USA / Canada Office
Tel +1-866-849-3441
Fax +1-866-628-8055
info@omniinstruments.net
www.omniinstruments.net
Instruction Manual 2009
DFS2 Doppler Flow Switch
Doppler Flow Switch - DFS2
Introduction
The Doppler Flow Switch - DFS2 measures the velocity of fluids in pipelines using
a totally non-intrusive principle.
NB! It is intended for use with sewage, pulps, mining slurries, and other fluids which
contain in excess of 0,1% suspended solids or bubbles. The particle size for
successful operation must be greater than 100 microns.
The DFS2 enclosure is rated IP65. The flow switch includes a relay with adjustable
high and low set point controls, plus delay-on and delay-off adjustable timers. The
DFS2 requires 24Vdc, 115 or 230Vac power supply.
Two selectable flow ranges of 0 – 2 m/s, or 0 – 6 m/s are available, and the flow rate
is displayed on a bar graph indicator.
Connections and Adjustments
Removal of the flow switch cover will reveal the plug-in connections and various
adjustments, detailed as follows :-
plug as indicated in Figure 1 Terminal No’s 9
to 12.
: Check that the operating voltage of the flow
switch is correct, (i.e. 24Vdc, 115Vac or
230Vac) before connecting the power supply.
: The relay has a changeover contact, which
can be used for pump control, or simply to
initiate an alarm condition. The single control
relay will operate when the flow measured is
outside the high or low trip settings and can
be configured to operate with or without
“latch”.
: JP2 Position 1 – ON (latch/reset)
• Relay energised in normal conditions
i.e. between high and low limits giving
a failsafe mode.
• In alarm condition the relay will
deenergise and latch in the
deenergised position.
• Close reset contact (7 & 8) to reset
relay to energised position. Resetting
will also reset timer T2.
• If alarm condition remains after T2
timer times out the relay will again
deenergise and latch.
• If used for pump protect either power
the DFS2 from the pump circuit or
close reset contact allowing normal
flow conditions to be established
before T2 timer times out.
Position 2 – OFF (No latch/reset)
• Relay is deenergised in normal
conditions i.e. between high and low
limits.
• In alarm conditions the relay will
energise.
Rev 3
2
Instruction Manual 2009
DFS2 Doppler Flow Switch
Adjustments
Range Selection : (refer JP1)
Range 1 (0 – 2 m/s) :- Jumper in position “1”
Range 2 (0 – 6 m/s) :- Jumper in position “2”
Setting Low Flow Trip Point :
Move slide switch “S1” to “Lo” position. Adjust the low trip potentiometer until the
bar graph displays the required alarm setting as a percentage of the flow range
selected.
Example : Range 1 (0 – 2 m/s)
Bar graph display – 50%
Trip point setting – 1,0 m/s
Setting High Flow Trip Point
Move slide switch “S1” to “Hi” position and adjust high trip potentiometer to display
the required alarm setting.
NB Return slide switch to centre position for normal operation.
Delay-Off Timer T1 :
Under normal operating conditions the flow may fluctuate beyond the high or low trip
settings momentarily. The adjustable 0 – 60 sec. timer is adjusted with
potentiometer “T1”. Turn clockwise to increase the delay before the relay operates.
Delay-On Timer T2 :
If the flow switch is used for pump control it is necessary to over-ride the trip settings
during start-up, until the flow is established.
The adjustable 0 – 60 sec. timer is adjusted with potentiometer “T2”. Turn clockwise
to increase the delay before the relay operates.
Rev 3
3
Instruction Manual 2009
IF HORIZONTAL
DFS2 Doppler Flow Switch
Mounting The Transducer
a) Select a location for mounting the sensor at a point where the flow profile is fully
developed. Generally the principle of 10 pipe diameters of straight pipe upstream,
and 5 pipe diameters downstream will suffice, but should valves or bends exist
upstream of the sensor, the amount of straight pipe immediately upstream will need
to be increased.
b) Ensure that the sensor is mounted as far as
possible from potential noise sources, such as
pumps, control valves etc. and mount the
sensor at approximately 3/9 o’clock on the pipe
3 O’CLOCK POSITION ON PIPE
(if horizontal) to avoid errors due to air pockets
on top, or sediment at the bottom of the pipe.
c) Either vertical or horizontal pipe runs are acceptable for sensor mounting.
d) Before attaching the transducer head to the pipe surface, an area slightly larger than
the flat surface of the transducer must be cleaned to bare metal. (A small amount of
pipe pitting, even with spots of paint or rust, will not cause problems).
e) The transducer must be mounted accurately, parallel to the pipe axis, for correct
performance, and transducer to pipe contact should be along the centre line of the
transducer head.
f) Bonding to the pipe is achieved with silicone
coupling compound. Be sure to fill in any air
gaps that may remain at the pipe transducer
interface with additional compound.
A pipe clamp kit is included with the flow switch.
It includes silicone coupling compound, a
Neoprene rubber pad, and four polyamide 12
straps for pipe diameters up to 300 mm. In
applications with excessive vibration it is
recommended that the Neoprene rubber pad is
inserted between the pipe and the transducer.
GOOD
Coupling compound must be applied to both
sides of the pad.
Mounting the Switch
The DFS2 electronics is housed in a water resistant housing, which should be
mounted in a location where the ambient temperature is within the range stated in
the specifications i.e. -10°C to 50°C.
Rev 3
4
Instruction Manual 2009
DFS2 Doppler Flow Switch
Trouble Shooting
Relay Operates With No Flow
Possible Cause - Trip points set too low
- Vibration on pipe
Corrective Action - Adjust trip points above 0 m/s
- Relocate transducer
- Use Neoprene rubber pad in transducer
mounting
Rev 3
Relay Does Not Operate
Possible Cause - High trip point set below low trip point
- Unit faulty
Corrective Action - Adjust high trip point above low trip point
- Return unit to factory
Signal Strength LED Not Illuminated, or Flickering slowly