayed is determined by the value of tag ITEM
A/M_SW. (R/L_SW is not referenced, which is different from Basic PID.)
DisplayA/M_SW (ITEM 086)
MAN0
AUTO1
This field is created as an ON/OFF Button using a Select Shape of type 2 and
switches to display AUTO/MAN characters. Control Flag input is disabled.
2: Alarm Status Display
Indication and Setting does not provide a deviation alarm, so there is no display.
3: Auto Input
The fixed characters “X1” are displayed as a Text object. The numeral display
field is display-only. (A Control Flag is set to disable input.)
The numeral display for X1 uses an engineering unit.
4: Switch to AUTO Button
This button switches operation to Auto mode and is displayed in red during
Auto mode.
The button is created as a momentary ON/OFF Button using a Simple Rectangle (Type 2), and the display color is determined according to the following
table.
56
Indication and Operation (Block Model 032)Section 6-5
(R/L_SW is not referenced, which is different from Basic PID.)
Display colorA/M_SW (ITEM 086)
Ye l l o w0
Red1
The label displays “AUTO” in the rough font.
By setting the following Touch OFF Timing macro, operation will switch to Auto
mode when touched.
$B32761=1;
WRITECMEM ([A/M_SW],$B32761,1) ;
This button is always displayed, without setting a Control Flag to disable the
display and input.
5: Switch to MAN Button
This button switches operation to manual mode and is displayed in red during
manual mode. The button is created as a momentary ON/OFF Button using a
Simple Rectangle (Type 2), and the display color is determined according to
the following table.
(The R/L_SW is not referenced, which is different from Basic PID.)
Red colorA/M_SW (ITEM 086)
Red0
Ye l l o w1
The label displays “MAN” in the rough font.
By setting the following Touch OFF Timing macro, operation switches to man-
ual mode when touched.
$B32761=0;
WRITECMEM ([A/M_SW],$B32761,1) ;
This button is always displayed, without setting a Control Flag to disable the
display and input.
6: SP Change Button and Switch to CAS Button
Indication and Setting does not provide an SP Change Button or Switch to
CAS Button.
The following diagram shows an Indication and Setting face plate built using
the Face Plate Auto-Builder for NS in a 640×480 screen resolution.
The whole face is built using 458×142 dots.
57
Indication and Operation (Block Model 032)Section 6-5
The display and operation of each object in the face plate is the same as the
version for 800×600 screen resolution.
6-5-2Tuning Screens
The Tuning Screens for Indication and Setting are almost the same as for
Basic PID (Block Model 011), except that it does not provide PID or AT.
4
1
3
2
1: AT
Indication and Setting does not provide an AT Button.
58
2: PID
Indication and Setting does not provide PID parameter settings.
3: Realtime Trend
Indication and Setting displays the tag ITEM X1 (ITEM 084) as a graph, and
not SP.
Indicator (Block Model 034)Section 6-6
4: Alarm Settings
The Indication and Setting does not provide a deviation alarm setting.
The following screen is a Tuning Screen for the Indication and Setting face
plate built using the Face Plate Auto-Builder for NS in a 640×480 screen resolution.
The display and operation of each object in the face plate is the same as the
version for 800×600 screen resolution.
6-6Indicator (Block Model 034)
This section describes only the differences between the Indicator and Basic
PID (Block Model 011). For details on the areas not covered here, refer to 6-1Basic PID (Block Model 011).
6-6-1Face Plates
The face plates are almost the same as for Basic PID (Block Model 011),
except that the Indicator does not provide functions related to SP and MV, and
it is used as a PV Indicator Operator Interface.
59
Indicator (Block Model 034)Section 6-6
1
2
3
4
5
1: Status Display
Indicator does not display the AUTO, MAN, and CAS status.
The PV error indication status is displayed. The status character string dis-
played is determined by referencing the value of tag ITEM PV_ABN.
DisplayPV_ABN (ITEM 019)
(No characters displayed.)
PV error indication1
0
These buttons are ON/OFF Buttons using a Select Shape of type 1 and switch
to display the PV error indication characters. Control Flag input is disabled.
