OmniSite XR50 User Manual

USER’S GUIDE
USER’S GUIDE
USER’S GUIDE
USER’S GUIDE
XR50 User’s
Guide
203 W. Morris St. Indianapolis, IN 46225
Telephone 317-885-6330 • support@omnisite.com
www.omnisite.com
v. 2.0
XR50 User’s Guide
203 W. Morris St. Indianapolis, IN 46225
Telephone 317-885-6330 • support@omnisite.com
www.omnisite.com
v. 2.0
©2009 OmniSite OmniSite XR-50 User’s Guide 4
3 OmniSite XR-50 User’s Guide ©2009 OmniSite
NOTICE
INSPECT CONTENTS IMMEDIATELY AND FILE CLAIM WITH DELIVERING
CARRIER FOR ANY DAMAGE
SAVE THE BOX
AND
PACKING MATERIAL
YOU ARE RESPONSIBLE FOR DAMAGE TO YOUR
UNIT IF RETURNED IMPROPERLY PACKED.
Limited Warranty
If it appears within one (1) year from the date of delivery to Purchaser that any products or component parts do not conform exactly to the specifications and physical dimen­sions referred to above, and the Purchaser, at its expense, returns the product or com­ponent parts to the Seller together with a report of defects, the Seller shall review the inspection report and inspect the items and shall authorize, at its option, either the repair or replacement of any non-conforming products or component parts, whether on warranty, contract of negligence, shall not in any case exceed the amount to be paid by the Seller in obtaining and repair or replacement of non-conforming products or component parts, and upon expiration of the warranty period, all liability of the Seller shall be terminated.This warranty does not cover damage due to acts of God (fire, flood, lightning, etc.) nor product misuse and acciden­tal damage.
Seller shall not be liable for any injury, loss or damage direct or consequential arising out of the use or the ability to use the product. This warranty gives specific legal rights. You may have other rights that vary from state to state. Some states do not allow the exclusion or limitation or incidental or consequential damages, so that the above limitation of exclusion may not apply to you
WARNING: The individual user should take care to determine prior to use whether this device is suitable,
adequate or safe for the use intended. Since individual appli­cations are subject to great variation, the manufacturer makes no representation or warranty as to suitability or fitness of these devices for any specific application.
©2009 OmniSite OmniSite XR-50 User’s Guide 6
5 OmniSite XR-50 User’s Guide ©2009 OmniSite
Introduction
Congratulations - you just bought the best. The OmniSite system provides two-way communications using our patented WINGS™ (Wireless Information Network Gateway Standard) over a cellular network. The low cost of the OmniSite method makes remote monitoring very affordable, and allows our devices to operate on GSM networks worldwide.We have the most complete coverage and best reputation in the industry.
OmniSite wireless monitoring devices provide a low cost wireless system for remote monitoring, measurement, and data collection anywhere wherever there is GSM service, Worldwide.
Overview
The OmniSite XR50 is a 10-channel monitoring device that has been optimized for use by the water and wastewater utilities. It is designed for indoor or outdoor environments, and operates from 120VAC or +15-20 VDC solar panels and
WARNING: To reduce risk of fire, electric shock, or injuries
always disconnect all sources of electrical power
before servicing or cleaning.
General Safety Instructions
Safety Signal Words
Danger: means if the safety information is not followed, someone will be seriously injured or killed.
Warning: means if the safety information is not followed, someone could be seri­ously injured or killed.
Caution: means if the safety information is not followed, someone may be seriously injured or killed.
1. To reduce the risk of fire or shock hazard, connect OmniSite RTU
directly to a 120 VAC electrical circuit. Do not use extension cords for permanent installation.
2. Cover of OmniSite RTU must be securely closed to prevent water
damage and electrical shock.
3. Never operate your OmniSite RTU while any part is missing or
damaged in any manner.
4. To reduce the risk of electrical hazard or damage, do not tilt, jolt or
tip RTU while unit is powered-on.
5. To reduce the risk of accidental electrical shock, do not touch the
electrical terminals or controls with wet hands.
