Omni OWR-150 Service Manual

Page 1
By
WASTE OIL FIRED MOBILE RADIANT HEATER
Operation and Service Instructions
Manual
Thank you and congratulations on your purchase of an Omni Waste Oil Fired Mobile
Radiant Heater. You have selected a high quality, precision-engineered piece of
equipment, designed to give you many benefits as well as years of outstanding
Econo Heat♦5714 1st Avenue♦Spokane Washington 99212.♦(509)534-1022♦www.econoheat.com 100267 Rev A2
MODEL OWR-150
performance.
Page 2
PRECAUTIONS
Waste oil may contain many foreign materials. Waste oil may also contain gasoline. Therefore, specific precautions on the handling and storage of waste oils are to be observed when using, cleaning and maintaining this heater. Use a
screen in a funnel when pouring oil into storage tank to catch foreign material, i.e., gasket material and sealant fibers, etc. WARNING: This appliance is not designated for use in hazardous atmospheres containing flammable vapors or combustible dust, or atmospheres containing chlorinated or halogenated hydrocarbons. Do not expose this unit to rain or moisture. If installed in high moisture atmosphere, a special cover for the integrated air compressor must be obtained from factory to avoid rusting of internal raw metals. If this occurs, see trouble-shooting guide for remedy. Uses only crank case oil, gear oil, hydraulic oils, auto trans. Fluid or #1
and #2 furnace oil. Do not use old, contaminated oils that have been stored in underground tanks or outside barrels for long periods. Excessive water and sludge may be present, causing quick filter plugging.
NOTES: The instructions contained in this manual apply to the operation and service of Omni Waste oil fired mobile radiant heaters. The following instructions should be carefully followed for obtaining the best possible installation, operation and service conditions. Specifications are subject to change without notice. This heater was designed to be an auxiliary heat source and provide economical disposal of waste oil. Proper operation depends on the consistency of the oil. Any water or foreign material in the oil may cause the unit to shut down. If a continuous stream of oil cannot be guaranteed at the heater, the main heating system should be set above freezing which will prevent any building damage if the waste oil heater were to overcome inoperative during subfreezing weather, i.e. supply tank empty, filter plugged, etc.
UNCRATING: Immediately upon uncrating units, check the unit for any damage that may have been incurred in shipment, if any damage is found, file a claim with the transporting agency. The unit has been tested and inspected at the factory prior to crating and was in perfect condition at that time. If anything is missing check packing slip for indications of possible backorder of those parts or components. Otherwise a claim must be for those missing parts.
2
Operation, and Service Instructions
Page 3
IMPORTANT
NOTICE TO OWNER
AND INSTALLER
To enjoy the long term benefits of burning your used oil in an Omni Waste Oil Burning appliance, it is necessary to become familiar with the correct operation and maintenance of your new heater. Before operating this appliance, make sure you read and understand this manual.
IMPROPER OR LACK OF MAINTENANCE
WILL VOID THE WARRANTY
The most critical sections of this manual are in order of importance as follows:
Basic Operation Knowledge
Oil Suction Line
Correct Draft Over Fire
General Maintenance Requirements
Identical to any gas or oil furnace, without adequate draft over the fire, the combustion gases cannot escape the furnaces. The flame will lengthen resulting in an overheated combustion chamber. Burning used oil is similar to burning wood. A fine gray ash accumulates
in the combustion chamber. This accumulation of ash will eventually affect the performance of the heater and must be removed.
These topics are discussed in detail on the following pages. Please familiarize yourself with these sections of your manual. Spending a few minutes to review this material will assure that you receive the return on investment that you expect from your Omni Radiant heater.
Operation and Service Instructions 3
Page 4
SPECIFICATIONS
BTU’S/HR OUTPUT 150,000 GALLONS PER HOUR 1.0 VOLTAGE REQUIREMENTS
120V 60Hz
Single Phase AMPS FULL LOAD 8.4 A WEIGHT 180 LBS TANK CAPACITY 10.6 Gallons DIMENSIONS L/W/H 50”x28”x34”
Notes:
1. All illustrations and specifications contained herein are based on the latest information
available at the time of publication approval. Econo Heat reserves the right to make changes at any time without notice, in materials, specifications, and models or to discontinue models.
