CAUTION indicates a hazardous condition which, if not avoided,
can result in minor or moderate injury.
WARNING
WARNING indicates a hazardous situation which, if not
avoided, can result in death or serious injury or moderate injury.
DANGER
DANGER indicates a hazardous situation which, if not
avoided, will result in death or serious injury.
1. Notes on this manual
1.1 Scope of Validation
The main purpose of this User’s Manual is to provide instructions and detailed procedures
for installing, operating, maintaining, and troubleshooting the following four series of Omnik
Inverters:
Omniksol-1k/1.5k-TL2-M
Omniksol-2k/2.5k/3k-TL3-S
Omniksol-3k/3.68k/4k-TL3
Omniksol-5k/6k-TL3
Please keep this user manual all time available in case of emergency.
1.2 Symbols Used
3
NOTICE
Hereby qualified personnel means he/she has the valid license
from the local authority in:
•Installing electrical equipment and PV power systems
(up to 1000 V).
• Applying all applicable installation codes.
• Analyzing and reducing the hazards involved in
performing electrical work.
•Selecting and using Personal Protective Equipment
(PPE).
WARNING
Do not use this product unless it has been successfully installed
by qualified personnel in accordance with the instructions in
Chapter 5, “Installation”.
NOTICE
NOTICE indicates a situation that can result in property
damage, if not avoided.
1.3 Target Group
Chapter 1, 2, 3, 4, 7, 8, 9, 10, 11 and Chapter 12 are intended for anyone who is
intended to use Omnik Grid Tie Solar Inverter. Before any further action, the operators
must first read all safety regulations and be aware of the potential danger to operate
high-voltage devices. Operators must also have a complete understanding of this
device’s features and functions.
Chapter 5 and Chapter 6 are only for qualified personnel who are intended to install
Or uninstall the Omnik Grid Tie Solar Inverter.
4
Public utility only
The PV inverter designed to feed AC power directly into the
public utility power grid,do not connect AC output of the
device to any private AC equipment.
WARNING
The installation, service ,recycling and disposal of the
inverters must be performed by qualified personnel only in
compliance with national and local standards and
regulations. Please contact your dealer to get the
information of authorized repair facility for any maintenance
or repairmen.
Any unauthorized actions including modification of product
functionality of any form will affect the validation of warranty
service; Omnik may deny the obligation of warranty service
accordingly.
DANGER due to electrical shock and high voltage DO
NOT touch the operating component of the inverter, it might
result in burning or death. TO prevent risk of electric shock
during installation and maintenance, please make sure that
all AC and DC terminals are plugged out. DO NOT stay close
to the instruments while there is severe weather conditions
including storm, lighting etc.
2. Preparation
2.1 Safety Instructions
5
Symbol
Description
Dangerous electrical voltage
This device is directly connected to public grid, thus all
work to the inverter shall only be carried out by
qualified personnel.
DANGER to life due to high electrical voltage!
There might be residual currents in inverter because
of large capacitors. Wait 10 MINUTES before you
remove the front lid.
NOTICE, danger!
This device directly connected with electricity
generators and public grid.
Danger of hot surface
The components inside the inverter will release a log
of heat during operation, DO NOT touch aluminum
housing during operating.
An error has occurred
Please go to Chapter 10 “Trouble Shooting” to remedy the
error.
This device SHALL NOT be disposed of in
residential waste
Please go to Chapter 9 “Recycling and Disposal” for
proper treatments.
Without Transformer
This inverter does not use transformer for the isolation
function.
CAUTION
The PV inverter will become hot during operation; please
don’t touch the heat sink or peripheral surface during or
shortly after operation. Risk of damage due to improper
modifications. Never modify or manipulate the inverter or
other components of the system.
2.2 Explanations of Symbols on Inverter
6
CE Mark
Equipment with the CE mark fulfils the basic
requirements of the Guideline Governing Low-Voltage
and Electromagnetic Compatibility.
No unauthorized perforations or modifications
Any unauthorized perforations or modifications are
strictly forbidden, if any defect or damage
(device/person) is occurred, Omnik shall not take any
responsibility for it.
3. Product Information
3.1 Overview
Industrial Layout (Sample)
、
7
Excellent Heat Elimination (Sample)
3.2 Major Characteristics
Omnik inverter has following characteristics which make Omnik inverter “High Efficiency,
High Reliability, High Cost Effective Ratio”
Wide DC input voltage and current ranges, enables more PV panels connected.
Wide MPP voltage range ensure high yield under various weather conditions.
High MPP tracking accuracy, ensure the minimum power loses during converting.
Complete set of protection methods.