6. Note the warning label shown below.
©2009 OmniSite OmniSite XR-50 User’s Guide 8
7 OmniSite XR-50 User’s Guide ©2009 OmniSite
OmniSite low voltage cables should be routed inside low voltage wiring duct in your existing control panels. If you are not sure if high & low voltages are mixed inside your panel, you can always “tie-wrap” your OmniSite sensor wires to the out­side of the wiring duct. This technique still provides an attractive installation while providing suitable separation from high voltages.
CAUTION - If you mount your OmniSite RTU inside of your existing electrical cabinet, then take extra care to ensure that the antenna coaxial cable is NOT routed with high voltage cables or alarm horn power wires. This can lead to unpredictable cellular reception or damage to the radio circuitry.
OmniSite RTU's can be mounted indoors or outdoors OmniSite's cellular devices can be mounted directly outdoors (if you purchased the NEMA 4X polycarbonate enclosure option), or inside of your existing electrical control panel if room allows. A common installation technique is to mount the RTU inside the existing electric con­trol panel you are monitoring; mount our “Phantom” antenna on top of your existing panel; then connect the antenna to the RTU using an OmniSite supplied coax jumper cable. Note that your antenna must be mounted outside of any metal electrical
enclosure
Little Known Fact about Solar Power: If you are planning on using a solar array to
power the XR50, this will obviously have an impact on your installation location.A solar array must have unobstructed sunlight during the day, which means it cannot be partially covered by a leaf shadow, or shadow of any kind. Solar arrays are wired in series, and if any part of it is in a shadow, then the entire array is dead (i.e. not put-
power supplies. The module's internal cellular modem module provides two-way communications through the fully automated OmniSite operations center to the www.OmniSite.com web site.
The standard operating program of the RTU monitors all (10) digital inputs and reports any changes. This information is immediately displayed on the web site, and user selectable alarm notifications for critical events can be sent via pager, e-mail, telephone call or any combination thereof. In addition, equipment status reports can be time scheduled in advance or requested at any time.
Installation and Operation is Very Simple:
Please note that your OmniSite product is a cellular device. No matter how
good the installation looks, without cellular reception, your device will not work! Therefore, your first step is to determine that suitable cellular service is available at the installation location BEFORE you start your actual installation. Connect your OmniSite unit to a temporary extension cord, and plug it in at the installation location. Look at the cellular signal strength LED on the XR50. If it is GREEN, you have a good signal, and can proceed with installation. If NOT GREEN, call OmniSite at 317-885­6330 to determine that your cellular signal strength is suitable. Once this is verified you can move-on to installing your equipment with confidence.
Observe good wiring practices - DO NOT MIX high and low voltage wiring inside your pump control panel. This creates a situation where high voltage cables can “induce” false signals onto your low voltage OmniSite inputs.
©2009 OmniSite OmniSite XR-50 User’s Guide 10
9 OmniSite XR-50 User’s Guide ©2009 OmniSite
STEP (3) Configuring Your Equipment on the OmniSite Website
Once your installation is complete, configuring your equipment on the OmniSite website is easy:
• This is a cellular device like a telephone, and has an associated monthly cellular service fee. YOU MUST contact OmniSite at 317-885-6330 with your billing information or this unit will not transmit alarms. We will activate the cellu­lar service and provide the User ID and Password you will use to sign-on to your secure web pages.
• Sign-on to the OmniSite website at www.omnisite.com using your newly select­ed User ID and Password.
• Once signed-on select “Setup” and then “Callout list” and also “Device Setup”.
• Follow the steps on the screen to complete the alarm message delivery. OmniSite devices can automatically send emails, text messages and voice calls in any sequence in response to an alarm event. These features are configured using the website interface.
• Helpful hint - If you get stumped use the “Help” link that is at the top of each page. It has very specific information as to how to fill-out the form you are currently working-on.