Indicator does not display an MV error indication.
2: Alarm Display
Indicator does not use the DV, MH, or ML alarms.
3: SP
Indicator does not provide an SP.
4: Switch to CAS/MAN/AUTO Button, SP Bar Display, and SP Change
Button
The Indicator does not provide a Switch to CAS/MAN/AUTO Button, SP bar
display, or Change SP Button.
5: MV and MV Index Position
The Indicator does not provide an MV or MV index position.
The following diagram shows face plate for the Indicator built using the Face
Plate Auto-Builder for NS in a 640×480 screen resolution.
The whole face is built using 458×142 dots.
60
Indicator (Block Model 034)Section 6-6
The display and operation of each object in the face plate is the same as the
version for 800×600 screen resolution.
6-6-2Tuning Screens
The Tuning Screens for Indicator are almost the same as for Basic PID (Block
Model 011), except that it does not provide SP or MV functions, and is used
as a PV Indicator Operator Interface.
1
2
4
3
1: AT
The Indicator does not provide an AT Button.
2: DV
The Indicator does not provide a deviation alarm setting.
61
Segment Program 2 (Block Model 157)Section 6-7
3: Parameters
The Indicator does not provide parameter settings.
4: Realtime trend
The Indicator displays a graph for PV only.
The following screen is a Tuning Screen for the Indicator face plate built using
the Face Plate Auto-Builder for NS in a 640×480 screen resolution.
The display and operation of each object in the face plate is the same as the
version for 800×600 screen resolution.
Indicator does not provide a setting field for each parameter, so up to eight
characters can be displayed for the unit character string, instead of the four for
Basic PID.
6-7Segment Program 2 (Block Model 157)
This section describes only the differences between the Segment Program 2
and Basic PID (Block Model 011). For details on the areas not covered here,
refer to 6-1 Basic PID (Block Model 011).
62
Segment Program 2 (Block Model 157)Section 6-7
6-7-1Face Plates
1
2
4
3
5
6
7
11
112
15
9
8
10
13
14
16
1: Status Display and Alarm Display
Segment Program 2 does not provide an alarm display. The X1 input error
(tag ITEM U1 (ITEM 015: X1 input error)) is displayed as the status display.
DisplayU1 (ITEM 015)
NR1
(No characters displayed.) 0
These fields are created as ON/OFF Buttons with a Select Shape of type 1
and are used to switch to the PV error indication characters. Control Flag
input is disabled.
2: X1 Display
The fixed string “X1” is displayed as a Text object.
3: X1 Numeral Display
A Numeral Display and Input object is used to display in engineering units the
value for tag ITEM X1 (ITEM 007: Reference input). A Control Flag is set to
disable input.
4: Y1 Display
The fixed string “Y1” is displayed as a Text object.
5: Y1 Numeral Display
A Numeral Display and Input object is used to display in engineering units the
value for tag ITEM Y1 (ITEM 008: Program input). A Control Flag is set to disable input.
6: Alarm Setting
Segment Program 2 does not provide a bar graph for the alarm settings.
7: X1 Bar Display
A Level Meter object is used to display tag ITEM X1 (ITEM 007: Reference
input). The meter color is green, maximum value is 11500 (115%), and minimum value is −1500 (−15%). The bar is set to display the zero point.
63
Segment Program 2 (Block Model 157)Section 6-7
8: Y1 Bar Display
A Level Meter object is used to display tag ITEM Y1 (ITEM 008: Program output). The meter color is yellow, maximum value is 11500 (115%), and minimum value is −1500 (−15%). The bar is set to display the zero point.
9: WAIT Button
When touched, 1 is set in the write address for tag ITEM S3 (ITEM 017).
When tag ITEM U10 (ITEM 019), Waiting, is 0, the button is yellow, and when
the value is 1, the button is displayed in red.