Also, following protection methods are integrated in Omnik inverter:
Internal overvoltage
DC insulation monitoring
Ground fault protection
Grid monitoring
Ground fault current monitoring
DC current monitoring
Integrated DC switch
8
Type
Omniksol-1k-TL2-M
Omniksol-1.5k-TL2-M
Input(DC)
Max. PV Module Power [W]
1250
1750
Max. Input Power [W]
1200
1700
Max. DC Voltage [V]
500
500
Nominal DC Voltage [V]
360
360
Operating MPPT Voltage
Range [V]
60 - 400 60 - 400
MPPT Voltage Range at
Nominal Power [V]
155 - 400 155 - 400
Start up DC Voltage [V]
70
70
Turn off DC Voltage [V]
50
50
Max. DC Current[A]
10
10
Max. Short Circuit Current [A]
12
12
Number of MPP trackers 1 1
Number of DC Connection 1 1
DC Connection Type
Amphenol Connector
Amphenol Connector
Output(AC)
Max. AC Appaeent Power
[VA]
1000
1500
Nominal AC Power [W]
1000
1500
Nominal Grid Voltage [V]
220 / 230 / 240
220 / 230 / 240
Nominal Grid Frequency [Hz]
50 / 60
50 / 60
Max. AC Current [A]
5
7.5
Grid Voltage Range [V]*
185 - 276
185 - 276
Grid Frequency Range [Hz]*
45 - 55 / 55 - 65
45 - 55 / 55 - 65
Power Factor 0.9i - 0.9c
0.9i - 0.9c
Total Harmonic Distortion
(THD)
<3%
<3%
Night time Power
Consumption [W]
<1
<1
AC Connection Type
Plug-in connector
Plug-in connector
Efficiency
Max. Efficiency
96.5%
96.5%
Euro Efficiency
95.8%
96.0%
MPPT Efficiency
99.9%
99.9%
see next page
3.3 Datasheet
Datasheet of Omniksol-1k/1.5k-TL2-M
9
Safety and Protection
Protection Functions
Array ground insulation resistance monitoring Output over current protection Residual current monitoring
Array polarity reverse protection Output over/under voltage protection Surge protection
Array over voltage protection Output over/under frequency protection Anti-island protection
Array over current protection Output short circuit protection Over temperature protection
Protection Class
Ⅰ(According to IEC 62103)
Overvoltage Category
PV Ⅱ / Mains Ⅲ(According to IEC 62109-1)
Reference Standard
Safety Standard
IEC/EN 62109-1,IEC/EN 62109-2
EMC Standard
EN 61000-6-1,EN61000-6-3,EN 61000-6-2,EN61000-6-4,EN61000-3-2,EN 61000-3-3
Grid Standard
VDE-AR-N 4105,VDE 0126-1-1,C10/11,G83/2,UTE C 15-721-1,CEI 0-21,
*The AC voltage and frequency range may vary depending on specific country grid
14
Type
Omniksol-5k-TL3
Omniksol-6k-TL3
Input(DC)
Max. PV Module Power [W]
6000
7200
Max. Input Power [W]
2800/2800
3300/3300
Max. DC Voltage [V]
580
580
Nominal DC Voltage [V]
360
360
Operating MPPT Voltage
Range [V]
120 - 500
120 - 500
MPPT Voltage Range at
Nominal Power [V]
270 - 500
320 - 500
Start up DC Voltage [V]
150
150
Turn off DC Voltage [V]
120
120
Max. DC Current[A]
A:10 / B:10
A:10 / B:10
Max. Short Circuit Current [A]
A:14 / B:14
A:14 / B:14
Number of MPP trackers
A:1 / B:1
A:1 / B:1
Number of DC Connection
A:1 / B:1
A:1 / B:1
DC Connection Type
Amphenol Connector
Amphenol Connector
Output(AC)
Max. AC Appaeent Power [VA]
5500
6600
Nominal AC Power [W]
5000
6000
Nominal Grid Voltage [V]
220 / 230 / 240
220 / 230 / 240
Nominal Grid Frequency [Hz]
50 / 60
50 / 60
Max. AC Current [A]
25
30
Grid Voltage Range [V]*
185 - 276
185 - 276
Grid Frequency Range [Hz]*
45 - 55 / 55 - 65
45 - 55 / 55 - 65
Power Factor 0.9i - 0.9c
0.9i - 0.9c
Total Harmonic Distortion
(THD)
<3% <3%
Night time Power Consumption
[W]
<1 <1
AC Connection Type
Terminal Blocks
Terminal Blocks
Efficiency
Max. Efficiency
98.1%
98.1%
Euro Efficiency
97.3%
97.3%
MPPT Efficiency
99.9%
99.9%
see next page
Datasheet of Omniksol- 5k&6k-TL3
15
Safety and Protection
Protection Functions
Array ground insulation resistance monitoring Output over current protection Residual current monitoring
Array polarity reverse protection Output over/under voltage protection Surge protection
Array over voltage protection Output over/under frequency protection Anti-island protection
Array over current protection Output short circuit protection Over temperature protection
Protection Class
Ⅰ(According to IEC 62103)
Overvoltage Category
PV Ⅱ / Mains Ⅲ(According to IEC 62109-1)
Reference Standard
Safety Standard
IEC/EN 62109-1,IEC/EN 62109-2
EMC Standard
EN 61000-6-1,EN61000-6-3,EN 61000-6-2,EN61000-6-4,EN61000-3-11,EN 61000-3-12
Grid Standard
G59/3,CEI 0-21,NB/T32004
Physical Structure