2. Output depends on BTU content of oil used.
3. Atomizing Air Pressure for all fuels 10 P.S.I.
Figure 1 – Temperature Diagram
4
Operation, and Service Instructions
Page 5
Figure 2 – Inclination
34”
50”
Figure 3 – Dimension
Operation and Service Instructions 5
Page 6
WIRING DIAGRAM
OIL
PREHEATER BL OCK
CONTROLLER
L1
L2
RED
RED
WHT
RED
BLU
WHT
PRI
WHT
WHT
WHT
BLK
BLK
ORN
WHT
Oil Valve
Fuse
BLK
BLK
BLOWER MOTOR
WHT
RED
BLOWER TIMER
8 9
Delay Timer
Power Switch
5
2
3
RED
Power Plug
WHT
THERMO­COUPLE
Bi METAL HIGH LIMIT SWITCH
500W HEAT ROD
OIL
PREHEATER
BLOCK
RED
WHT
HTR
BLU
WHT
HIGH
VOLTAGE
TRANS-
FORMER
BLK
OIL PRIMARY CONTROL
(IE, Honeywell, etc.)
PHOTO EYE
FLAME SENS OR
WHT
BLK
ORN
THERMOSTAT CONNECTION
RADIANT HEATER
6
Operation, and Service Instructions
Page 7
A
OIL BURNER
Igniter
Transformer
Air Band
(Combustion Air
Supply
djustment)
Figure 4 – Oil Burner (Back View Closed)
Run
Indicator
Power
Indicator
Oil Pressure
Gauge
Oil Primary
Control
Air Pressure
Gauge
Air Pressure
Adjuster
Air Compressor
Operation and Service Instructions 7
Page 8
Oil Pre-Heater
Pre-Heater Control
Circuit Board
Block
Air
Muffler/Filter
Photo Eye
Flame Sensor
Transformer
Igniter Springs
Figure 5 – Oil Burner (Back View Opened)
Electrical
Terminal Block
Heater
Electrical
Schematic
Oil Valve
Figure 6 – Oil Burner (Front View)
8
Burner
Motor
Electrodes
Nozzle
Flame Cone
Operation, and Service Instructions
Page 9
Fuel Regulator
Fuel Filter
Fuel Pump
Figure 7 – Radiant Heater (Back View)
Omni’s patented burner technology improves the efficiency of the oil burn process by continuous stabilization of the oil viscosity. Optimum atomization (spray) is accomplished by precisely pre­heating the oil and air prior to introduction to the combustion chamber. The waste oil enters into the Oil Pre-Heater Block (figure 5) and is pre-heated to operating thermo setpoint, then compressed air from the air compressor (figure 4) is mixed with the oil prior to spraying out the nozzle similar to fuel injection, by breaking up the oil droplets into a finer mist or spray (atomization). Electrodes mounted just above the nozzle (figure 6) provides continuous electrical arc across electrode to electrode igniting the fine oil mist as it sprays out of the nozzle. Once ignited the flame is forced into a swirl caused by the burners blower and specially designed flame cone (figure 6) providing a very efficient and thorough burn of the waste oil.
Burner Components
Igniter Transformer: (figure 4) Supplies high voltage to the electrodes generating electrical arc igniting the oil.
OIL BURNER TECHNOLOGY
Oil Valve: (figure 6) energizes when burner is running and de-energizes when burner is not running eliminating bleed back of oil out of the Pre-heater block.
Air Band: (figure 4) Adjusts amount of air introduced into the combustion chamber. Air band is adjusted at the factory for optimum performance ½ to ¾ inch. NO FIELD
Operation and Service Instructions 9
Page 10
ADJUSTMENT REQUIRED unless in high altitudes application where minor adjustment may be required.
Oil Primary Control: (figure 4) Controls the oil burner ignition. Checks for flame in the combustion chamber, if no flame is detected within 45 seconds, the oil primary will shutdown the oil burner. To restart the unit, reset the red button on the oil primary.
Oil Pre-Heater Block: (figure 5) Pre-heats the oil and air before entering combustion chamber.
Photo Eye: (figure 5) Senses flame in combustion chamber and signals oil primary when no flame is present.
Igniter Springs: (figure 5) Transfers the high voltage from the igniter transformer to the electrodes (when door is closed)
Air Pressure Gauge: (figure 4) Displays air pressure supplied by onboard air compressor.
Air Compressor: (figure 4) Supplies air used within pre-heater block to aid in atomization of the oil.
Air Muffler/Filter: (figure 5) Filters air and muffles the sound generated by the compressor.
