©2009 OmniSite OmniSite Crystal Ball User’s Guide 30
29 OmniSite Crystal Ball User’s Guide ©2009 OmniSite
Crystal Ball Menu Tree
1) Need Help?
Call OmniSite Ph. 317-885-6330
Or go online: www.omnisite.com
2) View Inputs
1) Analog 1 (-----/0-9999)
2) Analog 2 (-----/0-9999)
3) Analog 3 (-----/0-9999)
4) Analog 4 (-----/0-9999)
5) Input 1 (ON/OFF)
6) Input 2 (ON/OFF)
7) Input 3 (ON/OFF)
8) Input 4 (ON/OFF)
9) Input 5 (ON/OFF)
10) Input 6 (ON/OFF)
11) Input 7 (ON/OFF)
12) Input 8 (ON/OFF)
13) Input 9 (ON/OFF)
14) Input 10 (ON/OFF)
15) Input 11 (ON/OFF)
16) Pump 1 (ON/OFF)
17) Pump 2 (ON/OFF)
18) Pump 3 (ON/OFF)
19) Output 1 (ON/OFF)
20) Output 2 (ON/OFF)
21) Output 3 (ON/OFF)
22) Output 4 (ON/OFF)
23) Rain Pulses: (---/0-99)
24) Counter-1: (---/0-9999)
25) Counter-2 (---/0-9999)
26) P1 GPM: (0-2000)
27) P1 Runtime: (hrs:mins)
28) P1 Starts: (0-999)
• Key: (range or options;
default)
• View Inputs: Use this
menu option to view all connected equipment and operational status since the RTU
last reported to your web
page.
3) Pump Control
1)Pump Settings
2) Pump Bypass
3) Level Setup
4) Level Test
1) Sensors: (NONE, 4-20mA+FLT, 4-20mA,FLOATS; NONE)
2) # of Pumps: (00-03; 00)
3) Grease Cntrl %: (00-10; 00)
4) Alternate? (YES/NO; YES)
5) Pump Scheme: (DOWN/UP; DOWN)
6) Pump Fail Alm? (YES/NO; YES)
7) Control Only? (YES/NO; NO)
8) SETUP ANALOG INPUTS
1) Decimal Pos: (xxxx, xxx.x,xx.xx; xxxx)
2) Scaling 4mA = (0-9999; 0)
3) 20mA = (0-9999; 200)
4) Low Alarm: (NONE/O-9999; NONE)
5) High Alarm: (NONE/O-9999; NONE)
6) Dead Band: (0-9999; 0)
7)
8) Alarm Delay: (0-240 sec; 5 sec)
9) Report Value: (LAST/LIVE; LAST)
*On
AI#1 LIVE is the only option
ANALOG INPUT 2
ANALOG INPUT 3
ANALOG INPUT 4
1) P1 runs? (YES/NO; YES)
2) P1 control: (AUTO, ON, OFF; AUTO)
3) P2 runs? (YES/NO; YES)
4) P2 control: (AUTO, ON, OFF; AUTO)
5) P3 runs? (YES/NO; NO)
6) P3 control: (AUTO, ON, OFF; OFF)
7) Output 4: (ON/OFF; OFF)
1) P1: (ON/OFF; OFF) P2: (ON/OFF; OFF)
2) P3: (ON/OFF; OFF)
3) Tank Lvl (0-9999; 0)
4) Press Up/Down (just directions to change tank level above)
1) Stop Level: (0-9999; 0)
2) Lead Level: (0-9999; 0)
3) Lag Level: (0-9999; 0)
4) Lag-Lag Level: (0-9999; 0)
If you are using
the Crystal Ball
to control
pumps based
upon tank level,
then you must
answer the
questions in this
section of the
menu tree to
enable pump
control.
29) P1 Drawdwn: (hrs:mins)
30) P1 Amps: (0-999)
31) P2 GPM: (0-2000)
32) P2 Runtime: (hrs:mins)
33) P2 Starts: (0-999)
34) P2 Drawdwn: (hrs:mins)
35) P2 Amps: (0-999)
36) P3 GPM: (0-2000)
37) P3 Runtime: (hrs:mins)
38) P3 Starts: (0-999)
39) P3 Drawdwn: (hrs:mins)
40) P3 Amps: (0-999)
41) Well Fill: (mins:secs)
42) Inflow Rate: (0-99999)
ANALOG INPUT 1
same menus as Analog Input 1