Dimensions (WxHxD) [mm]
343 * 425 * 136
Weight [kg]
16.8
Environmental Protection
Rating
IP 65(According to IEC 60529)
Cooling Concept
Natural convection
Mounting Information
Wall bracket
General Data
Operating Temperature Range
[℃]
-25 to +60(derating above 45℃)
Relative Humidity
0% to 100%,no condensation
Max. Altitude (above sea level)
[m]
2000
Noise Level [dB]
<40
Isolation Type
Transformerless
Display
2 LED,Backlight,2 * 16 Character LCD
Data Communication Interfaces
RS485 / WiFi / GPRS optional
Guarantee
5 - 25 years optional
*The AC voltage and frequency range may vary depending on specific country grid
16
A B C
D
E F G
H
Object
Quantity
Description
A 1 Omnik inverter
B
1 pair
DC connector
C 1 AC connector
D 4 Screw (ST6×50)
E 4 Expansion tube
F 1 User manual
G
1
Installation position scale
H
1
Wall mounting bracket
4. Packing checklist
4.1 Assembly parts
After you receive the Omnik inverter, please check if there is any damage on the carton,
and then check the inside completeness for any visible external damage on the inverter or any
accessories. Contact your dealer if anything is damaged or missing.
17
Object
Description
A
LED light(Green) – RUN
B
LED light(Red) – FAULT
C
Function key for displays and choice of language
Object
Description
A
DC switch
B
Plug connectors for DC input.
C
Terminal for grid connection (AC output)
D
WiFi/GPRS/RS485 interface
B D C
C
A
B
A
4.2 Product Appearance
Front
Bottom (style 1)
18
Object
Description
A
DC switch
B
Plug connectors for DC input.
C
WiFi/GPRS/RS485 interface
D
Terminal for grid connection (AC output)
B D C
A
Bottom (style 2)
NOTE: The order of different models of A/B/C/D modules may change. Please refer to the
actual product.
4.3 Product Identification
You can identify the inverter by the side nameplate. Information such as type of the inverter
and inverter specifications are specified on the side name plate. The name plate is on the
middle part of the right side of the inverter housing. And the following figure is the side name
plate example as on Omniksol-3k-TL3-S
19
4.4 Further Information
If you have any further questions concerning the type of accessories or installation, please
check our website www.omnik-solar.comor contact our service hotline.
20
NOTICE
NOTICE due to the inappropriate or the harmonized
installation environment may jeopardize the life span
of the inverter.
Do not expose to direct sunlight to avoid power derating due
to increase in the internal temperature of the inverter.
Do not expose to rain and snow cover to enhance inverter life
time.
The installation site MUST have good ventilation condition.
DANGER
DANGER to life due to potential fire or electricity shock.
DO NOT install the inverter near any inflammable or
explosive items. This inverter will be directly connected with
HIGH VOLTAGE power generation device; the installation
must be performed by qualified personnel only in
compliance with national and local standards and
regulations.
5. Installation
5.1 Safety
21
MMaaxx 1155°°
5.2 Mounting Instructions
Omnik inverter is designed for indoors and outdoors installation
Please mount the inverter in the direction as illustrated above
Install the inverter in the vertical direction is recommended, with a max.15 degrees
backwards.
For the convenience of checking the LCD display and possible maintenance activities,
please install the inverter at eye level.
Make sure the wall you selected is strong enough to handle the screws and bear the
weight of the inverter
Ensure the device is properly fixed to the wall
It is not recommended that the inverter is exposed to the strong sunshine, because the
excess heating might lead to power reduction
The ambient temperature of installation site should be between -25 °C and +60 °C
Make sure the ventilation of the installation spot, not sufficient ventilation may reduce the
performance of the electronic components inside the inverter and shorten the life of the
inverter
22
Direction
Minimum clearance
Above
30 cm
Below
40 cm
Sides
10 cm
5.3 Safety Clearance
Observe the following minimum clearances to walls, other devices or objects to guarantee
sufficient heat dissipation and enough space for pulling the electronic solar switch handle.
23