Pre-Heater Control Circuit Board: (figure 5) Precisely controls temperature of the Oil Pre-Heater Block and controls safety feature of not allowing burner to energize until oil has established operating thermo setpoint or shutdown burner if Pre-Heater Block temperature falls below shutdown thermo setpoint.
Electrodes: (figure 6) Provides continuous high voltage electrical arc from electrode to electrode igniting the waste oil as it is being sprayed out of the nozzle.
Nozzle: (figure 6) Low pressure nozzle for oil spray pattern.
Flame Cone: (figure 6) Specially engineered flame cone forces the flame into a swirl
pattern improving the burn thoroughness.
Burner Motor: (figure 6) Multitask motor turns the burner blower and integrated air compressor.
Air Pressure Adjuster: (figure 4) Adjusts the air pressure going to the pre-heater block. Should be adjusted between 12 PSI and 13PSI as indicated on the Air Pressure Gauge on the burner for thorough burn of the waste oil.
Note: In order to insure proper air adjustment, air gauge must read 0 when burner
is cycled off or powered down.
Oil Pressure Gauge: (figure 4) Displays oil pressure at the burner. Adjust flame to 3/4 length of combustion chamber (figure 8) by increasing CW or decreasing CCW the adjuster located on the left side of burner (figure 9). The fuel regulator increases or decreases delivery of fuel to the burner. When you increase or decrease the fuel to the burner you will notice the flame length will increase or decrease.
IMPORTANT:
Once adjusted for correct flame length, take note of oil gauge setting for bench mark pressure reading needed when burning the specific fuel mixture generated by the owner. PLEASE NOTE- Once flame is set the oil pressure gauge can read various pressures when different viscosities of oils are used. The oil pressure gauge is an indicator of where the PSI reading will be when that oil viscosity is being burned. The oil gauge is used for servicing diagnostics assistance.
10
Operation, and Service Instructions
Page 11
Power Indicator: (figure 4) Indicates when power is present at the burner.
Run Indicator: (figure 4) Indicates that the burner is ready for operation after the initial
pre-heat time of approx. 5 minutes from initial power up.
Fuel Pump: (figure 7, 13) pumps fuel from fuel tank to burner.
Fuel Filter: (figure 7, 14) filters fuel prior to entering pump.
Fuel Regulator: (figure 7, 12) The fuel regulator increases or decreases delivery of fuel
to the burner. When you increase or decrease the fuel to the burner you will notice the flame length will increase or decrease. Adjust flame to 3/4 length of combustion chamber (figure 8) by increasing CW or decreasing CCW the fuel regulator located on the left side of burner (figure 9).
INITIAL START PROCEDURE
1. During the initial power up process the burner is locked out from energi zing until the oil has been properly pre-heated to operating thermo setpoint, approx 3 to 5 minute duration. Once the oil has been pre-heated, power is then applied to burner componenets an d oil pump.
2. Apply power to the heater. Switch heater main power switch to ON position. Burner motor will start to run but will not attempt to ignite. After allowing the oil pre-heater time to establish temperature setpoint, approximately 5 minutes, heater will start to establish flame. Once the burner is running, temporarily jump the “F” terminals on the Oil Primary. This will allow the burner to run during the pump priming process.
3. Priming the oil pump: Open bleeder valve one turn until all air is expelled. This may need to be done twice to insure all air is removed. IMPORTANT: When fully purged and flame is established remove temporarily jumpers on “F” terminals of the Oil Primary to allow safety features of the unit to operate properly.
4. Adjust air supply of integrated air compressor to 8-12 P.S.I. This is factory preset, however, due to freight handling settings may be compromised.
5. Combustion air band (figure 4) should be open approximately 1/2” or until flame is clear yellow, not orange. Opening the air band too far may cause delayed in starting or even prevent the flame from starting.
Apply Power
& Power Switch On.
Operational Sequence Chart
Operation and Service Instructions 11
Green Lamp On
Oil Pre-Heat
Time Period 3-5
Minutes
Burner Motor
Runs, No
Ignition
Power Supplied to Oil
Primary. Amber Lamp
On
Flame Not
Established Within
45 Sec, Burner Will
Shutdown
Normal Running
Operation Time
Ignition Start
Sequence 45 Sec
Power Switch Off (DO
NOT UNPLUG UNIT
AT THIS TIME) Green
6 Minute Cool
Burner Motor
& Amber Lamps Off
Down Time.
Runs, No
Ignition
Blower Motor Stops
Running. Safe To
Unplug Unit.