The button is built using a momentary ON/OFF Button with a Simple Rectangle (Type 2). The write address for tag ITEM S3 (ITEM 017) is set as the write
address, and the read address for tag ITEM U10 (ITEM 019) is set as display
address 1. The label displays “WAIT” in the rough font.
10: ADV Button
When touched, 1 is set in the write address for tag ITEM S4 (ITEM 018) step
command. Tag ITEM S4 (ITEM 018) is displayed in yellow when the value is
0, and in red when the value is 1.
The button is built as a momentary ON/OFF Button using a Simple Rectangle
(Type 2). The write address for tag ITEM S4 (ITEM 018) is set as the write
address, and the read address for tag ITEM S4 (ITEM 018) is set as display
address 1. The label displays “ADV” in the rough font.
11: START Button
When touched, 1 is set in the write address for tag ITEM S1 ITEM013, Run/
stop command. Tag ITEM S1 (ITEM 013) is referenced and the color is displayed according to the following table.
S1 (ITEM 013) valueColor
0Yellow
1Red
The button is built as a momentary ON/OFF Button using a Simple Rectangle
(Type 2). The write address is not set, and the read address for tag ITEM S1
(ITEM 013) is set as display address 1. The label displays “START” in the
rough font.
The following macro is set as a Touch OFF Timing macro, and when touched,
the fixed value 1 is written to the write address of tag ITEM S1 (ITEM 013).
$B32766=1;
WRITECMEM ([S1],$B32766,1) ;
12: STOP Button
When touched, 0 is set in the write address for tag ITEM S1 (ITEM 013), Run/
stop command. Tag ITEM S1 (ITEM 013) is referenced and the color is dis-
played according to the following table.
S1 (ITEM 013) valueColor
0Red
1Yellow
64
The button is built as a momentary ON/OFF Button with a Simple Rectangle
(Type 2). The write address is not set, and the read address for tag ITEM S1
(ITEM 013) is set as display address 1. The label displays “STOP” in the
rough font.
Segment Program 2 (Block Model 157)Section 6-7
The following macro is set as a Touch OFF Timing macro, and when touched,
the fixed value 0 is written to the write address of tag ITEM S1 (ITEM 013).
$B32766=0;
WRITECMEM ([S1],$B32766,1) ;
13: CONT Button
When touched, 0 is set in the write address for tag ITEM S2 (ITEM 014: Hold
switch). Tag ITEM S2 (ITEM 014) is referenced and the color is displayed
according to the following table.
S2 (ITEM 014) valueColor
0Red
1Yellow
The button is built as a momentary ON/OFF Button using a Simple Rectangle
(Type 2). The write address is not set, and the read address for tag ITEM S2
(ITEM 014) is set as display address 1. The label displays “CONT” in the
rough font.
The following macro is set as a Touch OFF Timing macro, and when touched,
the fixed value 0 is written to the write address of tag ITEM S2 (ITEM 014).
$B32767=0;
WRITECMEM ([S2],$B32767,1) ;
A Control Flag is used to reference tag ITEM S1 (ITEM 013), Run/stop command. If the value is 0, no display/input disabled is set.
14: PAUSE Button
When touched, 1 is set in the write address for tag ITEM S2 (ITEM 014), Hold
switch. Tag ITEM S2 (ITEM 014) is referenced and the color is displayed
according to the following table.
S2 (ITEM 014) valueColor
0Yellow
1Red
The button is built as a momentary ON/OFF Button using a Simple Rectangle
(Type 2). The write address is not set, and the read address for tag ITEM S2
(ITEM 014) is set as display address 1. The label displays “PAUSE” in the
rough font.
The following macro is set as a Touch OFF Timing macro, and when touched,
the fixed value 1 is written to the write address of tag ITEM S2 (ITEM 014).
$B32767=1;
WRITECMEM ([S2],$B32767,1) ;
A Control Flag is used to reference tag ITEM S1 (ITEM 013: Run/stop command). If the value is 0, no display/input disabled is set.
15: STEP Display
The fixed string “STEP” is displayed as a Text object.