Don't like computers? No problem. OmniSite will setup your alarm
message deliveries for a small fee. Simply call us at 317-885-6330. We will do the setup for you.
ting out much, if any, power). Therefore, pick your solar panel location wisely, and face it to the south at a 45 degree angle. Also, if you are using solar power you will need to configure the XR50 unit to use its low power mode. The default mode is for the cellular radio to remain powered on at all times when power is applied to the XR50 to allow remote control from the web site. In low power mode, the radio is pow­ered off after 1 minute of inactivity (see how to set low-power-mode in “Appendix A”)
STEP (1) Connect the OmniSite XR50 to the equipment to be monitored using the wiring diagrams in this manual and turn it on. The monitor will automatically establish 2 way communications over the pub­lic cellular network to the www.OmniSite.com web site.
STEP (2) Using the Local Display and Keypad
We have good news for you. If you have physically connected your field wires according to STEP-1 using the wiring diagrams in this manual, and you are using the XR50 to merely monitor alarms, and provide pump runtime and on/off cycle information, then there are not any parameters that you have to set with the local display and keypad. The XR50 default settings have been optimized for a typical sewage lift station at our factory, and it is going to work as such.
However, the XR50 does have some “neat” software features, available through the local display and keypad. If you are interested in getting “more” out of your new XR50 product, then refer to APPENDIX A - LOCAL PROGRAMMING
©2009 OmniSite OmniSite XR-50 User’s Guide 12
11 OmniSite XR-50 User’s Guide ©2009 OmniSite
1 2 3 4 5 6 7 8 9 10 + -
Dedicated Alarm Inputs
User
Selectable
Alarm
Input or
Rain
Gauge
User
Selectable
Alarm
Input or
Pulse
Counter
Reserved for
Pump 1,2, 3
Runtim e
Accumulation
Battery Backed 12VD C
L G N
XR50
P1 P2 P3
Field Jumper
1 2 3 4 5 6 7 8 9 10 + -
120 VAC Input Power
0.3 amps max
NOTE: The XR50 Universal Voltage Inputs cannot directly monitor a dr y contact. Example showes them being powered by Onboard 12VD C supply, but could be any source.
Pump 3 Run Contacts
Pump 2 Run Contacts
Pump 1 Run Contacts
Flow Meter Pulse Output
Rain Gauge Pulse Output
Each Pulse
= 0.01˝
( )
30 H Z
Max
( )
Example - Monitoring Dry, Unpowered Contacts
1 2 3 4 5 6 7 8 9 10 + -
Dedicated Alarm Inputs
User
Selectable
Alarm
Input or
Rain
Gauge
User
Selectable
Alarm
Input or
Pulse
Counter
Reserved for
Pump 1,2, 3
Runtim e
Accumulation
Battery Backed 12VD C
L G N
Any signal 12 VAC/VD C to 120 VAC/VDC. No polarity req’d. Typical for inputs 1-10
Note: Different voltages can be applied to different input channels as needed (I.E. Don’t all have to be the same)
120 VAC Input Power
0.3 amps max
XR50
1 2 3 4 5 6 7 8 9 10 + -
Wiring Diagrams
The XR50 Field Terminal Strip
©2009 OmniSite OmniSite XR-50 User’s Guide 14
13 OmniSite XR-50 User’s Guide ©2009 OmniSite
Dedicated Alarm Inputs
User
Selectable
Alarm
Input or
Rain
Gauge
User
Selectable
Alarm
Input or
Pulse
Counter
Reserved for
Pump 1,2, 3
Runtim e
Accumulation
Battery Backed
12VD C
1 2 3 4 5 6 7 8 9 10 + -
L G N
XR50
P1 P2 P3
Field Jumper
1 2 3 4 5 6 7 8 9 10 + -
D1-1
D1-2
D1-8
D1-9
X-2
X-2
X-1
X1 X2
120 VA C
CONTROL CIRCUI T
M
M
Pump-1
Starter
Pump-2
Starter
OFF
HAND
AUTO
OFF
AUTO
HAND
SEAL
FAILURE
HIGH LEVEL FLOAT
SEAL FAIL REL AY
SEAL FAILURE
LIGHT
HIGH LEVEL REL AY
HIGH LEVEL LIGHT
X2
X2
D1-8
D1-9
D1-2
D1-1
Wiring Diagrams - Cont’d