Page 12
To Adjust Lift Cap Up
To Lock Push Cap Down
Fuel Regulator
Back Side of Burner
Burner
Combustion
Chamber
Flame
¾ Length of Combustion
Chamber
Figure 8 – Flame Adjustment Figure 9 – Fuel Regulator
WEEKLY
--- Drain water from storage tank.
MONTHLY
--- clean stainless filter screen in filter (figure 14) periodically and drain off any water
accumulation. Monitor : every application is different and may vary depending on contamination of oils being used.
ONCE EACH SEASON
(OR MORE DEPENDING UPON USAGE OR CONTAMINATION OF OIL).
--- Clean flame cone. (figure 6).
--- Remove ash deposits from combustion chamber by opening front panel to gain access to
ash/drip pan inside combustion chamber. (figure 15).
--- Clean pump strainer. Remove pump cover for access. (figure 13). CAUTION!-Be careful of
gasket.
--- Clean air compressor filter element (figure 5).
YEARLY
--- Inspect electrode adjustment. (figure 11). Due to erosion, adjustment may change.
--- Replace nozzle every 3-5 years depending on usage (figure 6, 10). Will lose efficiency due to
erosion.
MAINTENANCE SCHEDULE
12
Operation, and Service Instructions
Page 13
ELECTRODE ADJUSTMENTS
Electrodes are adjusted at time of manufacture. However, they should be check periodically and at time of installation to be sure they are set as noted in the following dimensional drawing. Swing burner door back for inspection. (figure 5, 10, 11)
CAUTION: UNPLUG HEATER BEFORE CHECKING OR ADJUSTING ELECTRODE SETTING. NOZZLE POSITION IN RELATION TO ENDCONE/BURNER TUBE
Tip of nozzle must be ¼” ahead of inside radius of end-cone. If nozzle is behind inside radius of end-cone, coking will occur and end cone can become clogged. (figure 11). IMPORTANT NOTE: be sure nozzle is centered, if nozzle is higher than center, press nozzle down to bottom out pre­heater stand.
To adjust, loosen Preheat Sink securing nut and set screw, push fore or aft as needed. WARNING: This adjustment is done at the factory and should not be moved unless Fig 10 dimensions have been altered.
When cleaning, inspect all three pieces thoroughly. When disassembling and reassembling nozzle, keep facing up as shown.
Figure 10 – Nozzle Assembly Detail
Figure 11 – Electrode Adjustment Detail
Operation and Service Instructions 13
Page 14
Pre-Heater Control Card
Figure 12 – Pre-Heater Block Detail (Removed From Burner for Clarity)
Strainer
Pump Gasket
Allen Bolts (4)
Washer
Thermocouple
Filter Housing
Nut
Pump
Pump Cover
Filter Housing
Stainless Filter Screen
Figure 13 – Fuel Pump Figure 14 – Fuel Filter
Bolt & Washer
Figure 15 – Combustion Chamber Cleanout Door
14
Operation, and Service Instructions
Page 15
Operation and Service Instructions 15
Page 16
Symptom Cause Remed y
1. Heater shuts off Manual reset ♦Requiring manual restart by reset button on.
2. Loss of prime overnight ♦Vacuum air leak in fuel line ♦Check all fuel connections. Tighten fittings.
Won’t hold vacuum Plugged pump screen Check pump screen, may need cleaning-to access, remov e pump
IS TANK EMPTY? Plugged filter or tank oil empty Clean filter. Using vent port, reprime pump (See Figure 6 & 7).
3. Fails to start. Vacuum Leak ♦Open bleeder port if air present. Check and tight en fittings.
Inadequate Fuel Supply Clean filter. Check a ll fuel connections. Tighten fittings.
No Pressure Check, may need cleaning—to access, remove pump cover.
• Using vent port, reprime pump (See Figure 6 & 7)
No Pre-heat Be sure all wiring to pre-heater is tight-no loose connections.
• Bad firerod-Replace. Continuity at terminals.
Auto start circuit not functioning Check circuit control board and replace if necessary.(Call Factory)
• Check continuity at terminals of firerod limit snap switch.
Replace if needed.
No Arc • Check springs to electrode rod adjustment (under transformer)
make sure they make good contact. Open burner door and make sure electrode tips aren’t touching flame cone. Readjust.
No Air Pressure Check pressure regulator and adjust. Check air supply line for
restrictions or leaks. Pull compressor cover and inspect carbon
vanes. Ma y need to replace. Check filter, clean if needed.