65
Segment Program 2 (Block Model 157)Section 6-7
16: STEP Numeral Display
A Numeral Display and Input object is used to display the value for tag ITEM
Y3 (ITEM 011: Step output). A Control Flag is set to disable input.
Tag ITEM Y3 (ITEM 011) uses values 1 to 30 from the PLC device/communications, but the PLC or communications values are displayed with 2 integer
digits and 0 digits below the decimal point, without scaling the values on the
display.
Other Settings
Segment Program 2 does not provide an MV display, MV index position, SP
Change Button, or MV Change Button.
The following diagram shows the face plate for Segment Program 2 built with
the Face Plate Auto-Builder for NS in a 640×480 screen resolution. The whole
face is built using 458×142 dots.
The display and operation of each object in the face plate is the same as the
version for 800×600 screen resolution.
66
Segment Program 2 (Block Model 157)Section 6-7
6-7-2Tuning Screens
2
1
3
4
5
1: Status Display
This button switches the status between the status of the Stop block operation
command (tag ITEM MT_ST (ITEM 000)) and Disable Reference Input Switch
(tag ITEM S5 (ITEM 020)).
These buttons are built as alternate ON/OFF Buttons using Simple Rectangles (Type 2), according to the information in the following table.
ButtonTag
ITEM
Stop block
operation
command
Disable
reference
input
MT_ST
(ITEM
000)
S5
(ITEM
020)
OFF
color
GrayYellowOperating Sus-
GrayYellowRef. ONRef. OFFYes
ON
color
OFF label ON labelWrite
pended
Ye s
“OK?”
“OK?”
confirmation
message
The read address is set in the display address and the write address is set in
write address 1.
2: Alarm Setting/Parameters
Segment Program 2 does not provide alarm settings or parameter settings.
3: Realtime Trend Graph
Tag ITEM X1 (ITEM 007) and tag ITEM Y1 (ITEM 008) are displayed as
graphs.
Each tag ITEM is drawn using the following graph lines.
The realtime trend graph line color is indicated using a Text object and a Rectangle. (X1: Green Y1: Yellow)
5: Detail Setting
This button opens the Detail Setting Screen for Segment Program 2. This button is created only when the Enable for Making Detail Setting Screen of Seg-ment Program 2 option is selected in the build conditions.
The following screen is the Tuning Screen for Segment Program 2 built using
Face Plate Auto-Builder for NS in a 640×480 screen resolution.
The display and operation of each object in the face plate is the same as the
version for 800×600 screen resolution.
6-7-3Detail Setting Screens
Detail Setting Screens are created only when the Enable for making detail
setting screen of Segment Program 2 option is selected under the build conditions. For details, refer to Enable for Making Detail Setting Screen of SegmentProgram 2 (Project Version 4 or Later) on page 17.
68
Segment Program 2 (Block Model 157)Section 6-7
■ Time Width-Output Value Setting Screen
1234567
1: Time Width, Output Value, and Unit
The time width, output value, and unit are set for each step.
The unit is selected from a drop-down list. The time width and output value
are input from the ten-key pad. The time width and output value field will automatically open for ten-key pad when clicked.
2: Read Button
This button reads the setting and current values for reference input values,
output values, and steps for the Segment Program 2 function blocks set in the
Loop Control Board/Unit.
Any settings made on the screen will be discarded if the Read Button is
clicked before clicking the Write Button.
3: Write Button
The button writes the settings made on the screen to the Loop Control Board/
Unit.
Note Be sure to check the affect on the controlled system of any changes to be
made before actually writing them to the Loop Control Board/Unit.
4: Backup Button
This button backs up data during operation. This is performed to back up
changed settings to the flash memory in the Loop Control Board.
The backup during operation function backs up the function blocks in the RAM
in the Loop Control Board to the flash memory in the Loop Control Board. A
CS1W-LCB01/05 Loop Control Board Ver. 1.5 or later or a CS1D-CPU@@P
Process-control CPU Unit is required to back up data during operation.