Monitoring a Typical Pump Control Panel
©2009 OmniSite OmniSite XR-50 User’s Guide 16
15 OmniSite XR-50 User’s Guide ©2009 OmniSite
relays, coils, etc). No polarity has to be observed on these inputs. All alarm inputs have user adjustable alarm time delays adjustable thru the local display/keypad. Alternatively, these inputs can monitor and totalize pulses from a pulse output device at a max. rate of 30Hz (used to read flow and electric meters)
(Inputs 8 thru 10) These inputs are reserved to monitor the coil or auxiliary con-
tacts from Pump-1,2, and 3 motor starters. Connection of any “ON/OFF style” voltage signal in the range of 12VDC or 12 VAC thru 120 VAC or 120 VDC can be connected directly to these input circuits to monitor the pump run status. No polarity has to be observed on these inputs. These inputs provide daily reports of Pump-1,2,3 on/off cycles, total runtime, and GPM using timed draw downs on the well, as well as total station flow without the need for a flow meter. (Note: Flow calculations DO NOT work on stations using variable speed drives, and note that inputs 8,9,10 must be used with normally open contacts to correctly accumulate runtime (e.g. voltage is applied to input 8,9, or 10 when the respective pump is running)
(+ and - Terms) These terminals supply a continuous, battery backed
12 VDC to any dry un-powered contacts providing alarm moni­toring in the absence of AC power
XR50 Field Input Circuit Functionality
INPUT DESCRIPTION
(Inputs 1 thru 4) Connection of any “ON/OFF style” voltage signal in the range of
12VDC or 12 VAC thru 120 VAC or 120 VDC can be connected directly to these input circuits to monitor alarm signals (pilot lights, relays, coils, etc). No polarity has to be observed on these inputs, and different inputs can have different polarities/voltages. All alarm inputs have user adjustable alarm time delays adjustable thru the local display/keypad.
(Input 5) Connection of any “ON/OFF style” voltage signal in the range of
12VDC or 12 VAC thru 120 VAC or 120 VDC can be connected directly to this input circuit to monitor alarms (pilot lights, relays, coils, etc). No polarity has to be observed on this input. All alarm inputs have user adjustable alarm time delays adjustable thru the local display/keypad. Alternatively, this input can monitor and totalize pulses from a rain gauge (used to plot rainfall vs. well inflow rate)
(Inputs 6 and 7) Connection of any “ON/OFF style” voltage signal in the range of
12VDC or 12 VAC thru 120 VAC or 120 VDC can be connected directly to these input circuits to monitor alarms (pilot lights,
©2009 OmniSite OmniSite XR-50 User’s Guide 18
17 OmniSite XR-50 User’s Guide ©2009 OmniSite
XR50 Menu Tree
1) Need Help?
Call OmniSite Ph. 317-885-6330 Or visit us online www.omnisite.com
2) View Inputs
1) Input 1 (ON/OFF)
2) Input 2 (ON/OFF)
3) Input 3 (ON/OFF)
4) Input 4 (ON/OFF)
5) Input 5 (ON/OFF)
6) Input 6 (ON/OFF)
7) Input 7 (ON/OFF)
8) Pump 1 (ON/OFF)
9) Pump 2 (ON/OFF)
10) Pump 3 (ON/OFF)
11) Rain Pulses: (---/0-99)
12) Counter-1: (---/0-9999)
13) Counter-2 (---/0-9999)
14) P1 GPM: (0-2000)
15) P1 Runtime: (hrs:mins)
16) P1 Starts: (0-999)
17) P1 Drawdwn: (hrs:mins)
18) P2 GPM: (0-2000)
19) P2 Runtime: (hrs:mins)
20) P2 Starts: (0-999)
21) P2 Drawdwn: (hrs:mins)
22) P3 GPM: (0-2000)
23) P3 Runtime: (hrs:mins)
24) P3 Starts: (0-999)
25) P3 Drawdwn: (hrs:mins)
26) Well Fill: (mins:secs)
27) Inflow Rate: (0-99999)
View Inputs: Use this menu option to view all connected equipment and operational status since the RTU last reported to your web page.