4. Reduced air pressure, Gauge may be bad . Replace gauge.
cannot increase. Intake filter muffler is plugged Remove & Clean with carburetor cleaner,
with dust or dirt. dry thoroughly. Do Not Use.
Compressor vanes may be worn. Replace carbon canes.
• Exposed to water. • Remove cover, clean rust with emery cloth.
5. Hard starting diminished Partially plugged filter. Clean filter. Using vent port-repr ime pump (See Figure 6 & 7)
flame. Out of fuel Refill Storage. No oil to burner Clean pump screen-Remove pump cover. Using vent
port, reprime pump. (See figure 6 & 7)
Restriction in nozzle usually only Remove nozzle and check for foreign objects. (See Figure 9 and 11)
when initially installed. New lines Aluminum Block Pre-heater inside burner should not build may have foreign material in the m. up carbon. If carbon is present, pre-heat circuit is
malfunctioning. Thermocouple heat sensor wire could have open circuit. Heat control board may have blown
circuit and circuit board fuse. Inspect both and replace either if needed. (See Figure 11).
Air band open too far Close air band—while viewing flame; open air band
slowly until combustion chamber is clear, not orange.
6. Heater cycles frequently, Heater over firing. Investigate and locate reason for over firing. I.e., nozzle
without thermostat eroded, pump not functioning properly, decrease pump motor
TROUBLE SHOOTING
Most Likely Less Likely Least Likely
cover
speed.
16
Operation, and Service Instructions
Page 17
7. Heater rum bles and Pump setting wrong Pump not functioning properly-over firing. May need RPM excessive heat blow back readjust. Reset flame slightly less than ½ wa y down tube from flame vision port. combustion chamber. Use adjustment knob on pump motor.
(See Figure 7).
8. Heater establishes flame Photo eye cant see flame. Clean photo eye which is smoked up by back draft smoke. but locks out or shuts off. Need to reset primary.
Flame too small Increase pump motor speed (See Figure 7).
9. Poor or reduced heat Flame too small Nozzle may be plugged with debris-usually after filter is cleaned. production . Entire fuel su pply may be plu gged. Clean filter both, oil strainer and oil pump screen.
Operation and Service Instructions 17
Page 18
Omni Radiant Heater Limited Warranty
Econo Heat (manufacturer) warrants to the purchaser of the Radiant Heater listed above will be free from defects in materials and workmanship for the durations specified below, which duration begins on the date of delivery to the customer. Customer is responsible for maintaining proof of date of delivery.
If return is deemed necessary for warranty evaluation and determination of repair or replacement, radiant heater is to be sent to the factory with freight prepaid. Econo Heat Inc. reserves the right to determine appropriate action for repair or replacement.
No parts will be accepted by Econo Heat without RA# (return authorization number) clearly marked on outside of shipping package. Obtaining RA#
Warranty Covers:
This warranty is void if:
The above warranty is in lieu of all other warranties expressed or implied. Econo Heat does not authorize any person or representative to make or assume any other obligation or liability that is not in accordance with above warranty. Econo Heat Inc. is not responsible for any labor cost unless prior authorization
in writing has been obtained.
requires model and serial numbers, description of part being replaced and nature of defect. Call factory to receive RA#.
1. Combustion Chamber, one (1) year. (Parts Only)
2. Oil Heater Block, twenty (20) years. (Pa rts Only )
3. Oil Heater Block Controller PCB, three (3) years. (Parts Only)
4. All other components, one (1) year. (Parts Only)
1. Warranty registration card is not returned within thirty (30) days of purchase.
2. Any part or component subject to abuse or altered from original manufactures specifications.
3. Has not been properly m a i nta ined, operated or has been misused.
4. Radiant heater is operated in the presence of chlorinated vapors.
18
Operation, and Service Instructions
Page 19
WARRANTY CARD
Please fill our, tear off and return to manufacturer
Return following warranty information to manufacturer within thirty (30) days of purchase or warranty will not be valid. (Please print or type).
Date of Purchase_____________________________________________________________________ Serial #__________________________ Model ____________________________________________ Customer Name_____________________________________________________________________ Address____________________________________________________________________________ City _________________________ State ________________ Zip Code ________________________ Dealer ____________________________________________________________________________ Address ___________________________________________________________________________ City_________________________ State _________________ Zip Code _______________________ Installed at ________________________________________________________________________
Operation and Service Instructions 19