5: Scale Buttons
These buttons are used to change the scale of the output value axis (i.e.,
Scale on the Time Width-Output Value Setting Screen). Either a 0 to 100.0
(Scale 1) or a -300.0 to 300.0 (Scale 2) can be selected.
69
Indication and Setting (Block Model 031)Section 6-8
6: Wait Setting Button
This button displays the Wait Width Setting Screen for Segment Program 2.
7: Return Button
This button displays the Tuning Screen for Segment Program 2.
■ Wait Width Setting Screen
1234
1: Wait Width and Wait Time
The wait width and maximum wait time are input for each step. The ten-key
pad is used, just as it was for the Time Width-Output Value Setting Screen.
2: Read Button, 3: Write Button, and 4: Backup Button
The functions of these buttons are the same as those on the Time Width-Output Value Setting Screen.
6-8Indication and Setting (Block Model 031)
This section describes only the differences between the Indication and Setting
Block and Basic PID Block (Block Model 011). For details on the areas not
covered here, refer to 6-1 Basic PID (Block Model 011).
6-8-1Face Plates
The face place for the Indication and Setting Block is almost the same as the
one for the Basic PID Block (Block Model 011), except that the Indication and
Setting Block face plate does not have the MV-related functions and the SP
can be switched between LOCAL and CAS.
70
Indication and Setting (Block Model 031)Section 6-8
1
2
3
1: Status Display
Either CAS or LOCAL status is displayed. The value of tag ITEM R/L_SW
determines the status character string display.
DisplayR/L_SW (026)
LOCAL0
CSS1
This button is created as an ON/OFF Button using a Simple Rectangle (Type
1) to switch the label ON/OFF.
Control Flag input is disabled.
2: LOCAL Button
The LOCAL Button is displayed in red while in Local mode.
This button is set as a momentary ON/OFF Button using a Simple Rectangle
(Type 1), and the background color is determined according to the following
table.
Display colorR/L_SW (026)
Red0
Ye l l o w1
The label displays “LOCAL” in the rough font.
By setting a Touch OFF Timing macro as shown below, operation will switch
to Local mode when touched.
$B32760=0;
WRITECMEM ([R/L_SW],$B32760,1);
This button is always displayed, without setting a Control Flag to disable the
display and input, which is different from the Switch to CAS Button.
71
Indication and Setting (Block Model 031)Section 6-8
3: MV Display, MV Change Button, and MV Index Position
The Indication and Setting face plate does not provide an MV display, MV
Change Button, or MV index position.
The following diagram shows an Indication and Setting face plate built using
the Face Plate Auto-Builder for NS in a 640×480 screen resolution.
The whole face is built using 458×142 dots.
The display and operation of each object in the face plate is the same as the
version for 800×600 screen resolution.
6-8-2Tuning Screens
The Tuning Screen for the Indication and Setting Block is almost the same as
the one for the Basic PID Block (Block Model 011), except this screen does
not have the MV-related functions and the SP can be switched between
LOCAL and CAS.
72
1: AT
The Indication and Setting Block does not provide an AT Button.
2: DV
The Indication and Setting Block does not provide a deviation alarm setting.
Ratio Setting (Block Model 033)Section 6-9
3: Parameters
The Indication and Setting Block does not provide parameter settings.
4: Realtime trend
The Indication and Setting Block displays a graph for PV only.
The following screen is a Tuning Screen for an Indication and Setting face
plate built using the Face Plate Auto-Builder for NS in a 640×480 screen resolution.
The display and operation of each object in the face plate is the same as the
version for 800×600 screen resolution.
6-9Ratio Setting (Block Model 033)
This section describes only the differences between the Ratio Setting Block
and Basic PID Block (Block Model 011). For details on the areas not covered
here, refer to 6-1 Basic PID (Block Model 011).
6-9-1Face Plates
The Ratio Setting Block is used to set the ratio and bias and has PV-indicating
and ratio-setting functions.
1
2
3
1: Alarm Status Display
Unlike the Basic PID Block, this block does not output any of the high/low PV
alarms or the MV output's deviation alarm.