Appendix A - Local Programming
Easily navigate the XR50 display as follows:
• 4-button interface. Buttons will be UP, DOWN, ENT, EXIT.
• Display is 2x16.
• While working through menu structure:
- Pressing UP or DOWN will select the next or previous menu item in the list. To select that item, press ENTER.
- Pressing and holding EXIT for 2 seconds will return the user to the main menu.
- Pressing and releasing EXIT will return the user to the previous menu.
• While editing a value:
- If the value is numeric, the cursor will blink on the digit being edited.
- UP and DOWN will be used to scroll through lists and increment and decrement numeric digits.
- EXIT will cancel any editing WITHOUT saving the changes.
- ENTER will move the cursor to the next position. If currently editing the last position or a list value, the value will be saved and the user returns to the menu mode.
NOTE: The XR50 RTU must be disabled with the Intelligent ID key before setup changes can be made. When finished with setup, again use your Intelligent ID key to put the XR50 RTU back into service.
ENTER
DOWNUP
EXIT
Key: (range or options; default)
1) P1 GPM (0-2000)
2) P2 GPM (0-2000)
3) P3 GPM (0-2000)
©2009 OmniSite OmniSite XR-50 User’s Guide 20
19 OmniSite XR-50 User’s Guide ©2009 OmniSite
3) Enter setup (cont’d)
4) Pump GPM Calcs
2) Tank Shape
1) Cylinder xxx
2) Rectangle xxx
1) Decimal Pos. (xxx,xx.x,x.xx; xxx)
2) Stop-Lead (0-999ft; 0)
3) Diameter (0-999ft; 0)
4) Lead Vol. (0-99999g)
1) Decimal Pos (xxx, xx.x, x.xx;xxx)
2) Stop-Lead (0-999ft; 0)
3) Width (0-999ft; 0)
4) Length (0-999ft; 0)
5) Lead Vol. (0-99999g)
5) SD DATA LOG
1) Trend Log (ON/OFF; OFF)
2) Sample Rate (0-720 min; 2min)
Enter Pump GPM Rating and Well size - You have to answer these questions if you want the XR50 to calculate station flow, and calcu­late pump GPM rate.
XR50 Menu Tree
3) Enter setup
1) SETUP DIG INPUTS
2) Date & Time
3) Timed Reports
1) INP 1 (1s-3600s; 5s)
2) INP 2 (1s-3600s; 5s)
3) INP 3 (1s-3600s; 5s)
4) INP 4 (1s-3600s; 5s)
5) INP 5 (ALARM/RAIN; ALARM) (1s-3600s; 5s)
6) INP 6 (ALARM/COUNT; ALARM) (1s-3600s; 5s)
7) INP 7 (ALARM/COUNT; ALARM) (1s-3600s; 5s)
8) Power Failure (1s-3600s; 60s)
9) Low Battery (1s-3600s; 2s)
1) Date: (mm/dd/yyyy)
2) Time: (hh:mm, AM/PM)
1) Reports: (ON-OFF; ON)
2) Rep Freq: (15-1440m; 1440m)
3) Rep 1: (AlrmStats/InFlwData/ RainFall/PumpCalcs; PumpCalcs)
4) Scheduled Time: (hh:mm; 00:00)
Enter Setup: Use this option to make any desired field settings. The most frequently changed settings are as follows:
•Input alarm time delays -
For each alarm, define the alarm and the alarm time delay (i.e. the amount of time the input must remain in that position before a call is made).
• Make an input a counter or rain gauge -
Inputs 5,6,7 can be converted to totalize pulses from any pulsing device like flow meter, rain gauge, electric meter, etc.
• Set RTU Date & Time - If you want your reports to come in at a specific time each day, then make sure the correct time/date are set. If you do not set the time/date the reports will still arrive once every 24 hours.
