Hot Attachment of Power Supplies:
1. Unpack the power supply carefully. Inspect for any damages. If any damage is observed, do not use the power supply and call (949) 250-6510 to report the damage immediately and request a replacement unit.
2. Attach the power supply to the chassis and reconnect the 48VDC power source to the FlexPoint power supply.
3. Locate the 48VDC circuit breaker and switch the circuit breaker to the ON position.
4. Turn the FlexPoint Chassis power supply ON.
5. Observe the LED in the front of the chassis indicating that the power has been restored.
SPECIFICATIONS
Indicators:
Power ON: LED (2), Yellow, power applied
Dimensions / Weight: W:19.0"xD:7.0"xH:3.5" / 9 lb.Power: 48VDC / 3.0 Amps (for model 4386)
2ea. 48VDC / 3.0 Amps (for model 4385)
Environmental:
Temperature: 0 to 50 degrees C Humidity: 5-95% (non-condensing)
TECHNICAL SUPPORT
If you encounter problems in installing this product, contact Omnitron Tech Support: Phone: (949) 250-6510 Fax: (949) 250-6514 Address: Omnitron Systems Technology, Inc.
140 Technology Drive, #500
Irvine, CA 92618, USA E-mail: support@omnitron-systems.com URL: http://www.omnitron-systems.com
040-04385-001B 11/07
2 Omnitron Systems Technology, Inc.
It is very strongly recommended that a replacement power supply unit be installed as soon as possible in order to prevent overheating of the chassis unit.
THE POWER SUPPLIES ARE HOT-SWAPPABLE AND CAN BE REPLACED WITHOUT SHUTTING THE NETWORK DOWN. HOWEVER, WHEN REMOVING AND REPLACING A POWER SUPPL Y UNIT , THE FOLLOWING STEPS MUST BE STRICTL Y FOLLOWED IN ORDER TO PREVENT SERIOUS INJURY OR DEA TH, OR SERIOUS DAMAGE TO YOUR EQUIPMENT .
Hot Removal of Power Supplies:
1. Determine which power supply needs replacing by observing the LEDs in the front left of the chassis: the top LED indicates the power status of the right power supply (as observed from the front), the bottom LED indicates the power status of the left power supply (as observed from the front).
Notice that LED being ON indicates that the power supply is operational. The LED being OFF may indicate that the DC power is not applied, please verify that your DC power source is providing power.
2. Once you determine that your DC source is connected properly, and the power supply LED is still not ON, determine which is the failing power supply unit and proceed to the next step.
3. Locate the 48VDC circuit breaker, and switch the circuit breaker to the OFF position.
4. Remove the DC power cables of the faulty power supply from the FlexPoint power supply unit.
5. Loosen the 2 screws securing the power supply to the main chassis (observe the illustration above).
6. Remove the faulty power supply.
7
Power Supply Mounting Screws and guide pins. (2 each per unit)
Power Supply Mounting Screws and guide pins. (2 each per unit)
48V DC
DCPower Input
48VDC Present
5VDC
ON
OFF
48V DC
DCPower Input
48VDC Present
5VDC
ON
OFF
48 V
DC
DC Power Input
48 VDC Present
5 VDC
ON
OFF
Safety Considerations
Warning
The operating description in this Instruction Manual is for use by qualified personnel only. To avoid electrical shock, do not perform any servicing of this unit other than that contained in the operating instructions, unless you are qualified and certified to do so by Omnitron Systems Technology, Inc.
Caution
All user-required operations can be performed without opening the unit. Never attempt to open or remove the cover or tamper with the unit or tamper with the power supply module.
Warranty
This product is warranted to the original purchaser against defects in material and workmanship for a period of TWO YEARS from the date of shipment. A LIFETIME warranty may be obtained by the original purchaser by REGISTERING this product with Omnitron within 90 days from the date of shipment. TO REGISTER, COMPLETE AND MAIL OR F AX THE REGISTRA TION FORM INCLUDED WITH THIS INSTRUCTION MANUAL TO THE INDICATED ADDRESS. Or you may register your product on the Internet at http://www.omnitron-systems.com. During the warranty period, Omnitron will, at its option, repair or replace a product which is proven to be defective.
For warranty service, the product must be sent to an Omnitron designated facility, at Buyer’s expense. Omnitron will pay the shipping charge to return the product to Buyer’s designated US address using Omnitron’s standard shipping method.
Limitation of Warranty
The foregoing warranty shall not apply to defects resulting from improper or inadequate use and/or maintenance of the equipment by Buyer, Buyer-supplied equipment, Buyer-supplied interfacing, unauthorized modifications or tampering with equipment (including removal of equipment cover by personnel not specifically authorized and certified by Omnitron), or misuse, or operating outside the environmental specification of the product (including but not limited to voltage, ambient temperature, radiation, unusual dust, etc.), or improper site preparation or maintenance.
No other warranty is expressed or implied. Omnitron specifically disclaims the implied warranties of merchantability and fitness for any particular purpose.
Exclusive Remedies
The remedies provided herein are the Buyer’s sole and exclusive remedies. Omnitron shall not be liable for any direct, indirect, special, incidental, or consequential damages, whether based on contract, tort, or any legal theory.