73
Ratio Setting (Block Model 033)Section 6-9
2: SP Numerical Value Display and Input
This field sets the Ratio Setting SP. Settings from 0 to 1 represent 0.00% to
100.00% and the value multiplied by the K1 ratio (−10.00 to 10.00) can be set
and displayed.
Touch this field to display a ten-key pad below it.
Writing is performed for tag ITEM SP_W (ITEM 023) using the Before Writing
Numeral/String macro condition. The calculation given above is reversed and
the result (percent data) is written.
• Unit scale setting: Multiplier fixed at 0.01 and offset fixed at 0
• Input upper/lower limits: Upper limit fixed at 1,000 and lower limit fixed at
−1,000
• Macro: The Before Writing Numeral/String macro is set as follows:
When the ten-key pad is displayed, the tag ITEMs R/L_SW and CAS_SET are
referenced and if R/L_SW is 1 and CAS_SET is 1, a message is displayed
indicating that the SP cannot be set, and input is disabled. (The operation of
this error message is the same in the Basic PID Block (Block Model 011).)
3: SP Setting Scale
The upper limit of the scale displays the ITEM K1 value from the SP Numerical Value Display and Input Field.
• Unit scale setting: Multiplier fixed at 0.001 and offset fixed
• Display: The display is decimal, one-word signed INT, and displayed with
a precision of 1/100 (@@.@@) in the rough font. A Control Flag is set to
disable input without displaying a surrounding box.
• Communications address: Set K1 (054).
The lower limit of the scale fixes the label at 0.00 is displayed in the rough
font.
The following diagram shows a Ratio Setting face plate built using the Face
Plate Auto-Builder for NS in a 640×480 screen resolution.
The whole face is built using 458×142 dots.
74
Ratio Setting (Block Model 033)Section 6-9
The display and operation of each object in the face plate is the same as the
version for 800×600 screen resolution.
6-9-2Tuning Screen
The parameters required to operate the Ratio Setting Block can be set on this
tuning screen.
7
1
3
1: AT
The Ratio Setting Block does not provide an AT Button.
2: Alarm Setting
The Ratio Setting Block does not provide alarm settings.
3: Parameter Settings
These fields are used to display and set each parameter.
ML (Low MV limit)ML_LMT(ITEM077)
MV index positionMV_IDX(098)
Numeral Display and Input objects are used to create these fields, and a tenkey pad is displayed when a field is touched.
The following table shows the upper and lower limits of the setting ranges.
ParameterLower limitUpper limit
Ratio range−10.00010.000
Input bias−320.00320.00
Output bias−320.00320.00
MH (High MV limit)−320.00320.00
ML (Low MV limit)−320.00320.00
MV index position−15.00115.00
The following table shows the units that are displayed. These units are fixed.
ParameterUnit
Ratio rangeNone
Input bias%
Output bias%
MH (High MV limit)%
ML (Low MV limit)%
MV index position%
The following values are used in communications with the PLC.
ParameterValues used in PLC device/communications
Ratio range−10,000 to 10,000 (Displayed value × 1,000)
Input biasPercent data
Output biasPercent data
MH (High MV limit)Percent data
ML (Low MV limit)Percent data
MV index positionPercent data
Data is written to the write address of each tag ITEM using a Before Writing
Numeral/String macro, as follows:
The following screen is a Tuning Screen for a Ratio Setting face plate built
using the Face Plate Auto-Builder for NS in a 640×480 screen resolution.
76
High/Low Alarm (Block Model 111)Section 6-10
The display and operation of each object in the face plate is the same as the
version for 800×600 screen resolution.
6-10High/Low Alarm (Block Model 111)
6-10-1 Face Plates
This section describes only the differences between the High/Low Alarm
Block and Basic PID Block (Block Model 011). For details on the areas not
covered here, refer to 6-1 Basic PID (Block Model 011).
The High/Low Alarm Block indicates when the PV input (X1) has exceeded
the high alarm or low alarm setting.
7
1
2
5
3
4
6
77
High/Low Alarm (Block Model 111)Section 6-10
1: Status Display
Displays the alarm status. The values of tag ITEMs U1 and U2 determine
which status character string is displayed.