©2009 OmniSite OmniSite XR-50 User’s Guide 22
21 OmniSite XR-50 User’s Guide ©2009 OmniSite
4) Diagnostics (cont’d)
3) Clear All Calc’s
1) Clear all calc’d values? (YES/NO)
4) Smart ID Keys
1) ID: (xx xxxxxxx)
2) Remove id? (YES/NO)
5) Bootload
1) Update radio (YES/NO)
2) Update main (YES/NO)
XR50 Menu Tree
4) Diagnostics
1) RTU Status
2) Radio
1) Maint. Key# (--/00-99)
2) Battery (< 5.0=BAD/5.0 to 13.2V)
3) RTU Temp (-20.0 to 150.0F)
4) DC Power (0-18.0V)
5) Cell RSSI (-106dB to 0dB)
6) RTU Enabled (YES/NO)
7) PwrCycles (0-999;0)
8) CellCycles (0-999;0)
9) FailNetConns (0-999;0)
10) FailSrvConns (0-999;0)
11) SuccSrvConns (0-999;0)
12) AbandRpts (0-999;0)
13) Signal OK (0-100%;0%)
14) Network OK (0-100%;0%)
15) CellState (0-999;0)
16) DailyCellCycles (0-999;0)
17) Low Pwr Mode (ON/OFF; OFF)
18) EDIT POWER MODE (1) Low Power Mode Select: (Disabled/Enabled; Disabled)
19) Firmware: 50.xxxxx
20) CLEAR DIAG CNTRS
1) Lst FOCC Rcvd (--/00-99)
2) Domain Name: rtu.omnisite.com
3) Domain IP Addr:
68.255.116.1
4) Domain Port Num: 5001
5) Unit ID: XXXX (If you want to verify this number call OmniSite)
6) Server ID: OMNI
Diagnostics - This section is reserved for OmniSite trained field service personnel. Call OmniSite at 317-885-6330 with questions about this section.
7) Network APN C1.korem2m.com
8) Sim ID: (xxxxxxxxxxxxxxxxxxxx)
9) Ctrl. Rev. (X.X)
10) Soft. Rev.v (X.X.X)
11) Exec. Radio Test
12) Get Radio Log
13) Clear Radio Log
14) SELECT PROVIDER
1) Provider: (KM2M/AGSM; KM2M)
©2009 OmniSite OmniSite XR-50 User’s Guide 24
23 OmniSite XR-50 User’s Guide ©2009 OmniSite
System Key Switch Smart Key, 100 Million combinations Radio Frequency 850/900/1800/1900 Mhz Antenna 850/900/1800/1900 MHZ, phantom style Transmission Time 1-2 seconds, field-to-web page
Appendix C - Repair Parts
In the unlikely event that you should have a problem with your new OmniSite product, the following replacement parts are available for purchase from OmniSite. Note that the printed circuit boards (PCB), themselves, are not a field repairable part. If you have a problem with an OmniSite printed circuit board, the repair consists of replacing the entire (PCB) unit. Contact your OmniSite distributor for details.
Part Number Description
BATTI208 Rechargeable 800 mA gel cell battery KE “Crew on-site” replacement key EN XR-50 Weatherproof enclosure
*- All items are typically “in-stock” for immediate delivery
• For the repair or replacement parts you need call (317) 885-6330 between 8 am - 5 pm, Monday - Friday Eastern Daylight Time.
Appendix B - Hardware Specification
Specifications:
Power Supply 80-265 VAC +/-10% or 15-20 VDC +/-10% Max. Power Consumption 0.3 amps @ 120 VAC or 2.1 amps @15 VDC DI Inputs
(10) universal input 12VDC/VAC thru 120 VDC/VAC +/-10% Counter Inputs (2) avail. At 30Hz max. Freq Rain Gauge Input
(1) Avail for pulse only. Each pulse must = 0.01˝ rain Operating Temp. -20 to 150 F Storage Temp. -20 to 180 F Humidity 5-95% RH, non-condensing Enclosure Weatherproof, equivalent to NEMA 4X (Optional) Terminals Removable, spring clamp style Weight 5.6 lbs. Communications Local RS232 Port Memory Type EEPROM, Flash Isolation Voltage 4000 VAC opto-isolated Input Impedance 10Kohm min. Surge ANSI C37.90.1 Dimensions 8.25w x 8.6h x 2.75d Aux. Power Out 100 mA @ 12 VDC Battery Charger 15 VDC capable of charging 800 mAH -17 AH gell cell
©2009 OmniSite OmniSite XR-50 User’s Guide 26
25 OmniSite XR-50 User’s Guide ©2009 OmniSite
Trouble Probable Cause Remedy
Unit does not transmit alarms, and no control
panel lights are
illuminated.