Omnitron Systems Technology, Inc.3
FlexPointTM Powered Chassis
User’s Manual
GENERAL DESCRIPTION
The FlexPointTM Powered Chassis is a chassis capable of holding up to 14 FlexPointTM media converter modules. It is equipped with two power supplies in a power-redundant configuration.
This User’s Manual describes the following models:
Model Description 4385 Powered Chassis, rack-mountable chassis, 2 power supplies 4386 Powered Chassis, rack-mountable chassis, 1 power supply 4389 Power supply unit for models 4385 and 4386
6 Omnitron Systems Technology, Inc.
Cabling and Power-Up:
1. Insure that both FlexPoint Chassis power supply switches are in the OFF position.
2. Assure that the 48VDC circuit breaker can supply 3A of current per power supply.
3. Locate the 48VDC circuit breaker, and switch the 48VDC circuit breaker to the OFF position.
4. Cut the power cable to the length required.
5. Strip approximately 3/8 of an inch of insulation from the power cable wires.
6. Connect the power cables to the FlexPoint Chassis by fastening the stripped ends to the 48VDC connector.
WARNING: Note the wire colors used for making the positive, negative and
ground connections. Use the same color assignment for the connection at the circuit breaker.
7. Connect the power cable to the circuit breaker and switch the circuit breaker ON.
8. Turn both FlexPoint Chassis power supply switches on and check the power LED’s on the front panel of the powered chassis. The two LED’s should be ON.
9. Attach the L shaped tabs to the FlexPoint media converter units to be inserted into the chassis, Secure the FlexPoint module using the enclosed screws.
10. Save the unused tabs in a safe place or secure them to the chassis’ unused
Slots.
POWER SUPPLY REPLACEMENT
WARNING!
NEVER A TTEMPT T O OPEN OR SER VICE THE POWER SUPPLY UNIT. OPENING THE POWER SUPPLY UNIT
MA Y CAUSE SERIOUS INJUR Y OR DEATH.
The Powered Chassis is intended to be used with two power supplies in a power-redundant operation. A failure of a single supply should not disturb the operation of the chassis unit. However, certain power supply failures may cause a secondary failure to the associated fan and cause undesired overheating of the chassis unit.
4 Omnitron Systems Technology, Inc.
CONTROLS AND INDICATORS
LEDs Display:
The Powered Chassis features two LEDs on the left front of the chassis, these LEDs display the status of the two power supplies.
Function Color/State Description
Top LED Yellow / ON Power OK in right power supply Bottom LED Yellow / ON Power OK in left power supply
Note: Left/right direction as viewed from the front of the chassis.
SITE PREPARATION REQUIREMENTS
1. Power: Assure the 48VDC power can supply 3A of current.
2. The operating temperature of this equipment is 0-50 degrees C. If installed
in a closed or multiunit rack assembly, the operating ambient temperature of the rack must not exceed the maximum rated 50 degrees C temperature.
3. Installation of the equipment should be such that the air flow in the front
and back of the unit is not compromised or restricted.
4. Never use this equipment to carry any weight except its own, never use it as
a shelf to support weight of other equipment.
5. Installing this equipment into a rack in such a way as to make it unstable
may cause injury or death. Always make sure that the rack you are installing this equipment into is properly secure, stable, balanced and designed to carry the weight and weight distribution of this equipment.
6. When rack-mounting this equipment, the rack should be appropriately
earth-grounded.
7. This equipment requires 48 VDC / 3.0 Amps per power supply. Appropriate
overloading protection should be provided on all DC power source outlets utilized.
Omnitron Systems Technology, Inc.
8. Wiring methods used for the connection of the equipment to the primary power supply shall be in accordance with the National Electrical Code, ANSI/NFPA 70, and the Canadian Electrical Code, Part I, C22.1.
UNPACKING
a. Visual Inspection: Inspect equipment in order to detect any physical damage.
Any evidence of damage should be noted and reported immediately.
INVENTORY
Review contents, the following items should be included:
(1) FlexPoint Powered Chassis unit. (2) Power supplies (2 for model 4385, 1 for model 4386). (14) L shape tabs. (14) Screws (1) User’s manual (this document).
Please note any missing items or discrepancies and report them immediately.
INST ALLATION
WARNING: Only a DC power source that complies with safety extra low
voltage (SLEV) requirements can be connected to the DC-input power supply.
Tools and Equipment Required:
Flat-head screwdriver (not supplied) Wire cutter/stripper (not supplied) Three-conductor 14 AWG copper power cable (recommended; not supplied)
Preparation:
Assure that the FlexPoint Chassis is physically installed in accordance with the Site Preparation Requirements outlined earlier in this document.
WARNING REGARDING EARTHING GROUND:
a) This equipment shall be connected to the DC supply system earthing
electrode conductor or to a bonding jumper from an earthing terminal bar or bus to which the DC supply system earthing electrode is connected.
b) This equipment shall be located in the same immediate area (such as,
adjacent cabinets) as any other equipment that has a connection between the earthed conductor of the same DC supply circuit and the earthing conductor, and also the point of earthing of the DC system. The DC system shall not be earthed elswere.
c) The DC supply source is to be located within the same premises as this
equipment.
d) There shall be no switching or disconnecting devices in the earthed circuit
conductor between the DC source and the earthing electrode conductor.