DisplayU1: High alarm output (012) U2: Low alarm output (013)
NR00
L01
H10
H11
These buttons are created as ON/OFF Buttons using a Select Shape of type 3
to switch the graphic displaying the NR, H, or L characters.
Control Flag input is disabled.
2: Input Value
The fixed characters “X1” are displayed as a Text object. The numeral display
field is display-only. (A Control Flag is set to disable input.)
The numeral display for X1 uses an engineering unit.
3: H (High Alarm SV) Numerical Value Display and Input
A Numeral Display and Input object is used to display the value of tag ITEM
A1 (ITEM 009) in engineering units. Touch this field to display a ten-key pad
below it.
Data is written to the write address of tag ITEM A1 (ITEM 009) using the
Before Writing Numeral/String macro.
The upper and lower limit values are equivalent to −320% and 320% with
engineering units.
4: L (Low Alarm SV) Numerical Value Display and Input
A Numeral Display and Input object is used to display the value of tag ITEM
A2 (ITEM 010) in engineering units. Touch this field to display a ten-key pad
below it.
Data is written to the write address of tag ITEM A2 (ITEM 010) using the
Before Writing Numeral/String macro.
The upper and lower limit values are equivalent to −320% and 320% with
engineering units.
78
Timer (Block Model 205)Section 6-11
5: Alarm Setting
The alarm set values are displayed as a Bar graph. The set values for the H
and L alarms are displayed from right to left.
The set value for each alarm is displayed along with the X1 bar display on the
right side of the face plate, with the top value as 115% and the bottom value
as −15%.
Alarm type Alarm setting tag ITEM
L (Low alarm)A2 (010)
H (High alarm)A1 (009)
• The alarm settings are displayed in red.
• The maximum value displayed is 11500 (115%) and the minimum value
displayed is −1500 (−15%).
• The zero point is specified to be displayed.
6: MV Display, MV Change Button, and MV Index Position
The High/Low Alarm face plate does not provide an MV display, MV Change
Button, or MV index position.
7: Tuning Screen Button
The High/Low Alarm face plate does not provide a Tuning Screen Button.
The following diagram shows a High/Low Alarm face plate built using the Face
Plate Auto-Builder for NS in a 640×480 screen resolution.
The whole face is built using 458×142 dots.
The display and operation of each object in the face plate is the same as the
version for 800×600 screen resolution.
6-11Timer (Block Model 205)
This section describes only the differences between the Timer Block and
Basic PID Block (Block Model 011). For details on the areas not covered here,
refer to 6-1 Basic PID (Block Model 011).
79
Timer (Block Model 205)Section 6-11
6-11-1 Face Plates
The Timer indicates when a preset time has elapsed. A prediction SV can be
set for early notification.
12
1
2
3
4
5
6
7
8
9
10
11
1: Status Display
The Timer face plate does not provide a status display.
2: Y1 Value Display
A Numeral Display and Input object is used to display the value of tag ITEM
Y1 (ITEM 009).
A Control Flag is set to disable input.
3: SP Numerical Value Display and Input
A Numeral Display and Input object is used to display the value of tag ITEM
SP (ITEM 007). Touch this field to display a ten-key pad below it.
Data is written to the write address of tag ITEM SP (ITEM 007) using the
Before Writing Numeral/String macro.
A Bit Lamp indicates when the SV has been reached, as shown in the following table.
Display colorU1 (013)
Green0
Red1
6: PRSET Bit Lamp Display
A Bit Lamp indicates when the prediction value has been reached, as shown
in the following table.
Display colorU2 (014)
Green0
Red1
7: START Button
When this button is touched, the write address of tag ITEM S1 (ITEM 011) is
set to 1. The value of tag ITEM S1 (ITEM 011) is referenced to set the display
color, as shown in the following table.
Display colorS1 (011)
Ye l l o w0
Red1
The button is built as a momentary ON/OFF Button using a Simple Rectangle
(Type 2). The write address is not set, and the read address for tag ITEM S1
(ITEM 011) is set as display address 1. The label displays “START” in the
rough font.