No Power
Check 120 VAC or 12
VDC power source.
Unit does not transmit
alarms and power source
is present
Cellular signal
reception is not suitable
Inspect the cellular signal
strength LED on the face of the XR50.
If it is not GREEN, then you MAY have
a weak signal. Call OmniSite at 317-
885-6330. We will observe the transmitted signal strength suggest options
for you, which may include
replacing the antenna or
relocating the antenna.
My field alarm
contacts open and close,
but the
OmniSite unit does not appear to be doing anything.
Wiring problem
or contacts have
not remained open
or closed for at
least
5 seconds
The OmniSite RTU will
transmit an alarm signal if, it changes
“state” and remains in
that “state” for at least 5 seconds.
Note - this is a user adjustable
time delay, and may be longer for
your application. Next - disconnect the
field wires from the RTU for the alarm
input in question. Using a volt-ohm
Appendix D - Troubleshooting Chart
• For on-site repair service 24 hours a day, 7 days a week contact your local OmniSite distributor in your area.
• For the location of an OmniSite repair service center in your area call OmniSite at 317-885-6330.
• For information on purchasing an OmniSite Maintenance Agreement or to inquire about an existing Agreement call (317) 885-6330 between 8 am - 5 pm, Monday - Friday Eastern Daylight Time.
• The model number will be found on the OmniSite identification label.
• When requesting service or ordering parts, always provide the following information: Serial number, model number and part description.
©2009 OmniSite OmniSite XR-50 User’s Guide 28
27 OmniSite XR-50 User’s Guide ©2009 OmniSite
Trouble Probable Cause Remedy
The OmniSite units
keeps calling me with
alarms, and when I
visit the site, I can
not find any problems.
OmniSite RTU is
receiving “false”
alarms.
Your OmniSite RTU is a
sophisticated piece of electronic
monitoring equipment. It is only “as
good” as the equipment it is monitor-
ing. In other words, if
your control panel is issuing “false”
alarms, the OmniSite
RTU WILL REPORT them.
Contact your local OmniSite
distributor to locate causes
for “false” alarms from your equipment, or increase alarm time delays to eliminate “false” alarms.
Trouble Probable Cause Remedy
(Con’t) (Con’t)
meter, determine that your contacts
are actually opening and closing. If not,
make field repair.
If they are, check on the XR50 front
panel to see that the associated
LED goes on/off as your field signal
changes. Lastly, visit the OmniSite web-
site to confirm that you have
an associated alarm trigger and a call
out list specified for the event.
My pump runtime
readings are not
automatically updating
on the OmniSite
website
Time Scheduled
reports are not
enabled
The OmniSite RTU reports pump runtimes and other
values on time scheduled intervals
(typically once/day). You must manu-
ally “enable” this feature from the
OmniSite website. Additionally, you
can manually request the pump run-
time values at any time by
visiting the OmniSite website and
issuing the appropriate command.
©2009 OmniSite OmniSite XR-50 User’s Guide 30
29 OmniSite XR-50 User’s Guide ©2009 OmniSite
Appendix E - Location for Setting Software Parameters
Process Unit Web Site
Enter input time delays
Enter wet well dimensions
Enter datalogging parameters
View current pump calculations & counter readings
View current digital input status
Setup GPM override
Setup recipient email, phone and text information
Setup call-out list order and delays
Setup alarm state for inputs
Setup notification events
View charts, graphs and export data
View logs and history
Analyze inflow and rainfall
NOTESNOTES
©2009 OmniSite OmniSite XR-50 User’s Guide 32
31 OmniSite XR-50 User’s Guide ©2009 OmniSite
NOTESNOTES