The following macro is set as a Touch OFF Timing macro, and when touched,
the fixed value 1 is written to the write address of tag ITEM S1 (ITEM 011).
$B32766=1;
WRITECMEM([S1],$B32766,1);
8: STOP Button
When this button is touched, the write address of tag ITEM S1 (ITEM 011) is
set to 0. The value of tag ITEM S1 (ITEM 011) is referenced to set the display
color, as shown in the following table.
Display colorS1 (011)
Red0
Ye l l o w1
81
Timer (Block Model 205)Section 6-11
The button is built as a momentary ON/OFF Button using a Simple Rectangle
(Type 2). The write address is not set, and the read address for tag ITEM S1
(ITEM 011) is set as display address 1. The label displays “STOP” in the
rough font.
The following macro is set as a Touch OFF Timing macro, and when touched,
the fixed value 0 is written to the write address of tag ITEM S1 (ITEM 011).
$B32766=0;
WRITECMEM([S1],$B32766,1);
9: CONT Button
When this button is touched, the write address of tag ITEM S2 (ITEM 012) is
set to 0. The value of tag ITEM S2 (ITEM 012) is referenced to set the display
color, as shown in the following table.
Display colorS2 (012)
Red0
Ye l l o w1
The button is built as a momentary ON/OFF Button using a Simple Rectangle
(Type 2). The write address is not set, and the read address for tag ITEM S2
(ITEM 012) is set as display address 1. The label displays “CONT” in the
rough font.
The following macro is set as a Touch OFF Timing macro, and when touched,
the fixed value 0 is written to the write address of tag ITEM S2 (ITEM 012).
$B32766=0;
WRITECMEM([S2],$B32766,1);
10: PAUSE Button
When this button is touched, the write address of tag ITEM S2 (ITEM 012) is
set to 1. The value of tag ITEM S2 (ITEM 012) is referenced to set the display
color, as shown in the following table.
Display colorS2 (012)
Ye l l o w0
Red1
The button is built as a momentary ON/OFF Button using a Simple Rectangle
(Type 2). The write address is not set, and the read address for tag ITEM S2
(ITEM 012) is set as display address 1. The label displays “PAUSE” in the
rough font.
The following macro is set as a Touch OFF Timing macro, and when touched,
the fixed value 1 is written to the write address of tag ITEM S2 (ITEM 012).
$B32766=1;
WRITECMEM([S2],$B32766,1);
82
Counter (Block Model 208)Section 6-12
11: MV Display, MV Change Button, and MV Index Position
The Timer face plate does not provide an MV display, MV Change Button, or
MV index position.
12: Tuning Screen Button
The Timer face plate does not provide a Tuning Screen Button.
The following diagram shows a Timer face plate built using the Face Plate
Auto-Builder for NS in a 640×480 screen resolution.
The whole face is built using 458×142 dots.
The display and operation of each object in the face plate is the same as the
version for 800×600 screen resolution.
6-12Counter (Block Model 208)
This section describes only the differences between the Counter Block and
Basic PID Block (Block Model 011). For details on the areas not covered here,
refer to 6-1 Basic PID (Block Model 011).
83
Counter (Block Model 208)Section 6-12
6-12-1 Face Plates
The Counter counts ON/OFF transitions of a contact input and indicates when
the count exceeds the preset count SV. A prediction SV can be set for early
notification.
10
7
1
2
3
4
5
6
8
9
1: Status Display
The Counter face plate does not provide a status display.
2: Y1 Value Display
A Numeral Display and Input object is used to display the value of tag ITEM
Y1 (ITEM 009).
A Control Flag is set to disable input.
3: SP Numerical Value Display and Input
A Numeral Display and Input object is used to display the value of tag ITEM
SP (ITEM 007). Touch this field to display a ten-key pad below it.
Data is written to the write address of tag ITEM SP (ITEM 007) using the
Before Writing Numeral/String macro.